Aluminium conductor steel reinforced

advertisement
Power cables
ACSR
Aluminium conductor steel reinforced
Application
Temperature range
Bare conductor for overhead power transmission.
Highest permissible conductor temperature:
– in continuous operation . . . . . . . . . . . . . . . . . . . . . .80˚C
– in a short circuit (duration up to 5 s) . . . . . . . . . 200˚C
Standards
SFS 5701
IEC 61089
EN 50182
AS Draka Keila Cables
www.draka.ee
Construction
A conductor consisting aluminium and galvanized steel
wires, built up in concentric layers. The centre wires are
steel and outer layer aluminium wires.
Member of Prysmian Group
www.prysmian.com
Paldiski Road 31
76606 Keila, Estonia
Phone +372 674 7466
Fax
+372 674 7468
The technical specifications may
change any time without prior notice.
ACSR
Aluminium conductor steel reinforced
Basic data
Product name according to IEC
EAN code
Construction data
Aluminium
No of wires
Diameter of wire
Cross section
Weight (5)
Steel
No of wires
Diameter of wire
Cross section
Weight (5)
Complete conductor
No of wires
Diameter of conductor
Cross section
Weight (5)
Delivery data
Standard delivery length
Standard delivery drum
Total weight (1)
Mechanical data (2)
Minimum tensile strength of the conductor
Initial modulus of elasticity of conductor
Final modulus of elasticity of conductor
Coefficient of linear expansion of conductor
Electrical data (2)
Max. DC resistance of conductor (20˚C) (3) (5)
Current ratings
In air
Short circuit currents (2)
Max. permissible short circuit current for 1 sec. (4)
ACSR 34/6
SPARROW
34-A1/S1A-6/1
01 202 02-2
ACSR 42/25
SAVO
42-A1/S1A-12/7
01 202 28-2
ACSR 54/9
RAVEN
54-A1/S1A-6/1
01 202 05-3
ACSR 85/14
PIGEON
85-A1/S1A-6/1
01 202 09-1
ACSR 89/52
DOTTEREL
89-A1/S1A-12/7
01 202 31-2
6
2,68
33,8
92,9
1
2,68
5,64
43,9
7
8,04
39,5
137
12
2,12
42,4
117
7
2,12
24,7
193
19
10,6
67,1
310
6
3,37
53,5
147
1
3,37
8,92
69,4
7
10,1
62,4
216
6
4,25
85,1
234,0
1
4,25
14,2
110,0
7
12,8
99,3
344,0
6
3,08
89,4
247,0
7
3,08
52,2
408,0
19
15,4
142
654,0
kg
2500
K11
390
2500
K12
860
2200
K11
560
2000
K12
770
2500
K16
1790
kN
N/mm2
N/mm2
1/K
12,2
64000
78000
19,2 x 10–6
13,52
93000
102000
15,6 x 10–6
17,11
64000
78000
19,2 x 10–6
24,13
64000
78000
19,2 x 10–6
33,37
93000
102000
15,6 x 10–6
Ω/km
0,848
0,682
0,536
0,337
0,323
A
210
250
280
360
400
kA
3,7
5,4
5,8
9,2
11,4
64 100+
ACSR 152/25
OSTRICH
152-A1/S1A-26/7
01 202 15-2
ACSR 242/39
HAWK
242-A1/S1A-26/7
01 202 18-3
ACSR 305/39
DUCK
305-A1/S1A-54/7
01 202 21-3
ACSR 402/52
CONDOR
402-AL1/52-ST1A
01 054 07-2
ACSR 565/72
FINCH
565-A1/S1A-54/19
01 202 24-4
26
2,73
152
420
7
2,12
24,7
193
33
17,3
177
613
26
3,44
242
668
7
2,68
39,5
309
33
21,8
281
976
54
2,68
305
842
7
2,68
39,5
309
61
24,1
344
1151
54
3,08
402,3
1110,5
7
3,08
52,2
410
61
27,7
454,5
1520,5
54
3,65
565
1562
19
2,19
71,6
561
73
32,9
637
2123
kg
2500
K18
1760
2500
K20
2780
2200
K22
3290
2300
K22
3908
1400
K22
3380
kN
N/mm2
N/mm2
1/K
54,8
61000
76000
19,2 x 10–6
84,9
61000
76000
19,2 x 10–6
96,8
50000
67000
19,3 x 10–6
123,75
51000
68000
19,3 x 10–6
174
46000
63000
19,3 x 10–6
Ω/km
0,190
0,120
0,0949
0,0719
0,0512
A
550
745
845
1000
1250
kA
16,5
26,1
32,5
43,7
60,1
64 100+
mm
mm2
kg/km
mm
mm2
kg/km
mm
mm2
kg/km
m
Basic data
Product name according to IEC
EAN code
Construction data
Aluminium
No of wires
Diameter of wire
Cross section
Weight (5)
Steel
No of wires
Diameter of wire
Cross section
Weight (5)
Complete conductor
No of wires
Diameter of conductor
Cross section
Weight (5)
Delivery data
Standard delivery length
Standard delivery drum
Total weight (1)
Mechanical data (2)
Minimum tensile strength of the conductor
Initial modulus of elasticity of conductor
Final modulus of elasticity of conductor
Coefficient of linear expansion of conductor
Electrical data (2)
Maximum DC resistance of conductor (20˚C) (3) (5)
Current ratings
In air
Short circuit currents (2)
Maximum permissible short circuit current for 1 sec. (4)
mm
mm2
kg/km
mm
mm2
kg/km
mm
mm2
kg/km
m
1) Approximate value.
2) See the basic assumptions at general information of products.
3) Calculated with steel core.
4) Initial temperature of conductor before short circuit 40˚C, final temperature of conductor after short circuit 200˚C.
5) Nominal value according to standard.
AS Draka Keila Cables
www.draka.ee
Member of Prysmian Group
www.prysmian.com
Paldiski Road 31
76606 Keila, Estonia
Phone +372 674 7466
Fax
+372 674 7468
The technical specifications may
change any time without prior notice.
Download