Instruction Manual Microwave 328-24 Series Non-Contact Point Level System HiTECH Technologies, Inc. 301 Oxford Valley Road, Bldg 505 Yardley, PA 19067-7711 USA Tel: 215. 321. 6012 Fax: 215.321. 6067 www.hitechtech.com info@hitechtech.com Wiring Calibration Transmitter After installation is complete, adjust the following with the sensor in the UNBLOCK state. Receiver Transmitter De-energized 1 2 3 • After supplying 24 VDC, the POWER light (Green) will come on. Receiver 1 2 3 4 5 6 • After supplying 24 VDC, either the red BLOCKED LED light or the green UNBLOCKED light will come on. NC COM NO + - + Ground Power supply 24 VDC. - Ground • Turn mode selection switch A to BLOCK, turn the sensitivity switch S to L and turn the time delay potentiometer T fully counterclockwise (minimum). Power supply 24 VDC. Selection of detection mode and relay configuration. Beam broken BLOCKED Detection mode • Set the sensitivity potentiometer S to minimum. Beam unbroken UNBLOCKED Terminal number 4&5 5&6 4&5 5&6 Unpowered state Closed Open Closed Open Non-detecting state Open Closed Closed Open Detecting state Closed Open Open Closed Powered state Function of receiver switches and potentiometers S SENSITIVITY H L C A UNBLOCK BLOCK T F DELAY ON OFF 1 2 3 4 5 6 Description Part Name A T O F S C W O W Time delay adjustment BLOCK: Outputs on broken beam UNBLOCK: Outputs on unbroken beam 0.1 - 10 sec. delay after state changes Output indicator ON (red) : Illuminates on output Output indicator OFF (green) : Illuminates on no output Sensitivity switch H:High L:Low Mode selection switch Sensitivity potentiometer To adjust sensitivity Terminals • The red LED output indicator ON O will come on. • Slowly turn the sensitivity potentiometer C clockwise until the green output indicator OFF F comes on. This is to determine the actuation point. If this sensitivity setting is very high (more than 7 on the potentiometer switch the sensitivity switch S to H and repeat the above procedure. • For applications involving mainly paper and/or where there is little accumulation on the sensing head, increment the potentiometer S by 1 or 2 levels only. On the other hand, where the application involves material with a moderately high water content, i.e. wet garbage etc, then the potentiometer should be incremented by 3-4 steps. However, if the object to be detected absorbs microwaves well, (i.e. coal), then the rpotentiometer S can be incremented by more than 5 steps. • For an application where material is introduced from above, a suitable "delay" time must be provided to to avoid instantaneous detection of the falling material. • To use UNBLOCK output mode, switch the mode selection switch A to UNBLOCK.