13183_FIRE PROTECTION_2014.06.26

advertisement
3
4
5
6
7
8
8.5
9
10
10.5
11
12
13
14
15
16
17
18
19
20
BY
Rev.: 13.02
THIS DOCUMENT, THE IDEAS
AND DESIGNS INCORPORATED
THEREIN, AS AN INSTRUMENT OF
PROFESSIONAL SERVICES, IS THE
PROPERTY OF RUSSELL AND
DAWSON LLC, AND MAY NOT BE USED,
IN WHOLE OR IN PART, FOR ANY OTHER
PROJECT OR BY ANY OTHER PERSON
OR CORPORATION OTHER THAN THAT
NAMED HEREON WITHOUT THE
WRITTEN AUTHORIZATION OF RUSSELL
AND DAWSON LLC. ANY SUCH
UNAUTHORIZED USE WILL BE SOLELY
AT THE USER'S RISK AND RUSSELL
AND DAWSON LLC WILL BEAR NO
RESPONSIBILITY ARISING OUT OF
SUCH USE.
© 2013 by Russell and Dawson LLC
&
RD
A
A Limited Liability Company
1111 Main Street, East Hartford CT 06108
TEL: (860) 289−1100 FAX: (860) 289−3272 E−MAIL: info@rdaep.com
2
RUSSELL AND DAWSON
ARCHITECTURE &
ENGINEERING
1
VESTIBULE
001
LINEN STORE
030
EMPLOYEE
TOILET
032
KING STUDIO
103
ELEV. LOBBY
022
FLOW
SWITCH
SPRINKLER HEAD
AT BOTTOM OF
ELEV. SHAFT.
SPRINKLER
ROOM
034
H
DRYER
029
J
1
FP-200
REFER TO 1/FP-200 FOR ENLARGED
PLAN OF SPRINKLER ROOM
OS & Y VALVE WITH
TAMPER SWITCH
COMBINATION OF
WET AND STAND
PIPE
MECH.
022a
CLOSET
021
MECH.
019
CORRIDOR
025
0.2H
POOL VEST.
014
WOMEN
017
CORRIDOR
015a
MEETING
ROOM
020
MTG. RM
STOR.
018
ACCESSIBLE
KING STUDIO
129
MEN
016
POOL EQUIP.
ROOM
013a
KING STUDIO
131
ELECTRICAL
ROOM
012
POOL ROOM
013
N
EMPLOYEE
BREAK ROOM
031
REFER TO SITE PLAN
FOR CONTINUATION.
FIRST FLOOR FIRE PROTECTION
DESIGN DENSITY
SPRINKLER HEAD
(GPM/SQ. FT) (AREA
TEMP. RATING
OF COVERAGE SQ. FT.
SPRINKLER HEAD
COVERAGE SQ.FT /
SPRINKLER
LIGHT HAZARD
(0.1 * 1500)
165
225
DRAINAGE
(0.2 * 1500)
HAZARD GROUP 2
165
130
MR
NFPA 13 HAZARD
CLASSIFICATION
DATE:
HYDRONIC CALCULATIONS SHALL BE BASED ON
LATEST FLOW TEST AND ALL INFORMATION SHALL BE
PROVIDED BY FIRE PROTECTION CONTRACTOR AT THE
SUBMITTAL OF SHOP DRAWINGS INCLUDING ALL
HYDRULIC CALCULATIONS.
DESIGN CRITERIA SHALL BE PER THE FOLLOWING TABLE.
FIRST FLOOR PLAN
FIRE PROTECTION
A:STATIC PRESSURE PSI
B:RESIDUAL PRESSURE PSI
C:FLOW GPM
D:FLOW TEST HYDRANT LOCATIONS:
HYD.#1 LOCATION
HYD.#2 LOCATION
E:DATE OF TEST
F:TIME OF TEST
G:RESPONSIBLE PARTY CONDUCTING TEST
H:HYDRANT OUTLET DISCHARGE COEFFICIENT
13.183
FLOW TEST
PROJECT:
3/32" = 1'-0"
FILE NO:
FP-101
SHEET TITLE:
1
HAMPTON: INN & SUITES
PROVIDE POST
INDICATING VALVE
DRAWN BY:
K
FLOW
SWITCH
STAIR # 2
011
0.8F
CART STAND ELEV. EQUIP.
RM.
028
026
LAUNDRY
027
KING STUDIO
130
15 CONNECTOR ROAD WESTBOROUGH, MA
GUEST
LAUNDRY
037
KING STUDIO
101
SUITE SHOP
BUS CENTER
STOR.
005
040
023
KING STUDIO
128
FOOD PREP.
STORE
009
MECH.
009a
CORRIDOR
015
G
STORE
ROOM
036
MAIN LOBBY
002
MECH.
033
CORRIDOR
044
FITNESS
CENTER
010
DATE:06/26/2014
F
PANTRY
007
CHECKED BY:
COMPUTER/
PBX
039
COMBINATION OF WET
AND STAND PIPE
FRONT
DESK
003
BREAKFAST
AREA
006
PERMIT
WORK AREA
041
FOOD PREP.
008
ISSUED FOR
KING STUDIO
100
DOUBLE
QUEEN
106
SALES
043
MM/DD/YY
OS & Y VALVE WITH
TAMPER SWITCH
KING STUDIO
102
KING SOFA
104
8"ø
FLOW SWITCH
STAIR # 1
038
DESCRIPTION
E
NO.
MANAGER
042
NOT FOR
CONSTRUCTION
D
BACK OFFICE
004
STAMP:
SIAMESE
CONNECTION
VERIFY WITH
FIRE MARSHAL
REVISIONS
MECH
004a
C
DATE
B
SHEET NUMBER:
FP-101
1
FP-102
K
SECOND FLOOR FIRE PROTECTION
KING
205
DOUBLE
QUEEN
207
DOUBLE
QUEEN
209
DOUBLE
QUEEN
212
?
?
DOUBLE
QUEEN
211
LINEN CHUTE
ROOM
295
ELEV. LOBBY
291
C
D
DOUBLE
QUEEN
217
DOUBLE
QUEEN
213
VENDING
293
DOUBLE
QUEEN
219
ACCESS.
DOUBLEQUEEN
214
OPEN TO
BELOW
238
DOUBLE
QUEEN
221
14
KING SOFA
222
ACCESS. KING
223
15
KING
224
KING
225
16
KING
226
KING
227
17
KING STUDIO
228
KING STUDIO
229
18
KING STUDIO
230
KING STUDIO
231
19
KING STUDIO
232
COMBINATION OF
WET AND STAND PIPE
F
CORRIDOR
207
DATE
20
COMBINATION OF
WET AND STAND
PIPE
0.8F
0.2H
LINEN
STORAGE
234
KING STUDIO
233
DATE:06/26/2014
13
DESCRIPTION
12
PERMIT
NO.
11
ISSUED FOR
NOT FOR
CONSTRUCTION
A
REVISIONS
10.5
15 CONNECTOR ROAD WESTBOROUGH, MA
E
10
HAMPTON: INN & SUITES
B
STAMP:
9
MR
J
KING STUDIO
203
DOUBLE
QUEEN
210
8.5
CHECKED BY:
H
KING STUDIO
201
DOUBLE
QUEEN
208
8
DRAWN BY:
MAINT. RM.
236
DOUBLE
QUEEN
206
7
MM/DD/YY
G
KING STUDIO
202
KING SOFA
204
6
DATE:
13.183
STAIR # 1
237
5
SECOND FLOOR PLAN
FIRE PROTECCTION
3/32" = 1'-0"
KING STUDIO
200
4
PROJECT:
OS & Y VALVE WITH
TAMPER SWITCH
3
FILE NO:
FLOW SWITCH
2
SHEET TITLE:
1
N
STAIR # 2
235
SHEET NUMBER:
FP-102
BY
Rev.: 13.02
THIS DOCUMENT, THE IDEAS
AND DESIGNS INCORPORATED
THEREIN, AS AN INSTRUMENT OF
PROFESSIONAL SERVICES, IS THE
PROPERTY OF RUSSELL AND
DAWSON LLC, AND MAY NOT BE USED,
IN WHOLE OR IN PART, FOR ANY OTHER
PROJECT OR BY ANY OTHER PERSON
OR CORPORATION OTHER THAN THAT
NAMED HEREON WITHOUT THE
WRITTEN AUTHORIZATION OF RUSSELL
AND DAWSON LLC. ANY SUCH
UNAUTHORIZED USE WILL BE SOLELY
AT THE USER'S RISK AND RUSSELL
AND DAWSON LLC WILL BEAR NO
RESPONSIBILITY ARISING OUT OF
SUCH USE.
© 2013 by Russell and Dawson LLC
A Limited Liability Company
1111 Main Street, East Hartford CT 06108
TEL: (860) 289−1100 FAX: (860) 289−3272 E−MAIL: info@rdaep.com
RUSSELL AND DAWSON
ARCHITECTURE &
ENGINEERING
RD
&
SPRINKLER
HEAD AT THE
TOP OF
ELEVATOR
SHAFT
DOUBLE
QUEEN
313
K
LINEN CHUTE
ROOM
395
?
?
ELEV.
LOBBY
391
FLOW
SWITCH
DOUBLE
QUEEN
316
DOUBLE
QUEEN
317
DOUBLE
QUEEN
318
DOUBLE
QUEEN
319
DOUBLE
QUEEN
320
DOUBLE
QUEEN
321
KING SOFA
322
ACCESS KING
323
15
KING
324
KING
325
16
KING
326
KING
327
17
KING STUDIO
328
KING STUDIO
329
18
KING STUDIO
330
KING STUDIO
331
19
D
KING STUDIO
332
COMBINATION OF WET
AND STAND PIPE
STAIR # 2
235
F
FLOW
SWITCH
G
KING STUDIO
333
COMBINATION
OF WET AND
STAND PIPE
0.2H
LINEN
STORAGE
392
VEND.
393
DATE:06/26/2014
14
PERMIT
13
ISSUED FOR
NO.
12
NOT FOR
CONSTRUCTION
C
STAMP:
11
15 CONNECTOR ROAD WESTBOROUGH, MA
ACCESS. DBL.
QUEEN
314
10.5
MR
3/32" = 1'-0"
DOUBLE
QUEEN
311
DOUBLE
QUEEN
312
10
HAMPTON: INN & SUITES
E
9
CHECKED BY:
TYPICAL FLOOR FIRE PROTECTION
DOUBLE
QUEEN
309
DOUBLE
QUEEN
310
8.5
DRAWN BY:
FP-103
KING
305
DOUBLE
QUEEN
307
DOUBLE
QUEEN
308
8
MM/DD/YY
J
KING STUDIO
303
DOUBLE
QUEEN
306
7
DATE:
H
KING STUDIO
301
KING STUDIO
302
KING SOFA
304
6
TYPICAL FLOOR PLAN
FIRE PROTECTION
LINEN
STORAGE
394
KING STUDIO
300
5
PROJECT:
OS & Y VALVE WITH
TAMPER SWITCH
4
13.183
1
STAIR # 1
237
3
FILE NO:
FLOW SWITCH
2
SHEET TITLE:
1
20
N
0.8F
CORRIDOR
397
SHEET NUMBER:
FP-103
DESCRIPTION
REVISIONS
DATE
BY
Rev.: 13.02
THIS DOCUMENT, THE IDEAS
AND DESIGNS INCORPORATED
THEREIN, AS AN INSTRUMENT OF
PROFESSIONAL SERVICES, IS THE
PROPERTY OF RUSSELL AND
DAWSON LLC, AND MAY NOT BE USED,
IN WHOLE OR IN PART, FOR ANY OTHER
PROJECT OR BY ANY OTHER PERSON
OR CORPORATION OTHER THAN THAT
NAMED HEREON WITHOUT THE
WRITTEN AUTHORIZATION OF RUSSELL
AND DAWSON LLC. ANY SUCH
UNAUTHORIZED USE WILL BE SOLELY
AT THE USER'S RISK AND RUSSELL
AND DAWSON LLC WILL BEAR NO
RESPONSIBILITY ARISING OUT OF
SUCH USE.
© 2013 by Russell and Dawson LLC
A Limited Liability Company
1111 Main Street, East Hartford CT 06108
TEL: (860) 289−1100 FAX: (860) 289−3272 E−MAIL: info@rdaep.com
RUSSELL AND DAWSON
ARCHITECTURE &
ENGINEERING
RD
&
200°F (93°C)
180°F (82°C)
150°F (65°C)
GREEN
WHITE
INTERMEDIATE
212°F (100°C)
192°F (88°C)
150°F (65°C)
GREEN
WHITE
HIGH
286°F (141°C)
266°F (130°C)
225°F (107°C)
BLUE
BLUE
EXTRA HIGH
e
ULTRA HIGH
360°F (182°C)
340°F (171°C)
300°F (149°C)
MAUVE
RED
500°F (260°C)
480°F (249°C)
465°F (240°C)
BLACK
ORANGE
3.
THE DRAWINGS INDICATE A SUGGESTED SPRINKLER HEAD LAYOUT AND THAT EACH AREA IS COVERED BY SPRINKLER EXACT
LOCATIONS. REFER TO NFPA 13 FOR EXACT SPACING, DENSITY, AND LOCATION REQUIREMENTS. CONTRACTOR SHALL INSTALL
QUICK RESPONSE TYPE SPRINKLER IN ENTIRE BUILDING. USE OF EXTENDED COVERAGE, QUICK RESPONSE, TYPE SPRINKLER
MAY BE USED WITH THE APPROVAL OF THE OFFICE OF THE STATE FIRE MARSHAL.CONTRACT DOCUMENTS SHOW STANDARD
COVERAGE SPRINKLERS WITH STANDARD SPACING BETWEEN SPRINKLERS PER NFPA 13. USE OF EXTENDED COVERAGE TYPE
MAY REDUCE NUMBER OF SPRINKLERS ON THE PROJECT.
PIPING SHOWN ON DRAWINGS IS DIAGRAMMATIC, AND INDICATES GENERAL ARRANGEMENT OF
WORK. LOCATE SPRINKLER HEADS AS INDICATED ON DRAWINGS. CONNECT TO EXISTING, OR
RUN NEW PIPING, AS REQUIRED FOR A COMPLETE AND OPERATIONAL SYSTEM IN
ACCORDANCE WITH NFPA 13.
4.
SPRINKLERS IN FINISHED CEILING AREAS SHALL ALWAYS BE LOCATED IN THE CENTER OF CEILING TILES UNLESS
CODES AND STANDARDS
5.
THE FIRE PROTECTION CONTRACTOR SHALL REVIEW THE ARCHITECTURAL REFLECTED CEILING, ELEVATION AND SECTION
PLANS AS PART OF THIS CONTRACT FOR ADDITIONAL INFORMATION SUCH AS CEILING HEIGHTS, TYPES, SOFFITS AND
OR
OTHER DEVICE LOCATIONS.
NOTES:
1.
2.
SPRINKLER FINISHES:
BRASS, BRIGHT BRASS, POLISHED CHROME, WHITE (POLYESTER), WHITE PAINT,
BLACK TEFLON, NAVAJO WHITE (PAINT)
CORROSION RESISTANT COATINGS:
POLYESTER AND TEFLON IN ALL TEMPERATURES AND WAX,
AND/OR WAX OVER POLYESTER IN THE FOLLOWING TEMPERATURES:
135°F (57°C) WHITE WAX
155°F (68°C) LIGHT BROWN WAX
212°F (100°C) DARK BROWN WAX
175°F (79°C) DARK BROWN WAX
200°F (93°C) DARK BROWN WAX
6.
7.
NOTES:
a.
b.
c.
THE CORROSION RESISTANT COATINGS HAVE PASSED THE STANDARD CORROSION TEST
REQUIRED BY THE LISTED APPROVING AGENCIES. THESE TESTS CANNOT AND DO NOT
REPRESENT ALL POSSIBLE CORROSIVE ENVIRONMENTS. PRIOR TO INSTALLING, VERIFY
THROUGH THE END USER, THAT THE COATINGS ARE COMPATIBLE OR SUITABLE FOR THE
PROPOSED ENVIRONMENT. THE COATINGS INDICATED ARE APPLIED TO THE EXPOSED
EXTERIOR SURFACES ONLY AND THEREFORE CANNOT BE USED AS OPEN SPRINKLERS.
NOTE THAT THE SPRING IS EXPOSED ON THE TEFLON AND POLYESTER SPRINKLER.
d.
TEMPERATURE RATING IS STAMPED ON DEFLECTOR.
e.
SPRINKLERS OF ULTRA HIGH TEMPERATURE RATING ARE INTENDED FOR USE INSIDE
OVENS, DRYERS OR SIMILAR ENCLOSURES WITH NORMAL OPERATING TEMPERATURES
ABOVE 300°F (149°C). ANY TIME THE AMBIENT TEMPERATURE AROUND THE ULTRA HIGH
TEMPERATURE RATED SPRINKLER IS SIGNIFICANTLY REDUCED BELOW 300°F (149°C),
RESPONSE TIME OF THE ULTRA HIGH TEMPERATURE RATED SPRINKLER MAY BE
RETARDED.
8.
9.
10.
FIRE PROTECTION CONSTRUCTION PROCEDURES
2. THE FIRE PROTECTION CONTRACTOR MUST CONTACT THE OWNER'S CONSTRUCTION
COORDINATOR AND REQUEST THE SPRINKLER MAIN TO BE ISOLATED AND/OR DRAINED. THIS
PROCEDURE MUST BE ADHERED TO WHEN PRESSURE TESTING AND/OR PLACING SYSTEM IN OR
OUT OF SERVICE.
3. ALL WORK SHALL MEET THE REQUIREMENTS OF NFPA STANDARDS. INSTALLATION PROCEDURES
SHALL COMPLY WITH THE SAFETY RULES OF OSHA AND THE STATE OF FLORIDA FIRE SAFETY
CODE.
6. THE FIRE PROTECTION CONTRACTOR SHALL PROVIDE A MATERIAL TEST AND CERTIFICATION FORM
TO THE OFFICE OF THE STATE FIRE MARSHAL AND THE OWNER'S INSURANCE CARRIER SO AS TO
CERTIFY THAT THE SPRINKLER SYSTEM WAS INSTALLED IN ACCORDANCE WITH THE CONTRACT
DOCUMENTS, SPECIFICATIONS, FEDERAL, STATE, AND LOCAL CODES AND PROCEDURES.
7. UPON COMPLETION OF SYSTEM INSTALLATION, THE FIRE PROTECTION CONTRACTOR SHALL
PERFORM A HYDROSTATIC SYSTEM TEST ON ALL PIPING AND ATTACHED APPURTENANCES IN THE
PRESENCE OF A REPRESENTATIVE OF THE FIRE MARSHAL'S OFFICE. THE SYSTEM SHALL BE
HYDROSTATICALLY TESTED AT A PRESSURE OF 200 PSI AND SHALL MAINTAIN THAT PRESSURE
WITHOUT LOSS FOR 2 HOURS. LOSS SHALL BE DETERMINED BY A DROP IN GAUGE PRESSURE OR
VISUAL LEAKAGE. THE TEST PRESSURE SHALL BE READ FROM A GAUGE LOCATED AT THE LOW
ELEVATION POINT OF THE SYSTEM OR PORTION BEING TESTED. ALL TESTING THE SYSTEM SHALL
BE IN ACCORDANCE WITH NFPA 13 AND NFPA 25.
8. AS PER THE CONSTRUCTION PHASING OF THE PROJECT, THE EXISTING AREAS OF FIRE PROTECTION
MUST BE MAINTAINED. THE FIRE PROTECTION CONTRACTOR IS TO PROVIDE SERVICE TO THESE
AREAS FROM THE NEW FIRE PROTECTION SERVICE AS REQUIRED.
THE FIRE PROTECTION CONTRACTOR SHALL REVIEW THE HVAC DIVISION DRAWINGS AND COORDINATE THE FIRE PROTECTION
WORK WITH LOCATIONS OF CEILING MOUNTED DEVICES SUCH AS DIFFUSERS, GRILLS, REGISTORS, AND ALSO THE LOCATIONS OF
HEAT PRODUCING EQUIPMENT AND DUCTWORK REQUIRING SPRINKLER PROTECTION
BEFORE SUBMITTING A BID, THE FIRE PROTECTION CONTRACTOR SHALL VISIT THE SITE AND BECOME THOROUGHLY FAMILIAR
WITH ALL EXISTING FIRE PROTECTION CONDITIONS AND THAT OF THE OTHER TRADES (STRUCTURAL, MECHANICAL, ELECTRICAL,
PLUMBING, SITE, ETC.) THIS CONTRACT INCLUDES ALL MODIFICATIONS OF EXISTING SYSTEMS REQUIRED FOR THE INSTALLATION
OF THE NEW SYSTEM. THIS CONTRACT INCLUDES ALL NECESSARY OFFSETS, TRANSITIONS, AND MODIFICATIONS REQUIRED TO
INSTALL ALL NEW EQUIPMENT. ALL NEW EQUIPMENT AND SYSTEMS SHALL BE FULLY OPERATIONAL UNDER THIS CONTRACT
BEFORE THE JOB IS CONSIDERED COMPLETE. THE FIRE PROTECTION CONTRACTOR SHALL BE HELD RESPONSIBLE FOR ANY
ASSUMPTIONS, OMISSIONS, OR ERRORS MADE AS A RESULT OF THE CONTRACTOR'S FAILURE TO BECOME FULLY FAMILIAR WITH
THE EXISTING CONDITIONS AND THE CONTRACT DOCUMENTS OF ALL TRADES.
THE INSTALLATION OF THE SPRINKLER SYSTEM SHALL BE BASED ON THE FOLLOWING: LIGHT HAZARD: .10 GPM/SQ. FT. OVER 1,500
SQ. FT. MAXIMUM COVERAGE: 225 SQ. FT. PER SPRINKLER CONTRACTOR SHALL VERIFY REQUIREMENTS WITH OWNER'S
INSURANCE UNDERWRITER.
THE INSTALLATION OF THE SPRINKLER SYSTEM FOR MECHANICAL ROOMS, STORAGE ROOMS, AND OTHER ROOMS AS NOTED ON
THE DRAWINGS SHALL BE BASED ON THE FOLLOWING: ORDINARY HAZARD, : .20 GPM/SQ. FT. OVER 2,000 SQ. FT.MAXIMUM
COVERAGE: 225 SQ. FT. PER SPRINKLER CONTRACTOR SHALL VERIFY REQUIREMENTS WITH OWNER'S INSURANCE
UNDERWRITER.
THE CONTRACTOR SHALL PROVIDE SPRINKLER LAYOUT SHOP DRAWINGS, HYDRAULIC CALCULATIONS, SIGNED AND STAMPED BY
A PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF THE PROJECT. THESE DRAWINGS AND CALCULATIONS SHALL BE
SUBMITTED AS DESCRIBED IN THE SPECIFICATION. THESE SHOP DRAWINGS AND CALCULATIONS SHALL BE SUBMITTED TO AND
APPROVED BY THE OFFICE OF THE STATE FIRE MARSHAL AND OWNER'S INSURANCE CARRIER PRIOR TO INSTALLATION. THE
CONTRACTOR SHALL PROVIDE COPIES OF THE STATE FIRE MARSHAL'S AND OWNER'S INSURANCE CARRIER'S APPROVALS WITH
THEIR SHOP
DRAWING SUBMITTAL.
13.
THE FIRE PROTECTION CONTRACTOR SHALL COORDINATE ALL SPRINKLER WORK WITH NEW LIGHTING FIXTURES,
DIFFUSERS, DUCTWORK. THE CONTRACTOR SHALL PROVIDE PROPER SPRINKLER COVERAGE PER NFPA 13.
14.
SPRINKLERS SHALL BE INSTALLED UNDER FIXED OBSTRUCTIONS OVER 4 FT. (1.2M) WIDE PER NFPA 13, SECTION 5-5.5.3.1. THE
CONTRACTOR SHALL VERIFY ALL DUCTWORK DIMENSIONS IN THE FIELD AND INSTALL SPRINKLERS AS REQUIRED.
15.
16.
4. THE FIRE PROTECTION CONTRACTOR MUST PROVIDE A FIRE WATCH WHENEVER ANY WELDING IS
DONE WITHIN THE AREA BEING WORKED, DURING THE WELDING OPERATION, AND FOR ONE HOUR
AFTER WELDING IS COMPLETED.
5. NO STOCK OF FURNISHINGS SHALL BE ALLOWED IN THE AREAS BEING WORKED UNTIL THE ENTIRE
SYSTEM IS COMPLETED IN ACCORDANCE WITH THE ABOVE NOTES AND APPROVED BY THE OFFICE
OF THE FIRE MARSHAL.
THE FIRE PROTECTION CONTRACTOR SHALL REVIEW THE ELECTRICAL DIVISION DRAWINGS AND COORDINATE THE FIRE
PROTECTION WORK WITH LOCATIONS OF LIGHTS, AND CEILING MOUNTED DEVICES WHICH MAY INTERFERE WITH SPRINKLER
HEAD LOCATIONS OR SPRAY PATTERNS.
11. THE CONTRACTOR SHALL MAKE PROVISIONS FOR DRAINING THE ENTIRE SYSTEM PER NFPA 13.
12.
1. IT IS SOLELY THE FIRE PROTECTION CONTRACTOR'S RESPONSIBILITY TO OBTAIN APPROVAL OF
SHOP DRAWINGS FROM THE OWNER'S INSURANCE CARRIER AND OFFICE OF THE STATE FIRE
MARSHAL.
OTHERWISE.
INDICATED
BELOW IT.
BASED ON NATIONAL FIRE PREVENTION AND CONTROL ADMINISTRATION CONTRACT NO.
7-34860.
BASED ON NFPA-13, OTHER LIMITS MAY APPLY DEPENDING ON FIRE LOADING, SPRINKLER
LOCATION, AND OTHER AUTHORITY HAVING JURISDICTION REQUIREMENTS. REFER TO
SPECIFIC INSTALLATION STANDARDS.
INTENT OF DRAWINGS
ALL PIPING SHOWN SHOW BE LOCATED ABOVE THE CEILING OR IN SOFFIT SPACES UNLESS NOTED OTHERWISE OR IF THE ROOM
HAS NO CEILING. ALL SPRINKLER PIPING SHOWN SHALL BE RUN ABOVE LIGHTING FIXTURES SHOWN ON THE LIGHTING DRAWINGS.
COORDINATE THE ROUTING OF SPRINKLER PIPING WITH OTHER TRADES IN THE FIELD. COORDINATE SPRINKLERS AND
ASSOCIATED PIPING WITH THE ARCHITECTURAL CEILING/SOFFIT CONFIGURATION AND STRUCTURAL DRAWINGS.
ALL FIRE PROTECTION VALVES INSTALLED ABOVE CEILINGS SHALL BE PROVIDED WITH ACCESS PANELS (WHERE APPLICABLE)
AND 1/2"DIA. "DOT" VALVE INDICATORS WHERE VALVES ARE LOCATED.
VERIFY VALVE IDENTIFICATION REQUIREMENTS WITH OWNER'S STANDARDS IN THE FIELD
17.
THE FIRE PROTECTION DESIGN IS BASED ON MANUFACTURERS AND MODEL NUMBERS LISTED HEREIN. THE FIRE PROTECTION
CONTRACTOR MAY AT HIS/HER DISCRETION CHOOSE ANOTHER OF THE APPROVED EQUALS LISTED IN THE APPROPRIATE
SPECIFICATION SECTIONS AND CONTRACT DOCUMENTS. HOWEVER, BY DOING SO, THE FIRE PROTECTION CONTRACTOR ALSO
UNDERTAKES THE RESPONSIBILITY OF COORDINATION WITH EXISTING CONDITIONS, NOTIFICATION OF OTHER TRADES AND
ADDITIONAL COST INCURRED BY OTHER TRADES REQUIRED AS A RESULT OF THE SUBSTITUTION.
DO NOT SCALE DRAWINGS. CHECK EXISTING SPACE CONDITIONS AT THE JOB SITE.
STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS: NFPA 13 & 14.
PIPE HANGERS AND SUPPORTS: MSS SP-58.
OWNER'S INSURANCE COMPANY.
RUSSELL AND DAWSON
ARCHITECTURE &
ENGINEERING
PIPING IDENTIFICATION
CONSPICUOUSLY IDENTIFY NEW PIPING WITH SELF-ADHERING VINYL PLASTIC COLOR BANDS
AND PIPE MARKERS IMPRINTED WITH LEGEND, BASED ON ANSO A13.1 "SCHEME FOR THE
IDENTIFICATION OF PIPING SYSTEMS".
APPLY LEGENDS TO FEED AND CROSS MAIN PIPING ADJACENT TO CHANGES IN DIRECTION
WHERE PIPES PASS THROUGH WALLS OR FLOORS, AT INTERVALS NOT EXCEEDING 40 FEET
IN STRAIGHT PIPING RUNS, AND ADJACENT TO CROSS MAIN CONNECTIONS WITH FEED MAIN.
1/2" FOR PIPING 3/4" TO 1-1/4" OD
3/4" FOR PIPING 1-1/2" TO 2" OD
1-1/4" FOR PIPING 2-1/2" TO 6" OD
PRESSURE GAUGES: LISTED 3-1/2" DIAL, STEM MOUNTED, BOURDON TUBE TYPE, WITH
BRASS CASE AND RING, PHOSPHOR BRONZE TUBE, BRASS SOCKET, BRASS MOVEMENT,
HEAVY FLAT GLASS CRYSTAL, 0-300 PSI RANGE.
MINIMUM COLOR BAND WIDTH:
INSPECTORS TEST CONNECTION: U.L. LISTED, FM APPROVED, 300 PSI MAXIMUM WORKING
PRESSURE, ONE PIECE DUCTILE IRON BODY, ASTM A536, 1-1/4" INLET AND OUTLET
CONNECTIONS, EQUIPPED WITH BRONZE FITTED TEST AND DRAIN VALVES, ACRYLIC SIGHT
GLASS. INSTALL 1/2" ALUMINUM ORIFICE INSETS GIVING FLOW EQUAL TO ONE SPRINKLER
HEAD. VICTAULIC "TESTMASTER" STYLE 718/719.
8" FOR PIPING 3/4" TO 2" OD
12" FOR PIPING 2-1/2" TO 6" OD
IDENTIFICATION SIGNS
U.L. COMPLIANCE.
OPERATING INSTRUCTIONS
INSTRUCT OWNER'S OPERATING PERSONNEL ON PROPER CARE, MAINTENANCE AND
OPERATING PROCEDURES.
COMPLY WITH ALL APPLICABLE GOVERNMENTAL REGULATIONS. COMPLY WITH ALL FEDERAL,
STATE, CITY, INSURANCE UNDERWRITERS AND OTHER APPLICABLE CODES AND ORDINANCES.
IF ANY CONFLICT ARISES BETWEEN THESE SPECIFICATIONS, CODES AND ORDINANCES,
IMMEDIATELY NOTIFY THE ENGINEER. DO NOT DEVIATE FROM THE SPECIFICATIONS NOR
INSTALL ANY WORK WHICH MAY BE IN CONFLICT WITH CODES AND ORDINANCES UNTIL THE
CONFLICT IS RESOLVED AND THE SOLUTION APPROVED BY THE ENGINEER.
SUBMITTALS
PRODUCT DATA: SUBMIT MANUFACTURER'S TECHNICAL PRODUCT DATA, INCLUDING RATED
CAPACITIES OF SELECTED MODEL CLEARLY INDICATED, FURNISHED SPECIALTIES AND
ACCESSORIES; AND INSTALLATION INSTRUCTIONS.
SHOP DRAWINGS: SUBMIT MANUFACTURER'S ASSEMBLY TYPE SHOP DRAWINGS INDICATING
DIMENSIONS, ROUGHING-IN REQUIREMENTS, REQUIRED CLEARANCES, AND METHODS OF
ASSEMBLY OF COMPONENTS AND ANCHORAGES.
MAINTENANCE DATA: SUBMIT MAINTENANCE DATA AND PARTS LISTS FOR EACH TYPE OF
PLUMBING FIXTURE AND ACCESSORY; INCLUDING "TROUBLE SHOOTING" MAINTENANCE GUIDE.
INCLUDE THIS DATA, PRODUCT DATA AND SHOP DRAWINGS IN MAINTENANCE MANUAL.
MAKE SUBMITTALS OF SHOP DRAWINGS OF ALL FIRE PROTECTION EQUIPMENT AS FOLLOWS:
MAINTENANCE MANUAL
INCLUDE FOLLOWING IN MANUALS:
MANUFACTURER'S DESCRIPTIVE DATA
OPERATION AND MAINTENANCE INSTRUCTIONS
REPLACEMENT PART LISTS
WIRING DIAGRAMS
MANUFACTURER'S WARRANTY & SERVICE CERTIFICATES
INSTRUCTIONS FOR PERIODIC CLEANING AND MAINTENANCE
PROCEDURES FOR SYSTEMS START-UP AND SHUT-DOWN
VALVE LOCATION AND TAG NUMBER CHARTS
NFPA 13A "CARE AND MAINTENANCE OF SPRINKLER SYSTEMS"
SUBMIT WORKING SPRINKLER DRAWINGS TO LOCAL FIRE MARSHAL.
A COMPLETE SET OF DETAILED CONTRACTOR'S INSTALLATION DRAWINGS TO INCLUDE A FULL
HEIGHT CROSS SECTION, LOCATIONS OF ALL WALLS, PARTITIONS, LIGHTS, DIFFUSERS, GRIDS,
MAJOR EQUIPMENT AND DUCTWORK, SIZE OF SITE WATER MAIN AND PRESSURE, NOMINAL
PIPE SIZES, CUTTING LENGTHS AND FINISHED FLOOR TO PIPE ELEVATION LENGTH, LOCATION
OF ALL VALVES, MAINS, BRANCH PIPING AND SPRINKLER HEADS HYDRAULIC NAMEPLATE
DATA AND ALL PERTINENT INFORMATION.
SUBMITTAL INFORMATION OUTLINED IN NFPA 13 SECTION 1-9.
A COMPLETE SET OF DETAILED HYDRAULIC CALCULATIONS FOR EACH SYSTEM WITH
HYDRAULIC REFERENCE POINTS, AS PER NFPA 13. SUBMITTAL INFORMATION OUTLINED IN
NFPA 13 SECTION 7-3.
PERMITS AND FEES
SECURE AND PAY COSTS OF PERMITS, CERTIFICATES, LICENSES, INSPECTIONS AND
APPROVALS.
ADJUSTMENTS
UPON COMPLETION OF WORK, PERFORM THE FOLLOWING ADJUSTMENT PROCEDURES:
ADJUST SYSTEMS COMPONENTS FOR PROPER PERFORMANCE.
OPEN AND CLOSE VALVES, SET IN PROPER OPERATING POSITION.
ACCESSIBILITY
PLACE VALVES, UNIONS, DRAINS, AND ITEMS REQUIRING MAINTENANCE, ADJUSTMENT, OR
REPAIR, IN ACCESSIBLE LOCATIONS. COORDINATE ACCESS PANELS WITH ARCHITECT.
APPROVALS
OBTAIN INSURANCE SERVICE'S OFFICE APPROVAL OF WORKING DRAWINGS. OBTAIN
CERTIFICATES OF APPROVAL FROM FIRE ADMINISTRATION OFFICIAL.
REFERENCE PUBLICATIONS
AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM) AND AMERICAN NATIONAL
STANDARDS INSTITUTE (ANSI) PUBLICATIONS ARE REFERRED TO HEREIN, BECAUSE THESE
PUBLICATIONS ARE REVISED FREQUENTLY, DATES FOLLOWING PUBLICATION NUMBERS HAVE
BEEN OMITTED. REFER TO LATEST EDITION.
COORDINATION OF WORK
FIRE PROTECTION SYSTEMS SHALL BE COMPLETELY OPERATIONAL UPON COMPLETION OF
WORK. RE-PIPE AND RECONFIGURE SYSTEM FEED AND CROSS MAINS (AS REQUIRED) BACK
TO AUTOMATIC SPRINKLER RISER FOR WATER SUPPLY. TEST AND ENSURE THAT ALARM AND
TEST EQUIPMENT IS OPERATIONAL.
CAREFULLY CHECK SPACE REQUIREMENTS WITH OTHER TRADES TO INSURE THAT ALL
MATERIALS CAN BE INSTALLED IN THE SPACES ALLOTTED THERETO, INCLUDING FINISHED
SUSPENDED CEILING.
TRANSMIT TO OTHER TRADES ALL INFORMATION REQUIRED FOR WORK TO BE PROVIDED
UNDER THEIR RESPECTIVE SECTIONS IN AMPLE TIME FOR INSTALLATION.
WHEREVER WORK INTERCONNECTS WITH WORK OF OTHER TRADES, COORDINATE WITH OTHER
TRADES TO INSURE THAT ALL TRADES HAVE THE INFORMATION NECESSARY SO THEY MAY
PROPERLY INSTALL ALL THE NECESSARY CONNECTIONS AND EQUIPMENT. IDENTIFY ALL
WORK ITEMS (VALVES, DRAINS, ETC.) IN AN APPROVED MANNER IN ORDER THAT THE
CEILING SUBCONTRACTOR WILL KNOW WHERE TO INSTALL ACCESS DOORS AND PANELS.
CONSULT WITH OTHER TRADES REGARDING EQUIPMENT SO, WHEREVER POSSIBLE, MOTORS
AND CONTROL ARE OF THE SAME MANUFACTURER.
PENDENT HEADS - CONCEALED PIPING: BRIGHT CHROME PLATED BRONZE, FUSIBLE LINK,
WITH SPRINKLER CUP ASSEMBLY. VIKING MODEL 'M'.
HEAD GUARDS: REQUIRED FOR HEADS SUBJECT TO MECHANICAL INJURY.
SPARE HEAD CABINET: BAKED ENAMELED STEEL CABINET, HINGED COVER, OF ADEQUATE
SIZE TO CONTAIN HEADS AND WRENCH.
HEAD WRENCH: PROVIDE AT LEAST ONE, WITH SUITABLE OPENINGS.
ALARM VALVES
PROVIDE VIKING MODEL J-1 WET SYSTEM ALARM CHECK VALVE COMPLETE WITH TRIM KIT.
PROVIDE VIKING MODEL F-1 DRY SYSTEM ALARM CHECK VALVE COMPLETE WITH TRIM KIT
AND AIR MAINTENANCE.
VALVE SUPERVISORY DEVICES: U.L. LABELED FM APPROVED, TAMPER-PROOF SIGNALING
INITIATING SWITCH ARRANGED TO DETECT CLOSED VALVE POSITION. ELECTRICAL WIRING: 120
VAC. POTTER-ROEMER #6220.
UPON COMPLETION OF WORK, PERFORM THE FOLLOWING CLEANING PROCEDURES:
REMOVE PROTECTIVE COVERS AFTER PAINTING
CLEAN PIPING AND EQUIPMENT
REMOVE SURPLUS MATERIALS AND RUBBISH
RESTORE DAMAGED SURFACE FINISHES
ADJUSTMENTS
GUARANTEE
SUBMIT, TO BOTH STATE AND LOCAL FIRE MARSHAL, ONE SIGNED COPY OF "CONTRACTOR'S
MATERIAL AND TEST CERTIFICATE".
AUTOMATIC TYPE: UPRIGHT, CONCEALED PENDENT, OR SIDEWALL TO MEET CONDITIONS AND
OF PROPER TEMPERATURE RATING. DEFLECTOR TO BE MARKED TO INDICATE POSITION.
CLEAN PIPING PRIOR TO PAINTING.
CERTAIN TERMS SUCH AS "SHALL, PROVIDE, INSTALL, COMPLETE, START-UP" ARE NOT
USED IN SOME PARTS OF THESE SPECIFICATIONS. THIS DOES NOT INDICATE ITEMS SHALL
BE LESS THAN COMPLETELY INSTALLED OR THAT SYSTEMS SHALL BE LESS THAN
COMPLETE.
SUBMIT, FOR ENGINEER AND OWNER'S USE TWO PRINT COPIES OF UPDATED WORKING
DRAWINGS STAMPED "APPROVED" BY INSURANCE COMPANY.
SPRINKLER HEADS
VALVE SUPERVISORY DEVICES
UPON COMPLETION OF WORK, PERFORM THE FOLLOWING ADJUSTMENT PROCEDURES:
SUBMIT SHOP DRAWINGS OR CATALOG CUTS APPROVED BY "INSURANCE COMPANY"
SHOWING NEW SPRINKLER EQUIPMENT, ALARM EQUIPMENT, VALVES AND GAGES.
SPRINKLER EQUIPMENT
CLEANING
SPRINKLER HEADS
PIPES
SPECIALTIES
CONFORM THE FIRE PROTECTION WORK TO THE REQUIREMENTS HEREIN. PROVIDE OFFSETS,
FITTINGS, DRAINS AND ACCESSORIES WHICH MAY BE REQUIRED. INVESTIGATE THE
STRUCTURAL AND FINISH CONDITIONS AFFECTING THE WORK, AND ARRANGE THE WORK
ACCORDINGLY. PROVIDE SUCH PIPING, FITTINGS, VALVES AND ACCESSORIES AS MAY BE
REQUIRED TO MEET SUCH CONDITIONS.
TEST PIPE OUTLETS: CORROSION RESISTANT SMOOTH BORE PIPE NIPPLE HAVING FLOW
EQUIVALENT TO ONE SPRINKLER.
GAUGE VALVES: 1/4" SOFT METAL SEAT GLOBE VALVE WITH DRAIN PLUG.
AWWA STANDARDS.
COMPLY WITH REQUIREMENTS OF LOCAL AUTHORITY HAVING JURISDICTION.
CONTROL VALVES - 2-1/2 INCH AND SMALLER: ALL BRONZE, SLOW BUTTERFLY BALL WITH
BUILT IN SUPERVISORY SWITCH.
CONTROL VALVES - 3 INCH AND LARGER: IBBM OSY FLANGED GATE VALVE.
MINIMUM LETTER SIZE:
PROVIDE ENAMELED STEEL IDENTIFICATION SIGNS FOR ALL NEW ALARM DEVICES AND ALL
NEW CONTROL, DRAIN AND TEST VALVES.
COMPLY WITH REQUIREMENTS OF LOCAL UTILITY COMPANY.
CHECK VALVES - 2 INCH AND SMALLER: ALL BRONZE THREADED END.
CHECK VALVES - 2-1/2 INCH AND LARGER: IBBM, FLANGED.
ADJUST SYSTEMS COMPONENTS FOR PROPER PERFORMANCE
OPEN AND CLOSE VALVES, SET IN PROPER OPERATING POSITION.
SEAL CONTROL VALVES OPEN
SUPPLY TWO COPIES OF A WARRANTY COUNTERSIGNED AND GUARANTEED BY CONTRACTOR,
STATING THAT IMPERFECT SYSTEM OPERATION AND ALL DEFECTS IN LABOR AND MATERIALS
OF FIRE PROTECTION WORK WILL BE REPAIRED WITHOUT COST TO OWNER FOR A PERIOD
OF ONE YEAR FROM DATE OF SUBSTANTIAL COMPLETION, AND STATING THAT ALL FIRE
PROTECTION EQUIPMENT HAS BEEN FULLY SERVICED AND LEFT IN PROPER OPERATING
CONDITION.
ALSO GUARANTEE THAT SERVICING WILL BE PROVIDED WITHOUT COST DURING GUARANTEE
PERIOD.
PIPE SLEEVE INSTALLATION
PROVIDE FOR PIPING PASSING THROUGH WALLS, PARTITIONS AND SLAB, SLEEVES SIZED AT
LEAST 1 INCH LARGER THAN OD OF PIPE.
SLEEVES ARE REQUIRED FOR PIPING PASSING THROUGH FIRE-RATED WALLS CONSTRUCTED
OF METAL STUDS AND GYPSUM WALLBOARD.
TERMINATE SLEEVES THROUGH WALLS, PARTITIONS AND CEILINGS FLUSH WITH FINISHED
SURFACES: THROUGH SLABS 1/2" ABOVE FLOOR FINISH IN HABITABLE SPACES AND 2"
ABOVE ROUGH FINISH IN PIPE SPACES AND OTHER UNFINISHED AREAS.
SET SLEEVES IN PLACE BEFORE PLACING CONCRETE, OR SECURELY FASTEN AND GROUT IN
PLACE WITH CONCRETE. EXERCISE CARE IN LOCATING AND SETTING OF SLEEVES TO
ASSURE ACCURATE ALIGNMENT. IN ABSENCE OF SLEEVES, USE CORE DRILLED HOLES AND
PROVIDE CURBS TO PREVENT PASSAGE OF WATER.
FILL VOID SPACES BETWEEN PIPING AND PIPE SLEEVES WITH PENETRATION SEAL, OR
APPROVED ELASTROMERIC CAULKING MATERIALS.
ESCUTCHEON INSTALLATION
PROVIDE ESCUTCHEONS ON PIPE PROTRUSIONS AT WALLS, PARTITIONS, CEILING AND
FLOORS. ESCUTCHEONS SHALL FIT SNUGLY AROUND PIPING AND COVER SURFACE OPENING.
FIRE STOPPING
FILL VOID SPACE BETWEEN PIPING AND PIPING SLEEVES WITH DOW CORNING 3 - 6548
RTV SILICONE FOAM, OR WITH FIBROUS GLASS SEALED WITH FIRE TESTED AND APPROVED
ELASTOMERIC CAULKING MATERIALS.
ACCESSORIES
FLANGE DIMENSIONS, DRILLING AND FACING: ANSI B16.1
PIPE THREADS: ANSI B2.1
IDENTIFICATION OF PIPING SYSTEMS: ANSI A13.1
PIPE HANGERS AND SUPPORTS: MSS SP-58, NFPA 13, NON-METALLIC PIPE
FLANGE GASKETS: ANSI B16.21
WHERE PIPING IS TO BE RUN THROUGH EXPANSION JOINTS CONTRACTOR SHALL INSTALL
EXPANSION LOOPS AT THAT POINT.
PIPE HANGER COMPONENTS AND SUPPORT INSTALLATION (GENERAL)
TYPE OF HANGERS, HANGER COMPONENTS, SUPPORTS, SPACING AND INSTALLATION
METHODS SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF NFPA-13, CHAPTER
3-15.
PIPE SLEEVES
INSTALLATION
PIPE JOINTS
GENERAL: CUT PIPE ENDS SQUARE, REMOVE BURRS AND REAM TO ORIGINAL BORE. CLEAN
JOINT SURFACES PRIOR TO ASSEMBLY. WIPE OFF EXCESS JOINING COMPOUNDS.
SCREWED: USE AMERICAN STANDARD TAPER PIPE THREADS CUT SHARP AND TRUE, AND
SUITABLE FOR NORMAL ENGAGEMENT. SCREW THREADED ITEMS UP CLOSE TO SHOULDERS
WITH NOT MORE THAN THREE INCOMPLETE THREADS EXPOSED. DO NOT USE LAMP WICK,
CORD, WOOL, OR OTHER "WICKING" MATERIALS. REPAIR LEAKS WITH NEW MATERIALS, DO
NOT PREEN OF CAULK. "TEFLON" PIPE JOINT TAPE OR JOINT COMPOUNDS COMPOSED OF
RED LEAD AND GRAPHITE GROUND IN LINSEED OIL WILL BE PERMITTED, APPLIED TO MALE
THREADS.
FLANGED: USE FLANGES COMPATIBLE WITH SYSTEM MATERIALS. MATING FLANGES SHALL
HAVE SIMILAR FACINGS. ASSEMBLE JOINTS WITH GASKETS AND AMERICAN STANDARD
CARBON STEEL BOLTS AND HEX NUTS MADE-UP WITH TORQUE LIMITING WRENCH.
GROOVED PIPE COUPLINGS: USE MANUFACTURER'S MATERIAL AND METHODS.
PAINTING
N
PAINT FERROUS HANGER ROD AND PIPE HANGER COMPONENTS WITH ZINC CHROMATE
PRIMER, UNLESS FACTORY COATED.
VALVE SEALS
PROVIDE STURDY PADLOCKS, CHAIN AND OTHER SECURING DEVICES TO SEAL - OPEN ANY
NEW INDICATING VALVES 1-1/2" AND LARGER NOT EQUIPPED WITH VALVE SUPERVISORY
DEVICE.
PADLOCKS: CORROSION RESISTANT TUMBLER TYPE, BREAK RESISTANT, EXCEPT BY HEAVY
DUTY BOLT CUTTERS, KEYED ALIKE.
PROVIDE VALVES SMALLER THAN 1-1/2" WITH CORROSION RESISTANT TAMPER-PROOF
SEALS.
SPRINKLER INSTALLATION
INSPECTOR'S TEST CONNECTION: INSTALL AT END OF MOST REMOTE BRANCH LINE. PLACE
TEST VALVE IN ACCESSIBLE HEATED LOCATION, NOT OVER 7 FEET ABOVE FLOOR, AND PIPE
TO BUILDING EXTERIOR OR OTHER ACCESSIBLE DRAINAGE POINT. TERMINATE WITH 45
DEGREE ELBOW AND TEST PIPE OUTLET.
VALVE SUPERVISORY DEVICES: INSTALL ON ALL CONTROL VALVES.
DRAIN TERMINATIONS: PROVIDE GALVANIZED ESCUTCHEONS, 45 DEGREE ELBOW, AND PLAIN
END NIPPLE.
INSTALL SPRINKLER BENEATH DUCTS AND CEILING MOUNTED EQUIPMENT MORE THAN 4
FEET WIDE.
FLUSHING
FLUSH SPRINKLER PIPING BE HYDRAULIC METHOD. REMOVE PENDENT HEADS AFTER
FLUSHING, AND CLEAN.
TESTS
TEST ALL PIPING UNDER HYDROSTATIC PRESSURE OF 200 PSI FOR 2 HOURS. TEST
PRESSURE TO BE READ FROM A GAGE LOCATED AT THE LOWEST ELEVATION POINT OF THE
SYSTEM BEING TESTED. PERMISSIBLE LEAKAGE: NOT ALLOWED.
TEST WATER FLOW ALARM DEVICES UNDER OPERATING CONDITIONS.
CLOSE AND OPEN CONTROL VALVES UNDER SYSTEM WATER PRESSURE TO ENSURE PROPER
OPERATION.
INTERIOR PARTITIONS: #20 GAGE GALVANIZED STEEL, LOCK SEAM JOINT.
INTERIOR MASONRY WALL AND SLABS: SCHEDULE 40 GALVANIZED STEEL PIPE.
ESCUTCHEONS
PAINTED SURFACES: PRIME COATED SHEET STEEL. BEATON & CADWELL 13 OR 40.
DATE:06/26/2014
INTERMEDIATE
DRAIN AND TEST VALVES: ALL BRONZE THREADED AND GLOBE OR ANGLE VALVE.
15 CONNECTOR ROAD WESTBOROUGH, MA
WHITE
MR
YELLOW
CHECKED BY:
150°F (65°C)
TO FACILITATE ELECTRICAL CONNECTIONS EQUIP ELECTRICAL ITEMS WITH NEMA ENCLOSURES
HAVING ADEQUATE KNOCKOUTS, CONNECTORS, TERMINAL BLOCKS AND/OR CONTACTS.
PERMIT
155°F (68°C)
PROVIDE ALL ITEMS AND WORK CALLED FOR IN THIS DIVISION OF THE SPECIFICATIONS IN
ACCORDANCE WITH THE CONTRACT DOCUMENTS. THIS INCLUDES ALL INCIDENTALS,
EQUIPMENT, APPLIANCES, SERVICES, HOISTING, SCAFFOLDING, SUPPORTS, TOOLS,
SUPERVISION LABOR, CONSUMABLE ITEMS, FEES, LICENSES, ETC., NECESSARY TO PROVIDE
COMPLETE SYSTEMS. PERFORM START UP AND CHECK OUT EACH ITEM AND SYSTEM TO
PROVIDE FULLY OPERABLE SYSTEMS.
DRAWN BY:
175°F (79°C)
THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND SHOW THE GENERAL INTENT OF WORK. SEE DETAILS, RISERS,
AND SPECIFICATION FOR ADDITIONAL INFORMATION. THE CONTRACTOR IS RESPONSIBLE FOR A COMPLETE SYSTEM OR FULL
BUILDING COVERAGE. ADDITIONAL SPRINKLERS AND PIPING MAY BE REQUIRED TO ACCOMMODATE CONDITIONS SUCH AS
SOFFITS, DUCTWORK, STRUCTURE, LIGHTING, EQUIPMENT, BOOK STACKS, ETC. THE CONTRACTOR SHALL PROVIDE A COMPLETE
SPRINKLER INSTALLATION IN CONFORMANCE WITH- LATEST NFPA 13 FEDERAL AND STATE CODES AND THEIR APPLICABLE
SUPPLEMENTS, AND THE REQUIREMENTS OF THE OFFICE OF THE STATE FIRE MARSHAL.
A Limited Liability Company
1111 Main Street, East Hartford CT 06108
TEL: (860) 289−1100 FAX: (860) 289−3272 E−MAIL: info@rdaep.com
INTERMEDIATE
2.
RD
NONE
ISSUED FOR
RED
MM/DD/YY
100°F (38°C)
BY
135°F (57°C)
MECHANICAL GROOVED COUPLINGS: FM APPROVED, MALLEABLE OR DUCTILE IRON HOUSING,
RESILIENT ELASTMERIC GASKET, GROOVED PIPE CONFIGURATION.
DATE
155°F (68°C)
THESE GENERAL NOTES ARE APPLICABLE TO ALL FIRE PROTECTION DRAWINGS.
DESCRIPTION
ORDINARY
1.
NO.
NONE
GROOVED PIPE FITTINGS: FM APPROVED MALLEABLE/DUCTILE IRON
DATE:
ORANGE
POWER SUPPLY AND ALARM WIRING WILL BE PROVIDED UNDER DIVISION 16, AND
CONNECTIONS MADE TO ANY NEW WATER FLOW ALARM DEVICES, ALARM BELLS, VALVE
SUPERVISORY DEVICES, AND OTHER ELECTRICAL ITEMS.
FIRE PROTECTION
NOTES
100°F (38°C)
THESE SPECIFICATIONS CALL OUT CERTAIN DUTIES OF THE CONTRACTOR AND HIS
SUBCONTRACTOR. THEY ARE NOT INTENDED AS SUBCONTRACT DOCUMENTS, NOR ARE THEY
INTENDED AS A MATERIAL LIST OF ITEMS REQUIRED BY THE CONTRACT.
&
115°F (46°C)
FLANGE FITTINGS: CLASS 125, CAST IRON, ANSI B16.1, ASTM A126.
NOT FOR
CONSTRUCTION
135°F (57°C)
ELECTRICAL CONNECTIONS
HAMPTON: INN & SUITES
ORDINARY
FIRE PROTECTION GENERAL NOTES:
TECHNICAL REQUIREMENTS
13.183
MAX. RECOMMENDED
AMBIENT TEMP.b
FRAME
PAINT
COLOR
Rev.: 13.02
THIS DOCUMENT, THE IDEAS
AND DESIGNS INCORPORATED
THEREIN, AS AN INSTRUMENT OF
PROFESSIONAL SERVICES, IS THE
PROPERTY OF RUSSELL AND
DAWSON LLC, AND MAY NOT BE USED,
IN WHOLE OR IN PART, FOR ANY OTHER
PROJECT OR BY ANY OTHER PERSON
OR CORPORATION OTHER THAN THAT
NAMED HEREON WITHOUT THE
WRITTEN AUTHORIZATION OF RUSSELL
AND DAWSON LLC. ANY SUCH
UNAUTHORIZED USE WILL BE SOLELY
AT THE USER'S RISK AND RUSSELL
AND DAWSON LLC WILL BEAR NO
RESPONSIBILITY ARISING OUT OF
SUCH USE.
© 2013 by Russell and Dawson LLC
MAX. AMBIENT
a
TEMP. ALLOWED
d.
BULB
COLOR
REVISIONS
CEILING TEMPERATURE AT SPRINKLER
STAMP:
TEMP RATING
(FUSING POINT)
PROJECT:
NORMAL SPRINKLER
FILE NO:
SPRINKLER
TEMPERATURE
CLASSIFICATION
FIRE PROTECTION SPECIFICATIONS
FIRE PROTECTION GENERAL NOTES
SHEET TITLE:
SPRINKLER TEMPERATURE
CLASSIFICATION SCHEDULE
ACOUSTICAL SURFACES: FACTORY PAINTED TO MATCH SURFACE SHEET STEEL. BEATON &
CADWELL 13 OR 40.
PREFINISHED SURFACES: CHROME PLATED CAST BRASS.
BEATON & CADWELL 3S.
METAL FRAMING
MATERIAL: RUST RESISTANT, CONTINUOUS SLOT STEEL CHANNEL OR SLOTTED STEEL ANGLE,
WITH MATCHING FITTINGS ASSEMBLED WITH RUST RESISTANT HEX HEAD BOLTS AND NUTS.
DESIGN LOADING: AS RECOMMENDED BY MANUFACTURER.
PIPE, FITTINGS AND VALVES
FURNISH AND SET ALL SLEEVES FOR PASSAGE OF PIPES AND CONDUITS THROUGH
STRUCTURAL MASONRY AND CONCRETE WALL AND FLOORS, AND ELSEWHERE AS WILL BE
REQUIRED FOR THE PROTECTION OF EACH PIPE PASSING THROUGH BUILDING SURFACES.
PIPE: SCHEDULE 40 BLACK STEEL, ASTM A120 OR ASTM A3. CROSS MAIN AND BRANCH
LINE PIPING AT CEILINGS JOINED BY WELDING OR BE ROLL GROOVED PIPE COUPLING MAY
BE SCHEDULE 10 (LIGHT WALL) STEEL SPRINKLER PIPE, ASTM A135. SYSTEM RISERS AND
FEED MAINS MUST BE SCHEDULE 40 PIPE.
PROVIDE REQUIRED SUPPORTS AND HANGERS FOR PIPING, FIXTURES AND EQUIPMENT, SO
LOADING WILL NOT EXCEED ALLOWABLE LOADINGS OF STRUCTURE.
THREAD FITTINGS: 175 PSI WOG MALLEABLE IRON, ANSI B16.3 AND ASTM A47 OR CAST
IRON, ANSI B16.4 AND ASTM A126.
SHEET NUMBER:
FP-104
THE FIRE PROTECTION CONTRACTOR SHALL REVIEW THE ELECTRICAL DIVISION DRAWINGS AND COORDINATE THE FIRE PROTECTION
WORK WITH LOCATIONS OF LIGHTS, AND CEILING MOUNTED DEVICES WHICH MAY INTERFERE WITH SPRINKLER HEAD LOCATIONS OR
SPRAY PATTERNS.
7.
THE FIRE PROTECTION CONTRACTOR SHALL REVIEW THE HVAC DIVISION DRAWINGS AND COORDINATE THE FIRE PROTECTION WORK WITH
LOCATIONS OF CEILING MOUNTED DEVICES SUCH AS DIFFUSERS, GRILLES, AND REGISTERS, AND ALSO THE LOCATIONS OF HEAT
PRODUCING EQUIPMENT AND DUCTWORK REQUIRING SPRINKLER PROTECTION BELOW IT.
8.
THE FIRE PROTECTION CONTRACTOR SHALL PROVIDE PIPE EXPANSION JOINTS. ALL BUILDING EXPANSION JOINT LOCATIONS AND
EXPANSION LOOPS AT ALL BUILDING EXPANSION/SEISMIC JOINT LOCATIONS AS REQUIRED PER NFPA 13 AND BUILDING CODES. REVIEW
ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR EXACT LOCATIONS OF EXPANSION AND SEISMIC JOINTS. SEISMIC SEPARATION
ASSEMBLIES SHALL BE INSTALLED WHERE SPRINKLER PIPING, REGARDLESS OF SIZE, CROSSES BUILDING SEISMIC SEPARATION JOINTS
ABOVE GROUND LEVEL IN ACCORDANCE WITH NFPA 13.
9.
THIS PROJECT INVOLVES THE CONSTRUCTION OF A NEW BUILDING ON A N EXISTING BUILDING ON AN EXISTING SITE. BEFORE SUBMITTING
A BID, THE FIRE PROTECTION CONTRACTOR SHALL VISIT THE SITE AND BECOME THOROUGHLY FAMILIAR WITH ALL EXISTING FIRE
PROTECTION CONDITIONS AND THAT OF THE OTHER TRADES (STRUCTURAL, MECHANICAL, ELECTRICAL, PLUMBING, SITE, ETC.). THIS
CONTRACT INCLUDES ALL MODIFICATIONS OF EXISTING SYSTEMS REQUIRED FOR THE INSTALLATION OF THE NEW SYSTEM. THIS
CONTRACT INCLUDES ALL NECESSARY OFFSETS, TRANSITIONS, AND MODIFICATIONS REQUIRED TO INSTALL ALL NEW EQUIPMENT. ALL
NEW EQUIPMENT AND SYSTEMS SHALL BE FULLY OPERATIONAL UNDER THIS CONTRACT BEFORE THE JOB IS CONSIDERED COMPLETE. THE
FIRE PROTECTION CONTRACTOR SHALL BE HELD RESPONSIBLE FOR ANY ASSUMPTIONS, OMISSIONS, OR ERRORS MADE AS A RESULT OF
THE CONTRACTOR'S FAILURE TO BECOME FULLY FAMILIAR WITH THE EXISTING CONDITIONS AND THE CONTRACT DOCUMENTS OF ALL
TRADES.
5'-0"
LIMIT OF FIRE PROTECTION
CONTRACT
THE CONTRACTOR IS TO BE FULLY RESPONSIBLE FOR
CONTACTING THE LOCAL CABLE TELEVISION, POWER,
TELEPHONE, GAS, WATER, AND SEWER COMPANIES AND ANY
OTHER UTILITY COMPANIES WITHIN THE AREA PRIOR TO
PROCEEDING WITH ANY EXCAVATION. BY LAW, THE
CONTRACTOR IS REQUIRED TO CALL BEFORE DOING ANY
EXCAVATION, DIGGING HOLES, OR DRIVING POSTS
REGARDLESS OF WHETHER IT IS WITHIN THE STREET LINE OR
ON PRIVATE PROPERTY. CONTRACTOR CAN OBTAIN
INFORMATION REGARDING THE EXISTENCE AND LOCATION
OF ANY UNDERGROUND FACILITIES
4'-6"
MINIMUM COVER
UNION
FLEXIBLE
CONNECTION
THRUST
RODS
RISER
RISER CLAMP
45° ELBOW
SMOOTH BORE CORROSION
RESISTANT OUTLET GIVING
FLOW EQUIVALENT TO ONE
SPRINKLER HEAD. PROVIDE
WITH SPLASH BLOCK.
11
2" MINIMUM CLEARANCE,
CAULK WITH ELASTIC FILLER
PER SPECIFICATIONS.
STEEL WALL SLEEVE,
NEW FIRE PROTECTION SERVICE,
PROVIDED BY SITE UTILITIES CONTRACTOR.
REFER TO SITE PLAN FOR ADDITIONAL INFORMATION.
CONCRETE FLOOR SLAB
PROVIDE 2" MINIMUM
CLEARANCE, PER NFPA 13
NEW FIRE PROTECTION SERVICE, REFER TO SITE
AND FLOOR PLANS FOR ADDITIONAL INFORMATION.
(SEISMIC)
2
WET PIPE SYSTEM CONNECTION DETAIL
FP-105 SCALE=N.T.S.
FIRE PROTECTION SERVICE ENTRANCE INSTALLATION DETAIL
FP-105 SCALE=N.T.S.
10. THE INSTALLATION OF THE SPRINKLER SYSTEM SHALL BE BASED ON THE FOLLOWING:
LIGHT HAZARD: .10 GPM/SQ. FT. OVER 1,500 SQ. FT.
MAXIMUM COVERAGE: 225 SQ. FT. PER SPRINKLER
CONTRACTOR SHALL VERIFY REQUIREMENTS WITH OWNER'S INSURANCE UNDERWRITER.
12. THE FIRE PROTECTION CONTRACTOR SHALL PERFORM A FLOW TEST WITNESSED BY A REPRESENTATIVE OF THE OFFICE OF THE STATE
FIRE MARSHAL, OWNER, ARCHITECT, ENGINEER. DATA RECORDED AT THE TIME OF THIS FLOW TEST SHALL INCLUDE: DATE OF TEST, TIME
OF TEST, WITNESSED PRESENT. ALL PARTIES SHALL BE NOTIFIED OF THE DATE AND TIME OF THE TEST PRIOR TO FUTURE FLOW TESTS.
THE CONTRACTOR SHALL USE THE FLOW DATA FROM THIS TEST FOR HIS/HER HYDRAULIC CALCULATIONS. REFER TO SPECIFICATIONS FOR
ADDITIONAL REQUIREMENTS.
13. ALL PIPE SIZES SHOWN ON THE CONTRACT DOCUMENTS ARE ADEQUATELY SIZED FOR THE NEW SPRINKLER SYSTEM. THE PIPE SIZES
SHOWN ARE SUBJECT TO CHANGE UPON COMPLETION OF THE FIRE PROTECTION CONTRACTOR'S HYDRAULIC CALCULATIONS.
14. THE CONTRACTOR SHALL MAKE PROVISIONS FOR DRAINING THE ENTIRE SYSTEM PER NFPA 13 AND NFPA 14.
15. THE CONTRACTOR SHALL PROVIDE SPRINKLER LAYOUT SHOP DRAWING, SEISMIC BRACING CALCULATION AND HYDRAULIC CALCULATIONS,
SIGNED AND STAMPED BY A PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF THE PROJECT. THESE DRAWINGS AND
CALCULATIONS SHALL BE SUBMITTED AS DESCRIBED IN THE SPECIFICATIONS. THESE SHOP DRAWINGS AND CALCULATIONS SHALL BE
SUBMITTED TO AND APPROVED BY THE OFFICE OF THE STATE FIRE MARSHAL AND OWNER'S INSURANCE CARRIER PRIOR TO INSTALLATION.
THE CONTRACTOR SHALL PROVIDE COPIES OF THE STATE FIRE MARSHAL'S AND OWNER'S INSURANCE CARRIER'S APPROVALS WITH THEIR
SHOP DRAWING SUBMITTAL.
METAL SLEEVE
FIRE DEPARTMENT CONNECTION NOTES:
NOTE:
FILL COMPLETE SPACE BETWEEN PIPE
AND PIPE SLEEVE WITH(FIREPROOF)
APPROVED TYPE MATERIAL
1. FIRE PROTECTION CONTRACTOR SHALL COORDINATE
MOUNTING HEIGHT AND LOCATION OF THE FDC WITH THE
LOCAL FIRE DEPARTMENT'S REQUIREMENTS.
2. THE FIRE PROTECTION CONTRACTOR SHALL COORDINATE
THE CONNECTION THREAD TYPE WITH THE LOCAL FIRE
DEPARTMENT FOR COMPATIBILITY.
(2) 2 1/2" FIRE
DEPT. CONN.'S
3. THE FDC SHALL BE POLISHED CHROME PLATED WITH THE
FOLLOWING LETTERING: "AUTO SPKR".
SET SCREW
4. THE FIRE PROTECTION CONTRACTOR SHALL VERIFY WITH THE
LOCAL FIRE DEPARTMENT THE PREFERRED TYPE OF FDC TO
BE PROVIDED (FLUSH WALL OR EXPOSED WALL MOUNTED)
PRIOR TO INSTALLATION.
CENTER PIPE
IN SLEEVE
CAST IRON
ESCUTCHEON
PLATE W/SET
SCREW
4" CONNECTION
METAL
ESCUTCHEON
PLATE W/SET
SCREW
FINISHED GRADE
17. SPRINKLERS SHALL BE LOCATED IN THE CENTER OF TILES IN ROOMS WITH EITHER AN EXISTING OR NEW 2x4 OR 2x4 CEILING GRID.
18. UNOCCUPIED SPACES FITTED WITHOUT REFLECTED CEILINGS SHALL BE PROVIDED WITH PENDENT SPRINKLERS WITH WATER SHIELD PER
THE APPROVAL OF THE OFFICE OF THE STATE FIRE MARSHAL.
4
5
TYPICAL FIRE DEPARTMENT CONNECTION DETAIL
FP-105 SCALE=N.T.S.
19. SPRINKLERS SHALL BE INSTALLED UNDER FIXED OBSTRUCTIONS OVER 4 FT. (1.2M) WIDE PER NFPA 13, EDITION SECTION 5-5.5.3.1. THE
CONTRACTOR SHALL VERIFY ALL DUCTWORK DIMENSIONS IN THE FIELD AND INSTALL SPRINKLERS AS REQUIRED.
TYPICAL RISER ANCHOR DETAIL
FP-105 SCALE=N.T.S.
c
18" MINIMUM
42" MAXIMUM
16. THE FIRE PROTECTION CONTRACTOR SHALL COORDINATE ALL SPRINKLER WORK WITH NEW LIGHTING FIXTURES, DIFFUSERS, AND
DUCTWORK. THE CONTRACTOR SHALL PROVIDE PROPER SPRINKLER COVERAGE PER NFPA 13.
3
EXISTING EXTERIOR WALL
"LINK SEAL" TYPE
WATER PROOF UNIT
(OR APPROVED EQUAL)
SET SCREW
AUTO SPKR
NOT FOR
CONSTRUCTION
11. THE INSTALLATION OF THE SPRINKLER SYSTEM FOR MECHANICAL ROOMS, STORAGE ROOMS, AND OTHER ROOMS AS NOTED ON THE
DRAWINGS SHALL BE BASED ON THE FOLLOWING:
ORDINARY HAZARD: .20 GPM/SQ. FT. OVER 2,000 SQ. FT.
MAXIMUM COVERAGE: 225 SQ. FT. PER SPRINKLER
CONTRACTOR SHALL VERIFY REQUIREMENTS WITH OWNER'S INSURANCE UNDERWRITER.
A Limited Liability Company
1111 Main Street, East Hartford CT 06108
TEL: (860) 289−1100 FAX: (860) 289−3272 E−MAIL: info@rdaep.com
RD
WARNING: UNDERGROUND UTILITIES
COAT EXTERIOR SURFACES
WITH TAR COMPOUND
ALL AROUND
DATE:06/26/2014
6.
FINISHED GRADE
PERMIT
THE FIRE PROTECTION CONTRACTOR SHALL REVIEW THE ARCHITECTURAL REFLECTED CEILING, ELEVATION AND SECTION PLANS AS PART
OF THIS CONTRACT FOR ADDITIONAL INFORMATION SUCH AS CEILING HEIGHTS, TYPES, SOFFITS AND/OR OTHER DEVICE LOCATIONS.
PLAN VIEW
TEST VALVE IN READILY
ACCESSIBLE LOCATION
ISSUED FOR
5.
8"
FIRST FLOOR
BY
SPRINKLERS IN FINISHED CEILING AREAS SHALL ALWAYS BE LOCATED IN THE CENTER OF CEILING TILES UNLESS OTHERWISE INDICATED.
CEILING
DATE
4.
EXTERIOR WALL
DESCRIPTION
THE DRAWINGS INDICATE A SUGGESTED SPRINKLER HEAD LAYOUT AND THAT EACH ARE IS COVERED BY SPRINKLER PROTECTION AS
REQUIRED BY CODE. THE SPRINKLER QUANTITIES SHALL NOT BE COUNTED, AS A TAKE OFF OR AS EXACT LOCATIONS. REFER TO NFPA 13
FOR EXACT SPACING, DENSITY, AND LOCATION REQUIREMENTS. CONTRACTOR SHALL INSTALL QUICK RESPONSE TYPE SPRINKLERS IN THE
ENTIRE BUILDING. USE OF EXTENDED COVERAGE, QUICK RESPONSE TYPE SPRINKLERS MAY BE USED WITH THE APPROVAL OF THE OFFICE
OF THE STATE FIRE MARSHAL. CONTRACT DOCUMENTS SHOW STANDARD COVERAGE SPRINKLERS WITH STANDARD SPACING BETWEEN
SPRINKLERS PER NFPA 13. USE OF EXTENDED COVERAGE TYPE MAY REDUCE THE NUMBER OF SPRINKLERS ON THE PROJECT.
NEW FIRE PROTECTION
SERVICE, REFER TO PLANS
FOR SIZE.
NO.
3.
PITCH
TO BRANCH
PIPING
&
THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND SHOW THE GENERAL INTENT OF WORK. SEE DETAILS, RISERS AND SPECIFICATIONS
FOR ADDITIONAL INFORMATION. THE CONTRACTOR IS RESPONSIBLE FOR A COMPLETE SYSTEM FOR FULL BUILDING COVERAGE.
ADDITIONAL SPRINKLERS AND PIPING MAY BE REQUIRED TO ACCOMMODATE CONDITIONS SUCH AS SOFFITS, DUCTWORK, STRUCTURE,
LIGHTING, EQUIPMENT, BOOK STACKS, ETC. THE CONTRACTOR SHALL PROVIDE A COMPLETE SPRINKLER INSTALLATION IN CONFORMANCE
WITH NFPA 13 - 1999 EDITION, NFPA 13R - 1999 EDITION, NFPA 14 - 1999 EDITION, FEDERAL AND STATE CODES AND THEIR APPLICABLE
SUPPLEMENTS, AND THE REQUIREMENTS OF THE OFFICE OF THE STATE FIRE MARSHAL.
Rev.: 13.02
THIS DOCUMENT, THE IDEAS
AND DESIGNS INCORPORATED
THEREIN, AS AN INSTRUMENT OF
PROFESSIONAL SERVICES, IS THE
PROPERTY OF RUSSELL AND
DAWSON LLC, AND MAY NOT BE USED,
IN WHOLE OR IN PART, FOR ANY OTHER
PROJECT OR BY ANY OTHER PERSON
OR CORPORATION OTHER THAN THAT
NAMED HEREON WITHOUT THE
WRITTEN AUTHORIZATION OF RUSSELL
AND DAWSON LLC. ANY SUCH
UNAUTHORIZED USE WILL BE SOLELY
AT THE USER'S RISK AND RUSSELL
AND DAWSON LLC WILL BEAR NO
RESPONSIBILITY ARISING OUT OF
SUCH USE.
© 2013 by Russell and Dawson LLC
2.
2'-0"
REVISIONS
THESE GENERAL NOTES ARE APPLICABLE TO ALL FIRE PROTECTION DRAWINGS.
STAMP:
1.
RUSSELL AND DAWSON
ARCHITECTURE &
ENGINEERING
FIRE PROTECTION GENERAL NOTES
WATERTIGHT SLEEVES THRU CONCRETE FOUNDATION WALLS
FP-105 SCALE=N.T.S.
N
20. VERIFY DISTANCE BETWEEN CEILING AND BOTTOM OF STRUCTURAL BEAMS IN ALL AREAS WITH REFLECTED CEILINGS.
HAMPTON: INN & SUITES
22. ALL SPRINKLER PIPING SHOWN SHALL BE RUN ABOVE LIGHTING FIXTURES SHOWN ON THE LIGHTING DRAWINGS. COORDINATE THE
ROUTING OF SPRINKLER PIPING WITH OTHER TRADES IN THE FIELD. COORDINATE SPRINKLERS AND ASSOCIATED PIPING WITH THE
ARCHITECTURAL CEILING/SOFFIT CONFIGURATION AND STRUCTURAL DRAWINGS.
TEST AND DRAIN VALVE GENERAL NOTES:
1. TEST AND DRAIN INLET/OUTLET SHALL BE SIZED
AS FOLLOWS:
RISER OR MAIN SIZE
DRAIN SIZE
UP TO 2"
3/4" OR LARGER
2-1/2" TO 3-1/2" 1-1/4" OR LARGER
4" AND LARGER
2" ONLY
OFF
DRAIN
OUT
PUSH
YELLOW: FIRE PROTECTION
TEST AN DRAIN
FLOW
26. FLOW AND TAMPER SWITCHES SHALL BE PROVIDED BY THE FIRE PROTECTION CONTRACTOR; ALL WIRING SHALL BE PROVIDED BY DIVISION
16. ALL WORK SHALL BE COORDINATED BETWEEN THE TWO TRADES IN THE FIELD.
27. FLOW DATA PROVIDED BY THE WATER REGIONAL WATER AUTHORITY, FROM FLOW TEST PERFORMED ON 00/00/00, AT (INSERT ADDRESS),
IS AS FOLLOWS:
2. TEST AND DRAIN VALVE SHALL BE AS FOLLOWS:
TESTANDRAIN
VERIFY VALVE IDENTIFICATION REQUIREMENTS WITH OWNER'S STANDARDS IN THE FIELD.
AGF MODEL 2"1011T OR ENGINEERED APPROVED
EQUAL.
MODEL SHALL BE SUPPLIED WITH COMMERCIAL
TRIM WITH RELIEF VALVE AND MEET ALL
REQUIREMENTS OF NFPA 13.
EXTERIOR WALL
FLANGE
3. PREPACKAGE SYSTEM CONSISTING OF A FLOW
SWITCH, PRESSURE GAUGE, AND TEST AND DRAIN
VALVE SHALL BE AS FOLLOWS:
MODEL SHALL BE SUPPLIED WITH COMMERCIAL
TRIM WITH RELIEF VALVE AND MEET ALL
REQUIREMENTS OF NFPA 13.
6
TEST AND DRAIN ASSEMBLY INSTALLATION DETAIL
1/8"
MIN.
14" DIA.
FP-105 SCALE = N.T.S.
36" AFF.
MIN.
COMBINED FLOW:
AVAILABLE FLOW:
TABLE 1
NOTES:
28. STANDPIPE SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 14. THE STANDPIPE SYSTEM SHALL BE HYDRAULICALLY DESIGNED
TO PROVIDE THE REQUIRED WATERFLOW RATE AT A MINIMUM RESIDUAL PRESSURE OF 100 PSI AT THE OUTLET OF THE HYDRAULICALLY
MOST REMOTE 2 1/2" HOSE CONNECTION AND 65 PSI AT THE OUTLET OF THE HYDRAULICALLY MOST REMOTE 1 1/2" HOSE STATION.
18-1/2"
SLEEVE
SET SCREW
PIV
4. POST (WALL) INDICATING VALVES SHALL
BE PROPERLY PROTECTED AGAINST
DAMAGE WHERE NEEDED.
COUPLING
LOWER STEM
(SQUARE TUBE)
UPPER
STEM
(SQUARE TUBE)
5. POST (WALL) INDICATING VALVES SHALL
BE LOCATED OPEN WITH CHAIN AND
PADLOCK TO PREVENT TAMPERING.
OPTIONAL PIPE
SLEEVE 5" SCH.
10 15-3/4"
PLAN VIEW
FLOW
PIPE SLEEVE
DIMENSIONS IN INCHES
VALVE SIZE
A
B
TURNS TO OPEN
4
13.00
11.44
14-1/2
6
16.12
14.38
20-1/2
8
20.12
18.38
27
10
24.50
22.38
33-1/2
12
27.88
25.38
39-1/2
14
32.12
29.62
46
DIMENSIONS A & B FOR MUELLER IBBM DOUBLE
DISC POST INDICATOR VALVES
3. WALL INDICATING VALVES SHALL BE
LOCATIONS BY BLANK WALLS WHERE
THE POSSIBILITY OF INJURY BY FALLING
WALLS ARE UNLIKELY.
COTTER
PIN
3/4" BOLT HOLES
ON 10-1/2" DIA.
BOLT CIRCLE.
1. ALL PIPING SHALL BE RESTRAINED
WITH RODDING OR RETAINING GLANDS
AS REQUIRED PER NFPA 24.
2. POST INDICATING VALVE SHALL BE
INSTALLED AT EACH FIRE MAIN INTO
BUILDING AT A MINIMUM OF 40'-0"
FROM THE BUILDING. WHEN THE PIV
CANNOT BE PLACED AT THIS DISTANCE,
THEY ARE PERMITTED TO BE LOCATED
CLOSER OR WALL INDICATOR VALVES
SHALL BE USED.
OPEN
14" DIA.
32. UPRIGHT OR PENDENT TYPE SPRINKLERS SHALL BE INSTALLED AT THE TOP OF THE ELEVATOR HOISTWAY. SPRINKLERS ARE NOT
REQUIRED AT THE TOPS OF NONCOMBUSTIBULE HOISTWAYS OF PASSENGER ELEVATORS WITH CAR ENCLOSURE MATERIALS THAT MEET
THE REQUIREMENTS OF ASME A17.1, SAFETY CODE FOR ELEVATORS AND ESCALATORS.
33. THE FIRE PROTECTION DESIGN IS BASED ON MANUFACTURERS AND MODEL NUMBERS LISTED HEREIN. THE FIRE PROTECTION
CONTRACTOR MAY AT HIS/HER DISCRETION CHOOSE ANOTHER OF THE APPROVED EQUALS LISTED IN THE APPROPRIATE SPECIFICATIONS
SECTIONS AND CONTRACT DOCUMENTS. HOWEVER, BY DOING SO, THE FIRE PROTECTION CONTRACTOR ALSO UNDERTAKES THE
RESPONSIBILITY OF COORDINATION WITH EXISTING CONDITIONS, NOTIFICATION OF OTHER TRADES AND ADDITIONAL COST INCURRED BY
OTHER TRADES REQUIRED AS A RESULT OF THE SUBSTITUTION.
'B'
12" DIA.
FLANGE
a, THE ROOM DEDICATED TO ELECTRICAL EQUIPMENT "ONLY".
b. "ONLY" DRY TYPE ELECTRICAL EQUIPMENT IS USED.
c. ELECTRICAL EQUIPMENT IS INSTALLED IN A 2 HOUR, FIRE RATED, ENCLOSURE INCLUDING PROTECTION
OF PENETRATIONS.
d. "NO" COMBUSTILE STORAGE IS PERMITTED TO BE STORED IN THE ROOM.
31. AUTOMATIC SPRINKLERS IN ELEVATOR MACHINE ROOMS AND AT TOPS OF HOISTWAYS SHALL BE OF ORDINARY OR INTERMEDIATE
TEMPERATURE RATINGS.
FLOW
11/16"
29. SPRINKLER PROTECTION SHALL BE REQUIRED IN ALL ELECTRICAL EQUIPMENT, COMMUNICATION ROOMS, ETC. SPRINKLER HOODS OR
SHIELDS SHALL BE INSTALLED TO PROTECT IMPORTANT ELECTRICAL EQUIPMENT FROM SPRINKLER DISCHARGE. HOODS/SHIELDS SHALL
BE NONCOMBUSTILE MATERIAL. SPRINKLERS SHALL NOT BE REQUIRED WHERE "ALL" THE FOLLOWING CONDITIONS ARE MET:
30. SIDEWALL SPRINKLER SHALL BE INSTALLED AT THE BOTTOM OF EACH ELEVATOR HOISTWAY NOT MORE THAN 2 FEET ABOVE THE FLOOR
OF THE PIT. FOR ENCLOSED, NONCOMBUSTIBULE ELEVATOR SHAFTS THAT DO NOT CONTAIN COMBUSTIBULE HYDRAULIC FLUIDS, THE
SPRINKLER AT THE BOTTOM OF THE SHAFT SHALL NOT BE REQUIRED.
'A'
3-1/2"
FIELD CUT
EXCEPTION NO. 1: WHERE THE AUTHORITY HAVING JURISDICTION (AHJ) PERMITS LOWER THAN 100 PSI FOR A 2 1/2" HOSE CONNECTION.
BASED ON SUPPRESSION TACTICS. THE PRESSURE PERMITTED TO BE REDUCED TO NOT LESS THAN 65 PSI.
EXCEPTION NO. 2: IN OTHER THAN HIGH RISE BUILDINGS, THE AUTHORITY HAVING JURISDICTION (AHJ) SHALL BE ALLOWED TO REDUCE THE
MINIMUM PRESSURE REQUIREMENTS IF THE BUILDING IS PROTECTED THROUGHOUT BY AN APPROVED AUTOMATIC SPRINKLER SYSTEM.
28" MAX.
3" MIN.
TABLE 2
TYPICAL WALL TYPE POST INDIACTING VALVE INSTALLATION KIT DETAIL HORIZONTAL
FP-105 SCALE=N.T.S.
20"
5-1/4"
MIN.
FINISHED GRADE
3'-6"
MIN.
ADJUSTABLE UPPER
AND LOWER BARREL
MECHANICAL JOINT TAPPING
VALVE WITH FLANGE FOR
CONNECTION TO POST
INDICATING VALVE BARREL
1'-0"
DIMENSIONS IN INCHES
VALVE SIZE
A
B
TURNS TO OPEN
4
14.31
12.72
14-1/2
6
18.12
16.53
20-1/2
8
21.25
19.66
27
10
26.38
24.79
33-1/2
12
29.50
27.91
39-1/2
DIMENSIONS A & B FOR MUELLER IBBM DOUBLE
DISC POST INDICATOR VALVES
7
(4) 3/4"HOLES
FOR 5/8"FASTENERS
8
NEW FIRE SERVICE,
BURIED, SEE FLOOR
PLANS FOR ADDITIONAL
INFORMATION.
SAND BEDDING,
REFER TO SPECIFICATION.
PLAN VIEW
TYPICAL WALL TYPE POST INDICATING VALVE INSTALLATION KIT DETAIL VERTICAL
FP-105 SCALE = N.T.S.
DATE:
STATIC: -- PSI
RESIDUAL: --PSI
OUTLET SIZE:
PITOT PRESSURE:
HYDRANT FLOW:
HANDWHEEL
FIRE PROTECTION
NOTES & DETAILS
AGF MODEL 8011 OR ENGINEERED APPROVED
EQUAL.
POST HEAD
13.183
FLOW DATA PROVIDED BY THE REGIONAL WATER AUTHORITY, FROM FLOW TEST PERFORMED ON 00/00/00, AT (INSERT ADDRESS), IS AS
FOLLOWS:
ANGLE WALL POST
KIT, REFER TO
MANUFACTURER'S
REQUIREMENTS.
LOCKING STRAPE
FILE NO:
OUT
TEST AND DRAIN VALVE
SHEET TITLE:
STATIC: --PSI
RESIDUAL: --PSI
FLOW: ---- GPM @ 20 PSI
PROJECT:
IN
MR
TEST
25. ALL FIRE PROTECTION VALVES INSTALLED ABOVE CEILINGS SHALL BE PROVIDED WITH ACCESS PANELS (WHERE APPLICABLE) AND 1/2" DIA.
"DOT" VALVE INDICATORS WHERE VALVES ARE LOCATED. COLORS ARE AS FOLLOWS:
CHECKED BY:
IN
DRAWN BY:
24. ALL PIPE HANGERS AND SUPPORTS SHALL BE PROVIDED WITH SEISMIC RESTRAINT BRACING PER NFPA 13, STATE AND LOCAL
REQUIREMENTS.
MM/DD/YY
23. PROVIDE U.L. LISTED SWING JOINT ASSEMBLIES ("METRAFLEX" FIRELOOP, OR EQUAL) WHERE SPRINKLER PIPING CROSSES BUILDING
EXPANSION JOINTS.
15 CONNECTOR ROAD WESTBOROUGH, MA
21. ALL PIPING SHOWN SHALL BE LOCATED ABOVE CEILING OR IN SOFFIT SPACES UNLESS NOTED OTHERWISE OR IF THE ROOM HAS NO
CEILING.
SHEET NUMBER:
FP-105
FLOW SWITCH
FHV
PRESSURE GAUGE
&
1" DROP NIPPLE
WATER FLOW SWITCH
WITH SUPERVISORY
SWITCH
1"x1/2" REDUCER
54"
CEILING
2"
FLOW
TO SYSTEM
FLOW
TO SYSTEM
INLET NIPPLE
SUPPORT ANCHOR
(TYPICAL)
(NEW CONSTRUCTION ONLY)
CROSSMAIN
THREAD-O-LET
NOTES:
IN
TEST
FP-106 SCALE=N.T.S.
SELF CONTAINED, ALARM
TEST AND DRAIN ASSEMBLY,
SEE NOTE #2.
GALVANIZED SLEEVE AND
FIRE STOPPING (TYPICAL)
3
FIRE PROTECTION SYSTEM FIRE DEPARTMENT
STAND PIPE CONNECTION DETAIL
4
FP-106 SCALE=N.T.S.
1.
INSTALLATION SHALL BE IN ACCORDANCE WITH NFPA
13, LATEST EDITION, STATE AND LOCAL CODE
REQUIREMENTS AND ORDINANCES.
2.
ALARM TEST ASSEMBLY; AGF INDUSTRIES MODEL
2"1011T OR ENGINEERED APPROVED EQUAL. MOUNT
TEST MODULE APPROXIMATELY 7'-0" A.F.F. MAXIMUM.
FLOW
TO DRAIN
OUT
PUSH
PITCH @1/8" PER FOOT
TO FLOOR DRAIN, MOP SINK,
OR EXTERIOR OF BUILDING.
TEST AND DRAIN
FP-106 SCALE=N.T.S.
CONCEALED SPRINKLER HEAD DETAIL
OFF
2
FLOOR CONTROL VALVE TEST AND DRAIN PIPING DETAIL
DRAIN
1
FINISHED FLOOR
OUTLET NIPPLE
FIRE PROTECTION SYSTEM ZONE CONTROL VALVE AND TEST DRAIN PIPING DETAIL
FP-106 SCALE=N.T.S.
DESCRIPTION
CONCEALED SPRINKLER
HEAD
UNION WITH CORROSION RESISTANT
ORIFICE GIVING FLOW EQUAL TO THE
SMALLEST SPRINKLER ORIFICE IN THE
SYSTEM.
STANDPIPE FIRE RISER,
REFER TO RISER FOR
SIZE.
REVISIONS
SECTIONAL DRAIN VALVE
Rev.: 13.02
THIS DOCUMENT, THE IDEAS
AND DESIGNS INCORPORATED
THEREIN, AS AN INSTRUMENT OF
PROFESSIONAL SERVICES, IS THE
PROPERTY OF RUSSELL AND
DAWSON LLC, AND MAY NOT BE USED,
IN WHOLE OR IN PART, FOR ANY OTHER
PROJECT OR BY ANY OTHER PERSON
OR CORPORATION OTHER THAN THAT
NAMED HEREON WITHOUT THE
WRITTEN AUTHORIZATION OF RUSSELL
AND DAWSON LLC. ANY SUCH
UNAUTHORIZED USE WILL BE SOLELY
AT THE USER'S RISK AND RUSSELL
AND DAWSON LLC WILL BEAR NO
RESPONSIBILITY ARISING OUT OF
SUCH USE.
© 2013 by Russell and Dawson LLC
FLOOR CONTROL VALVE
WITH SUPERVISORY SWITCH
2 1/2"
RISER
BY
TEST VALVE
DATE
SIGHT GLASS
TO DRAIN, SEE PLANS
FOR ROUTING.
RD
TO FIRE ALARM SYSTEM
(ALARM SYSTEM) BY
ELECTRICAL CONTRACTOR.
FIRE DEPARTMENT CONNECTION:
2 1/2"x2 1/2" U.L./FM RATED
FIRE HOSE VALVE WITH 2 1/2"x1 1/2" REDUCER, CAP AND CHAIN.
FIRE HOSE VALVE SHALL BE
COMPATIBLE WITH LOCAL FIRE
DEPARTMENT STANDARDS, (TYPICAL).
A Limited Liability Company
1111 Main Street, East Hartford CT 06108
TEL: (860) 289−1100 FAX: (860) 289−3272 E−MAIL: info@rdaep.com
TO FIRE ALARM SYSTEM
(TROUBLE SYSTEM) BY
ELECTRICAL CONTRACTOR.
SPRINKLER BRANCH
PIPING
PRESSURE GAUGE
TS
RUSSELL AND DAWSON
ARCHITECTURE &
ENGINEERING
INDICATING TYPE FLOOR CONTROL
VALVE WITH SUPERVISORY SWITCH
NO.
TO FIRE ALARM SYSTEM (TROUBLE SYSTEM)
BY ELECTRICAL CONTRACTOR
FLOOR CONTROL VALVE
WITH SUPERVISORY SWITCH
WATER FLOW SWITCH
2 ELLS
PRESSURE GAUGE
AREA OF BEARING FACE OF CONCRETE THRUST BLOCKS
1" INLET NIPPLE
8"
FLOOR CONTROL VALVE
WITH SUPERVISORY SWITCH
4"
4"
AREAS IN TABLE HAVE BEEN DERIVED USING A WATER
PRESSURE OF 225 POUNDS PER SQUARE INCH AND A SOIL
RESISTANCE OF 2000 POUNDS PER SQUARE FOOT.
8"
8"
NORMAL
POSITION
2 ELLS &
NIPPLE "E"
NORMAL
POSITION
4"
MULTIPY BEARING AREAS FOR DIFFERENT SOILS BY THE FOLLOWING
FACTORS:
PLAN
LONGITIDINAL MOVEMENT
SAND AND GRAVEL, CEMENTEAD WITH CLAY:
SAND AND GRAVEL:
SAND:
SOFT CLAY:
SHALE:
WATER FLOW SWITCH
INSPECTOR'S TEST
S
FINISH CEILING
(TOP LEVEL)
FINISH FLOOR
(TOP LEVEL)
SMOKE DETECTOR FOR ELEVATOR
RECALL CONTROLS BY ELECTRICAL
CONTRACTOR (TYP.)
PITCH @ 1/8" PER FOOT
TO DRAIN RISER
ELL
STAIR
ST2
2 1/2" FIRE DEPARTMENT HOSE VALVE
WITH 2 1/2" x 1 1/2" REDUCER. SEE NOTE #3.
ELL
FLOW
2
5
COMBINATION
FSP/SPKR. RISER
LATERAL MOVEMENT
ELL
6
HORIZONTAL VIEWS
TO SPRINKLER
SYSTEM
7
SEISMIC INSTALLATION DETAIL SEISMIC SEPERATION ASSEMBLY
FP-106 SCALE = N.T.S.
CROSSMAIN
6
6
8
FLOW
F
T
SPRINKLER MAIN SUPPLY
SPRINKLER BRANCH FOR
MACHINE ROOM
SPILL TO DRAIN
FINISH CEILING
(LOWER LEVEL)
SPRINKLER BRANCH
RUN WITHIN WALL
2" x 4" POCKET IN FOUNDATION
WALL FOR BRANCH PIPING
ELEVATOR PIT
SELF CONTAINED ALARM TEST AND
DRAIN ASSEMBLY, NOTE #2
5
ELEVATOR HOIST WAY SPRINKLER DETAIL
ADJUSTABLE FOG NOZZLE
2" TEST AND DRAIN RISER
FLOW
FLOW
1" OUTLET NIPPLE
6
6
TO FIRE ALARM SYSTEM
(TROUBLE SYSTEM) BY
ELECTRICAL CONTRACTOR
HOSE RACK
1OO'-O" OF 1 1/2" HOSEUNLESS OTHERWISE
INDICATED
FLOW
FLOW
2 1/2" FIRE DEPARTMENT HOSE
VALVE WITH 2 1/2" x 1 1/2"
REDUCER. SEE NOTE #3.
STAIR
ST2
STANDPIPE SHUTOFF VALVE WITH SUPERVISORY
SWITCH. PROVIDE ACCESS DOOR TO MATCH FIRE RATING
OF WALL OR CEILING AS REQUIRED. REFER
TO FLOOR PLANS FOR EXACT VALVE LOCATION.
NOTES:
1. INSTALLATION SHALL BE IN ACCORDANCE WITH NFPA 13, AND 14, LATEST EDITION,
STATE AND LOCAL CODE REQUIREMENTS AND ORDINANCES.
2. ALARM TEST ASSEMBLY: AGF INDUSTRIES MODEL 1" 1011T OR ENGINEERED APPROVED
EQUAL. MOUNT TEST MODULE APPROXIMATELY 7'-0" A.F.F. MAXIMUM.
3. HOSE CONNECTION AND HOSE STATIONS SHALL BE UNOBSTRUCTED AND SHALL BE
LOCATED NOT LESS THAN 3 FEET OR MORE THAN 5 FEET ABOVE FINISHED FLOOR.
CONCRETE SPLASH BLOCK
SEE FLOOR PLAN FOR SIZE
6"
PITCH @ 1/8" PER FOOT
TO DRAIN RISER
ITEM
No.
1
Name
NOTES
O.S.&Y. GATE
VALVE WITH
TAMPER SWITCH
FIRST FLOOR
COORDINATE LOCATION OF
SPRINKLER HEAD AND PIPING
WITH ELEVATOR TOE GUARD
2" DRAIN TO GRADE, THE DRAIN CONNECTION SHALL BE CAPABLE OF ACCEPTING FULL FLOW UNDER
SYSTEM PRESSURE, OR TO ANOTHER LOCATION WHERE WATER DAMAGE WILL NOT RESULT.
2" DRAIN PIPING THROUGH WALL, TERMINATE WITH
45° ELBOW TO 6" ABOVE GRADE WITH SPLASH BLOCK.
REFER TO PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION.
CABINET
2 1/2" x 8" NIPPLE
2 HR. RATED WALL
2
PRESSURE GAUGE
WITH SHUTOFF COCK
3
NOT USED
4
FEED MAIN
5
WATERFLOW INDICATOR
6
FIRE PROTECTION SYSTEM RISER IN STAIR
WITH CONTROL VALVE AND TEST DRAINPIPING DETAIL
FP-106 SCALE=N.T.S.
175, 250, 350 &
500 P.S.I. W.W.P.
RATED VALVES, VALVE
LOCATION AS PER
SPRINKLER RISER
DIAGRAM.
ITEM
No.
Name
NOTES
6
PIPE CLAMP
7
GLOBE VALVE (DRAIN)
8
GLOBE VALVE (TEST)
9
TESTMASTER SIZE AS PER NFPA#13;
WITH 1/2" TEST ORIFICE PLATE
10
SIGHT GLASS
11
CHECK VALVE (DRAIN-TEST)
F.S.P. RISER
8"
SIDEWALL SPRINKLER HEAD ORDINARY
TEMPERATURE INSTALL 24" ABOVE THE
FLOOR OF THE ELEVATOR PIT
FP-106 SCALE=N.T.S.
6
2 1/2"
CROSSMAIN
10
2 1/2" X 1 1/2" REDUCER FITTING
FLOW
1" INLET NIPPLE
SHORT CLIP HANGER
1" x 1/2" REDUCING ELBOW
2 1/2" HOSE VALVE W/PRV
COMBINATION STANDPIPE/
SPRINKLER RISER (SIZE
PER HYDRAULIC CALCULATIONS)
FLOW
WATER FLOW SWITCH
2x4 STUD WALL
OFFSET IN POCKET
FIRE PROTECTION RISER
SEE DWG. FOR SIZE
10
FLOOR CONTROL VALVE
WITH SUPERVISORY SWITCH
FLOW
S
SECOND FLOOR
TO FIRE ALARM SYSTEM
(TROUBLE SYSTEM) BY
ELECTRICAL CONTRACTOR
INSPECTOR'S TEST
H
8"
9
13.183
ELEVATOR
HOISTWAY
OUT
1
PITCH @ 1/8" PER FOOT TO DRAIN RISER
2 1/2" FIRE DEPARTMENT HOSE VALVE
WITH 2 1/2" x 1 1/2" REDUCER. SEE NOTE #3.
IN
TEST
STAIR
ST2
1" OUTLET NIPPLE
DRAIN
7
FLOW SWITCH
BUTTERFLY CONTROL VALVE
WITH TAMPER SWITCH
4
DRAIN RISER
2" TEST AND DRAIN RISER
1" INLET NIPPLE
SELF CONTAINED ALARM TEST
AND DRAIN ASSEMBLY, NOTE #2
8"
4"
ELEVATION
FLOW
FLOW
FP-106 SCALE = N.T.S.
NORMAL
POSITION
NIPPLE "E"
8-1/2" FOR 3" PIPE
7-1/2" FOR 2-1/2"
PIPE
"D"
FLOOR CONTROL VALVE
WITH SUPERVISORY SWITCH
N
TYPICAL THRUST BLOCK INSTALLATION DETAIL
"C"
TO FIRE ALARM SYSTEM (TROUBLE SYSTEM)
BY ELECTRICAL CONTRACTOR
S
"B"
4"
THIRD FLOOR
WATER FLOW SWITCH
CONCRETE BLOCK ELEVATOR
SHAFT WALL
ELL
"A"
2" TEST AND DRAIN RISER
9
15 CONNECTOR ROAD WESTBOROUGH, MA
FLOW
1" OUTLET NIPPLE
SPILL TO DRAIN
VERTICAL
MOVEMENT
FIRE SPINKLER
MAIN
8
FIRE HOSE CABINET
FP-106 SCALE=N.T.S.
10
SEE FLOOR PLAN
FOR SIZE
SPRINKLER VALVE RIG
FP-106 SCALE=N.T.S.
MR
CROSSMAIN
CHECKED BY:
FLOW
SELF CONTAINED ALARM TEST
AND DRAIN ASSEMBLY, NOTE #2
TOP OF ELEVATOR
SHAFT
COUPLING (TYP.)
1" INLET NIPPLE
BUTTERFLY CONTROL VALVE
TAMPER SWITCH
DRAWN BY:
T
1
1.33
2
4
.4
DATE:06/26/2014
8"
FOURTH FLOOR
4"
FIRE SPRINKLER
MAIN
PERMIT
CL
PRESSURE GAUGE
F
2
4
6
9
13
DATE:
FLOW SWITCH
2
3
5
7
10
FIRE PROTECTION
DETAILS
H
2
5
8
13
18
ISSUED FOR
CL
TO FIRE ALARM SYSTEM (TROUBLE
SYSTEM) BY ELECTRICAL CONTRACTOR
S
4"
6"
8"
10"
12"
MM/DD/YY
2 1/2" FIRE DEPARTMENT HOSE
VALVE WITH 2 1/2" x 1 1/2" REDUCER. SEE NOTE #3.
TEES, PLUGS, CAPS
(SQ. FT.)
"B"
"A"
STAIR
ST2
1/8" BEND
(SQ. FT.)
NOT FOR
CONSTRUCTION
PITCH @ 1/8" PER FOOT
TO DRAIN RISER
1/4" BEND
(SQ. FT.)
COUPLING
2" TEST AND DRAIN RISER
1" OUTLET NIPPLE
PIPE SIZE
(IN INCHES)
STAMP:
10" LONG NIPPLE "D"
HAMPTON: INN & SUITES
UPRIGHT OR PENDENT SPRINKLER
HEAD ORDINARY TEMP. INSTALL AT
TOP OF THE ELEVATOR HOISTWAY
10" LONG
NIPPLE "C"
FLOW
PROJECT:
SELF CONTAINED ALARM
TEST AND DRAIN ASSEMBLY, NOTE #2
FILE NO:
AUTOMATIC FIRE ALARM
HEAT DETECTOR (135
DEGREES F) BY ELECTRICAL
CONTRACTOR
CROSSMAIN
SHEET TITLE:
FLOW
SHEET NUMBER:
FP-106
1
4
6
8
TS
FIRE DEPARTMENT SIAMESE CONNECTION
5. MAINTENANCE OF THE DCDA DEVICE SHALL BE THE RESPONSIBILITY OF THE LOCAL
WATER COMPANY. THE DCDA SHALL BE DISASSEMBLED AND OVERHAULED EVERY
FIVE YEARS.
ALARM CHECK VALVE ASSEMBLY
6. IT IS UNLAWFUL TO TAMPER WITH THE DCDA, TO INSTALL ANY OUTLET OR
CONNECTION AHEAD OF THE DEVICE, TO INSTALL AN UNPROTECTED BYPASS
AROUND THE DEVICE OR TO REMOVE THE DEVICE FROM SERVICE WITHOUT THE
APPROVAL OF THE WATER COMPANY.
11
7
19
18
16
3
LIGHT HAZARD CLASSIFICATION
A.B.D.
AUTOMATIC BALL DRIP
1. ALARM CHECK VALVE
13. OS&Y CONTROL VALVE W/TAMPER SWITCH
A.D.
ACCESS DOOR
2. RETARDING CHAMBER
14. 2" DRAIN VALVE
3. LOCAL ALARM EQUIPMENT
15. TO FIRE PROTECTION SYSTEM
4. RESTRICTED VENT
16. DRAIN
5. AUTOMATIC DRIP
17. DRAIN
6. DRIP CUP
18. TO SPRINKLER FUNNEL DRAIN
7. ALARM TEST VALVE(NORMALLY SHUT)
19. FROM FIRE SERVICE WATER SUPPLY
EL.
ELEVATION
F.H.C.
FIRE HOSE CABINET
SYMBOL NO.
TUSHAR
8. ALARM SHUT-OFF VALVE & CHECK
VALVE(NORMALLY OPEN)
FL.
FLOOR
DRAIN VALVE
NOTE: EXACT SIZE OF TRIM
PIPING,VALVES,ETC.
TO CONFORM
TO ALARM CHECK VALVE
MANUFACTURERS REQUIREMENTS.
11. DRIP CUP DRAIN LINE
F.D.
12. ALARM RELAY
SYSTEM
BYPASS
VALVE
THROTTLE
VALVE
1
ALARM CHECK VALVE ASSEMBLY
1
6"
15
O.S.&Y.
P.O.
PLUGGED OUTLET
N.A.S.
6"
1
5
PIPE SLEEVE
G.C.
GENERAL CONTRACTOR
A.F.F.
ABOVE FINISHED FLOOR
T.S.
TAMPER SWITCH
7
4
FINISHED FLOOR 0'-0"
8"
3
14
6"
5
1
PUMP BASE DRAIN,
PIPE TO FLOOR
DRAIN OR EXTERIOR
OF ROOM
NO AUTOMATIC SPRINKLERS
RISER CONTROL
VALVE
12 13
4
REDUCED PRESSURE
BACKFLOW PREVENTER
R.C.V.
7
2
GROUT
R.P.B.
F.P.
REFER TO
PART PLAN FOR
CONTINUATION.
16
6" FIRE PROTECTION
MAIN TO DOUBLE
CHECK VALVE
ASSEMBLY. REFER TO
PART PLAN FOR
CONTINUATION.
3/4" ROD EXTEND 4"
ABOVE THE PAD
PUMP BASE
NEW 6" FP SERVICE
FIRE PUMP ROOM
6"
6"
HUNG CEILING
OUTSIDE SCREW
& YOKE
1
11
10
FP-107 SCALE=N.T.S.
H.C.
T.S.
T.S.
FIRE PUMP
METER
9
FLOOR DRAIN
CHECK VALVE
3
ECCENTRIC REDUCER
4
ELECTRIC FIRE PUMP
5
ELECTRIC JOCKEY PUMP
6
CONCENTRIC INCREASER
7
WATER PRESSURE GAUGE
8
FLOOR DRAIN
9
FIRE PUMP TEST HEADER
10
FIRE PUMP METER
11
BY-PASS
12
6"
AUTOMATIC AIR RELEASE VALVE
13
CASING RELIEF VALVE
14
14
CONCRETE PAD:
MINIMUM 12" A.F.F
15
PRESSURE SENSING LINE
TO FIRE PUMP CONTROLLER.
16
PRESSURE SENSING LINE
TO JOCKEY PUMP CONTROLLER
8
FIRE PUMP INSTALLATION DETAIL (ELEVATION)
FP-107 SCALE = N.T.S.
3/4" HEX NUT
CONCRETE PAD
T & D-R
TEST & DRAIN-RISER
TYP.
TYPICAL
VALVED OUTLET
CONNECT TO A TAPPED BOSS
OR OTHER SUITABLE OUTLET
BETWEEN THE INDICATING
CONTROL VALVE AND CHECK
VALVE.
FIRE PUMP PAD DETAIL
FP-107 SCALE = N.T.S.
INDICATING CONTROL
VALVE WITH TAMPER
SWITCH
F.S.
FIRE SERVICE
W.F.S.
WATERPROOF PIPE SLEEVE
T.S.
THAN 5'-0"
GLOBE VALVE
FIRE PUMP
PS
PRESSURE GAUGE
PRESSURE SWITCH
SUCTION
FIRE HOSE RACK
PS
PRESSURE SWITCH
AIR VENT
1/2" GLOBE VALVE
(TYPICAL)
FIRE
PUMP
METER
T.S.
THROTTLE
VALVE
SYSTEM
BYPASS
VALVE
T.S.
FIRE PUMP PRESSURE SENSING PIPING LEGEND
SYMBOL
DESCRIPTION
CHECK VALVE
W/ 3/32" HOLE
IN CLAPPER
5'-0"
T.S.
MIN.
FIRE
PUMP
CONTROLLER
T.S.
TO FIRE PUMP
TEST HEADER
T.S.
FIRE
PUMP
FLOW
T.S.
T.S.
JOCKEY
PUMP
TYPICAL PIPING CONNECTION FOR EACH AUTOMATIC
PRESSURE SWITCH DETAIL FOR FIRE OR JOCKEY PUMPS
FP-107 SCALE = N.T.S.
MAIN FIRE PROTECTION
PIPING
PRESSURE SENSING
PIPING
OS&Y GATE VALVE
W/ TAMPER SWITCH
T.S.
T.S.
DOUBLE CHECK VALVE ASSEMBLY
W/OS&Y GATE VALVES
& TAMPER SWITCH
PRESSURE GAUGE
AIR VENT
MAIN FIRE PROTECTION
PIPING
PRESSURE SENSING
PIPING
MIN.
JOCKEY
PUMP
CONTROLLER
"TEST
CONNECTION
AT POINT "A" OR "B"
1/2" GLOBE VALVE
(TYPICAL)
T.S.
TO FIRE
PROTECTION
SYSTEM
T.S.
5
"B"
1/4" PLUG
(TYPICAL)
DATE:
FIRE HOSE CABINET W/FIRE EXTINGUISHER
"A"
1/4" PLUG
(TYPICAL)
FIRE PROTECTION
DETAILS
BRONZE CHECK VALVE
WITH 3/32" ORIFICE
IN CLAPPER
FIRE HOSE CABINET
WATER SUPPLY
FROM STREET
OS&Y GATE VALVE
W/ TAMPER SWITCH
13.183
F-3
T.S.
FILE NO:
F-2
DESCRIPTION
CHECK VALVE
W/ 3/32" HOLE
IN CLAPPER
1/2"CORROSION RESISTANT
PIPE OR TUBING AND
FITTINGS
CONTROL PANEL
DISCHARGE
F-1
SYMBOL
SHEET TITLE:
V.O.
2
BRONZE CHECK VALVE
WITH 3/32" ORIFICE
IN CLAPPER
IF WATER PULSATION CAUSES
ERRATIC OPERATION OF THE
PRESSURE SWITCH OR THE
RECORDER, A SUPPLEMENTAL
AIR CHAMBER OR PULSATION
DAMPER SHALL BE INSTALLED.
PROJECT:
TEST & DRAIN-CONNECTION
LEGEND
CHECK VALVE
NOT LESS
FINISHED FLOOR
T & D-C
A Limited Liability Company
1111 Main Street, East Hartford CT 06108
TEL: (860) 289−1100 FAX: (860) 289−3272 E−MAIL: info@rdaep.com
RD
&
N
5'-0"
MR
FIRE HOSE VALVE
3/ "
4
2
CHECKED BY:
F.H.V.
STRUCTURAL BEAM
1O.
OS&Y GATE VALVE WITH
TAMPER SWITCH
DRAWN BY:
FIRE HOSE RACK
1
CEILING
9. WATER PRESSURE GAUGE
F.H.R.
DESCRIPTION
DATE:06/26/2014
DOWN
15 CONNECTOR ROAD WESTBOROUGH, MA
DN.
FIRE PUMP INSTALLATION DETAIL LEGEND
PERMIT
CEILING
MM/DD/YY
CLG.
FIRE SERVICE DOUBLE CHECK DETECTOR ASSEMBLY INSTALLATION DETAIL (ELEVATION)
FP-107 SCALE = N.T.S.
ISSUED FOR
14
9. THE DOUBLE CHECK DETECTOR ASSEMBLY SHALL BE INSTALLED WHERE THE
POTENTIAL HEATH HAZARD DOES NOT EXIST AND IN ACCORDANCE WITH
NFPA 13, AND ALL STATE AND LOCAL CODE STANDARDS AND ORDINANCES.
REVISIONS
FROM FIRE SERVICE
WATER SUPPLY
NO.
L.H.
61-5/8"
8. THE DCDA WILL CAUSE A DECREASE IN WATER PRESSURE. REFER TO
MANUFACTURER'S FLOW CURVES FOR PRESSURE LOSSES. PRESSURE LOSS
THROUGH THE DCDA SHALL BE ACCOUNTED FOR IN THE HYDRAULIC
CALCULATIONS OF THE SPRINKLER SYSTEM.
O.S.&Y. GATE VALVE WITH TAMPER SWITCH
ORDINARY HAZARD CLASSIFICATION
95
0
WI
XL
LK
IN
S
COORDINATE LENGTHS OF ALTERNATE DCD WITH INSTALLATION CONDITIONS PRIOR
TO SUBMITTING ALTERNATES.
THE SPECIFIED ALTERNATE DCD'S SHALL MEETING ALL THE REQUIREMENTS FOR
USE ON FIRE PROTECTION SYSTEMS AS SPECIFIED BY THE LOCAL AUTHORITY:
WATER DEPARTMENT
7. THE DOUBLE CHECK DETECTOR ASSEMBLY SHALL FACE FORWARD,
WITH ADEQUATE ACCESS TO THE TEST COCKS TO FACILITATE
TESTING AND MAINTENANCE.
17
O.H.
P
C
WATTS: DCD= 757DCDAOSY
1O
WATERFLOW SWITCH
U
12. APPROVED ALTERNATE DOUBLE CHECK DETECTOR ASSEMBLY SHALL BE
AS FOLLOWS:
DESCRIPTION
13
30" MIN.
60" MAX.
NOT FOR
CONSTRUCTION
FLOOR CONTROL VALVE ASSEMBLY(FCVA)
12" MIN.
30" MAX.
HAMPTON: INN & SUITES
9
4. THE DOUBLE CHECK DETECTOR ASSEMBLY SHALL BE TESTED AFTER INITIAL INSTALLATION
AND INSPECTED ANNUALLY BY A CERTIFIED TESTER AND ALL RESULTS SHALL BE REPORTED
TO THE LOCAL WATER COMPANY AND OWNER. IN ADDITION TO REPORTING ALL RESULTS TO
THE WATER COMPANY, THE CONTRACTOR IS TO RETURN A COMPLETE COPY OF "REPORT
ON TEST AND MAINTENANCE OF BACKFLOW PREVENTION DEVICES" TO THE WATER COMPANY
AND OWNER AFTER INITIAL TESTING.
STAMP:
SPRINKLER
FROM FIRE PUMP.
REFER TO DRAWING
FOR CONTINUATION.
WILKINS
ZURN
8"
BY
5
TO BUILDING'S FIRE
PROTECTION SYSTEM.
REFER TO DRAWING
CONTINUATION.
37-3/4"
OPEN
29-1/4"
CLOSED
DATE
9
TEST AND DRAIN PIPING
T&D
3. THE CONTRACTOR SHALL PROVIDE ADEQUATE SUPPORT FOR THE DCD ASSEMBLY. THE DCD
SHALL BE INSTALLED AT A MINIMUM OF 30" ABOVE FINISH FLOOR WITH A MINIMUM OF
18" BEHIND AND 30" IN FRONT OF THE DEVICE FOR MAINTENANCE.
4.5
SPRINKLER PIPING (SPKR)
SP
3/ "
4
B6
2. ALL (DCDA) DEVICES MUST BE FROM AN APPROVED LIST OF THE LOCAL WATER
COMPANY HAVING JURISDICTION.
T.S.
P SI
FIRE (DISTRIBUTION) PIPING (F)
F
T.S.
175
15
15
TO FIRE PROTECTION
SYSTEM
DCDA-1:
6" DOUBLE CHECK DETECTOR
ASSEMBLY, WILKINS MODEL
350ADA-OSY-40 WITH
FLANGED END OS&Y GATE
VALVES, GPM METER AND
TAMPER SWITCHES.
10
2
FIRE STANDPIPE/SPRINKLER RISER
11. INSTALL NEW 6" DOUBLE CHECK DETECTOR ASSEMBLY,
WILKINS MODEL 350ADA-OSY-40.
PROVIDE WITH THE FOLLOWING OPTIONS:
- WITH FLANGED END OS&Y GATE VALVES
- WITH GPM WATER METER ON BYPASS
- REPAIR KIT
- OS&Y GATE VALVE TAMPER SWITCH
DOUBLE CHECK DETECTOR BACKFLOW PREVENTION ASSEMBLY SHALL BE ASSE
LISTED 1048, AND SUPPLIED WITH FULL PORT GATE VALVES. THE MAIN BODY AND
ACCESS COVER SHALL BE EPOXY COATED DUCTILE IRON (ASTM A536, GRADE 4),
THE SEAT RING AND CHECK VALVE SHALL BE NORYL (NSF LISTED), THE STEM
SHALL BE 300 SERIES STAINLESS STEEL (ASTM A276) AND THE SEAT DISC
ELASTOMETERS SHALL BE EPDM. THE FIRST AND SECOND CHECK VALVES SHALL
BE ACCESSIBLE FOR MAINTENANCE WITHOUT REMOVING THE DEVICE FROM THE
LINE.
THE SPECIFIED DCDA SHALL MEETING ALL THE REQUIREMENTS FOR USE ON FIRE
PROTECTION SYSTEMS AS SPECIFIED BY THE LOCAL AUTHORITY:
WATER DEPARTMENT
TAMPER SWITCH: WIRE TO FIRE
ALARM SYSTEM (TROUBLE SYSTEM)
BY ELEC. CONTRACTOR (TYPICAL)
180
°F
NOTE: THE KEY OF SYMBOLS INDICATED ARE FOR CONVENIENCE ONLY AND ITEMS
INDICATED ARE NOT NECESSARILY WITHIN THE SCOPE OF WORK.
X
10. DOUBLE CHECK DETECTOR ASSEMBLY SHALL BE PROVIDED WITH METERED
BY-PASS TO DETECT LEAKS AND UNAUTHORIZED WATER USE. REFER TO
STATE AND LOCAL CODE REQUIREMENTS FOR ADDITIONAL INFORMATION.
1. THIS RISER IS REPRESENTATIONAL OF THE CONCEPTUAL BACKFLOW PREVENTION
ARRANGEMENT AND ASSOCIATED DRAINAGE REQUIREMENTS FOR THE FIRE PROTECTION
SERVICE FOR THE PURPOSE OF DEMONSTRATING BACKFLOW PREVENTION CODE
COMPLIANCE. THE FIRE PROTECTION CONTRACTOR SHALL FURNISH AND INSTALL ALL
MATERIALS NECESSARY TO COMPLETE THE ACTUAL FIRE PROTECTION SYSTEM. THE FIRE
PROTECTION CONTRACTOR IS RESPONSIBLE FOR THE PROPER ERECTION OF THE ACTUAL
COMPLETE WORKING SYSTEM OF PIPING AND DEVICE PER ALL APPLICABLE CODES AND
STANDARD PRACTICES.
DOUBLE CHECK DETECTOR ASSEMBLY.
E
KEY OF SYMBOLS
FSP
RUSSELL AND DAWSON
ARCHITECTURE &
ENGINEERING
FIRE PROTECTION SERVICE RISER GENERAL NOTES:
Rev.: 13.02
THIS DOCUMENT, THE IDEAS
AND DESIGNS INCORPORATED
THEREIN, AS AN INSTRUMENT OF
PROFESSIONAL SERVICES, IS THE
PROPERTY OF RUSSELL AND
DAWSON LLC, AND MAY NOT BE USED,
IN WHOLE OR IN PART, FOR ANY OTHER
PROJECT OR BY ANY OTHER PERSON
OR CORPORATION OTHER THAN THAT
NAMED HEREON WITHOUT THE
WRITTEN AUTHORIZATION OF RUSSELL
AND DAWSON LLC. ANY SUCH
UNAUTHORIZED USE WILL BE SOLELY
AT THE USER'S RISK AND RUSSELL
AND DAWSON LLC WILL BEAR NO
RESPONSIBILITY ARISING OUT OF
SUCH USE.
© 2013 by Russell and Dawson LLC
3
ASS
12
SHEET NUMBER:
6
TYPICAL FIRE PUMP INSTALLATION WITH PRESSURE SENSING PIPING DIAGRAM
FP-107 SCALE = N.T.S.
FP-107
C. FIRE PUMP CONTROLLER
THE FIRE PUMP CONTROLLER, SHALL BE A FIRETROL MODEL FTA 1900, 208V/60/3 , UL LISTED, FM, SPECIFICALLY FOR FIRE PUMP SERVICE. THE ENCLOSURE
SHALL BE A NEMA TYPE 2. THE CONTROLLER SHALL BE COMBINED MANUAL AND AUTOMATIC REDUCED VOLTAGE, SOLID STATE, SOFT START/STOP TYPE WITH
ADJUSTABLE PAUSE CONTROL RATED FOR THE HP SPECIFIED AND INCLUDING VOLTAGE SURGE ARRESTERS. THE CONTROLLER SHALL DISPLAY SYSTEM
PRESSURE, RECORD HISTORICAL OPERATING DATA AND SYSTEM EVENTS WHICH MAY BE DOWNLOADED TO ITS INTERNAL FLOPPY DISK DRIVE OR ACCESSED BY
THE BUILDING MANAGEMENT SYSTEM THROUGH THE NETWORK READY MOD BUS PROTOCOL. THE CONTROLLER SHALL BE CAPABLE OF INTERRUPTING A SHORT
CIRCUIT CURRENT AT LEAST EQUAL TO THE AVAILABLE SHORT CURRENT IN THE CONTROLLER SUPPLY CIRCUIT. THIS FIRE PUMP INSTALLATION REQUIRES AN
INTERRUPTING CAPACITY, WITHSTAND RATING OF NOT LESS THAN 100,000 AMPS RMS SYMMETRICAL AT THE OPERATING VOLTAGE. THE FIRE PUMP CONTROLLER
SHALL BE FACTORY ASSEMBLED AND WIRED WITH A POWER TRANSFER SWITCH LISTED BY U.L. FOR TRANSFER SWITCH AND FIRE PUMP SERVICE. POWER
TRANSFER SWITCHSHALL BE PM APPROVED.
5
6
THE CONTROLLER MUST BE CAPABLE OF PERFORMING OR CONTAIN THE FOLLOWING FEATURES:
· PRESSURE SWITCH.
· AUTOMATIC START ON LOW PRESSURE.
· TIMING RELAY FOR AUTOMATIC STOP, TO BE FIELD CHANGEABLE OR MANUAL STOP.
7
THE CONTROLLER SHALL BE FURNISHED WITH A PAIR OF AUXILIARY ALARM CONTACTS FOR INDICATION OF:
· PUMP RUN.
· PHASE FAILURE.
· PHASE REVERSAL.
JOCKEY PUMP SYSTEM JP-1 :
10.0 GPM JOCKEY PUMP, GRUNDFOS MODEL CR3-11 OR ENGINEER APPROVED EQUAL.
300 TDH
2.0 HP
3,452 RPM
ELECTRICAL: 208V/60/3
SYSTEM BY-PASS VALVE, OS&Y GATE VALVE WITH TAMPER SWITCH. TAMPER SWITCH TO BE
WIRED TO EXISTING BUILDING FIRE ALARM SYSTEM BY ELECTRICAL CONTRACTOR.
NEW 6" FIRE PROTECTION MAIN UP, RUN TIGHT TO STRUCTURE
16
FIRE PUMP CONTROLLER (FPC):
FIRETROL MODEL FTA 1900 50 HP, 100,000 AMP SYM, SOLID STATE SOFT START/STOP,
480V/60/3 .
17
FIRE PUMP AUTOMATIC TRANSFER SWITCH (ATS):
FIRETROL MODEL FTA 900, EMERGENCY GENERATOR POWER SERVICE, 22,000 AMPS RMS
SYM WR, 50 HP, 208V/60/3 .
18
JOCKEY PUMP CONTROLLER (JPC):
PEERLESS PUMP MODEL PJPC 2.0 HP, 208V/60/3 , W/MIN RUN TIMER
19
NEW 6" FIRE PROTECTION MAIN UP, RUN TIGHT TO STRUCTURE
20
SPARE SPRINKLER CABINET(S) SHALL BE INSTALLED IN THE FIRE SERVICE ROOM.
CABINET SHALL BE WALL MOUNTED, APPROXIMATELY 48" ABOVE FINISHED
FLOOR. CABINET SHALL CONTAIN SPARE SPRINKLERS PER TYPE SO THAT ANY
SPRINKLER THAT HAS BEEN OPERATED OR DAMAGED IN ANY WAY CAN BE
PROMPTLY REPLACED. THE NUMBER OF SPRINKLER SHALL BE AS FOLLOWS:
THROTTLE VALVE, OS&Y GATE VALVE WITH TAMPER SWITCH. TAMPER SWITCH TO BE WIRED
TO EXISTING BUILDING FIRE ALARM SYSTEM BY ELECTRICAL CONTRACTOR.
9
BY-PASS, RUN TIGHT TO STRUCTURE IN THIS AREA. (SHOW OFFSET FOR CLARITY).
10
6" FIRE PUMP TEST HEADER RUN ABOVE NEW FIRE PROTECTION PIPING IN THIS AREA.
11
PROVIDE 2" DRAIN VALVE ON UNDERSIDE OF TEST HEADER PIPING IN THIS AREA. PIPE
DRAIN PIPING DOWN ALONG FLOOR AND THROUGH WALL TO EXTERIOR OF ROOM.
TERMINATE WITH 45° ELBOW WITH INSECT SCREEN IN GARAGE.
12
FIRE PUMP TEST HEADER:
POTTER ROEMER MODEL 5865-B-2-7 OR ENGINEER APPROVED EQUAL.
CAST IRON BODY. BRASS PLATE LETTERED "PUMP TEST CONNECTION".
SUPPLY WITH BRASS NRS HOSE GATE VALVES, WITH EVERY OTHER VALVE
HAVING A LOOSE BONNET, AS REQUIRED FOR INSTALLATION. 4" FEMALE NPT
INLET x 2-1/2" MALE HOSE THREAD OUTLET, WITH CAPS AND CHAIN. TEST
HEADER HOSE VALVE SHALL MEET THE REQUIREMENTS OF THE CITY OF
NORWALK, CT FIRE DEPARTMENT. COORDINATE LOCATION OF TEST CONNECTION
WITH FIRE DEPARTMENTS REQUIREMENTS IN THE FIELD.
NUMBER AND SIZE OF HOSE VALVES: (6) 2-1/2"
LOCATE TEST HEADER 48" ABOVE FINISHED GRADE.
FIRE PROTECTION CONTRACTOR SHALL PROVIDE AND INSTALL (4) 4"DIA. x 48" HIGH
CONCRETE BOLLARDS TO PROTECT TEST HEADER FROM DAMAGE. COORDINATE FINAL
LOCATION WITH FACILITIES DEPARTMENT REQUIREMENTS IN THE FIELD.
NUMBER OF SPRINKLERS
MINIMUM NUMBER OF
IN SYSTEM:
SPARE SPRINKLERS:
UNDER 300
6
300 - 1,000
12
OVER 1,000
24
21
THESE SPRINKLERS SHALL CORRESPOND TO THE TYPES AND TEMPERATURE
RATINGS OF THE SPRINKLERS IN THE PROPERTY. THE SPRINKLERS SHALL BE
KEPT IN THE CABINET LOCATED WHERE THE TEMPERATURE TO WHICH THEY
ARE SUBJECTED WILL AT NO TIME EXCEED 100°F AND NOT EXPOSED TO
CORROSIVE ATMOSPHERES. CABINET(S) SHALL BE LOCATED IN AN EASILY
ACCESSIBLE LOCATION. A SPECIAL SPRINKLER WRENCH SHALL ALSO BE
PROVIDED AND KEPT IN THE CABINET TO BE USED IN THE REMOVAL AND
INSTALLATION OF EACH TYPE OF SPRINKLER IN THE PROPERTY.
CABINET SHALL BE PAINTED IN A HIGH-GLOSS RED ENAMEL INTERIOR AND
EXTERIOR, CHROME PLATED DOOR KNOB. CABINET SHALL BE MADE OF
20 GAUGE, COLD ROLLED STEEL, CABINET SHELVES SHALL BE MADE OF
16 GAUGE, COLD ROLLED STEEL.
.
18"
1"
2"
18"
5"
CONDUIT ENTRANCE
TOP AND BOTTOM
(6) MOUNTING SLOTS
PER ENCLOSURE
9/16"x1"
TOP VIEW
ENLARGED SPRINKER ROOM
GARAGE DECK
26-7/8"
2-5/8"
APPROXIMATE
SHIPPING WEIGHT
MARK II
DIGITAL DISPLAY &
DATA ACQUISITION SYSTEM
POWER AVAILABLE
PHASE FAILURE
PHASE REVERSAL
ALARM
TRANSFER SWITCH NORMAL
TRANSFER SWITCH EMERGENCY
MENU
PRINT
DISPLAY
HOME
ON
ON
OFF
OFF
ENTER
SAVE TO
DISK
ALARM
SILENCE
AUTOMATIC TRANSFER
SWITCH
FIRE PUMP
CONTROLLER
DO NOT INSTALL IN AMBIENT
TEMPERATURES BELOW 41°F.
61-5/8"
114"
50"
48"
AUXILIARY
ENCLOSURE
METER
LOW PRESSURE
PUMP RUNNING
DELUGE OPEN
INTERLOCK ON
EMERGENCY ISOLATING
SWITCH OFF
DATE:
3-60
3-60
3-75
3-100
3-150
3-200
R
ENLARGED PLAN,
NOTES & SCHEDULES
200
208
220-240
380-415
440-480
550-600
MARK II
True RMS Metering
R
Firetrol
13.183
MOTOR
HORSEPOWER
PROJECT:
645 LBS.
HIGH WITHSTAND RATINGS
200-600V - 200,000 AMPS RMS SYM.
LINE
VOLTAGE
(6) 9/16" DIA.
MTG. HOLES
21"
FILE NO:
INTERMEDIATE WITHSTAND RATINGS
200-600V - 150,000 AMPS RMS SYM.
21"
SHEET TITLE:
STANDARD WITHSTAND RATINGS
200-600V - 100,000 AMPS RMS SYM.
19"
1"
14"
47-1/4"
MR
DOOR SWING
34-1/2"
DRAWN BY:
1/2" = 1'-0"
CHECKED BY:
SYSTEM PRESSURE
1/2" FNPT
CONNECTION.
MM/DD/YY
29-3/4"
L. SERVICE CONTRACT
THE MANUFACTURER'S AUTHORIZED SERVICE REPRESENTATIVE SHALL PROVIDE A ONE (1) YEAR SERVICE CONTRACT. THE SERVICE CONTRACT PERIOD SHALL
COMMENCE AFTER ACCEPTANCE OF THE EQUIPMENT. THE SERVICE CONTRACT SHALL INCLUDE A COMPLETE SYSTEM INSPECTION TWICE A YEAR INCLUDING:
CHECK OF PROPER PUMP SEQUENCING AND ALARM ACTIVATION WITH ADJUSTMENTS, AS REQUIRED; AND REVIEW OF INSTRUCTIONS FOR OPERATING PERSONNEL,
IF REQUESTED. ANY REQUIRED SERVICE WORK TO BE NOTED IN A FORMAL INSPECTION REPORT ALONG WITH A DETAILED PROPOSAL FOR THE REPAIRS.
THE SERVICE REPRESENTATIVE SHALL PROVIDE FOR 24 HOUR EMERGENCY SERVICE.
15 CONNECTOR ROAD WESTBOROUGH, MA
5"
K. START_UP & WARRANTY
THE PUMP MANUFACTURE'S REPRESENTATIVE SHALL HAVE SINGLE SOURCE RESPONSIBILITY FOR THE PUMPS AND COMPLETE CONTROL SYSTEM. START_UP
SERVICES INCLUDING PUMP ALIGNMENT, ADJUSTMENT AND FIELD CALIBRATION OF CONTROLS, OPERATOR INSTRUCTION AND SYSTEM WARRANTY SHALL BE
INCLUDED IN THE PRICE FOR THE SYSTEM. THE WARRANTY SHALL BE 12 MONTHS FROM DATE OF START_UP NOT TO EXCEED 18 MONTHS FROM TIME OF
SHIPMENT.
ALL DIMENSIONS - INCHES
SHIPPING WEIGHT - POUNDS
THIS DIMENSION DRAWING COVERS FTA1900
CONTROLLERS AT THE HORSEPOWER,
VOLTAGE AND WITHSTAND RATINGS AS
LISTED IN THE TABLE.
(6) 9/16" DIA.
MTG. SLOTS.
8"
12"
SIDE VIEW
2"
OPTIONAL WALL
MOUNTING BRACKETS.
52-1/4"
76-1/2"
12"
TWO 1-1/2" DIA.
HOLES FOR PIPE
ENTRANCE.
6"
SPECIFICATIONS AND DIMENSIONS SUBJECT
TO CHANGE WITHOUT NOTICE. DO NOT USE
FOR CONSTRUCTION. REQUEST
CONSTRUCTION DRAWINGS FROM FIRETROL
OR YOUR LOCAL FIRETROL
REPRESENTATIVE.
6"
1
FP-200
CONDUIT ENTRANCE
TOP AND BOTTOM
HAMPTON: INN & SUITES
REFER TO SITE PLAN
J. FIELD ACCEPTANCE TEST
A FIELD ACCEPTANCE PERFORMANCE TEST SHALL BE CONDUCTED UPON COMPLETION OF PUMP INSTALLATION. THE TEST SHALL BE MADE BY FLOWING WATER
THROUGH CALIBRATED NOZZLES, APPROVED FLOW METERS OR OTHER ACCURATE DEVICES AS MAY BE SELECTED BY THE AUTHORITY HAVING JURISDICTION AND
FURNISHED BY THE CONTRACTOR. THE TEST SHALL BE CONDUCTED AS RECOMMENDED IN NFPA PAMPHLET 20 BY THE CONTRACTOR, IN THE PRESENCE OF
THE MANUFACTURER'S REPRESENTATIVE AND THE AUTHORITY HAVING JURISDICTION AND WITH THE AUTHORITY'S FINAL APPROVAL AND ACCEPTANCE. FAILURE TO
SUBMIT DOCUMENTATION OF FACTORY AND FIELD TESTS WILL BE JUST CAUSE FOR EQUIPMENT REJECTION.
6"
6"
N
10"
BELOW SLAB WATER MAIN
1"
2-1/2"
H. PUMP MANUFACTURER'S FACTORY TESTS
THE FIRE PUMP SHALL BE HYDROSTATICALLY TESTED AND RUN TESTED PRIOR TO SHIPMENT, BY THE PUMP MANUFACTURER. THE PUMP SHALL BE
HYDROSTATICALLY TESTED AT A PRESSURE OF NOT LESS THAN ONE AND ONE HALF TIMES THE NO FLOW (SHUTOFF) HEAD OF THE PUMP'S MAXIMUM
DIAMETER IMPELLER PLUS THE MAXIMUM ALLOWABLE SUCTION HEAD, BUT IN NO CASE LESS THAN 250 PSIG. CHARACTERISTIC CURVE OF PUMP PERFORMANCE,
EFFICIENCY AND BRAKE HORSEPOWER SHALL BE DRAWN FROM THE TEST RESULTS AND FURNISHED TO THE CONSULTING ENGINEERING AND CONTRACTOR.
4"
DATE:06/26/2014
2"
PERMIT
18"
1"
1"
ISSUED FOR
50-1/4"
22"
G. JOCKEY PUMP CONTROLLER
THE JOCKEY PUMP CONTROLLER SHALL BE PEERLESS PUMP MODEL PJPC 2.0 HP, 208V/60/3 IN A NEMA 1 ENCLOSURE WITH MIN RUN TIMER,
COMBINATION DISCONNECT SWITCH/OVERLOAD RELAY, MOTOR CONTACTOR, H-O-A SWITCH, POWER ON LIGHT, CONTROL CIRCUIT TRANSFORMER WITH FUSED
SECONDARY, PRESSURE SWITCH, SPDT, 15-290 PSIG RANGE, 15-120 PSIG DIFFERENTIAL, FRESH WATER APPLICATIONS, AND RUNNING PERIOD TIMER.
1"
FIRE
PUMP
F. JOCKEY PUMP
THE JOCKEY PUMP SHALL BE GRUNDFOS MODEL CR3-11 RATED FOR 10 GPM AT 300' TDH. THE PUMP SHALL BE VERTICAL MULTI-STAGE CAST IRON
STAINLESS STEEL FITTED. THE PUMP SHALL BE CLOSE COUPLED TO A 2 HP, 3,600RPM, 208 VOLT, 3 PHASE, 60 HZ, 40 OC AMBIENT, ODP MOTOR WITH
1.15 SERVICE FACTOR.
NOT FOR
CONSTRUCTION
E. FITTINGS
ALL COMPONENTS ON THE DISCHARGE SIDE OF THE PUMP SHALL HAVE A RATED WORKING PRESSURE GREATER THAN PUMP SHUT-OFF HEAD PLUS MAXIMUM
SUCTION PRESSURE. THE FOLLOWING ACCESSORIES AND FITTINGS SHALL BE PROVIDED:
1.ECCENTRIC SUCTION REDUCER, IF REQUIRED.
2.CONCENTRIC DISCHARGE INCREASER, IF REQUIRED.
3.AUTOMATIC AIR RELEASE VALVE.
4.CASING RELIEF VALVE, PIPE TO FLOOR DRAIN.
5.SUCTION AND DISCHARGE GAUGES.
6.HOSE VALVE HEAD WITH VALVES, CAPS, CHAINS AND DRAIN VALVE.
FIRE DEPT.
CONNECTION
REFER TO FLOOR
PLAN
A Limited Liability Company
1111 Main Street, East Hartford CT 06108
TEL: (860) 289−1100 FAX: (860) 289−3272 E−MAIL: info@rdaep.com
15
FIRE PUMP FLOW METER FPM-1 .
VENTURI FLOW METER, PRESO MODEL CV 91WD OR ENGINEER APPROVED EQUAL, RATED
FOR 750 GPM NOMINAL FLOW RATE. METER SHALL BE GROOVED END STL.
8
DOUBLE CHECK DETECTOR ASSEMBLY (DCDA-1):
WILKINS MODEL 350ADA-0SY40, 6" WITH OS&Y GATE VALVES AND TAMPER SWITCHES.
PROVIDE WITH GPM METER.
RD
FIRE PUMP SYSTEM FP-1 :
750 GPM FIRE PUMP, PEERLESS PUMP MODEL 6AEF10 OR ENGINEER APPROVED EQUAL.
100 TDH, 72.2 % EFF
100 HP
3,600 RPM
ELECTRICAL: 208V/60/3
14
STAMP:
BFP
D. FIRE PUMP CONTROLLER POWER TRANSFER SWITCH
THE POWER TRANSFER SWITCH SHALL BE A FIRETROL MODEL FTA 900, 208V/60/3 , 50 HP, 22,000 AMPS, RMS SYR WR, EMERGENCY GENERATOR POWER
SERVICE FOR NORMAL UTILITY POWER AND ENGINE GENERATOR SET EMERGENCY POWER.
THE POWER TRANSFER SWITCH SHALL BE HOUSED WITHIN THE FIRE PUMP CONTROLLER ENCLOSURE OR IN A NEMA TYPE 2 (IEC IP11) DRIP-PROOF
ENCLOSURE ATTACHED DIRECTLY TO THE FIRE PUMP CONTROLLER. WHERE THE POWER TRANSFER SWITCH IS PROVIDED IN AN ATTACHED ENCLOSURE, THE
ENCLOSURES SHALL BE FITTED SO THAT THE ASSEMBLY CONSTITUTES A SINGLE UNIT. THE FIRE PUMP CONTROLLER/POWER TRANSFER SWITCH SHALL BE
FACTORY ASSEMBLED, WIRED AND TESTED AS A UNIT PRIOR TO SHIPMENT.
THE POWER TRANSFER SWITCH SHALL INCLUDE A MOTOR RATED DISCONNECT/ISOLATING SWITCH CAPABLE OF INTERRUPTING THE MOTOR LOCKED ROTOR
CURRENT. THE DISCONNECT/ISOLATING SWITCH SHALL BE MECHANICALLY INTERLOCKED SO THAT THE ENCLOSURE DOOR CANNOT BE OPENED WITH THE HANDLE
IN THE ON POSITION EXCEPT BY A HIDDEN TOOL OPERATED DEFEATER MECHANISM. THE DISCONNECT/ISOLATING SWITCH SHALL BE CAPABLE OF BEING
PADLOCKED IN THE OFF POSITION WITH UP TO THREE PADLOCKS FOR INSTALLATION AND MAINTENANCE SAFETY, AND SHALL ALSO BE CAPABLE OF BEING
LOCKED IN THE ON POSITION. THE ENCLOSURE DOOR SHALL HAVE A LOCKING TYPE HANDLE AND THREE POINT CAM AND ROLLER TYPE VAULT HARDWARE.
AN AUXILIARY CONTACT SHALL BE PROVIDED ON THE TRANSFER SWITCH TO PREVENT STARTING OF THE EMERGENCY GENERATOR SET WHEN THE TRANSFER
SWITCH OR THE MAIN FIRE PUMP CONTROLLER ARE BEING SERVICED.
THE TRANSFER SWITCH CIRCUITRY SHALL BE CAPABLE OF SENSING BOTH THE NORMAL POWER SOURCE AND THE EMERGENCY POWER SOURCE. THE NORMAL
POWER SOURCE PICKUP SHALL BE SET AT 95% NOMINAL VOLTAGE. THE EMERGENCY POWER SOURCE SHALL BE SET TO PICK UP AT 90 % NOMINAL VOLTAGE
AND 95 % NOMINAL FREQUENCY. ALL VOLTAGE SENSING, FREQUENCY SENSING, AND TIME DELAYS SHALL BE FIELD ADJUSTABLE TO ACCOMMODATE INDIVIDUAL
INSTALLATION REQUIREMENTS. THE TRANSFER SIGNAL SHALL BE DELAYED FOR ONE SECOND, DELAYING THE TRANSFER AND ENGINE START SIGNALS SO AS TO
COMPENSATE FOR MOMENTARY, NORMAL POWER OUTAGES. AN AUTOMATIC DELAY OF THREE SECONDS SHALL BE PROVIDED UPON TRANSFER TO OR FROM THE
EMERGENCY POWER SOURCE TO ALLOW THE MOTOR TO SLOW SUFFICIENTLY, PREVENTING THE DISTURBANCES THAT COULD TRIP EITHER THE GENERATOR SET
OR FIRE PUMP CIRCUIT BREAKERS.
THE TRANSFER SWITCH SHALL HAVE TRANSFER SWITCH NORMAL, TRANSFER SWITCH EMERGENCY AND EMERGENCY ISOLATING SWITCH OFF LED'S, TEST AND
TRANSFER BYPASS SWITCHES, AN AUDIBLE ALARM DEVICE AND SILENCE ALARM PUSHBUTTON MOUNTED ON THE FLANGE OF THE ENCLOSURE.THE POWER
TRANSFER SWITCH SHALL BE FURNISHED WITH BOTH NORMALLY OPEN AND NORMALLY CLOSED AUXILIARY CONTACTS FOR AN ENGINE START SIGNAL WHEN
NORMAL POWER FAILURE OCCURS. AUXILIARY CONTACTS SHALL ALSO BE PROVIDED AND WIRED TO TERMINALS TO INDICATE THE TRANSFER SWITCH POSITION.
THE TRANSFER SWITCH SHALL BE ELECTRICALLY OPERATED AND MECHANICALLY HELD, AND SHALL BE CAPABLE OF BEING OPERATED BY A MANUAL TRANSFER
MECHANISM LOCATED ON THE SWITCH.
CONTROL VALVE WITH TAMPER SWITCH. CONTROL VALVE SHALL BE IDENTIFIED AS FOLLOWS:
FIRE VALVE #63, CHILLER PLANT, SPRINKLER/FIRE HOSE SHUT-OFF, MAIN PAVILION.
TAMPER SWITCH TO BE WIRED TO EXISTING BUILDING FIRE ALARM SYSTEM BY ELECTRICAL
CONTRACTOR.
BY
THE ELECTRIC MOTOR SHALL BE 50 HP, 3.600 RPM, 208 VOLT, 3 PHASE, 60 HZ, NEMA DESIGN B, ODP WITH 1.15 SERVICE FACTOR, LISTED FOR FIRE PUMP
SERVICE. LOCKED ROTOR CURRENT SHALL NOT EXCEED THE VALVES SPECIFIED IN NFPA PAMPHLET NO. 20. THE PUMP AND MOTOR SHALL BE MOUNTED ON A
COMMON STEEL BASE WITH FLEXIBLE COUPLING AND COUPLING GUARD. THE CONTRACTOR SHALL COMPLETELY FILL THE BASE WITH NON-SHRINKING GROUT, IN
ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS, PRIOR TO PUMP START-UP.
INSTALL FLEXIBLE COUPLINGS FOR STRAIN RELIEF WHERE FIRE MAIN PENETRATES
FOUNDATION. REFER TO DETAIL FOR ADDITIONAL INFORMATION.
CONTROL VALVE WITH TAMPER SWITCH. CONTROL VALVE SHALL BE IDENTIFIED AS
FOLLOWS: FIRE VALVE #64, CHILLER PLANT, SPRINKLER/FIRE HOSE SHUT-OFF, MAIN
PAVILION.
TAMPER SWITCH TO BE WIRED TO EXISTING BUILDING FIRE ALARM SYSTEM BY
ELECTRICAL CONTRACTOR.
DATE
4
13
DESCRIPTION
3
NEW 6" FIRE PROTECTION SERVICE, DOWN ALONG WALL AND DOWN INTO NEW FIRE PUMP
ROOM. COORDINATE ROUTING OF NEW MAIN WITH NEW CONDITIONS IN THE FIELD. REFER
TO DRAWING FPB-1 FOR CONTINUATION.
NO.
2
B. FIRE PUMP AND MOTOR
PEERLESS MODEL 6AEF10, HORIZONTAL FIRE PUMP RATED FOR 750 GPM AT (100 PSI) TDH. THE PUMP SHALL ALSO
DELIVER 150 % OF RATED CAPACITY AT NOT LESS THAN %
65OF RATED HEAD. SHUT-OFF HEAD SHALL NOT EXCEED 96 PSI, EXCLUDING SUCTION
PRESSURE. THE PUMP SHALL BE HORIZONTAL SPLIT CASE DOUBLE SUCTION WITH CAST IRON CASING, BRONZE ENCLOSED MPELLER, BRONZE CASING
WEAR RINGS, STEEL SHAFT, BRONZE SHAFT SLEEVES, STUFFING BOX WITH ADJUSTABLE STAINLESS STEEL PACKING GLAND AND BRAIDED PACKING. THE
PUMP SHALL HAVE ANSI 125 LB. SUCTION AND 125 LB DISCHARGE FLANGES. THE CONTRACTOR SHALL PIPE THE PUMP GLAND DRAINS TO THE FLOOR
DRAIN.
SPRINKLER
ROOM
034
RUSSELL AND DAWSON
ARCHITECTURE &
ENGINEERING
1
REVISIONS
A. SCOPE FURNISH AND INSTALL AN AUTOMATIC ELECTRIC FIRE PUMP WITH ACCESSORIES AS MANUFACTURED BY PEERLESS . THE FIRE PUMP AND
CONTROLLER SHALL MEET ALL REQUIREMENTS OF THE NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
PAMPHLET NO. 20 AND SHALL BE UNDERWRITERS LABORATORIES (UL) LISTED, FACTORY MUTUAL (FM) THE CONTRACTOR SHALL FURNISH ALL INTERCONNECTING
PIPING AND FITTINGS AS REQUIRED FOR A COMPLETE INSTALLATION IN ACCORDANCE WITH ALL CODE REQUIREMENTS.
THE SYSTEM SHALL BE DESIGNED FOR A FLOW OF 750 GPM AT A SYSTEM PRESSURE OF 160 PSIG. THE SUCTION PRESSURE AT THE PUMP FLANGE
SHALL BE VERIFIED PRIOR TO INSTALLATION OF FIRE PUMP WITH NEW WATER FLOW TEST TO BE DONE BY THE LOCAL WATER COMPANY.
&
FIRE PUMP ROOM NOTES
Rev.: 13.02
THIS DOCUMENT, THE IDEAS
AND DESIGNS INCORPORATED
THEREIN, AS AN INSTRUMENT OF
PROFESSIONAL SERVICES, IS THE
PROPERTY OF RUSSELL AND
DAWSON LLC, AND MAY NOT BE USED,
IN WHOLE OR IN PART, FOR ANY OTHER
PROJECT OR BY ANY OTHER PERSON
OR CORPORATION OTHER THAN THAT
NAMED HEREON WITHOUT THE
WRITTEN AUTHORIZATION OF RUSSELL
AND DAWSON LLC. ANY SUCH
UNAUTHORIZED USE WILL BE SOLELY
AT THE USER'S RISK AND RUSSELL
AND DAWSON LLC WILL BEAR NO
RESPONSIBILITY ARISING OUT OF
SUCH USE.
© 2013 by Russell and Dawson LLC
FIRE PUMP GENERAL SPECIFICATIONS
SHEET NUMBER:
FP-200