INSTALLATION INSTRUCTIONS FOR LED EMERGENCY LIGHTING FIXTURE READ AND FOLLOW ALL SAFETY INSTRUCTIONS IMPORTANT SAFEGUARDS: IMPORTANT: Let the battery charge up for at least 24 hours. Then normal operation of this unit should take effect. To check, press the “ TEST “ button. The LED lamps on the unit should turn ON. During an electrical power failure, the led lamps will automatically come on for a minimum of 90 minutes. In accordance with NFPA 101, your emergency lighting system must be tested monthly for a minimum of 30 seconds and annually for 90 minutes. Refer to your local codes for any additional requirements that may apply. WARNING: FAILURE TO FOLLOW THESE INSTRUCTIONS AND WARNINGS MAY RESULT IN DEATH, SERIOUS INJURY OR SIGNIFICANT PROPERTY DAMAGE - For your protection, read and follow these warnings and instructions carefully before installing or maintaining this equipment. These instructions do not attempt to cover all installation and maintenance situations. WARNING: RISK OF FIRE - Lamps are hot. Keep combustible material away from hot parts. Observe lamp manufacture’s warnings, recommendations and restrictions on lamp operation and maintenance. Make sure lamps are correctly installed. • A ll service shall be performed by qualified service personnel. This product must be installed and maintained in accordance with the applicable installation codes by a person familiar with the construction operation of the product and the hazards involved. • This product must be installed in accordance with the applicable installation codes and ordinances. • Before wiring to power supply, turn off electricity at fuse or circuit breaker. • Disconnect A.C. power and unplug battery before servicing. • Consult your local building code for approved wiring and installation. • May be used outdoors under cover. (0°C-50°C) • Do not let power supply cord touch hot surfaces. • Do not mount near gas or electric heater. • E quipment should be mounted in Iocations and at heights where it will not readily be subjected to tampering by unauthorized personnel. • T he use of accessory equipment not recommended by the manufacturer may cause an unsafe condition. • Do not use this equipment for other than intended use. • T he AC voltage rating of this equipment is specified on the product label. Do not connect equipment to any other voltage. SAVE THESE INSTRUCTIONS 1300 South Wolf Rd • Des Plaines, IL 60018 • Phone: 847-827-9880 • www.junolightinggroup.com ©2016 Acuity Brands Lighting, Inc. Printed in China Rev 2/13 P3508 pg 1 of 4 INSTALLATION INSTRUCTIONS FOR LED EMERGENCY LIGHTING FIXTURE IMPORTANT: Let the battery charge up for at least 24 hours. Then normal operation of this unit should take effect. To check, press the “TEST” button. The LED lamps on the unit should turn ON. During an electrical power failure, the led lamps will automatically come on for a minimum of 90 minutes. In accordance with NFPA 101, your emergency lighting system must be tested monthly for a minimum of 30 seconds and annually for 90 minutes. Refer to your local codes for any additional requirements that may apply. USE FLEXIBLE CONDUIT ONLY. INSTALLATION CONDUIT 1. Secure back plate to wall surface. Route wires through hole in conduit flange and make conduit connection. For 120V, use black and white wires and for 277V, use red and white wires. J-BOX MOUNTING 1. Feed fixture leads through the back plate and connect to AC power supply (Fig A). For 120V use black and white wires and for 277V, use red and white wires. 2. Attach back plate to J-Box and secure with screws. 3. Complete the battery connection. (Fig. B) 4. Align snaps and push housing directly onto the back plate (Fig. C). Apply continuous AC power and press “TEST” button to check light. 2. Complete the battery connection (Fig. B). 3. Align snaps and push housing directly onto the back plate (Fig. C). Apply continuous AC power and press “TEST” button to check light. WARNING: Unused wires must be capped using enclosed wire nuts. BATTERY CONNECTOR PLUG IN FIG. A FIG. B FIG. C 1300 South Wolf Rd • Des Plaines, IL 60018 • Phone: 847-827-9880 • www.junolightinggroup.com ©2016 Acuity Brands Lighting, Inc. Printed in China Rev 2/13 P3508 pg 2 of 4 INSTALLATION INSTRUCTIONS FOR LED EMERGENCY LIGHTING FIXTURE OPERATION 1. During an electrical power failure, the LED lamps will automatically come on for a minimum of 90 minutes. 2. To test, depress the “TEST” switch. The emergency LED lamps will illuminate. When the switch is released, the lamps will go off. WIRING DIAGRAM REMOTE CAPABLE REGULAR CHARGER BOARD CHARGER BOARD AC INPUT CONNECTOR (MOUNTING PLATE) 277V RED 120V BLACK 0V NOTE: Unused input lead must be properly insulated with wire nut or other approved method WHITE AC INPUT CONNECTOR (MOUNTING PLATE) 277V RED 120V BLACK 0V WHITE YELLOW(+) YELLOW(+) BLUE(-) BLUE(-) YELLOW(+) YELLOW(+) BLUE(-) LAMP BLUE(-) LAMP YELLOW(+) LAMP BLUE(-) LAMP RED BLACK RED BLACK BATTERY TO REMOTE READY TEST BATTERY READY TEST NOTE: Use 18-22 AWG stranded wire to connect remote lamp heads. WARRANTY Juno Lighting Group provides five year limited warranty on LED components from date of purchase. Juno Lighting Group’s obligation is expressly limited to repair or replacement, without charge, at Juno Lighting Group’s factory after prior written return authorization has been granted. This warranty shall not apply to products which have been altered or repaired outside of Juno Lighting Group’s factory. This warranty is in lieu of all other warranties, expressed or implied, and without limiting the generality of the foregoing phrase, excludes any implied warranty of merchantability. Also, there are no warranties which extend beyond the description of the product on the company’s literature setting forth terms of sale. Product Services Phone (888) 387-2212 1300 South Wolf Rd • Des Plaines, IL 60018 • Phone: 847-827-9880 • www.junolightinggroup.com ©2016 Acuity Brands Lighting, Inc. Printed in China Rev 2/13 P3508 pg 3 of 4 INSTALLATION INSTRUCTIONS For Units Equipped with Self Diagnostics Option 1) Introduction Once the unit is properly installed according to the Installation instruction sheet and AC power is supplied, the unit will come ON. The dual-color LED indicator will also come ON, automatically initiating the self-diagnostic test function. The LED indicator points out the current unit status. A STEADY GREEN on the LED indicator indicates a normal service; BLINKING GREEN indicates that the unit is in testing mode; GREEN/RED FLASHING indicates that the battery is charging; RED (STEADY and BLINKING) would indicate a fault or a service alert. Refer to section 3 – Fault Indication for more details. The LED indicator would be OFF when the unit is in Emergency mode. 2) Self – Diagnostic Service The self-diagnostic function is factory preset without any field adjustment. The automatic self-diagnostic feature serves the following tests – a. On-line real time monitoring of battery and lamps: Identifies battery charging, disconnection and failure along with lamp failure. b. Self-testing and a 30-second discharge once every 30 days (conforming to NFPA code requirements), after AC power has been supplied for a minimum of 24 hours. c. Self-testing and a 30-minute discharge once every 180 days, after AC power has been supplied for a minimum of 24 hours. d. Self-testing and a 90-minute discharge once every 365 days (conforming to NFPA code requirements), after AC power has been supplied for a minimum of 24 hours. 3) Fault Indication Function Unit is in normal mode Battery Disconnected LED Indication Battery Recharge STEADY Green STEADY Red Red and Green (flashing alternatively) Battery Recharge Failure* FLASHING Red Battery Failure** Red BLINKING ‘2’ times LAMP Failure Red BLINKING ‘4’ times Remote LAMP Failure Red BLINKING ‘5’ times * A battery recharge failure will come up if the battery is NOT able to recharge within the 24hrs charging time ** A battery failure will come up if the battery is NOT able to operate the lamps for the period of a discharge test 4) Manual Testing This unit also provides for manual testing by pushing the test switch in a specific pattern. The different patterns and the resulting tests are listed in the table below. ACTION REACTION AND LED INDICATION Push test button once (within 2 seconds) 30-second test; FLASHING Green Push test button ‘2’ times (within 2 seconds) 30-minute test; Green BLINKING ‘2’ times Push test button ‘3’ times (within 2 seconds) 90-minute test; Green BLINKING ‘3’ times Push & Hold test button (3-5 seconds) System Interruption Push & Hold test button (more than 6 seconds) System Reset 5) Operation During an electrical power failure, the lamps will automatically come ON for a minimum of 90 minutes. To test this unit, the battery needs to be charged initially for 2 hours before depressing the test switch (to do manual test). On pressing the test switch, the Lamps will illuminate. The Lamps will turn OFF after 30-sec /30-min /90-min depending on the number of times the switch has been pressed. 1300 South Wolf Rd • Des Plaines, IL 60018 • Phone: 847-827-9880 • www.junolightinggroup.com ©2016 Acuity Brands Lighting, Inc. Printed in China Rev 2/13 P3508 pg 4 of 4