IH/WC Series Dehumidifier Outdoor Air Design Parameters for Indoor Pools I NTRODUCTION Outside Air Ductwork with 0.20" - 0.45" wc Pressure Drop ASHRAE 62 recommends that outdoor air be introduced to commercial pool facilities. Please refer to DESERT AIRE Technical Bulletin No. 5 for a detailed analysis of these recommendations. To ensure that the moisture removal capacity of the DESERT AIRE dehumidifier is maintained, the outdoor air must be balanced with the return air. The outdoor air must be introduced between the evaporator and reheat coils, as shown in the diagram. Outside Air Pre-Heater * Dehumidifier Supply Air The exhaust fan should be sized for the same or slightly more CFM as the outdoor air volume and be interlocked to operate in conjunction with the motorized outdoor air damper. D AMPER OPERATION The contractor must install the air filter, two-position motorized damper, and appropriate insulated duct, per code and local regulations. As an option, DESERT AIRE can supply the filter/damper combination factory installed. R E H E A T Electrical Panel Terminal Strip D1 E V A P Outside Air Air Filter Motorized Outside Air Damper Return Air To Damper Actuator (Dry Contact) To Damper Power Supply D2 E1 E2 To Exhaust Fan (Dry Contact) *Outside air pre-heater is necessary in IH/WC applications where mixed air temperatures may fall below 45°F and outside air compliance is required at all times. A IR FLOW BALANCE The IH/WC Series utilizes a two-position damper, which allows air to bypass the evaporator coil. With the outdoor air damper opening and closing, the amount of outdoor air changes and a new balance must be achieved across the evaporator coil to ensure proper moisture removal (i.e., to maintain velocity across the coil face). The two-position damper obtains this balance automatically. System air flow balance must be established during start-up by the installing contractor. Mode Damper Position Occupied Open Unoccupied Closed Model O/A CFM O/A Flange Size Loss of Blower Closed IH/WC 100 125 5” x 10” < 45°F Mixed Air Temperature Closed IH/WC 200 250 5” x 10” IH/WC 300 350 6” x 14” IH/WC 500 500 8” x 14” IH/WC 750 900 10” x 16” IH/WC 1000 1000 12” x 16” IH/WC 1200 1300 12” x 18” IH/WC 1500 1800 12” x 26” All IH/WC models are equipped with an air temperature sensor which monitors conditions inside the unit. To prevent internal condensation from freezing when frigid outdoor air mixes with warm, humid air, a call for outdoor air will be overridden whenever mixed air temperatures in the blower compartment fall below 45°F. NOTE: In applications where outdoor air code compliance is required at all times and where outdoor temperatures may fall below freezing, preheating of outdoor air will be required. Please note that this caution is not specific to DESERT AIRE units. Customers should be aware of the design details for handling frigid outdoor air with any unit they are evaluating. 8300 West Sleske Court Milwaukee, WI 53223 (414) 357-7400 FAX: (414) 357-8501 www.desert-aire.com 217 4/02