CITY OF EDGEWATER FIRE STATION 55 50% CONSTRUCTION DOCUMENTS June 14, 2010 SECTION 15781 – SPLIT DX A/C & HEAT PUMP EQUIPMENT PART 1 - GENERAL 1.01 1.02 DESCRIPTION OF WORK A. The extent of work is shown on drawings and in schedules, and by the requirements of this section. B. The types of units required for this project include split DX air conditioner and heat pump systems. QUALITY ASSURANCE A. Manufacturers: Firms regularly engaged in manufacture of split DX air conditioners, of types, sizes and capacities required, whose products have been in satisfactory use in similar service for not less than 5 years. B. Installer: A firm with at least 3 years of successful installation experience on projects with packaged room air-conditioning units. C. Codes and Standards: The following codes and standards apply to all or part of the products or procedures covered in this specification. Individual items of the specification may refer more specifically to applicable sections of these codes or standards. 1. 2. 3. 4. 5. 1.03 1.04 Air-Conditioning and Refrigeration Institute (ARI). American National Standards Institute, Inc. (ANSI) American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE). National Fire Protection Association (NFPA). Underwriters Laboratories (UL). SUBMITTALS A. In Accordance with 15010. B. Submit manufacturer's technical product data, including rated capacities or selected model clearly indicated, weights, furnished specialties and accessories; and installation and start-up instructions. PRODUCT DELIVERY, STORAGE AND HANDLING A. Deliver units in factory-fabricated protective containers. B. Handle units carefully to avoid damage to components, enclosures and finish. Do not install damaged components; replace and return damaged components to unit manufacturer. C. Store units in clean dry place and protect from weather and construction traffic. SPLIT DX A/C EQUIPMENT 15781-1 CITY OF EDGEWATER FIRE STATION 55 1.05 50% CONSTRUCTION DOCUMENTS June 14, 2010 WARRANTY A. Provide with a five year compressor and aluminum coil warranty in addition to the manufacturer's standard one year equipment warranty. PART 2 - PRODUCTS 2.01 AIR-HANDLING UNIT (AHU) A. Provide DX air handling unit(s) of the size, model, and capacity indicated on drawings. B. General: Indoor, direct-expansion, AHU. Unit shall be shipped complete with cooling coil, heating coil, fan, fan motor, piping connectors, and electrical controls. C. Unit Cabinet: Cabinet shall be constructed of G-90 galvanized steel, phosphatized, and finished with baked acrylic enamel paint. Bases, corner posts and tops shall be minimum 18 gauge. Access panels shall be minimum 20 gauge. D. Cabinet Insulation: The interior of the cabinet shall be thermally insulated with 1-inch thick foil-faced, rigid fiberglass with a minimum R-value of 4.2. The insulation and adhesive shall meet NFPA 90A requirements for flame spread and smoke generation. E. Evaporator Coil: Evaporator coil shall be copper tube with aluminum fins. Fins shall be firmly bonded to the tubes by mechanical expansion. Coils shall be drainable and have non-trapping circuits. Coils shall be factory leak tested. F. Condensate Drain Pan: Unit shall have factory-installed, double-sloped condensate drain pan fabricated from plastic or stainless steel. Bottom of drain pan shall be insulated to prevent condensation. Condensate drain connection(s) shall be minimum 3/4 inch and shall have fittings exposed to the outside of the cabinet. Pan and drains shall comply with ASHRAE Standard 62-2001. G. Blower: Blower shall be a forward-curved, centrifugal type, and shall be statically and dynamically balanced. H. Motors: Motors shall have sealed and permanently lubricated ball bearings, and shall have inherent overload protection. Fan motor shall be variable speed. 2.02 I. Electric Heater: Provide factory electric heat as scheduled. J. Filters: Unit shall have factory-supplied pleated disposable 30% efficient filters installed at the air inlet. AIR-COOLED HEAT PUMPS (HP) A. Provide air-cooled heat pump unit(s) of the size, model, and capacity indicated on drawings. B. Unit shall be matched to coil and capacity of associated air handling unit. SPLIT DX A/C EQUIPMENT 15781-2 CITY OF EDGEWATER FIRE STATION 55 50% CONSTRUCTION DOCUMENTS June 14, 2010 C. The units shall be complete with all factory controls, refrigerant piping, refrigerant accessories, and refrigerant valving indicated and as necessary to achieve the function specified on the drawings and schedules, and under this Section. D. Unit Cabinet: Cabinet shall be constructed of galvanized steel, phosphatized, and finished with baked acrylic enamel paint. All exterior hardware shall be stainless or aluminized steel for corrosion resistance. Fully weatherproof for outdoor installation. Openings provided for power and refrigerant connections. Panels removable to provide access for servicing. E. Compressor: Compressor shall be a scroll hermetic type with crankcase heater. Motors shall be equipped with internal overheat-overload protection. F. Condenser Coils: Condenser coils shall be copper tube with aluminum fins. Fins shall be firmly bonded to the tubes by mechanical expansion. Coils shall be drainable and have non-trapping circuits. Coils shall be factory leak tested. G. Condenser Fan(s): Condenser fan(s) shall be propeller type arranged for vertical discharge. Fans shall be statically and dynamically balanced, each fan driven by separate fan motor. Each fan shall be protected by a heavy gauge, vinyl-coated fan guard. H. Condenser Fan Motor(s): Condenser fan motor(s) shall be direct drive and have sealed and permanently lubricated ball bearings, and shall have inherent overload protection. 2.03 I. Refrigerant Circuit: Included in the refrigerant circuit shall be condenser fan cycling head pressure control, accumulator, filter-drier, high pressure safety control (manualreset), low pressure safety control/loss of charge protector (auto-reset), hot gas bypass valve with solenoid and dual gauge connections for high and low pressure readings. A 24-volt pump down solenoid valve is shipped loose with the condensing unit and is to be field installed in the liquid line as close to the air handler as possible. Where reheat coil is used, the valve shall be factory installed in the air handler. The refrigerant circuit shall be factory charged for shipment with dry nitrogen that can be vented to the atmosphere. J. Electric Controls: Internally wired controls shall include the compressor anti-short cycle timer, fan and compressor motor contactors or starters and 24v transformer mounted in the sheet metal control panel. The 24-volt control circuit shall include a low voltage terminal board. APPROVED MANUFACTURERS A. Subject to compliance with the above specified requirements: . 1. 2. 3. 2.04 Trane Carrier Approved Equivalent SPLIT DUCTLESS AC UNIT SPLIT DX A/C EQUIPMENT 15781-3 CITY OF EDGEWATER FIRE STATION 55 50% CONSTRUCTION DOCUMENTS June 14, 2010 A. Provide split ductless ac unit(s) of the size, model, and capacity indicated on drawings. B. Unit shall be matched to coil and capacity of associated air handling unit. C. The units shall be complete with all factory controls, refrigerant piping, refrigerant accessories, and refrigerant. D. Unit shall be installed with factory wall-mounted controller. PART 3 - EXECUTION 3.01 INSTALLATION OF AIR-COOLED HEAT PUMP UNITS A. Set HP on 6-inch thick reinforced concrete pad on ground outside building in location shown on plans. Concrete pad shall extend 6 inches beyond each side of unit. Set unit level and bolt down. Maintain manufacturer recommended clearances for proper air circulation and service. B. Provide all refrigerant piping complete with all fittings, valves, refrigerant specialties. The supports for the refrigerant lines shall be installed in a manner to maintain minimum line vibration. C. Provide all control wiring for unit operation as required. The Electrical Contractor will furnish and install power wiring to all motors (including disconnect switches furnished under the heating and cooling contract). D. Installation shall be in accordance with refrigerant practices and shall conform to the manufacturer's instructions. 3.02 REFRIGERANT PIPING INSTALLATION A. Provide all refrigerant piping complete with all fittings, valves, refrigerant specialties. The supports for the refrigerant lines shall be installed in a manner to maintain minimum line vibration. B. The refrigerant piping shall be sized by the manufacturer's recommendations, submitted and approved by the Engineer. C. The refrigerant piping shall be installed as indicated on the drawings. Provide refrigerant pipe routing as indicated on plans. Installation shall be in accordance with refrigerant practices and shall strictly conform to the manufacturer’s instructions and recommendations D. All tubing shall remain capped until assembled. E. All equipment and piping shall be maintained absolutely dry and clean during handling and assembly. F. Flux and solder, and scale if any, shall be thoroughly cleaned from the tube. SPLIT DX A/C EQUIPMENT 15781-4 CITY OF EDGEWATER FIRE STATION 55 50% CONSTRUCTION DOCUMENTS June 14, 2010 G. Tubing shall be filled with nitrogen while soldering to prevent oxidation. H. The piping shall be carefully jointed with silver solder and completely leak tested with a Halide torch or approved refrigerant leak tester. I. The suction piping shall have an oil trap and the suction line shall pitch down in the direction of flow. J. Charging valves, expansion valve, solenoid valve, back seating type service valves, and any other valves necessary for the safe and proper operation of the refrigerating system shall be included in the installation. Seal caps shall be used on all refrigerant valves. K. Should any of the above valves be furnished as a part of the manufacturer's equipment, additional valves serving the same purpose will not be required. L. A suitable refrigerant filter-dryer which can be serviced without breaking the inlet and outlet refrigerant connections shall be installed in the liquid line on the supply side of the solenoid valve. M. See Section 15250 for insulation on liquid and suction line. END 15781 SPLIT DX A/C EQUIPMENT 15781-5