Section VII. Technical Specifications 66 Technical Specifications LOT 1 – (JFPR-01-s2014) Conductors (44,000 Meters Conductor, Bare, ACSR #4/0, AWG 6/1) (44,000 Meters Conductor, Bare, ACSR #2/0, AWG 6/1) Bidders must state under the Column “Statement of Compliance” either “Comply” or “Not Comply” against each of the individual parameters of each Specification stating the corresponding performance parameter of the equipment offered. Statements of “Comply” or “Not Comply” must be supported by evidence in a Bidders Bid and cross-referenced to that evidence. Evidence shall be in the form of manufacturer‟s un-amended sales literature, unconditional statements of specification and compliance issued by the manufacturer, samples, independent test data etc., as appropriate. A statement that is not supported by evidence or is subsequently found to be contradicted by the evidence presented will render the Bid under evaluation liable for rejection. A statement either in the Bidders statement of compliance or the supporting evidence that is found to be false either during Bid evaluation, post-qualification or the execution of the Contract may be regarded as fraudulent and render the Bidder or supplier liable for prosecution subject to the provisions of ITB Clause 3.1(a)(ii) and/or GCC Clause 2.1(a)(ii) . SPECIFICATIONS STATEMENT OF COMPLIANCE GENERAL: ACSR conductors shall conform in all respects to the dimensional and performance requirements of this document, which covers: 1. Steel core wire 2. Aluminum wire The ACSR conductors shall be classified as Class A as designated in American Society for testing and materials B232. STEEL CORE: Material: The steel wire shall be fabricated from steel obtained by the open-hearth, electric furnace, of basic oxygen process and conforms to the chemical composition specified in 67 BIDDER’S BID / FORM OF EVIDENCE Section 3 of ASTM B498 as follows: Testing: The steel wire shall be tested in accordance with Section 5, 6 and 10 of ASTM B498. Corrosion Protection: The steel wire shall be coated with zinc to Class A requirement with coating weight described in Table 4 of ASTM B498. Additional protection for ACSR conductor against corrosion of the steel core shall be provided by use of a suitable corrosion inhibition, grease or oil. ALUMINUM WIRES: Materials: The round aluminum sire shall be drawn from rods that conform to the chemical requirement of Tab le 2, ASTM B230. Testing: The aluminum wire shall have tensile strengths depending on temper as shown in Table 1 of ASTM B233. Resistivity: The electrical resistivity limits and values of the aluminum rods are presented in Table 4 of ASTM B230. LAY FACTOR: The lay factor of the aluminum wire shall be not less than 12 nor more than 14.5 times the outside diameter of the conductor. The preferred lay factor is 13 times the diameter, with the lay in a right hand direction. CONSTRUCTION: The number and diameter of aluminum and steel wires and the stranding shall conform to the requirements of Table 1, 2 and 3 of ASTM B232. 68 CONDUCTOR STRENGTH: The rated strength shall be the aggregate strength of the steel and aluminum wires determined by the methods described in Section 9.1 of ASTM B232. WEIGHT AND ELECTRICAL RESISTANCE: The weight and electrical resistance of the stranded conductor shall be determined by the methods described in Section 11 of ASTM B233. CHARACTERICTICS: ACSR conductors shall have the following characteristic: FINISH: The conductor shall be free of imperfections, sharp protrusions and blemishes not consistent with good commercial practice. SPECIFICATIONS STATEMENT OF COMPLIANCE TESTS & INSPECTION: The manufacturer shall conduct conductor tests and inspections in accordance with Section 16 of ASTM B232 or IEC 888, in so far as applicable. NEA reserves the right to witness factory tests and inspections and shall request test reports. The manufacturer shall also conduct conductor reel tests and inspections and submit test reports before shipment to verify that the reel and lagging comply with the requirements of this Standard. NEA shall also have the prerogative to inspect conductor reels at any time to ensure compliance of this standard. Non- conforming reels and lagging are unacceptable. 69 PACKAGING AND SHIPPING: Conductor shall be shipped on non-returnable reels manufactured from “aluminum steel” or export quality preservative treated wood lagging. Wood reels and all lagging shall be constructed from new lumber which shall be square sawn, be of smooth surface, with not splits, warps, crooks, loose fibers, decay or insect infestation. The lumber used for wood reels and all lagging shall be preservative treated in accordance with “American Wood Preserves Associates Standards”. REEL READY FOR SHIPPING 70 (47,000 Meters Conductor, Insulated, ACSR #2/0, AWG 6/1) Bidders must state under the Column “Statement of Compliance” either “Comply” or “Not Comply” against each of the individual parameters of each Specification stating the corresponding performance parameter of the equipment offered. Statements of “Comply” or “Not Comply” must be supported by evidence in a Bidders Bid and cross-referenced to that evidence. Evidence shall be in the form of manufacturer‟s un-amended sales literature, unconditional statements of specification and compliance issued by the manufacturer, samples, independent test data etc., as appropriate. A statement that is not supported by evidence or is subsequently found to be contradicted by the evidence presented will render the Bid under evaluation liable for rejection. A statement either in the Bidders statement of compliance or the supporting evidence that is found to be false either during Bid evaluation, post-qualification or the execution of the Contract may be regarded as fraudulent and render the Bidder or supplier liable for prosecution subject to the provisions of ITB Clause 3.1(a)(ii) and/or GCC Clause 2.1(a)(ii). SPECIFICATIONS SCOPE: This standard establishes the dimensional and performance requirements of bare coated steel-reinforced concentriclay-stranded aluminum conductors (ACSR), Crosslinked polyethylene insulated (black colored), 600V to be used on Coop distribution lines. This conductor is made of round aluminum wires wrapped around a central zinc-coated round steel-wire core. STATEMENT OF COMPLIANCE GENERAL: ACSR conductors shall conform in all respects to the dimensional and performance requirements of this documents, which covers: 1. Steel core wire. 2. Aluminum wire: The ACSR conductors shall be classified as Class A as 71 BIDDER’S BID / FORM OF EVIDENCE designated in ASTM B232 3. Steel Core: The steel core shall consist of wires which meet the following requirements: (a) Material: The steel wire shall be fabricated from steel obtained by the openhearth, electric furnace. (b) Testing: The steel wire shall be tested in accordance with Section 5, 6 and 10 of ASTM B498. (c) Corrosion Protection: The steel wire shall be coated with zinc to Class A requirements with coating weight described in Table 4 of ASTM B498 [2]. Additional protection for ACSR conductor against corrosion of the steel core shall be provided by use of a suitable corrosion inhabitation, grease or oil. (d) Aluminum Wires: 1. Materials: The round aluminum wire shall be drawn from rods that conform to the chemical requirements of table 2, ASTM B230 [3] 2. Testing : The aluminum wire shall have tensile strengths depending on temper as shown in Table 1 of ASTM B233 [4] 3. Resistivity: The electrical resistivity limits and values of the aluminum rods are presented in Table 4 of ASTM B230 [3]. 4. General : Aluminum wires used shall meet the requirements of ASTM B230 [3]. (e) Construction: The number and diameter of 72 aluminum and steel wires and the stranding shall conform to the requirements of Table 1, 2 and 3 of ASTM B232. [1] (f) Conductor Strength: The rated strength shall be the aggregate strength of the steel and aluminum wires determined by the methods described in Section 9.1 of ASTM [1]. (g) Weight and Electrical Resistance The weight and electrical resistance of the stranded conductor shall be determined by the methods described in Section 11 of ASTM B232 [1]. Insulation Jacket Thickness of cables are: Conductor Size AWG 2/0 Insulation Thickness (mils) 60 73 SPECIFICATIONS Performance Requirement: The cable shall be tested to demonstrate compliance with the requirements of Section 6 of ICEA S-66-524 (NEMA WC7, [14], in so far as applicable. PACKAGING AND SHIPPING: Conductor shall be shipped on non-returnable reels manufactured from “aluminum steel” or export quality preservative treated wood lagging. Wood reels and all lagging shall be constructed from new lumber which shall be square sawn, be of smooth surface, with not splits, warps, crooks, loose fibers, decay or insect infestation. The lumber used for wood reels and all lagging shall be preservative treated in accordance with “American Wood Preserves Associates Standards”. REEL READY FOR SHIPPING 74 Hardware Bidders must state under the Column “Statement of Compliance” either “Comply” or “Not Comply” against each of the individual parameters of each Specification stating the corresponding performance parameter of the equipment offered. Statements of “Comply” or “Not Comply” must be supported by evidence in a Bidders Bid and cross-referenced to that evidence. Evidence shall be in the form of manufacturer‟s un-amended sales literature, unconditional statements of specification and compliance issued by the manufacturer, samples, independent test data etc., as appropriate. A statement that is not supported by evidence or is subsequently found to be contradicted by the evidence presented will render the Bid under evaluation liable for rejection. A statement either in the Bidders statement of compliance or the supporting evidence that is found to be false either during Bid evaluation, post-qualification or the execution of the Contract may be regarded as fraudulent and render the Bidder or supplier liable for prosecution subject to the provisions of ITB Clause 3.1(a)(ii) and/or GCC Clause 2.1(a)(ii). All line hardwares / materials shall meet the performance requirements application criteria and manufacturing tolerances passed on the following standards and other applicable standards. STATEMENT OF SPECIFICATIONS COMPLIANCE ANSI C B5. 1-1979 American National Standard for Galvanized Steel bolts and nuts for overhead line construction. ANSI C135. 31-1980 American National Standard for Galvanized ferrous Single and Double Upset Spool Insulator bolts for Overhead line Construction. ANSI C29.3-1986 American National Standard for Wet-process porcelain insulator (Spool type) ASTM A663-82 Standard Specification for steel bars, carbon, merchant quality, mechanical properties. ASTM A675-82 Standard Specification for steel bars, carbon, hot wrought, special quality, mechanical properties. ASTM A675-82 Standard Specification for steel bars, carbon, hot wrought, special quality, mechanical properties. ASTM A570-79 Standard Specification for hot-rolled, carbon, steel sheet and strip, structural quality. MATERIALS QTY 75 UNIT STATEMENT OF COMPLIANCE Attachment, Guy, Malleable Type With 11/16" Hole Diameter Bolt, Carriage 3/8" X 4-1/2" 758 pcs. 334 pcs. Bolt, Double Arming, 5/8" X 22" Bolt, Double Upset, 5/8" X 10" Bolt, Oval Eye, 5/8" X 9" Bolt, Oval Eye, 5/8" X 10" Bolt, Oval Eye, 5/8" X 12" Bolt, Oval Eye, 5/8" X 18" Bolt, Machine, 1/2" X 6" Bolt, Machine, 1/2" X 12" Bolt, Machine, 5/8" X 8" Bolt, Machine, 5/8" X 9" Bolt, Machine, 5/8" X 10" Bolt, Machine, 5/8" X 12" Bolt, Machine, 5/8" X 14" Bolt, Single Upset, 5/8" X 8" Bolt, Single Upset, 5/8" X 10" Brace, Crossarm, 28", Steel Brace, Sidearm, Vertical, 50 inches Brace, Sidearm, Diagonal, 7 Feet Bracket, Clevis Deadend Without Spool Clamp, Hot Line, #2 - #4/0 ACSR Main to #2 - #4/0 Clamp, Anchor Rod Bonding, Single Eye Clamp, Loop Deadend, #2/0 ACSR Clamp, Deadend Strain, #2/0 ACSR, Socket Eye Fitting included Clamp, Guy Straight, 3 Bolt, Heavy Duty Steel Clamp, Suspension, Aluminum Alloy Clevis, 2 Bolts, #2/0 ACSR Max, Socket Eye Fitting included Clevis, Secondary Swinging Without Spool Shackle, Anchor, Forged Steel, Galvanized, see drawing in Annex “B” Clip, Groundwire Connector, Compression, #2 - #4/0 ACSR Run To #6 - #2 Connector, Compression, #2/0 - #4/0 ACSR Run To #2/0 - #4/0 Connector, Ground Rod (Clamp) For 5/8" Steel Rod Connector, Split Bolt Pin, Crossarm, Steel, 5/8" X 10-3/4" Hook, Guy Insulator, Pin Type, Polymer, ANSI, Class 55 - 3 Insulator, Pin Type, Polymer, ANSI, Class 55 - 5 164 403 538 1,130 90 60 10 5 1,039 103 504 161 64 140 298 334 5 5 190 229 758 2,902 448 pcs. pcs. pcs. pcs. pcs. pcs. pcs. pcs. pcs. pcs. pcs. pcs. pcs. pcs. pcs. each pcs. pcs. pcs. pcs. pcs. pcs. pcs. 1,560 13 pcs. pcs. 1,469 73 pcs. pcs. 748 2,744 pcs. pcs. 601 pcs. 404 886 146 43 250 146 pcs. pcs. pcs. pcs. pcs. pcs. 76 These items must be “Forged Type” Insulator, Spool, 1-3/4", ANSI, Class 53 - 2 Insulator, Spool, 3", ANSI, Class 53 - 4 Insulator, Suspension, 6", Clevis Type Polymer Nut, Eye, 5/8", Conventional Nut, Lock, Mf Type, 3/8" Nut, Lock, Mf Type, 1/2" Nut, Lock, Mf Type, 5/8" Pin, Pole Top, Channel, 1" Thread, 20" Long, Nylon Thread Plate, Grounding, Pole Butt Plate, Guy Rod, Anchor, Threaded, Single Eye, 5/8" X 7' Rod, Armor, Preformed, #2/0 ACSR, Single Support Rod, Armor, Preformed, #2/0 ACSR, Double Support Rod, Tapping, Preformed, #2/0 ACSR Rod, Ground Steel, Galvanized, 5/8" X 10' Lag, Screw, 1/2" X 4" Spacer, Pipe, 3/4" X 1-1/2" Staple, Groundwire, 1/2" X 2" Washer, Square, Flat, 2-1/4" X 2-1/4" X 3/16", 13/16" Diameter Hole Washer, Square, Flat, 4" X 4" X 1/2" With 7/8" Diameter Hole Washer, Round, 1-3/8" Diameter With 9/16" Diameter Hole Wire, Tie, Aluminum Alloy, Soft, #4 AWG Wire, Tape, Armor, Aluminum Alloy, 0.5 " X 0.3" Wire, Grounding, Aluminum Alloy, 3 Strand, #4 AWG Wire, Grounding, Galvanized, 3 Strand, 5/16" Diameter Wire, Guy, Steel, 3/8", 7 Strand Rectangular Crossarm, Steel, 8 ft. x 3” x 4 ”, gauge 3.2mm, Bare Metal Thickness, Hot Dip Galvanized, 86 Microns 77 1,189 1,310 922 275 334 14 4,714 250 pcs. pcs. pcs. pcs. pcs. pcs. pcs. pcs. 349 43 764 1,357 50 229 404 172 58 703 4,946 pcs. pcs. pcs. sets sets sets pcs. pcs. pcs. pcs. pcs. 272 pcs. 14 pcs. 8,299 1,512 9,017 ft. ft. ft. 3,492 ft. 39,432 176 ft. pcs. LOT 2 – (JFPR-02-s2014) Steel Poles Bidders must state under the Column “Statement of Compliance” either “Comply” or “Not Comply” against each of the individual parameters of each Specification stating the corresponding performance parameter of the equipment offered. Statements of “Comply” or “Not Comply” must be supported by evidence in a Bidders Bid and cross-referenced to that evidence. Evidence shall be in the form of manufacturer‟s un-amended sales literature, unconditional statements of specification and compliance issued by the manufacturer, samples, independent test data etc., as appropriate. A statement that is not supported by evidence or is subsequently found to be contradicted by the evidence presented will render the Bid under evaluation liable for rejection. A statement either in the Bidders statement of compliance or the supporting evidence that is found to be false either during Bid evaluation, post-qualification or the execution of the Contract may be regarded as fraudulent and render the Bidder or supplier liable for prosecution subject to the provisions of ITB Clause 3.1(a)(ii) and/or GCC Clause 2.1(a)(ii). STATEMENT OF COMPLIANCE SPECIFICATION S C O P E : This specification establishes the physical characteristics and performance requirements of steel poles for use on Eastern Samar Electric Cooperatives, Inc. electric distribution system. Poles furnished to NEA specifications shall conform in all respects to the performance of this standard. The text, figures and references of other standards supplement each other and shall be considered part of this standard. The poles are to be of the embedded type and not to require a special foundation. MATERIAL: Steel poles shall be fabricated from structural quality hot rolled steel which conforms to ASTM A570-79, 'Standard Specification for HotRolled Carbon Steel Sheet and Strip, Structural Quality.' FINISHING: The pole shall be cleaned of scale, rust, oil, paint and other surface contaminants and then rinsed in an alkaline cleaning bath. The steel 78 BIDDER’S BID / FORM OF EVIDENCE shall then be bathed in a diluted acid (sulfuric or hydrochloric) bath for at least five minutes. Just prior to galvanizing, the acid cleaned steel shalt be immersed in a flux solution of 30% zinc ammonium chloride with wetting agents and maintained at 65 deg. C until galvanizing is completed. Steel poles shall be hot dip galvanized in accordance with ANSVASTM A153-82, Standard Specification for Zinc Coating (Hot Dip) on Iron and Steel Hardware. This standard requires a minimum zinc coating of 610 grams / sq. m. The coating shall be continuous, smooth, reasonably uniform in thickness and free of blemishes and other imperfections which are inconsistent with commercial practice. Galvanized articles shall be free from coated areas, blisters, flux deposits, acid and black spots, and dross inclusions. Lumps, projections, globules, or heavy deposits of zinc which will interfere with the intended use of the material will not be permitted. All holes shall be clean and reasonably free from excess zinc. DIMENSION: The poles are specified in accordance with the ANSI Standard for classification of wood poles; that is by length andstrength class. The first number is the overall length in feet and the second numberis the designation of the strength class. A 35 foot pole with a strength classification of 5 is abbreviated 35/5.The diameter of the pole at ground line shall be similar to an equivalent wood pole of that height and class to assure that the earth surrounding the pole will provide the necessary resistance to develop the strength of the pole. S T R E N G T H : The strength of the pole is specified as force acting at 90 degrees to the center line of the pole at a point two feet from the top of the pole. The amount of force in pounds that each classification must be able to withstand without damage is shown on the table below; POLE STRENGTH AND GROUND LINE DIMENSION POLE STRENGTH PIECES LENGTH 30/2 3700 588 35/2 3700 362 40/2 3700 40 Pole length in feet and strength classification. 79 Pole strength designated as a force in pounds acting at right angles to the centerline of the pole at a point two feet below the top of the pole, and is applicable to both axes of the pole cross section. STATEMENT OF COMPLIANCE SPECIFICATIONS MARKINGS: Each steel pole shall be identified by the supplier by stamping into the pole, prior to coating, with letters not less than 1/2" high squarely on the face of the pole at ten (10) feet from the butt of the pole. The following information shall be stamped into the pole: Supplier's name Month and year of manufacture Length of pole Class of pole Type of coating Pole production or serial number The marks shall be legible after application of the protective coating. INSPECTION AND TESTING: The manufacturer shall conduct factory tests to verify that the poles comply with the requirements of this standard. NEA reserves the right to witness ANY OR ALL factory tests and the Supplier shall notify NEA fifteen (15) days before each test is to be conducted. The Supplier is required to furnish NEA a copy of all test reports. NEA expects to commission an internationally recognized third party, independent inspection and/or testing agency for independent inspection and/or testing at the factory, prior to shipping or after receipt of the poles in the Philippines. The galvanizing shall be tested in accordance with ASTM Standard A 123-89. Any pole that fails an inspection is automatically rejected and additional poles from that lot must be tested in accordance with the following testing schedule: TESTING SCHEDULE: One pole out of every lot of 25 poles shall be tested to 50 percent of its rated strength and a record kept of the deflection after a two (2) minute hold at each multiple of 10 percent. This is a non-destructive test unless it shows some weakness indicating the pole could not meet the strength requirements and then it is to be 80 carried to destruction. One pole out of every lot of 100 poles shall be tested to destruction. If it fails at less than rated strength, then four additional poles from the same lot shall be tested to rated load. If they all pass, the lot is considered to have passed that test. If two or more of the additional test poles fail, the entire lot will be rejected. If only one of them fails, ten more from the same lot may be tested to rated load. If there are no failures, the remaining poles of that lot are considered to have passed that test, however, if there are any failures in these ten, and then the lot is automatically rejected. PROCEDURE Proof Load Test: Initially set the dynamometer to a load of 40% of the minimum breaking load. Apply load steadily until it reaches 40%. Hold for two (2) minutes. Note for the development of weld cracks or splitting. If any appear at the 40 % load, the pole is considered to have FAILED the test and the batch represented shall be rejected. Break Load Test: Initially set the dynamometer to a load of 40% of the minimum breaking load. Apply load steadily until it reaches 40%. Hold for one (1) minute. Note for the development of weld splits or cracks. If cracks appear at 40% load, the pole is considered to have failed the test. The batch represented shall be rejected. If no cracks or splits appear after the application of 40% load, set the dynamometer to a load of 50% of the minimum breaking load. Apply load steadily until it reaches 50%. Hold for one (1) minute. Note for the development of cracks or splits. If found the pole is considered to have failed the test. Release load to zero. Upon removal of the load, immediately increase the load gradually to 70% of the minimum breaking load and hold for two (2) minutes. Note for the development of additional cracks or splits. Again remove the load and sussessivety increase the load by an amount equal to 10% of the minimum 81 breaking load up to 80% and thereafter increase by 5% of the minimum breaking load until failure occur, hold each load for two (2) minutes. Measure load at the point of failure to the nearest 5 kilograms. The pole is considered to have failed the break load test if it yielded at less than the minimum breaking load. REPORT For tests conducted at source, the test shall be prepared by the manufacturer in coordination with the witnessing inspection engineer or test engineer. The following test data shall be collected and recorded in accordance with the attached format: Manufacturer's serial numbers of the test pole sample. Pole Class Date Manufactured Date Tested Pole dimensions Load, including point of failure Deflection Recovery Galvanizing thickness measured at ground line, pole butt and pole top Height Thicknes (ft.) s (mm) Butt Diameter (mm) Tip Desig Diamet n er Load (mm) (kg) Yield Zinc Stress Coating (MPA) (microns) 30 3.5 226 127 750 345 86 35 3.5 248 127 750 345 86 40 3.5 317 127 750 345 86 82 Logo: The bidder shall provide a 50cm×30cm high quality sticker with reflective face painted with JFPR and ODA logo for each pole 83 84 85 86 87 88 89 90 91 92 93 94 772 Expanding Anchor Bidders must state under the Column “Statement of Compliance” either “Comply” or “Not Comply” against each of the individual parameters of each Specification stating the corresponding performance parameter of the equipment offered. Statements of “Comply” or “Not Comply” must be supported by evidence in a Bidders Bid and cross-referenced to that evidence. Evidence shall be in the form of manufacturer‟s un-amended sales literature, unconditional statements of specification and compliance issued by the manufacturer, samples, independent test data etc., as appropriate. A statement that is not supported by evidence or is subsequently found to be contradicted by the evidence presented will render the Bid under evaluation liable for rejection. A statement either in the Bidders statement of compliance or the supporting evidence that is found to be false either during Bid evaluation, post-qualification or the execution of the Contract may be regarded as fraudulent and render the Bidder or supplier liable for prosecution subject to the provisions of ITB Clause 3.1(a)(ii) and/or GCC Clause 2.1(a)(ii). MATERIALS QTY Anchor, Expanding, 8,000 Pounds, 772 8 Way, Hot Dip Galvanized Steel, 8mm Galv. Steel, Base Plate Inches, 8", top plate sq. inch 135 UNIT pcs. 95 STATEMENT BIDDER’S BID / OF FORM OF COMPLIANCE EVIDENCE LOT 3 – (JFPR-03-s2014) Kwh Meters (76 pieces Single Phase Socket Type) Bidders must state under the Column “Statement of Compliance” either “Comply” or “Not Comply” against each of the individual parameters of each Specification stating the corresponding performance parameter of the equipment offered. Statements of “Comply” or “Not Comply” must be supported by evidence in a Bidders Bid and cross-referenced to that evidence. Evidence shall be in the form of manufacturer‟s un-amended sales literature, unconditional statements of specification and compliance issued by the manufacturer, samples, independent test data etc., as appropriate. A statement that is not supported by evidence or is subsequently found to be contradicted by the evidence presented will render the Bid under evaluation liable for rejection. A statement either in the Bidders statement of compliance or the supporting evidence that is found to be false either during Bid evaluation, post-qualification or the execution of the Contract may be regarded as fraudulent and render the Bidder or supplier liable for prosecution subject to the provisions of ITB Clause 3.1(a)(ii) and/or GCC Clause 2.1(a)(ii). PARAMETERS SINGLE PHASE KWH METER SPECIFICATIONS Accuracy class Class 0.5 or better Wire 2 wire Volt 240 V Current Range 0.1 A to 200 A Frequency 60 Hz Register Type LCD Cover Plastic Base Plastic Phase Voltage Power Consumption Current Power Consumption 1 phase < 2.5 VA, 1w < 0.25 VA 96 STATEMENT OF COMPLIANCE BIDDER’S BID / FORM OF EVIDENCE KWH,KW, Current, Voltage LCD Display (7 pieces Three Phase Socket Type) PARAMETERS 3 PHASE KWH METER SPECIFICATIONS Accuracy CA 0.2 or better Class 200 Wire 4 wire Volt 120-480V Test Amper 30A Frequency 60 Hz Register Type LCD Meter Constant (Kh) 21.6 Cover Plastic Vbase Plastic Form FM16S Phase 3 Phase TOU Ready Soft Switch A, K, N, P LCD Display Programmable STATEMENT OF COMPLIANCE BIDDER’S BID / FORM OF EVIDENCE (12 pieces Three Phase Bottom Type) PARAMETERS 3 PHASE KWH METER SPECIFICATIONS Accuracy CA 0.5 or better Class 20 Wire 4 wire Volt 120-480V Test Amper 2.5A Frequency 60 Hz Register Type LCD Meter Constant (Kh) 1.8 Cover Plastic Vbase Plastic Form FM48A Phase 3 Phase TOU Ready Soft Switch A, K, N, P LCD Display Programmable STATEMENT OF COMPLIANCE 97 BIDDER’S BID / FORM OF EVIDENCE SPECIFICATIONS STATEMENT OF COMPLIANCE Transparent glass cover (good plastic) for durability and easy reading. Glass cover shall effectively seal the meter to prevent the entry of rain and dust into its internal parts. It shall be designed to operate continuously for the normal life of the meter in an unsheltered outdoor tropical location exposed to the elements without rust, corrosion, or other damage which might adversely affect the meters‟ accuracy or reliability. The kwh meter shall have “ESAMELCO” printed in English with black letters at least 3/8, to be checked (3.2 cm) high on the face plate. Bidder shall submit dimensional drawings, pictures, catalog information, data on starting watts and losses, characteristic performance curves and instruction bulletins for adjustment, installation and storage meters. INSPECTION: The manufacturer shall perform the necessary inspection and test to determine if the watt-hour meters comply with the specifications and supply certified test reports that give proof of conformance to the performance standards in all respects. All information, test reports, instruction look, etc., shall be written in English. NEA reserves the right to witness factory tests. PACKAGING: The kWh meters shall be individually packaged in a suitable container for a tropical climate. Each container (box) shall be clearly labeled with manufacturer name and catalog no. The purchaser reserves the right to check, and test the meters after they arrive in the cooperative, ESAMELCO, if they are found not to conform to the standard in all respects, they are automatically rejected. The kWh meter shall have the following features: a. Anti-pilferage capability (pilferage proof) b. Tamper proof-can measure reverse current c. Wrong wiring alarm 98 d. Current flow display e. With provisions for sealing using wire and security seals. f. Temperature - Can withstand temperature of -20°c to +70°c - Humidity of up to 95% non-condensing g. Voltage- can withstand to 180 volts uo to 290 volts. h. Multiple level password permission of meter i. With back light display j. With built-in battery for LCD display and back-up battery k. Large digit LCD display, 16 x 7.1 mm (with backlight-optional) l. TOU programmable ready m. Watt lost= 0.5 watt or better Starting watts= less than 5 watts - Measured/display: - True RMS voltage - True RMS current - Calendar - Time n. 5 to 7 Digits display ACCESSORIES Bidders must state under the Column “Statement of Compliance” either “Comply” or “Not Comply” against each of the individual parameters of each Specification stating the corresponding performance parameter of the equipment offered. Statements of “Comply” or “Not Comply” must be supported by evidence in a Bidders Bid and cross-referenced to that evidence. Evidence shall be in the form of manufacturer‟s un-amended sales literature, unconditional statements of specification and compliance issued by the manufacturer, samples, independent test data etc., as appropriate. A statement that is not supported by evidence or is subsequently found to be contradicted by the evidence presented will render the Bid under evaluation liable for rejection. A statement either in the Bidders statement of compliance or the supporting evidence that is found to be false either during Bid evaluation, post-qualification or the execution of the Contract may be regarded as fraudulent and render the Bidder or supplier liable for prosecution subject to the provisions of ITB Clause 3.1(a)(ii) and/or GCC Clause 2.1(a)(ii). Parameters Primary Voltage BIL Frequency Ratio Acc. Class Current Transformer 15KV 110KV 60Hz 15/10:5 0.3 Statement of Compliance 99 Potential Transformer 15Kv 110Kv 60Hz 70:1 0.3 Statement of Compliance RF Primary Bushing 2.0 Double Single SPECIFICATIONS L Softswitch kWh Meter Seal, Twist Seal kWh Meter Box, Stainless Steel Standard Meter Box for Form 48A, Hub 1" (upper position) Socket Meter Base, Rectangular, 4 Jaws, 200 Amperes Continuous, 600 Volts Socket Meter Base, Rectangular, 7 Jaws, 200 Amperes Continuous, 600 Volts Test Block, 30 Amperes, 600 Volts, 10 color Weather Head Cap, 1" Weather Head Cap, 2"x8 inches diameter, G.I. Wire, Stranded, Single, #10 AWG, THHN or THWN 600 volts Miscellaneous Accessories (male adaptor, solvent, t-connector) Bushing Reducer, G.I., 2" x 1" Nipple, G.I., 2" Dia. X 8" L QTY 76 158 12 pcs. pcs. pcs. 75 pcs. 8 pcs. 12 pcs. 19 76 pcs. pcs. 19 19 boxe s pcs. 7 76 pcs. pcs. 100 STATEMENT OF COMPLIANCE BIDDER’S BID/ FORM OF EVIDENCE LOT 4 – (JFPR-04-s2014) Distribution Transformer, Accessories and Protection Bidders must state under the Column “Statement of Compliance” either “Comply” or “Not Comply” against each of the individual parameters of each Specification stating the corresponding performance parameter of the equipment offered. Statements of “Comply” or “Not Comply” must be supported by evidence in a Bidders Bid and cross-referenced to that evidence. Evidence shall be in the form of manufacturer‟s un-amended sales literature, unconditional statements of specification and compliance issued by the manufacturer, samples, independent test data etc., as appropriate. A statement that is not supported by evidence or is subsequently found to be contradicted by the evidence presented will render the Bid under evaluation liable for rejection. A statement either in the Bidders statement of compliance or the supporting evidence that is found to be false either during Bid evaluation, post-qualification or the execution of the Contract may be regarded as fraudulent and render the Bidder or supplier liable for prosecution subject to the provisions of ITB Clause 3.1(a)(ii) and/or GCC Clause 2.1(a)(ii). SPECIFICATIONS: ELECTRICAL CHARACTERISTICS Statement of Compliance Quantity 20 18 35 51 7620 v 7620 v/ 13200Y v 7620v/ 13200Y v 7620 v/ 13200Y v Secondary (v) 240 240 240 240 Frequency (H2) 60 Hz 60 Hz 60 Hz 60 Hz 95 95 95 30 30 30 2 2 2 2 ± 10% tolerance ± 10% tolerance ± 10% tolerance ± 10% tolerance 36 50 80 105 95 T of compliaBIL (KV) HV LV 30 % Impedance Load losses (watts) 101 25 Statement of Compliance 10 Voltage Primary 15 Statement of Compliance KVA RATING 37.5 Statement of Compliance No load-losses (watts) 120 195 290 360 Audible Sound Level (decibels) 48 db 48 db 48 db 48 db Cooling Class OA OA OA OA No. of bushings 1 2 2 2 Polarity Additive Additive Additive Additive SPECIFICATIONS: ELECTRICAL CHARACTERISTICS KVA RATING 50 Quantity 15 Voltage Primary Statement of Compliance Statement of Compliance 75 100 2 1 7620v/ 13200Y v 240 Secondary (v) 240 7620 v/ 13200Y v 240 Frequency (H2) 60 Hz 60 Hz 60 Hz BIL (KV) HV LV 95 95 95 30 30 30 2 2 2 ± 10% tolerance ± 10% tolerance ± 10% tolerance Load losses (watts) 135 190 210 No load-losses 500 650 850 Audible Sound Level (decibels)48 db 48 db 48 db Cooling Class OA OA OA No. of bushings 2 2 2 Polarity Additive Additive Additive 7620 v % Impedance (watts) SPECIFICATIONS STATEMENT OF COMPLIANCE Applicable Standards: All transformers furnished under this specification shall be designed, manufactured and tested to meet or exceed the requirements of the latest revision of the following IEEE, ANSI IEEE. NEMA and ASTM Standards or equivalent 102 Statement of Compliance BIDDER’S BID/ FORM OF EVIDENCE IEC standards: Frequency: The transformer shall be designed to operate at 60 Hz. KVA Ratings: The kVA rating shall be continuous and based on not exceeding either a 65 °C average winding temperature rise or an 80 °C hottest-spot temperature rise above an ambient of 30 °C. The temperature rise of the insulating oil shall not exceed 65 °C when measured near the top of the tank (IEEE Std C57.12.20). Short-Circuit Characteristics: The transformer shall withstand the mechanical and thermal stresses produced by external shortcircuit currents specified in IEEE Std 057.12.00, latest revision. Loading Capability: The transformer shall be guaranteed to have the loading capability in accordance with ANSI IEEE Std C 57.92, latest revision Audible Sound Level: Transformers shall he designed so that the average sound level does not exceed the values specified. Cooling Class: The cooling method employed for transformers supplied under this specification shall be self-cooled (OA or ONAN). Core-Coil Assembly: Transformer core shall be manufactured using either low-loss high-permeability grain-oriented silicon steel or amorphous metal. Transformer windings shall be made of high-conductivity copper, The core and coil assembly shall be mounted rigidly in the tank. The assembly shall not shift in direction during shipping, handling, installation, or during normal operation due to vibrations. The core and coil assembly shall he vacuum processed to ensure maximum penetration of the insulating liquid to the coil insulation system. Insulating Liquid: The transformer shall be filled with unused mineral oil meeting the requirements of the latest revision of ASTM D3487 (Specification of Mineral Insulating Oil Used in Electrical Apparatus). Insulating Liquid must not contain more than 2 PPM of Polychlorinated Biphenyl (PCB), classified as “PCB Free”. Hardware: All energized hardware, i.e., bolts, nuts and washers shall be made of tinned copper alloy material such as silicon bronze or equivalent. All other hardware shall be hot-dip galvanized. Nameplate: The transformer shall be provided with a nameplate in accordance with the latest revision of IEEE Std C57.12.00. The nameplate shall be made of stainless steel with the technical information etched on the surface and coated with black enamel. The following minimum information shall appear on the nameplate: 103 a.) Serial Number b.) Class c.) Number of phases d.) Frequency e.) Voltage rating f.) kVA rating g.) Temperature rise, °C h.) Polarity i.) Percent impedance j.) BIL k.) Total weight, kg l.) Connection diagram m.) Name of manufacturer n.) Installation and operating instructions reference o.) The word „Transformer‟ p.) Type of insulating liquid (generic name q.) Conductor material for each winding) r.) Equipment identification number Standard support lugs shall be he provided on the tank wall for securely mounting the transformer on the pole. The type of support lug to be provided corresponding to the transformer size shall he as shown in IEEE Std C57.12.20, latest revision. Lifting facilities for the core-coil assembly shall be provided. The tank shall surge arrester mounting provision adjacent to the high-voltage bushing per IEEE Std C57.12.20. It shall consist of two steel pads with a ½ inch-13 NC tapped holes 11 mm (0.44 in) deep and located on the side of the tank in line vertically with the high voltage bushing. The arrester mounting provisions shall have centerline-to centerline spacing as shown in IEEE Std 057.12.20, latest revision. Corrosion-resistant flanged cup shall be installed to protect the threaded opening of the unused arrester mounting pads. The 104 correct oil level at 25 °C shall be marked inside the tank. The tank shall be painted with two (2) coats of outdoor type, light gray paint conforming to Munsell Notation 5BG7.0/0.4, ANSI70 Gray, over a suitable prime coat. Tank Markings: Transformer kVA rating shall be painted in black using 3-inch block letters and numerals. The location of the kVA marking shall be below the low-voltage bushings. The JFPR Logo shall be embossed on the tank wall using 3-inch block letters. The location of the name shall be below the kVA marking. Tap Changer: The transformer shall be provided with a tap changer designed for de-energized operation only. The tap changer shall be provided with an external operating handle mounted on the tank wall that can be rotated in a clockwise direction from a high tap voltage to low tap voltage. It shall be provided with stops when rotating from the highest to the lowest tap positions and shall be designed to prevent accidental operation by requiring a preliminary step before the tap setting can be changed. A caution: „DO NOT OPERATE WHEN ENERGIZED‟ shall be marked near the tap changer-operating handle, clearly visible to the operator. Tap positions and caution markings shall be marked with reflector, non-weathering decals at least 25 mm (1.0 inch) high. “1” shall be assigned to the highest tap. Tests: Each transformer shall be subjected to the following routine production tests in accordance with procedures specified in IEEE StdC57.12.60 and IEEE Std C57.12.90, latest revisions: a) Winding resisting measurement tests b) Ratio Test c) Polarity Test and Phase Relation d) No-Load Losses and Excitation Current at rated voltage and frequency e) Impedance Voltage and Load Loss Measurement f) Induced Potential Test (Low-frequency Dielectric Test) g) Dielectric Test of Insulating Oil h) Mechanical (Leak Test) Design Tests: Copies of certified test reports from a reputable, internationally-accepted testing facility shall be submitted as proof 105 of meeting the requirement in the following design tests: a) Temperature Rise b) Lightning Impulse c) Insulation Power Factor d) Insulation Resistance e) Short-Circuit Capability Primary Bushings: The transformer shall be furnished at the primary side with cover-mounted high-voltage bushing. The high-voltage bushings shall be made from high-grade, wet process porcelain with the entire exposed surface to be glazed. The color of the bushings shall be Light Gray ANSI 70, Munsell Notation 5BG 7.0/0.4. The high-voltage bushing/s shall be designated as H1 (for single bushings transformer) of H1 & H2 (for double bushing transformer) and shall be arranged in accordance with the latest revision of IEEE Std C57.12.20. For single-bushing transformers, the H2 end of the primary winding shall be brought out through a high-voltage neutral bushing, which shall be designated as H2. The high-voltage neutral bushing shall be sidewall-mounted, 1.2 kV class, 30 kV BIL, made from high-grade, wet, process porcelain, colored Light Gray ANSI 70. It shall be externally grounded to the tank wall using a removable copper ground strap. Secondary Bushings: The transformer shall be furnished at the secondary side with sidewall-mounted, low-voltage bushings. The number and characteristics of the low-voltage bushings are shown in Table 8. Transformer Secondary Bushings Number and Characteristics Transformer Secondary Voltage Rating Low-Voltage Bushing Number and Characteristics 240 V Number 2 Voltage Class (kV) 1.2 BIL Withstand(kV,min) 30 60 Hz Withstand, 1-min dry (kV, min) 10 60 Hz Withstand, 10-s dry (kv,min) 6 106 STATEMENT OF COMPLIANCE SPECIFICATIONS The low-voltage bushings shall be made from high-grade, wetprocess porcelain with the entire exposed surface to be glazed. The color of the bushings shall be Light Gray ANSI 70, Munsell Notation 5BG 7.0/0.4. The low-voltage bushings shall be designated as X1, X2, X3, and X4, depending on the transformer secondary voltage rating, shall be arranged in accordance with the latest revision of IEEE Std C57.12.20. The low-voltage bushings of transformers rated 167 kVA and above shall be designed to withstand without damage or leakage a minimum cantilever force of 40 kg. Bushing Terminals: The high-voltage bushing and high-voltage neutral bushing shall be equipped with eye-bolt-type connectors made from tinned copper-alloy material and provided with stainless steel spring washers. The terminal connectors shall accommodate (AWG No.8) solid to 30 mm2 (AWG No. 2) stranded copper conductor. Terminal detail shall be in accordance with the latest revision of IEEE Std C57.12.20. The low-voltage bushings shall be equipped with the tinned copper alloy, eyebolt-type connectors or tinned spade terminal pads, arranged for vertical takeoff of cables. Size of terminal openings and cables, and type of spade terminal pads are shown in Table 9. Terminal details shall be in accordance with IEEE Std C57.12.20, latest revision. Terminal markings shall be in accordance with IEEE Std C57.12.70, latest revision. Size of Low-Voltage Terminals and Conductor Range Size of Terminal Openingmm (in) (5/8) Size of Conductor that the Terminal Will Accommodate mm2 (AWG/kcmil) 30 mm2 (AWG No. 2) solid to AWG No. 4/0 Polarity: Transformers supplied under this specification shall have the polarity specified below. Transformer Polarity kVA Range Transformer Primary Voltage Rating 107 BIDDER’S BID / FORM OF EVIDENCE 13 200GrdY/ 7620 V 167 kVA and below Additive Tank: The transformer tank shall be made of steel. It shall be of sealed-type construction with a steel cover. The tank cover shall be provided with a reusable gasket. The tank cover shall be grounded to the tank body using a copper strap adequately sized for the shortcircuit of the transformer. The tank shall be provided with a tank grounding connector located near the base of the tank. The connector shall be eyebolt-type, made from tinned copper alloy material, and designed to accommodate 8 mm2 (AWG No. 8) to 30 mm2 (AWG No. 2) stranded copper conductors. Standard support lugs shall be provided on the tank wall for securely mounting the transformer on the pole. The type support lug to be provided corresponding to the transformer size shall be as shown in IEEE Std C57.12.20, latest revision. Lifting lugs shall be permanently attached near the top of the transformer tank to allow for balanced vertical lift. The design of the lifting lugs shall incorporate a safety factor of 5. Lifting facilities for the core-oil assembly shall be provided. The tank shall have surge arrester mounting provision adjacent to the high-voltage bushing. It shall consist of two steel pads with a ½ inch-13 NC tapped holes 11 mm (0.44 in) deep and located on the side of the tank in line vertically with the high voltage bushing. The arrester mounting provisions shall have centerline-to-centerline spacing as shown in IEEE Std C57.12.20, latest revision. Corrosionresistant flanged cup shall be installed to protect the threaded opening of unused arrester mounting pads. The correct oil level at 25 °C shall be marked inside the tank. The tank shall be painted with two (2) coats of outdoor type, light gray paint conforming to Munsell Notation 5BG7.0/0.4, ANSI170 Gray, over a suitable prime coat. 108 Logo: The bidder shall provide a 12cm×18cm high quality sticker with reflective face painted with JFPR and ODA logos for each transformer. 109 Accessories and Protection 12 SPECIFICATION OF 15 KV VACUUM RECLOSER Outdoor Vacuum 15 kV Reclosers Manufacturer: “Subject to Eligibility Requirements under Bid Data Sheet Clauses 5.1, 5.2 and 7” Nominal operating voltage : 2.4-14.4 KV Rated Power frequency : 60 HZ Rated Continuous current : 630 Amps Control voltage : 90-265 VAC / 125 VDC Rated symmetrical interrupting current : 8 / 10 / 12.5 / 16 A Rated lightning impulse withstand(BIL) 110/125 Dry withstand 60 Hz 1 Min. : 50 Wet withstand 60 Hz 10 Sec. : 45 Phase spacing : 15.50 ( 394 ) External creep distance, H2-ground : 38.00 ( 960 ) External creep distance, H1-H2 : 45.00 ( 1160 ) Min. External strike distance : 9.50 ( 240 ) Max. interrupting time : 0.030 s Max. closing time : 0.055 s Accessories o Vacuum interrupter o Epoxy bushing o Earthing point o Stainless steel tank o Magnetic actuator o Memory card o Control cable(User Measured Length) o Manual trip ring o Buzzer alarm when tripped o One (1) Unit Brand New Laptop in every three (3) units of 15KV Vacuum Recloser, for programming and event downloading o Tripped counter o Copper terminal lugs Recloser functions : o Remote control o Local control o Sensitive Earth Fault o Earth Fault o Auto reclose mode o Close/Trip ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ISOLATE Alarms status such as: o Auxiliary supply fail o Battery supply fail o Lockout Battery o 2 sets 48 VDC, 12 AH battery bank (Std. Cabinet) or 48 VDC, 7.2 AH battery bank 110 STATEMENT OF COMPLIANCE BIDDER’S BID / FORM OF EVIDENCE o Sealed led acid rechargeable battery pack o Monitor locally and remotely o Easily accessible in low voltage control cabinet o Allows up to 48 hours (15-27 kV) / 24 hours carryover and multiple operations upon loss of power o Includes capacitor backup in case of discharge or disconnected battery Features of 15 kV Vacuum Circuit Breaker: o Protection setting and fault history o Line measurement and historical data o Metering data such as: o Kw, Kvar, Pf, Kva, etc o Distribution System Automation (DSA) or SCADA System. Information on recloser status and fault current values transmitted to system control allows fast location of the faulted line section. o Substation mount or pole mount -Cable requirement upon user needs. AUTOMATIC CIRCUIT RECLOSER, 1-Phase, Brand New, 15 kV max. rated voltage, 100 amperes or higher continuous current, 110 kV rated lightning impulse, 50 kV power frequency insulation level test voltage, 12.5/16 kA rated symmetrical interrupting current, 20/25 kA rated asymmetrical interrupting current, 32.5/41 rated peak making current, 10,000 OPS mechanical life, up to 250 OPS permissible shortcircuit operations, -40 to +55 ambient temp. range, 265 mm flashover dist. phase/ground, 810 mm creepage dist. phase/ground, 1,170 mm between line-side and load side terminal, Min. Trip Current: 40 A phase faults, 4 A ground faults, Operation Time: <60 ms Closing Time, <35 ms Opening Time, <15 ms Arcing Time, <50 ms Interrupting Time, Dead Time: 0.2 to 14,400 s dead time after first open, 2 to 14,400 s dead time after second and third open, 30 to 14,400 s dead time after fourth open. 69 KV POWER CIRCUIT BREAKER Standards for outdoor installation with spring operated mechanism Manufacturer: “Subject to Eligibility Requirements under Bid Data Sheet Clauses 5.1, 5.2 and 7” Rated Voltage : 75 kV Rated Nominal Voltage : 69 kV Rated Maximum Voltage : 75 kV Rated Frequency : 60 Hz Test Voltage 60 Hz 1 min : 140 kV rms BIL (peak) : 350 kV Rated Current : 1250 A Maximum Interrupting Current: 31.5 kA Rated Duration of short circuit: 3 sec. Momentary Current : 64 kA (ANSI) Opening Time : 35 ms max. Closing Time : 60 ms max. Close – Open Time : 40 ms. Max. Resistance across breaking unit: 50 micro ohms Rated Tripping Voltage : 125 Vdc Ambient air temp. Range : 30 deg. C to +40 deg. C 111 7 1 Special Tools – SF6 Handling Equipment: o SF6 Filing Equipment o SF6 leakage detector o 2 – Cylinder with 10 kg. SF6 Gas Accessories: o Closing Coil o Tripping Coil Cylinder with 10 kg. SF6 Gas o Auxiliary Switch/Relays o Contactor Features of 69 kV Power Circuit Breaker: o suitable for three phase auto reclosing o creepage distance : 1,810 mm o color porcelain : brown (RAL 8016) o protection class IP 54 o Differential relay o 50 / 51 o phase center distance : 1,050 mm o six A high voltage terminal pads, drilled according to NEMA o circuit breaker poles will be delivered with 0.02-05 Mpa SF6 pressure o SF6 density monitor with color and graduated scale (Mpa/bar) o Nameplate in English Features of Spring Operating Mechanism: o - operating voltage of auxiliary circuits : DC 125 V o - 1 universal motor per operating mechanism : DC 125 V o alternate current circuit (heating, lighting) : Ac 230 V o operating range of coil: Trip 70% / close 85% (IEC) o anti-condensation heater, permanently o red/green position indicator lamps included o A.C. supply protected with M.C.B. o SF6 density control included o Two independent trip coils, one closing coil o mechanically coupled auxiliary switch with 13 NC, 11 NO and 1 wiping contact free o local mechanical and local electrical C/O operation with /Off remote selector switch o without motor protection o wiring 1.5 sq. mm, stranded wire with ferrules o terminal strip UK5 with 16 sq. mm earthing wire with ferrules o no numbering ferrules o lighting of operating mechanism housing included o with socket (outlet) o door of housing lockable o mechanical interlock Ronis included o “I/Q” position indicator red-green included Surface Protection: o Aluminum alloy parts will not be painted o Ferrous parts are hot-dip galvanized o flanges of insulators are anodized aluminum sheets and operating mechanisms get two protective coats of paint (RAL 7044) 112 Potential Transformers: Voltage Transformers according to the following specifications: 3 Brand: “Subject to Eligibility Requirements under Bid Data Sheet Clauses 5.1, 5.2 and 7” Installation : Outdoor System Voltage : up to 75 kV Rated Voltage : 69 kV Ratio : (69000 V / 40250 V:115V) BIL : 350 kV @ < 1,000 m Thermal Rating : 25-kA/1 sec. (IEC) Momentary Current : 40 kA (ANSI) Flag type 4 Hole Terminal Lugs : Tap to 336.4 acsr thru ampact 69 kV Current Transformers for SF6 Power Circuit Breaker: Current Transformers are three (3) single phase units in live tank design. The coil respective core data are properly designed with protection and metering system. Current Transformer designed as per IEC/ANSI standard. Brand: “Subject to Eligibility Requirements under Bid Data Sheet Clauses 5.1, 5.2 and 7” Type : Dry Type Cast Resin Installation : Outdoor Rated Voltage : 75 kV Frequency : 60 Hz BIL : 350 kV Ratio : 100/50:5 A, Multi Ratio Metering Core : 0.3, B-1 Class Protection Core 1 : C100 Class Protection Core 2 : C100 Thermal Rating : 31.5 kA/1 sec. (IEC) Momentary Current : 51 kA (ANSI) 1-min Power Freq. Voltage : 140 kV Dynamic withstand current : 80 kA Total Creepage Distance : 1810 mm Arcing Distance : 700 mm Lightning Impulse : 350 kVp Straight Paddle 4 Hole Terminal: Lugs Tap to 336.4 acsr thru ampact FUSE LINKS: Fuse Links shall conform in all respects to the requirements of this document. The fuse links covered in this specification are intended for use in open-type distribution fuse cutouts. The fuse links shall be of the buttonhead-type to be used in the overcurrent protection of distribution transformers and circuits. The fuse links shall meet the electrical and mechanical interchangeability requirements for fuse links used in open-type cutouts as described in Sections 3.2 of ANSI C37.42 [1]. 113 3 RATINGS: Voltage and current ratings of the fuse links shall be based on the service condition defined in ANSI C37.40 and as specified in ANSI C37.42. Rated maximum voltage which is determined by the highest voltage rated cutout with which the fuse link is designed to be used and yet conform to the interchangeability requirement of Section 3.2.1 of ANSI C37.42. MARKINGS: Each fuse link shall bear the manufacturer‟s identification mark or symbol and rated continuous current followed by the fuse type identifier. PACKAGING: Fuse links shall be package in lots of 25 per box with each fuse links in an individual container. All fuse link in a given lot shall be of the same type and ampere rating. Boxes containing lots of fuse links of the same type and ampere rating shall be packagedin shipping cases as required to meet the quantities specified in the tender documents. Each individual container, lot box and shipping case shall be clearly marked to show the following minimum information: 1. 2. 3. 4. 95 Quantity Manufacturer‟s identification Manufacturer‟s Catalog number and type identification. Rated continuous current. The type identification “K” shall follow the rated current. LIGHTNING ARRESTER: (POLYMER) Rated Voltage : 10 KV MCOV : 8.4 KV BIL : 110 KV Type : Outdoor High Current Operating Duty : 110 KV CUTOUT AND ARRESTER COMBINATION, POLYMER GENERAL: Arrester shall protect pole-mounted equipment from voltage impulses or surges resulting from lightning strokes, system faults, circuit switching, load rejection or other events. The arresters shall limit such over voltage levels below equipment BIL ratings. SERVICE CONDITIONS: Arresters shall meet the following physical and system conditions: 1. Ambient temperature above 40°C 2. Altitude up to 1,800 meter above sea level 3. Nominal system frequency 60 Hertz 4. Arresters shall be rated 9/10 kV MCOV, for phase to ground connection on a 13.2/7.62 kV grd Y system. CONSTRUCTION: Arrester shall be gapless type, described briefly as follows: Gapless arresters shall have valve elements fabricated from non-linear resistance metal oxide materials to perform both the surge discharge and power frequency reseal functions. CONNECTORS: Both line-lead and isolator terminals shall accommodate # 6 solid through 2/0 AWG stranded copper or aluminum 114 138 pcs . 238 conductors. PROTECTIVE CHARACTERISTICS: Arresters shall have protective characteristic based on standard rms data cycle voltage as summarized from ANSI C62.11 [1]. NAMEPLATE: Information required for identification must be embossed on an nameplate firmly fixed to the arrester and shall include: a. Arrester classification b. Manufacturer‟s identification or symbol c. Arrester model and identification number d. Arrester voltage rating e. Date of manufacture The nameplate must be eligible over the lifetime of the arrester. MOUNTING: Distribution arrester shall be supplied with a crossarm mounting bracket that conforms to the requirement of NEMA Pub. No.1 PH25, [3], or with appropriate bracket when supplied as a cutoutarrester combination on it. All mounting bolts and conductor connections require lock washers. Lock washer shall be fabricated from material that complies with the requirements of ANSI B18.21.1 [5]. PACKAGING: Arrester shall be securely packaged for shipping. Each package shall be clearly marked with the manufacturer‟s name and catalog number. SPECIFICATIONS FUSE CUT-OUT and ARRESTER COMBINATION Fuse Cut-out & Arrester Assembly: Manufacturer: “Subject to Eligibility Requirements under Bid Data Sheet Clauses 5.1, 5.2 and 7” Rated Voltage Lightning Arrester: Rated Voltage : : : : Duty : : : : 15 kVAmpere Frame 100 AFFuse Link Rating 5A 10 KVMCOV 8.4 KVBIL 110 KVType Outdoor High Current Operating 110 KV 138 CUTOUT, FUSE, SINGLE-SHOT GENERAL: Fuse cutouts furnished shall conform in all respects to the requirements of this specification. These fuse cutouts shall be of the open, expulsion, dropout, type and shall be satisfactory for use in a tropical climate with high relative humidity. RATINGS: 115 1. Rated Voltage a. Nominal System Voltage-13.2/7.62 KV grd Y b. Rated Maximum Voltage-15,000 volts c. Low Frequency Withstand KV, RMS -dry, 60 sec. -35 -wet, 10 sec. -30 2. Rated Impulse withstand voltage - 95 KV 3. Rated Frequency - 60 Hertz 4. Rated Continuous Current - 100 amperes DESIGN: 1. Fuse Support Assembly a. Fuse Support Insulator - wet process porcelain b. Markings Manufacturer‟s identification Product type Rated continuous current Rated maximum voltage Rated interrupting current Basic impulse level c. Contacts - silver d. Connectors – tin-plated bronze parallel grove type, for #6 to 4/0 AWG copper or aluminum conductors. e. 2. Loadbuster tool attachment hooks. Fuse Tube Assembly a) Fuse tube – bone fiber lining with exterior painted gray, nonexpendable cap. b) Contacts – silver plated c) Fuse Link Position – The fuse tube shall be designed so the fuse link is centered in the tube, with provision for mechanical ejection of the fuse link leader on low current faults. d) Opening and Lifting Eyes - the fuse holder shall hang vertically from the fuse support assembly when in the open position, and shall have opening and lifting eyes suitable for removal and installation of the assembly, and opening and closing of the cutout with a switch stick described in ANSI C37 42-1981, [3]. e) Thumb Screw – for securing the fuse link to fuse holder assembly. 3. Mounting Bracket : Each distribution fuse cutout shall be provided with a mounting bracket meeting the requirements of ANSI C37 42-1981, Section 2.4 for type A mounting when specified and ordered as a combination cut-out arrester unit. 116 4. Lock Washer : All mounting bolts and conductor connectors require lock washers. Lock washers shall be fabricated from material that comply with the requirements of ANSI B18.21.1-1983, [4]. PACKAGING: Each distribution fuse cutout and arrester if ordered in combination, together with its mounting bracket shall be securely packaged in a box clearly labeled to show the manufacturer‟s name, product, identification and type and voltage and current ratings. 117