-0 S SR EW N OSHPD Pre-Approved System Multi-Directional Bracing For Electrical Conduit, Cable Tray And Mechanical Piping Systems SYSTEMS THAT MAKE SENSE 2 SEISMIC RESTRAINTS INTRODUCTION INTRODUCTION What is Seismic Bracing? Seismic forces are exerted on a building and its contents during an earthquake. These forces act horizontally upon the structure itself, as well as the piping, cable trays, ductwork, and other building systems within. Typical supports for piping, trays, and other equipment are designed for the gravity, or vertical, loads but do not take into account the horizontal loading caused by earthquakes. Seismic restraints (i.e. braces) resist the horizontal forces and keep the systems in place and secure. The main purpose of seismic bracing is safety- to minimize the loss of life due to an earthquake. Seismic Bracing Requirements The rules and requirements for the seismic restraints are published in the model building codes: The Uniform Building Code (International Conference of Building Officials), National Building Code (Building Officials and Code Administrators) and the Standard Building Code (Southern Building Code Congress International). Each code is similar in nature, and has a chapter on structural forces which defines the level of seismic force must be used in the design of seismic restraints. The amount of seismic force (as determined by the building code) is given as a percent of the components’ weight, or g-force. If the horizontal force is determined to be 50 percent of the piping weight, for example, the seismic force is .5g. The seismic "g-value" can vary greatly depending on the nature of the project. Critical buildings in a high seismic zone have larger g-value requirements than warehouses in zone 1. Factors that govern the seismic g-values used for design: • Seismic Zone • Soil Type • Building Type • Distance from known faults • Elevation within building • Anchorage Type • System being braced The design professional should use these factors and the applicable building code requirements to determine the proper g-values to be used for the project. While this manual has been developed under the requirements of the 2001 California Building Code, this manual may also be used under other building codes as the California Building Code requires more stringent seismic design criteria. This brochure contains seismic bracing details that can be used for seismic bracing projects up to 1.0g (ASD) or 1.4g. The brace spacing charts, required details, and rod loads must be determined for the specific g-value for the project and shall be submitted to the engineer of record prior to construction. The determination of the seismic force level shall also be submitted to the engineer of record and to OSHPD for hospital projects in the state of California prior to construction. However, the seismic force level need not be submitted to the engineer of record or OSHPD if included in the original construction documents. This brochure contains charts for a variety of g values, however custom charts can be created to reflect different g-values as required for the project. Contact B-Line Engineering at 618-654-2184 with your requirements. A copy of the complete Seismic Restraints Manual shall be on the jobsite for the duration of the project. COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 618-654-2184 Fax: 618-654-1917 Date: Page No. Sheet Number: 12 - 9 - 02 i of Raafat S. Aboulhosn Structural Engineer S 3913 **SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 1 TABLE OF CONTENTS General Information & Notes ................................ ....... 12 - 16 .................................... 17 - 20 ........................................................ 21 - 22 Single Pipe/Conduit Bracing Selection Trapeze Bracing Selection Trapeze Members 1 - 11 Structural Attachment Selection ................................. 23 Concrete .......................................................................... 24 - 33 Wood ................................................................................. 34 - 37 Steel .............................................................................................. 38 Hanger Rod Attachments & Approved Components ....................................................... 39 Concrete .......................................................................... 40 - 46 Wood ............................................................................................ 47 Steel ................................................................................... 48 - 56 Approved Components Rod Stiffeners ................................................................ 57 - 58 Adjustable Hinge .......................................................... 59 - 60 Hardware ......................................................................... 61 - 62 Pipe Hangers/Clamps .............................................. Anchoring Components .......................................... 63 - 71 72 - 78 Metric Conversion Charts .................................. 79 Seismic Map ....................................................... 80 Appendix 1 Additional Support Spacing Charts For Single Pipe/Conduit Applications (.15g, .30g, .45g, .50g, .75g and 1.00g) ................... 82 - 106 Appendix 2 Additional Support Spacing Charts For Trapeze Applications (.15g, .30g, .45g, .50g, .75g and 1.00g) .................................. 108 - 145 Appendix 3 Proof Test Instructions For Concrete Anchors (IR26-6) ........................................... 146 Appendix 4 Calculating Your Seismic Force Level .... 147 - 155 Appendix 5 (Beyond the scope of OSHPD) Additional Engineering Approvals ................... 156 COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 618-654-2184 Fax: 618-654-1917 Raafat S. Aboulhosn Structural Engineer S 3913 Date: Page No. Sheet Number: 12 - 9 - 02 ii of **SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 2 GENERAL INFORMATION B-LINE SEISMIC RESTRAINT SYSTEMS are designed to resist seismic loading while minimizing installation time and providing superior performance. On the following pages, several methods of seismic bracing are illustrated. The choice of brace design should be governed by the system requirements and location of supports. Actual applications may vary and are not strictly limited to the combinations of fittings and supports shown. Any changes to the depicted designs should be in accordance with standard engineering practices and be approved by OSHPD (California Office of Statewide Health Planning & Development) if necessary. For additional information on hangers, channels, fittings, and hardware shown, see the latest B-Line Strut Systems Catalog or Pipe Hangers and Supports Catalog. Seismic restraints are designed to resist the horizontal seismic force in two primary directions: Transverse (perpendicular) and Longitudinal (parallel) to the run. The braces are attached to the building with a structure attachment (for concrete, steel, wood, etc.) of various anchor sizes. Typically, the stronger the structure attachment, the greater the brace spacing allowed. The following steps detail how to use the brochure: Step 1: Select the bracing details for single pipe hangers or trapeze supports. Step 2: Obtain required force level (%g) from applicable code for local jurisdiction or from the structural engineer of record. Example: 2001 California Building Code As defined in the 2001 California Building Code, Chapter 16A, Section 1632A, the seismic horizontal force, Fp, may be calculated using the following formula: Fp = h apCaIp (1 + 3 • x )Wp Rp hr Except that: Fp shall not be less than 0.7 Ca Ip Wp and need not be more than 4 Ca Ip Wp. Where: Fp = Seismic Force Level ap = Amplification Factor (Table 16A-O) Rp = Component Response Modification Factor (Table 16A-O) = 3.0 for electrical, mechanical and plumbing equipment and associated conduit, ductwork and piping utilizing deeply embedded anchors. (Table 16A-O) = 1.5 for installations using concrete anchors with an embedment-to-diameter ratio less than 8. i.e. a 1/2" diameter concrete anchor with an embedment of less than 4" inches. COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 618-654-2184 Fax: 618-654-1917 Date: Page No. Sheet Number: 12 - 9 - 02 1 of Raafat S. Aboulhosn Structural Engineer S 3913 **SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 3 GENERAL INFORMATION Ip = Importance Factor (Table 16A-K) = 1.5 for Essential facilities such as Hospitals, Fire Stations, Police Stations, Aviation Control Towers, etc. consult Table 16A-K in CBC for a detailed listing. = 1.0 for most other occupancies Ca = Seismic Coefficient. This is a cumulation of several factors: Zone, Soil Properties, and distance from known fault. (Table 16A-I, Table 16A-J, Table 16A-Q, Table 16A-S, and Table 16A-U) hx = Element or component attachment elevation with respect to grade. Note: hx shall not be taken less than 0.0 hr = Structure Roof Elevation with respect to grade. Special Note: This manual is based on allowable stress design (ASD), where as the seismic force level (%g or Fp) for non-structural components provided in building codes are based on strength design. For use in this manual, the seismic force level (Fp) from the building code are converted to allowable stress design by dividing the result by 1.4. Example: If the building code yields, (Fp) = 1.4g, this value is converted to allowable stress design (ASD) as used in this catalog as follows: Fp=1.4g/1.4=1.0 g Strength Design to Allowable Stress Design Conversions .21g from building code = .15g (ASD) .42g from building code = .30g (ASD) .63g from building code = .45g (ASD) .70g from building code = .50g (ASD) 1.05g from building code = .75g (ASD) 1.40g from building code = 1.00g (ASD) Example One, Deeply Embedded Anchors: Cable tray system is suspended on the 1st floor of a 40-foot tall, 2-story surgical center in California. The cable tray is actually suspended from the bottom of the 2nd floor, which has an elevation of 20 feet above grade. Location of the surgical center is in seismic zone 4 with a rock soil profile. Fp = apCaIp h (1 + 3 • x )Wp Rp hr ap = 1.0 from Table 16A-O COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 618-654-2184 Fax: 618-654-1917 Raafat S. Aboulhosn Structural Engineer S 3913 Date: Page No. Sheet Number: 12 - 9 - 02 2 of **SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 4 GENERAL INFORMATION Ca = .40Na from Table 16A-Q, which is combination of Zone and Soil profile Zone 4 = .40, from Table 16A-I Rock Soil Profile = SB, from Table 16A-J Seismic Source Type = B, for faults other than Type A & C (Table 16A-U) Near Source Factor (Na) = 1.0, for 5 km from known seismic source (Table 16A-S) Ip = 1.5 from Table 16A-K, Occupancies having surgery and emergency treatment areas. Rp = 3.0 from Table 16A-O for deep embedded anchors hx = 20 feet hr = 40 feet Fp = (1.0)(0.40(1.0))(1.5) 20 (1 + 3 • )Wp = 0.50Wp = 0.50g 3.0 40 Check if value falls within limits: Fp shall not be taken less than, 0.7CaIpWp = 0.7(.40)(1.5)Wp = .42g Fp shall not be greater than, 4.0CaIpWp = 4.0(.40)(1.5)Wp = 2.4g 2.4g > .5 > 0.42g Therefore allowing the use of 0.50g To convert this Fp from a strength design to an Allowable Stress Design (ASD) used in this catalog divide by 1.4. 0.50g Fp = = 0.36g (ASD) 1.4 0.36g is the Allowable Stress Design Seismic Load Factor determined from 2001 California Building Code. Special Note: A table for .36g (ASD) is not available in this catalog. When seismic force levels (%g or Fp) falls between catalog table values (i.e.: .15g, .3g, .45g, etc.) the seismic force level shall be rounded up to the next highest cataloged force level. Example: If Fp = .36g (ASD), then use catalog tables for .45g (ASD). Example Two, Shallow Embedded Anchors: Special Note: Installations using concrete anchors installed with an embedment length-to-diameter ratio of less than 8, also referred to as shallow embedment anchors, have an adjusted Component Response Factor. The adjusted factor Rp = 1.5. COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 618-654-2184 Fax: 618-654-1917 Date: Page No. Sheet Number: 12 - 9 - 02 3 of Raafat S. Aboulhosn Structural Engineer S 3913 **SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 5 GENERAL INFORMATION Cable tray system is suspended on the 1st floor of a 40-foot tall, 2-story surgical center in California. The cable tray is actually suspended from the 2nd floor, which has an elevation of 20 feet above grade. Location of the surgical center is in seismic zone 4 with a rock soil profile, shallow embedment anchors are used for brace locations. Fp = h apCaIp (1 + 3 • x )Wp Rp hr ap = 1.0 from Table 16A-O Ca = .40Na from Table 16A-Q, which is combination of Zone and Soil profile Zone 4 = .40 from Table 16A-I Rock Soil Profile = SB from Table 16A-J Seismic Source Type = B for faults other than Type A & C (Table 16A-U) Near Source Factor (Na) = 1.0 for 5 km from known seismic source (Table 16A-S) Ip = 1.5 from Table 16A-K, Occupancies having surgery and emergency treatment areas. Rp = 1.5 adjusted for Shallow Embedment Anchors hx = 20 feet hr = 40 feet (1.0)(0.40(1.0))(1.5) 20 Fp = (1 + 3 • )Wp = 1.0Wp = 1.0g 1.5 40 Check if value falls within limits: Fp shall not be taken less than, 0.7CaIpWp = 0.7(.40)(1.5)Wp = .42g Fp shall not be greater than, 4.0CaIpWp = 4.0(.40)(1.5)Wp = 2.4g 2.4g > 1.0g > 0.42g Therefore allowing the use of 1.0g To convert this Fp from a strength design to an Allowable Stress Design (ASD) used in this catalog divide by 1.4. 1.0g Fp = = 0.71g (ASD) 1.4 0.71g is the Allowable Stress Design Seismic Load Factor determined from 2001 California Building Code for shallow embedment anchors. Special Note: A table for .71g (ASD) is not available in this catalog. When seismic force levels (%g or Fp) falls between catalog table values (i.e.: .15g, .3g, .45g, etc.) the seismic force level shall be rounded up to the next highest cataloged force level. Example: If Fp = .71g (ASD), then use catalog tables for .75g (ASD). Note: For other Code examples see Appendix 4 COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 618-654-2184 Fax: 618-654-1917 Raafat S. Aboulhosn Structural Engineer S 3913 Date: Page No. Sheet Number: 12 - 9 - 02 4 of **SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 6 GENERAL INFORMATION Step 3: With required force level (%g), obtain the transverse and longitudinal brace spacing from Appendix 1 (single pipe) or Appendix 2 (trapeze hanger). The following notes shall be followed: a) Break the length of pipe into separate straight runs, which are considered to be a single straight section between any bends in the pipe except where the bend is at an offset of less than the maximum offset length as defined below. Table 1 - Steel Pipe or Conduit Nominal Pipe Size 5 6 8 10 Table 2 - Copper Tubing Max. Offset Length (ft) 0.15g 0.3g 4 6 10 10 4 6 10 10 Nominal Tubing Size 0.5g 0.75g 1.0g 4 6 10 10 4 6 9 10 3 5 7 9 12 Max. Offset Length (ft) 0.15g 0.3g 4 4 0.5g 0.75g 1.0g 4 4 4 Note: The tabulated values represent pipe and tubing with moment and shear transfering joints. Therefore, for use of these tables pipes shall have welded, brazed, or UL Listed grooved joints. Pipe and tube sizes not listed above or joined as reqiuired shall be limited to a maximum offset length of 2 ft. Maximum Offset Length (ft.) b) Brace each straight run in the transverse direction at both ends. Where several short runs occur, see note e) on the following page. Straight Run Transverse bracing at both ends of the pipe run COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 618-654-2184 Fax: 618-654-1917 Date: Page No. Sheet Number: 12 - 9 - 02 5 of Raafat S. Aboulhosn Structural Engineer S 3913 **SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 7 GENERAL INFORMATION c) Check the required spacing for transverse bracing (Appendixes 1 & 2) and compare it to the length of the straight run. If the length of the straight run is greater than the allowable distance for transverse bracing add transverse braces until the spacing does not exceed the allowable transverse brace distance. Straight Run Additional Transverse Braces d) Each straight run must have at least one longitudinal brace. Add longitudinal braces so that the spacing does not exceed the allowable longitudinal brace spacing in Appendixes 1 & 2. Straight Run Longitudinal Brace (Transverse brace for the adjacent run) Longitudinal Brace 24” (610mm) Max. Longitudinal Brace (Transverse brace for the adjacent run) 24” (610mm) Max. Note: A transverse brace may dually act as a longitudinal brace for an adjacent run when it is located within 24” of the adjacent straight run. However, Appendixes 1 & 2 shall be reviewed to use the stronger of the longitudinal or transverse brace requirements, i.e. anchor and other component sizes. COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 618-654-2184 Fax: 618-654-1917 Raafat S. Aboulhosn Structural Engineer S 3913 Date: Page No. Sheet Number: 12 - 9 - 02 6 of **SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 8 GENERAL INFORMATION e) In many cases, several short runs occur one after the other. Based on previous requirements, each straight run requires a longitudinal brace when the adjacent short runs exceed the maximum offset length (ft.). When the adjacent short runs do not exceed the maximum offset length (ft.) the longitudinal braces can act as transverse braces as long as the allowable transverse brace spacing (Appendixes 1 & 2) is not exceeded. In the following layout, transverse braces are used as longitudinal braces when the straight runs are less than the maximum offset length (ft.). When a straight run exceeds the maximum offset length (ft.) additional braces are required. Second Transverse Brace First Transverse Brace Longitudinal brace Two braces may be required. Short run less than the maximum offset length (ft.) Straight run exceeding the maximum offset length (ft.) Longitudinal brace Multiple offsets can be treated as a single run when the total offset is less than the maximum offset length (ft.). Plan or Elevation COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 618-654-2184 Fax: 618-654-1917 Date: Page No. Sheet Number: 12 - 9 - 02 7 of Raafat S. Aboulhosn Structural Engineer S 3913 **SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 9 GENERAL INFORMATION f) When a flexible connection or swing joint is used, such as at a pipe drop to mechanical equipment, the pipe may cantilever at a length equal to or less than half the allowable transverse brace spacing (Appendixes 1 & 2). When greater than half the allowable transverse brace spacing, support to the floor is required as shown below. Transverse brace at the end of horizontal run Straight Run Requires a flexible connection or swing joint between equipment. Allowable Transverse Brace Spacing 2 Mechanical equipment. If < 6 ft. Support to Floor Is Required. Floor Step 4: Note the structure connection type (brace anchor requirements) from the Appendix, and select the brace anchorage detail to suit (pages 23 thru 38). Step 5: Note the hanger rod load from the Appendix, and select a rod attachment to structure to suit (pages 39 thru 56). Step 6: Check if rod stiffeners are required (pages 57 & 58) to prevent the hanger rod from buckling. Seismic restraints may typically be omitted from the following installations: (Verify with structural engineer of record for site specific project.) 1. Fuel piping less than 1 inch (25 mm) inside diameter. 2. All other piping less than 21/2 inches (63 mm) inside diameter, except medical gas including vacuum piping. 3. All piping suspended by individual hangers 12 inches (305 mm) or less in length from the top of the pipe to the bottom of the support for the hanger; where rod hangers are not subject to bending moments. (To eliminate bending moment flexible connections may be used such as the B752 on page 49 or B446 & B446C on page 56) 4. All electrical conduit less than 21/2 inches (63 mm) trade size. 5. All rectangular air handling ducts less than 6 sq. ft. (.56 m2) in cross sectional area. 6. All round air handling ducts less than 28 inches (711 mm) in diameter. 7. All ducts suspended by hangers 12 inches (305 mm) or less in length from the top of the duct to the bottom of the support for the hanger; where rod hangers are not subject to bending moments. (To eliminate bending moment flexible connections may be used such as the B752 on page 49 or B446 & B446C on page 56) NOTE: Reference building code enforced by local authority having jurisdiction for specific requirements. COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 618-654-2184 Fax: 618-654-1917 Raafat S. Aboulhosn Structural Engineer S 3913 Date: Page No. Sheet Number: 12 - 9 - 02 8 of **SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 10 GENERAL NOTES FOR SEISMIC BRACING GENERAL NOTES FOR SEISMIC BRACING A) The seismic restraint assemblies shown in this pre-approval document are designed to resist vertical loading simultaneously with seismic loading (transverse & longitudinal loading). Design recommendations shown are for single standard weight steel pipes filled with water. Contents other than water shall be evaluated by the user. Pipes of other approved materials shall be supported in accordance with their approved installation standards. Details not shown in this pre-approval shall be submitted to OSHPD for approval before installation if necessary. B) This bracing system is limited to the pipe sizes and support details shown. Special consideration must be given for pipe material and connections, insulation, thermal movement, vibration, and building seismic joints. C) Transverse and longitudinal braces shall be no more than 45° above or below the centerline of the pipe, duct, or tray. D) All channel and pipe clamp nuts and bolts shall be tightened to the following torques: 1/4"-20 to 6 ft.-lbs. (8 N•m) 3/8"-16 to 19 ft.-lbs. (26 N•m) 1/2"-13 to 50 ft.-lbs. (68 N•m) 5/8"-11 to 65 ft.-lbs. (88 N•m) 3/4"-10 to 75 ft.-lbs. (101 N•m) E) The transverse and longitudinal bracing spacing listed in Appendix 1 & 2 is based on ductile piping (steel, copper, etc.) with ductile connections (welded, brazed, etc.) and has the following limitations: 1) Transverse bracing shall not exceed 40’-0” (12.2 m). Longitudinal bracing shall not exceed 80’-0” (24.4 m). 2) Fuel piping shall have transverse bracing 20'-0" (6.1 m) o.c. maximum and longitudinal bracing 40'-0" (12.2 m) o.c. maximum. 3) Non-ductile piping, and piping with non-ductile connections shall have transverse bracing 20'-0" (6.1 m) o.c. maximum and longitudinal bracing 40'-0" (12.2 m) o.c. maximum or 1/2 of the calculated brace spacing indicated in Appendix 1 or 2, whichever is more restrictive. F) Transverse bracing for one pipe section may also act as longitudinal bracing for the pipe section connected to it, if the bracing is installed within 24 inches (609 mm) of the elbow or tee of similar size. Figures 2 and 4 do not serve as adequate longitudinal braces. COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 618-654-2184 Fax: 618-654-1917 Date: Page No. Sheet Number: 12 - 9 - 02 9 of Raafat S. Aboulhosn Structural Engineer S 3913 **SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 11 GENERAL NOTES FOR SEISMIC BRACING G) Branch lines of a smaller diameter shall not be used to brace main lines. H) Where rod stiffeners are required a minimum of two hanger rod stiffener assemblies shall be installed. (Part number SC-228 or SC-UB) I) It is important to check anchorage details against the applicable building code requirements. Seismic design forces may increase substantially when anchors are considered “shallow” (embedded less than 8 times the anchor diameter). J) When bracing trapeze type hangers, the bracing shall be attached directly to the trapeze hanger assembly and piping secured to the trapeze assembly with pipe straps. K) A rigid piping system shall not be braced to different parts of a building that may respond differently during an earthquake. Example: Solid concrete wall and a roof (metal deck filled with lightweight concrete). Special care should be taken to avoid bracing rigid pipe on both sides of a building seismic joint without allowing for pipe and building movement. L) The pre-approval document is based on British Units (Inches & Pounds) and values noted in parenthesis (Metric or S.I. Units) are equivalent values. In case of conflicts, British Units will be the standards for evaluating the proper application of pre-approvals. M) The designer of the structure shall determine the adequacy of the support structure to carry the load of the piping and equipment. Engineer of record for a site specific project shall verify that the structure can support the connection loads of the hanger rod and the bracing attachments. This pre-approval document is not intended for the seismic design of the piping itself. The dynamic properties of the building structure and piping should be considered when selecting the type of piping to be installed. N) Seismic bracing shall not limit the expansion and contraction of the piping system. Always consider thermal movements when selecting brace locations and materials. The design for thermal movements is beyond the scope of OSHPD pre-approval. P) No portion of this pre-approval shall be taken out of context and used in other systems, design or purpose. Q) On transverse bracing, the pipe insulation material may be part of the brace assembly (i.e) in the load path. In this case the insulating material shall be capable of withstanding the lateral forces without damage and shall include a pipe shield for hangers or a pipe saddle for rollers. For longitudinal bracing, clamping must be applied directly to the pipe with any insulation being installed directly over the hanger and brace assembly. In these applications the mechanical engineer of record shall be contacted for insulating recommendations. COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 618-654-2184 Fax: 618-654-1917 Raafat S. Aboulhosn Structural Engineer S 3913 Date: Page No. Sheet Number: 12 - 9 - 02 10 of **SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 12 B-LINE CHANNEL BRACES The following B-Line channels may be used as brace members for Figures 1 - 11 using the following structure connection types: Channel Type* Maximum Structure Connection Type** B54 IV B52 IV B42 V B32 V B24 IV B22 V B22A V B11 IV Maximum Brace Length Channel Height (m) 4’-10” 4’-8” 5’-10” 8’-0” 9’-7” 9’-5” 10’-10” 11’-7” Channel Width (mm) (1.47) 13/16” (1.42) 13/16” (1.78) 1” (2.44) 13/8” (2.92) 15/8” (2.74) 15/8” (3.30) 31/4” (3.53) 31/4” Material Thickness (mm) (mm) (20.6) 1 5/8” (41.3) 14 Ga. (1.9) (20.6) 1 5/8” (41.3) 12 Ga. (2.6) 1 5/8” (41.3) 12 Ga. (2.6) 1 5/8” (41.3) 12 Ga. (2.6) 1 5/8” (41.3) 14 Ga. (1.9) 1 5/8” (41.3) 12 Ga. (2.6) 1 5/8” (41.3) 12 Ga. (2.6) 1 5/8” (41.3) 12 Ga. (2.6) (25.4) (34.9) (41.3) (41.3) (82.5) ( 82.5) *Slotted channel (SH) versions of all the above types may also be used for brace members. See page 21 for channel details. **The Structure Connection Type is the brace anchorage requirement. See pages 23 - 38 for brace attachment details. Note: Do not exceed the maximum brace length or maximum structure connection type for the channels listed. Commentary: Appendix 1 & 2 list the allowable structure connection type (I, II, III, IV, or V) for each brace spacing listed. The structure connection type limits the amount of axial load (in tension or compression) which is applied to the brace member. The axial load is listed for each structure connection detail on pages 23 - 38, and is as follows: Structure Connection Type I II III IV V Maximum Axial Load in Brace Member ....................................... ...................................... ...................................... ...................................... ...................................... 175 lbs. 300 lbs. 450 lbs. 675 lbs. 975 lbs. (0.78 kN) (1.33 kN) (2.00 kN) (3.00 kN) (4.33 kN) The B-Line channel brace member must have a capacity greater than the value listed in the above table for the maximum recommended brace length. COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 618-654-2184 Fax: 618-654-1917 Date: Page No. Sheet Number: 12 - 9 - 02 11 of Raafat S. Aboulhosn Structural Engineer S 3913 **SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 13 SINGLE PIPE/CONDUIT BRACING Single Rod Hanger Pipe Bracing 1) Layout piping run and determine size and location of piping. 2) Select vertical supports (single rod pipe hangers). a) Select type of hanger dependent on type of pipe, thermal expansion and contraction, etc. b) Determine maximum spacing of hanger rods and minimum hanger rod diameter. (Appendix 1) c) Select hanger rod connection to the structure based on structure type, rod size and hanger rod load from Appendix 1. Refer to section on hanger rod attachment for details (pages 39 thru 56) d) Engineer of record for a site specific project shall verify that the structure can support the connection loads. 3) Select lateral bracing (transverse and longitudinal bracing). a) Select bracing details (transverse & longitudinal) from Figures 1 thru 8. b) Determine maximum spacing for transverse and longitudinal braces. (Appendix 1) c) Determine the type of structure connection required. (Appendix 1) Refer to section on structural attachments for connection details. d) Determine if rod stiffener is required. (pages 57 & 58) e) Engineer of record for a site specific project shall verify that the structure can support the connection loads. 4) Review the design and revise layout where loads exceed the limitations of the hanger rods, hangers or connection details. COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 618-654-2184 Fax: 618-654-1917 Raafat S. Aboulhosn Structural Engineer S 3913 Date: Page No. Sheet Number: 12 - 9 - 02 12 of **SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 14 SINGLE PIPE BRACING CLEVIS HANGER TRANSVERSE BRACING (Figure 1) ATR All Threaded Rod Pipe Size (See Page 57 for minimum diameter) Rod Stiffener (See Pages 57 & 58) 1 (Min.) B-Line Channel Transverse Brace 1 Adjustable Hinge Part No. Pipe Sleeve Part No.* N/A in. (mm) Clevis Hanger Part No. 1/2" (15) B3100-1/2 N/A 3/4" (20) B3100-3/4 N/A N/A 1" (25) B3100-1 B335-2-3/8 B3100PS-1 11/4" (32) B3100-11/4 B335-2-3/8 B3100PS-11/4 11/2" (40) B3100-11/2 B335-2-3/8 B3100PS-11/2 2" (50) B3100-2 B335-2-3/8 B3100PS-2 21/2" (65) B3100-21/2 B335-2-3/8 B3100PS-21/2 3" (80) B3100-3 B335-2-3/8 B3100PS-3 31/2" (90) B3100-31/2 B335-2-3/8 B3100PS-31/2 B335-2-Bolt Size Adjustable Hinge 4" (100) B3100-4 B335-2-3/8 B3100PS-4 5" (125) B3100-5 B335-2-1/2 B3100PS-5 (See Page 59) 6" (150) B3100-6 B335-2-1/2 B3100PS-6 8" (200) B3100-8 B335-2-5/8 B3100PS-8 10" (250) B3100-10 B335-2-3/4 B3100PS-10 12" (300) B3100-12 B335-2-3/4 B3100PS-12 (See page 11) B3100PS Pipe Sleeve B3100 Series Clevis Hanger * Not included when ordering standard B3100 Series Clevis Hanger. (See Page 63) Notes: Pipe sleeve required over cross bolt of Clevis Hanger when using the brace connection shown above (Figure 1). Pipe sleeve is not required when clevis hanger is used in conjunction with the bracing shown in Figure 5 - page 15. Refer to Note Q) on page 10 for installations requiring insulated pipe. "J" HANGER TRANSVERSE BRACING (Figure 2) Rod Stiffener May Be Required (See Pages 57 & 58) 1 Min. Pipe Size 1 ATR All Threaded Rod (See Page 57 for minimum diameter) B-Line Channel Transverse Brace (See page 11) B335-2-Bolt Size Adjustable Hinge (See Page 59) B3690 Series 'J' Hanger (See Page 64) Adjustable Hinge Part No. N/A in. (mm) "J" Hanger Part No. 1/2" (15) B3690-1/2 3/4" (20) B3690-3/4 1" (25) B3690-1 B335-2-3/8 11/4" (32) B3690-11/4 B335-2-3/8 11/2" (40) B3690-11/2 B335-2-3/8 2" (50) B3690-2 B335-2-3/8 21/2" (65) B3690-21/2 B335-2-1/2 3" N/A (80) B3690-3 B335-2-1/2 31/2" (90) B3690-31/2 B335-2-1/2 4" (100) B3690-4 B335-2-1/2 5" (125) B3690-5 B335-2-1/2 6" (150) B3690-6 B335-2-1/2 8" (200) B3690-8 B335-2-1/2 Note: Refer to Note Q) on page 10 for installations requiring insulated pipe. COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 618-654-2184 Fax: 618-654-1917 Date: Page No. Sheet Number: 12 - 9 - 02 13 of Raafat S. Aboulhosn Structural Engineer S 3913 **SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 15 SINGLE PIPE BRACING PIPE CLAMP TRANSVERSE BRACING (Figure 3) ATR All Threaded Rod Rod Stiffener May Be Required (See Page 57) (See Pages 57 & 58) 1 (Min.) in. (mm) Pipe Clamp * Part No. Adjustable Hinge Part No. 11/2" (40) B3144-11/2 B335-2-1/2 2" (50) B3144-2 B335-2-1/2 (65) B3144-21/2 B335-2-1/2 Pipe Size 21/2" 3" (80) B3144-3 B335-2-1/2 4" (100) B3144-4 B335-2-5/8 5" (125) B3144-5 B335-2-5/8 6" (150) B3144-6 B335-2-3/4 8" (200) B3144-8 B335-2-3/4 10" (250) B3144-10 B335-2-3/4 12" (300) B3144-12 B335-2-3/4 B-Line Channel Transverse Brace 1 B3200 Series Weldless Eye Nut (See page 11) B335-2-Bolt Size Adjustable Hinge (See Page 59) B3144 Series Double Bolt Pipe Clamp (See Page 65) Note: Refer to Note Q) on page 10 for installations requiring insulated pipe. * See note D) on page 9 for clamp torque values. PIPE ROLLER TRANSVERSE BRACING (Figure 4) ATR All Threaded Rod (See Page 57 for minimum diameter) Rod Stiffener (See Pages 57 & 58) Pipe Size 1 (Min.) Pipe Roller Part No. Adjustable Hinge Part No. in. (mm) 21/2" (65) B3110-21/2 B335-2-1/2 3" (80) B3110-3 B335-2-1/2 31/2" (90) B3110-21/2 B335-2-1/2 B-Line Channel Transverse Brace 4" (100) B3110-4 B335-2-1/2 5" (125) B3110-5 B335-2-5/8 (See page 11) 6" (150) B3110-6 B335-2-3/4 1 B335-2-Bolt Size Adjustable Hinge (See Page 59) B3110 Series Adjustable Steel Yoke Pipe Roll (See Page 66) Note: Refer to Note Q) on page 10 for installations requiring insulated pipe. COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 618-654-2184 Fax: 618-654-1917 Raafat S. Aboulhosn Structural Engineer S 3913 Date: Page No. Sheet Number: 12 - 9 - 02 14 of **SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 16 SINGLE PIPE BRACING TRANSVERSE BRACING (Figure 5) 1 (Min.) B2400 Series Pipe Strap 1 (See Page 71) B-Line Channel Transverse Brace (See page 11) 3” min. (76mm) Channel Nuts & Bolts Not Included (See Pages 61 & 62) Notes: Install brace within 4" (101mm) of hanger. (Hanger not shown for clarity. See Figure 6 below) Refer to Note Q) on page 10 for installations requiring insulated pipe LONGITUDINAL BRACING (Figure 6) Rod Stiffener May Be Required (See Pages 63 & 64) B335V-Bolt Size Adjustable Half Hinge in. (mm) Pipe Clamp* Part No. 1" (25) B3140-1 B335V-1/2 B3373-1 B335V-1/2 (32) B3140-11/4 B335V-1/2 B3373-11/4 B335V-1/2 (40) B3140-11/2 B335V-1/2 B3373-11/2 B335V-1/2 (50) B3140-2 B335V-1/2 B3373-2 B335V-1/2 (65) B3140-21/2 B335V-1/2 B3373-21/2 B335V-1/2 Pipe Size (See Page 59) 11/4" B-Line Channel Longitudinal Brace 11/2" (See page 11) 21/2" 2" 4” max. (101mm) B3140 Pipe Clamp or B3373 Riser Clamp Series (See Pages 67 & 69) Riser Clamp * Part No. Adjustable Half Hinge Part No. (80) B3140-3 B335V-1/2 B3373-3 B335V-1/2 31/2" (90) B3140-31/2 B335V-1/2 B3373-31/2 B335V-1/2 4" (100) B3140-4 B335V-5/8 B3373-4 B335V-1/2 5" (125) B3140-5 B335V-5/8 B3373-5 B335V-1/2 6" (150) B3140-6 B335V-3/4 B3373-6 B335V-1/2 8" (200) B3140-8 B335V-3/4 B3373-8 B335V-5/8 10" (250) -- -- B3373-10 B335V-5/8 12" (300) -- -- B3373-12 B335V-5/8 3" Pipe Hanger or Support Adjustable Half Hinge Part No. * See note D) on page 9 for clamp torque values. Notes: Install brace within 4" (101mm) of hanger. Refer to Note Q) on page 10 for installations requiring insulated pipe. COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 618-654-2184 Fax: 618-654-1917 Date: Page No. Sheet Number: 12 - 9 - 02 15 of Raafat S. Aboulhosn Structural Engineer S 3913 **SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 17 SINGLE PIPE BRACING - COPPER TUBING CLEVIS HANGER TRANSVERSE BRACING (Figure 7) ATR All Threaded Rod Copper Tubing Size (See Page 57 for minimum diameter) Adjustable Hinge Part No. Pipe Sleeve Part No.* N/A in. (mm) Clevis Hanger Part No. 1/2" (15) B3104CT-1/2 N/A 3/4" (20) B3104CT-3/4 N/A N/A 1" (25) B3104CT-1 B335-2-3/8 B3104CTPS-1 11/4" (32) B3104CT-11/4 B335-2-3/8 B3104CTPS-11/4 11/2" (40) B3104CT-11/2 B335-2-3/8 B3104CTPS-11/2 2" (50) B3104CT-2 B335-2-3/8 B3104CTPS-2 21/2" (65) B3104CT-21/2 B335-2-3/8 B3104CTPS-21/2 B335-2-Bolt Size Adjustable Hinge 3" (80) B3104CT-3 B335-2-3/8 B3104CTPS-3 (See Page 59) 31/2" (90) B3104CT-31/2 B335-2-3/8 B3104CTPS-31/2 4" (100) B3104CT-4 B335-2-3/8 B3104CTPS-4 Rod Stiffener (See Pages 57 & 58) 1 (Min.) B-Line Channel Transverse Brace 1 (See page 11) B3104CTPS Pipe Sleeve * Not included when ordering standard B3104CT Series Clevis Hanger. B3104CT Series Clevis Hanger (See Page 68) Notes: Pipe sleeve required over cross bolt of Clevis Hanger when using the brace connection shown above (Figure 7). Refer to Note Q) on page 10 for installations requiring insulated pipe. LONGITUDINAL BRACING (Figure 8) Rod Stiffener May Be Required (See Pages 57 & 58) B335V-Bolt Size Adjustable Half Hinge Copper Tubing Size (See Page 59) B-Line Channel Longitudinal Brace (See page 11) Pipe Hanger or Support 4” max. (101mm) Note: Install brace within 4" (101mm) of hanger. Refer to Note Q) on page 10 for installations requiring insulated pipe. COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 618-654-2184 Fax: 618-654-1917 S 3913 (mm) 1" (25) B3373CT-1 B335V-1/2 B335V-1/2 11/4" Adjustable Half Hinge Part No. (32) B3373CT-11/4 11/2" (40) B3373CT-11/2 B335V-1/2 2" (50) B3373CT-2 B335V-1/2 21/2" (65) B3373CT-21/2 B335V-1/2 3" (80) B3373CT-3 B335V-1/2 31/2" (90) B3373CT-31/2 B335V-1/2 4" (100) B3373CT-4 B335V-1/2 * See note D) on page 9 for clamp torque values. B3373CT Riser Clamp Series (See Page 69) Raafat S. Aboulhosn Structural Engineer in. Riser Clamp * Part No. Date: Page No. Sheet Number: 12 - 9 - 02 16 of **SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 18 TRAPEZE BRACING Trapeze Assembly Bracing 1). Layout piping and/or conduit runs and determine number, size and location of items to be supported by the trapeze 2). Determine trapeze support spacing (LT). This is usually determined by the maximum support spacing of the smallest pipe or conduit on the trapeze. 3). Select trapeze supports. a). Determine the total vertical load (TL) for each trapeze. TL = LT x WT TL = Total vertical load for each trapeze support (lbs.) LT = Trapeze support spacing (ft.) WT = Weight of all piping, cable tray, ductwork, conduit, etc. in lbs./ft. supported by the trapeze b). Determine length of trapeze, making sure sufficient length is added to attach the all threaded rod and bracing attachments. All channel nuts shall be fully engaged within strut. (13/16” (20mm) minimum distance from edge of strut to center line of bolt.) c). Select type of trapeze member (B22, B22AMIG, etc.) by selecting a member with loading greater than the total load (TL). See Table 4 on page 22 for strut loading data, noting that the trapeze beam span is the distance between the hanger rods. Also determine whether the applied load is uniform or concentrated, and follow notes on page 22 accordingly. Variations in pipe sizes (simular to concentrated load assembly on page 22) shall be treated as a concentrated load, where as same sized pipes evenly distributed across the span (similar to uniform load assembly on page 22) may be treated as a uniform load. Uniform loads on page 22 are converted to a concentrated load by a 50% reduction. Do not exceed the beam span length given by Table 4A on page 22, which limits overloading due to longitudinal seismic force. d). Determine hanger rod size from Appendix 2 based on total weight (WT) and trapeze support spacing (LT). Rod sizes are given for trapeze supports with braces attached and unbraced trapezes. e). Select a hanger rod connection to structure (pages 39 thru 56) that is greater than the hanger rod loads listed in Appendix 2. 4). Select transverse and longitudinal bracing. a). Select bracing detail from Figures 9 - 11. b). Determine spacing of transverse / longitudinal bracing from Appendix 2 based on total weight (Wt) and the trapeze support span (Lt). Note the corresponding structure attachment type (Roman numeral I - V) for each possible brace interval. When supporting multiple pipe sizes, do not exceed the maximum spacing for the smallest pipe as given in Appendix 1. Verify that the specific forces do not exceed the capacity of the pipe clamps on pages 70 & 71. c). Determine if rod stiffener is required (pages 57 & 58). d). Engineer of record for a site specific project shall verify that the structure can support the connection loads. 5). Review the design and revise layout where loads exceed the limitations of the hanger rods, strut trapeze supports, or connection details. COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 618-654-2184 Fax: 618-654-1917 Date: Page No. Sheet Number: 12 - 9 - 02 17 of Raafat S. Aboulhosn Structural Engineer S 3913 **SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 19 TRAPEZE BRACING TRAPEZE TRANSVERSE AND LONGITUDINAL BRACING (Figure 9) B-Line Channel Longitudinal Brace B335-2-Bolt Size Adjustable Hinge (See page 11) ATR All Threaded Rod (See Page 57) (See Page 59) Rod Stiffener (See Pages 57 & 58) B2400 Series Pipe Straps 1 (See Page 71) 1 (Min.) B-Line Channel Transverse Brace B-Line Channel Transverse Brace (See page 11) (See page 11) B335-2-1/2 Adjustable Hinge Transverse Brace B335-2-1/2 Adjustable Hinge Longitudinal Brace Hex Nut & (See Page 59) Square Washer (See Page 59) B-Line Channel - Size as Required B2000 Series Pipe Straps (See Page 22 - Table 4 & 4A For Channel Load Data) (See Page 62) (See Page 70) See Note 3b on page 17 Notes: 1). B335-2 adjustable hinges for longitudinal braces may be attached on either side adjacent to the all thread rod, or attached to the all thread rod itself. 2). B335-2 adjustable hinges for transverse braces may be attached to the all thread rod. 3). Two B335-2 adjustable hinges may be attached to the strut trapeze using the same bolt or all thread rod. 4). It is not necessary to install both transverse braces and longitudinal braces on the same trapeze support. Either set of braces may be removed to form a longitudinal brace only or a transverse brace only if desired. 5). Longitudinal braces, when needed, must be installed at both ends of trapeze. 6). The equipment shown on this trapeze support is generic in nature. Any number of pipes, conduits, ductwork or cable tray may be supported following the system weight and support spans listed in Appendix 2 - Table 1. 7). Torque all nuts per Note D, page 9. 8). Refer to note Q, page 10 for installations requiring insulated pipe. COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 618-654-2184 Fax: 618-654-1917 Raafat S. Aboulhosn Structural Engineer S 3913 Date: Page No. Sheet Number: 12 - 9 - 02 18 of **SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 20 TRAPEZE BRACING TRAPEZE TRANSVERSE AND LONGITUDINAL BRACING (Figure 10) B-Line Channel Longitudinal Brace (See page 11) B335-2-Bolt Size Adjustable Hinge ATR All Threaded Rod (See Page 57) (See Page 59) Rod Stiffener (See Pages 57 & 58) 1 Cable Tray 1 (Min.) B-Line Channel Transverse Brace B-Line Channel Transverse Brace (See page 11) (See page 11) B335-2-1/2 Adjustable Hinge Transverse Brace B335-2-1/2 Adjustable Hinge Longitudinal Brace Hex Nut & (See Page 59) Square Washer (See Page 59) (See Page 62) B-Line Channel - Size as Required B2000 Series Pipe Straps (See Page 22 - Table 4 & 4A For Channel Load Data) (See Page 70) See Note 3b on page 17 B2400 Series Pipe Straps (See Page 71) Notes: 1). B335-2 adjustable hinges for longitudinal braces may be attached on either side adjacent to the all thread rod, or attached to the all thread rod itself. 2). B335-2 adjustable hinges for transverse braces may be attached to the all thread rod. 3). Two B335-2 adjustable hinges may be attached to the strut trapeze using the same bolt or all thread rod. 4). It is not necessary to install both transverse braces and longitudinal braces on the same trapeze support. Either set of braces may be removed to form a longitudinal brace only or a transverse brace only if desired. 5). Longitudinal braces, when needed, must be installed at both ends of trapeze. 6). The equipment shown on this trapeze support is generic in nature. Any number of pipes, conduits, ductwork or cable tray may be supported following the system weight and support spans listed in Appendix 2 - Table 1. 7). Torque all nuts per Note D, page 9. 8). Refer to note Q, page 10 for installations requiring insulated pipe. COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 618-654-2184 Fax: 618-654-1917 Date: Page No. Sheet Number: 12 - 9 - 02 19 of Raafat S. Aboulhosn Structural Engineer S 3913 **SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 21 TRAPEZE BRACING TRAPEZE TRANSVERSE AND LONGITUDINAL BRACING (Figure 11) B-Line Channel Longitudinal Brace (See page 11) ATR All Threaded Rod (See Page 57) Rod Stiffener 1 B2400 Series Pipe Straps (See Pages 57 & 58) 1 (Min.) (See Page 71) B-Line Channel Transverse Brace (See page 11) B-Line Channel Size as Required (See Page 22 Table 4 & 4A For Channel Load Data) B335-2-1/2 Adjustable Hinge Longitudinal Brace Hex Nut & Square Washer B2000 Series Pipe Straps (See Page 59) (See Page 62) (See Page 70) See Note 3b on page 17 Notes: 1). B335-2 adjustable hinges for longitudinal braces may be attached on either side adjacent to the all thread rod, or attached to the all thread rod itself. 2). B335-2 adjustable hinges for transverse braces may be attached to the all thread rod. 3). Two B335-2 adjustable hinges may be attached to the strut trapeze using the same bolt or all thread rod. 4). It is not necessary to install both transverse braces and longitudinal braces on the same trapeze support. Either set of braces may be removed to form a longitudinal brace only or a transverse brace only if desired. 5). Longitudinal braces, when needed, must be installed at both ends of trapeze. 6). The equipment shown on this trapeze support is generic in nature. Any number of pipes, conduits, ductwork or cable tray may be supported following the system weight and support spans listed in Appendix 2 - Table 2. 7). Torque all nuts per Note D, page 9. 8). Refer to note Q, page 10 for installations requiring insulated pipe. COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 618-654-2184 Fax: 618-654-1917 Raafat S. Aboulhosn Structural Engineer S 3913 Date: Page No. Sheet Number: 12 - 9 - 02 20 of **SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 22 APPROVED COMPONENTS Seismic Approvals: Trapeze Hanger, Longitudinal Brace, Transverse Brace, Threaded Stiffener Single Channel “A” Channel Y 15/8" (41mm) 3/8" 3/8" 7/8" (9mm) ‘Hx’ (9mm) (22mm) 9/32" Y (7mm) X ‘H’ X ‘H’ X X ‘Hx’ Notes: Y Y Standard Lengths: 10 ft. (3.05 m) & 20 ft. (6.09 m) Finishes: Plain, Dura-Green Epoxy, and Pre-Galvanized 13/16" 13/16" (20mm) (20mm) 15/8" (41mm) Height Dimensions Channel ‘H’ B54 B52 B42 B32 B24 B22 B22A B12 B12A B11 B11A B_ _SH ‘Hx” in. (mm) 13/16” (20) 13/16” (20) 1” 13/8” 15/8” 15/8” 31/4” 27/16” 47/8” 31/4” 61/2” (25) in. (mm) 0.3422 0.3366 0.4226 0.6052 0.7304 0.7189 1.6250 1.1127 2.4375 1.5112 3.2500 (35) (41) (41) (82) (62) (124) (82) (165) 9/16" (14mm) x 7/8" (22mm) slots 2" (51mm) on centers. 1" (25mm) from end of channel to center of first slot. (8.7) (8.5) (10.7) (15.4) (18.5) B_ _SHA (18.2) (41.3) 9/16" (14mm) x 7/8" (22mm) slots 2" (51mm) on centers. 1" (25mm) from end of channel to center of first slot. All B12SHA & B11SHA channels are mig welded. (28.2) (61.9) (38.4) (82.5) Table 3 SECTION PROPERTIES Channel B54 B52 B42 B32 B24 B22 B22A B12 B12A B11 B11A Weight lbs./ft. kg/m 1.01 1.31 1.47 1.73 1.44 1.90 3.80 2.47 4.94 3.05 6.10 (1.51) (1.95) (2.18) (2.58) (2.15) (2.83) (5.65) (3.67) (7.35) (4.54) (9.08) X -X Axis Areas of Section in.2 (cm2) Moment of Inertia (I) in.4 Section Modulus (S) (cm4) .299 (1.93) .0263 (1.09) .386 (2.49) .0320 (1.33) .432 (2.79) .0554 (2.31) .510 (3.29) .1252 (5.21) .424 (2.74) .1494 (6.22) .559 (3.61) .1850 (7.70) 1.118 (7.21) .9379 (39.04) .727 (4.69) .5203 (21.65) 1.453 (9.37) 2.8132 (117.09) .897 (5.79) 1.0917 (45.44) 1.794 (11.59) 6.2139 (258.64) in.3 (cm3) Y - Y Axis Radius of Gyration (R) in. .0560 (0.92) .297 .0673 (1.10) .288 .0968 (1.59) .358 .1626 (2.67) .496 .1670 (2.74) .594 .2042 (3.34) .580 .5772 (9.46) .924 .3927 (6.43) .852 1.1541 (18.91) 1.402 .6278 (10.29) 1.112 1.9120 (31.33) 1.876 (cm) (0.75) (0.73) (0.91) (1.26) (1.51) (1.47) (2.34) (2.16) (3.56) (2.82) (4.76) Moment of Inertia (I) in.4 (cm4) .1106 .1404 .1645 .2098 .1857 .2340 .4681 .3306 .6611 .4271 .8542 (4.60) (5.84) (6.85) (8.73) (7.73) (9.74) (19.48) (13.76) (27.52) (17.78) (35.55) Section Modulus (S) in.3 (cm3) .1361 (2.23) .1728 (2.83) .2025 (3.32) .2582 (4.23) .2286 (3.75) .2880 (4.72) .5761 (9.44) .4068 (6.66) .8137 (13.33) .5256 (8.61) 1.0513 (17.23) Radius of Gyration (R) in. .608 .603 .617 .642 .662 .653 .653 .679 .679 .696 .696 (cm) (1.55) (1.53) (1.57) (1.63) (1.68) (1.66) (1.66) (1.72) (1.72) (1.77) (1.77) Calculations of section properties are based on metal thicknesses as determined by the AISI Cold-Formed Steel Design Manual. For channel loading see page 22. COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 618-654-2184 Fax: 618-654-1917 Date: Page No. Sheet Number: 12 - 9 - 02 21 of Raafat S. Aboulhosn Structural Engineer S 3913 **SRS2002-OSpg.ii-25 (11/02) N 1/3/03 4:35 PM Page 23 TRAPEZE BRACING Typical Trapeze ATR ATR Beam Span (BS) Beam Span (BS) B-Line Channel (See below) Uniform Load Concentrated Load Table 4 Channel Type & Uniform Beam Load Rating Beam Span (BS) B22SH lbs. (kN) B22 B22A B12 B12A* (kN) B11 B11A* in. (mm) lbs. (kN) lbs. (kN) lbs. (kN) lbs. lbs. (kN) 12" (305) 2553 (11.35) 2837 (12.62) 8165 (36.32) 5498 (24.45) 3259 (14.49) 4395 (19.54) 4309 lbs. (19.16) (kN) 24" (610) 1276 (5.68) 1418 (6.31) 4083 (18.16) 2750 (12.23) 3259 (14.49) 4395 (19.54) 4309 (19.16) 36" (914) 851 (3.78) 946 (4.21) 2722 (12.11) 1833 (8.15) 3259 (14.49) 2930 (13.03) 4309 (19.16) 48" (1219) 638 (2.84) 709 (3.15) 2042 (9.08) 1374 (6.11) 3259 (14.49) 2197 (9.77) 4309 (19.16) 60" (1524) 511 (2.27) 568 (2.52) 1633 (7.26) 1100 (4.89) 3231 (14.37) 1758 (7.82) 4309 (19.16) 72" (1829) 426 (1.89) 473 (2.10) 1361 (6.05) 916 (4.07) 2693 (11.98) 1465 (6.51) 4309 (19.16) 84" (2133) 365 (1.62) 405 (1.80) 1167 (5.19) 785 (3.49) 2308 (10.26) 1256 (5.58) 3824 (17.01) 96" (2438) 319 (1.42) 354 (1.57) 1021 (4.54) 687 (3.05) 2019 (8.98) 1011 (4.49) 3346 (14.88) 108" (2743) 284 (1.26) 315 (1.40) 908 (4.04) 611 (2.72) 1795 (7.98) 977 (4.34) 2974 (13.23) 120" (3048) 255 (1.13) 283 (1.26) 817 (3.63) 550 (2.44) 1616 (7.19) 879 (3.91) 2677 (11.91) • Loads shown in chart have a safety factor of 2. • Based on uniformly loaded simple span with adequate lateral bracing using an allowable stress of 21,000 psi (144.7 MPa). • To determine concentrated load capacity at mid-span, multiply the uniform load by 0.5. • Refer to note 3c) on page 17 for uniform and concentrated load requirements. • Use 90% of the solid channel loads for corresponding SH and SHA channels. • Refer to note Q) on page 10 for installations requiring insulated pipe. * These back to back channels are mig welded. Table 4A Structure Connection Type B22SH Channel type and maximum beam span for longitudinal beam loading B22A B12 B12A* B22 B11 B11A* in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) I 176 (4470) 196 (4978) 391 (9931) 276 (7010) 552 (14021) 357 (9068) 714 (18135) II 103 (2616) 114 (2895) 228 (5791) 161 (4089) 322 (8179) 208 (5283) 416 (10566) III 68 (1727) 76 (1930) 152 (3861) 107 (2718) 215 (5461) 139 (3530) 278 (7061) IV 46 (1168) 51 (1295) 101 (2565) 72 (1829) 143 (3632) 93 (2362) 185 (4699) V 32 (813) 35 (889) 70 (1778) 50 (1270) 99 (2514) 64 (1625) 128 (3251) COOPER B-Line 509 West Monroe Street Highland, Illinois 62249 Phone: 618-654-2184 Fax: 618-654-1917 Raafat S. Aboulhosn Structural Engineer S 3913 Date: Page No. Sheet Number: 12 - 9 - 02 22 of