INSMCR INSTALLATION INSTRUCTIONS FOR INFOSTREAMTM MULTI-CHANNEL RACEWAY SYSTEM 1 6.4 sq. in. 2 Base and Cover with No Devices 3 Offset Box with Data (OB) 4 5 6 Power and Data Inline using Raised Brackets (REB, RDB) Data Only using Raised Bracket (RDB) Wire Fill Chart LOW VOLTAGE Wire Type Raceway Channel 1 6.40in2 Area of Raceway Channel 2 Channel 3 1.220in2 4.260in2 Channel 4 Channel 5 Channel 6 5.880in2 0.800in2 2.450in2 Wire Size OD of Wire Spec Max Spec Max Spec Max Spec Max Spec Max Spec Max Twisted Pair 24 AWG Unshielded 2 Pr. 3 Pr. 4 Pr. Cat 5e 4 Pr. Cat 6 4 Pr. Cat 6a 25 Pr. 0.140 0.150 0.217 0.240 0.354 0.410 166 144 69 56 26 19 249 217 103 84 39 29 31 27 13 10 4 3 47 41 19 16 7 5 110 96 46 37 17 12 166 144 69 56 25 19 152 229 133 199 63 95 51 77 23 35 17 26 20 18 8 7 3 2 31 27 12 10 4 3 63 55 26 21 9 7 95 83 39 32 14 11 Coax RG58/U RG6/U 0.193 0.242 0.270 87 55 44 131 83 67 16 10 8 25 15 12 58 37 29 87 55 44 80 51 41 120 76 61 10 6 5 16 10 8 33 21 17 50 31 25 Fiber Optic FA Jacket OFNP 2 Strand 4 Strand 6 Strand 0.175 0.185 0.210 106 95 73 159 142 110 20 18 14 30 27 21 70 63 49 106 95 73 97 87 67 146 131 101 13 11 9 19 17 13 40 36 28 61 54 42 Fiber Optic 62.5/125/900 PVC Jacket OFNR 2 Strand 4 Strand 6 Strand 8 Strand 10 Strand 0.175 0.185 0.210 0.230 0.250 106 95 73 61 52 159 142 110 92 78 20 18 14 11 9 30 27 21 17 14 70 63 49 41 34 106 95 73 61 52 97 87 67 56 47 146 131 101 84 71 13 11 9 7 6 19 17 13 11 9 40 36 28 23 19 61 54 42 35 29 RG59/U or RG62/U Electrical Wire 14 AWG THHN 12 AWG THHN 10 AWG THHN 0.105 0.122 0.153 30 25 19 21 15 9 - - 14 11 8 - Formula used to calculate communications wire fill capacity - Numbers of wires = duct / {1/4 x 3.14 x (wire o.d.)2} x 0.4 or 0.6. Per ANSI/TIA/EIA-569-A-: SPEC = 40% fill which is recommended for planning perimeter pathways MAX (for data) = 60% fill which is allowed to accommodate unplanned additions after initial installation MAX (for power) = Maximum number determined by UL temperature testing Note: It is recommended to place electrical cables loosely in raceway The adhesive strip may serve only as a positioning aid during installation. The raceway shall be secured by mechanical fastening. Rev: 5 / Rev Date: 10/1/2012 Page 1 of 2 BASE AND COVER Part Numbers: MCR_-B8, MCR_-B10, MCR_-C8, MCR_-C10 Recommend raceway mounted every 16” - 24” Appropriate mounting hardware should be used to secure the raceway to the mounting surface. Recommend use of #8 round or pan-head screws. 1 3 2 DIVIDERS Part Number for Side Divider: MCRW-SD8, MCRW-SD10 Dividers are snapped into the base on the center or side position to separate the power wires and communication wires. The center or side divider is included with the base. The center divider is taller and has ribs near the top. The side divider is white in color. 2 1 Side Center 3 Side Center 7930 N. Faulkner Rd. Milwaukee, WI 53224 Phone: (800) 537-1512, (414) 355-1130 • Fax: (800) 848-9866, (414) 355-7341 www.hellermann.tyton.com • email: corp@htamericas.com Rev: 5 / Rev Date: 10/1/2012 Page 2 of 2