INSTALLATION INSTRUCTION
MHT-CL/RCL
1. Main Data For RCL
Fixture
Model
Lamp
Type
RCL-40E
RCL-55E
MHT-ST-40-U
Power
Factor
(COSφ)
0.95
Net
Weight
(lbs)
8.0
0.49~0.21
MHT-ST-55-U
0.95
8.0
74
0.61~0.27
MHT-ST-70-U
0.95
8.4
84
0.70~0.30
MHT-ST-80-U
0.95
8.4
Input Wattage
(W)
Current (A)
Ballast Model
RT40W
42
0.35~0.15
58
RCL-70E
RT55W 110V ~ 277V
RT70W AC 50/60Hz
RCL-80E
RT80W
2.
Power Supply
(VAC)
Circuit Diagram:
Without Photocell
With Photocell
(Button Type)
3.
Brown
L Black
White
N
Green
E
L
N White
E Green
Induction lamp
Red
Red
Black
Brown
Ballast
Lamp
Red
Outline and Dimensions: (mm)
※ Installation: Standard Surface Mount & 3/4” Pendant. Optional 1/2” Pendant with adapter.
Phone # (718) 524-4370
Fax # (718) 524-4390
www.MHTLIGHTING.com
INSTALLATION INSTRUCTION
4.
MHT-CL/RCL
Installation and Maintenance Instruction:
4.1 The efficient and reliable grounding is a must not only for the personal protection, but
also for the proper use of electronic ballast to meet the national standard of EMC
without interference to other equipments.
4.2 The Luminaire shall be installed in the area with good ventilation, no corrosive gas and
no combustible and explosive objects.
4.3 The supply voltage is allowed to be varied at 110V-277V. It will influence the normal
start and operation of lamp and damage the electronic ballast if it is outside of this
range.
4.4 The maintenance can only be done after the power is cut off and the lamp is cold down
to prevent scald and electric shock accident.
4.5 Do not remove the lamp when power on.
4.6 The product shall be installed and serviced by the competent and certified electrician.
Note:1. The cover shall be replaced when it is cracked
. 2. The above data is subject to change without notice
Warning:
The efficient and reliable ground is a must when install Luminaire, to prevent
electric leakage and electric shock accident. End user should be responsible for the
consequence if against the instruction.
Phone # (718) 524-4370
Fax # (718) 524-4390
www.MHTLIGHTING.com
INSTALLATION INSTRUCTION
MHT-CL/RCL
1. Main Data For CL
Fixture Model
Lamp
Type
MHT-CL-40E
RT40W
MHT-CL-55E
RT55W
MHT-CL-70E
RT70W
MHT-CL-80E
RT80W
Supply Voltage
(VAC)
120V~277V AC
(-10%~+10%)
50/60Hz
MHT-CL-100E RT100W
Power
Input
Working
Net
Wattage Current Ballast Model Factor Weight
(W)
(A)
(COSφ) (lbs)
42
8.7
0.35~0.15 MHTST-40-U
58
0.49~0.21 MHTST-55-U
8.7
74
0.61~0.27 MHTST-70-U ≥0.95
9.4
84
0.70~0.30 MHTST-80-U
9.8
105
0.88~0.38 MHTST-100
10.0
2. Circuit Diagram
Without Photocell
With Photocell
(DTL Button Type)
Brown
L Black
Electronic
White
N
Green ballast
E
Red
绿
L
N White
E Green
Red
Lamp
Black
Brown
Ballast
Lamp
Red
3. Outline Dimensions (inch/mm)
Mounting: Surface Ceiling/Pendant/Hook
Min distance of 0.8m (2.62ft) should be maintained between the fixture and the objects
4. Installation and Maintenance Instruction
4.1 The efficient grounding is a must, not only for the personal protection, but also for the proper use of
electronic ballast to meet the national standard of EMC without interference to the equipment.
4.2 The Luminaire should be installed in an area with good ventilation, with no corrosive gas and no
combustible or explosive objects.
4.3 The supply voltage is allowed to be varied at +10% to -10%. It will influence the normal start and
operation of lamp and damage the electronic ballast if it is outside of this range.
4.4 The maintenance can be done only after the power is cut off and the lamp is has cooled down.
4.5 The product is to be installed and serviced by a competent and certified electrician.
4.6 The wiring inside the Luminaire is tool-free and it is not allowed to disconnect with the lamp while
the power is on.
4.7 The ambient temperature is allowed to be -20°F to +120°F
4.8 Operation while the glass cover is open is forbidden.
Phone # (718) 524-4370
Fax # (718) 524-4390
www.MHTLIGHTING.com
INSTALLATION INSTRUCTION
MHT-CL/RCL
Note: The above data is subject to change without notice.
! Warning: The Luminaire shall be grounded reliably to avoid accidental power leakage and
electric shock.
Installation:
Loosen two screws
on Ballast Enclosure
(Top Cover)
Fig.1 Loose two screws on Cover
Disconnect Quick
Connectors
Fig.2 Disconnect connectors
Seal Connector
Ballast
Enclosure
(Top Cover)
Fig.3 Separate the lamp compartment
and the ballast enclosure
Anchoring screw
for ceiling
Concave plot
Fig.4 Drill small holes on the
concave plot
Fig.7 Put the power cord through
the Seal Connector and make
connection to Terminal Block
Phone # (718) 524-4370
Fig. 5 Knock out the ½” knockout
and fasten the Seal Connector
Fig.8 Slide in Lamp Compartment
back to Ballast Enclosure and
reconnect Quick Connectors
Fax # (718) 524-4390
Fig. 6 Secure the
Enclosure to the ceiling
Ballast
Fig.9 Secure Ballast Enclosure
with the screws
www.MHTLIGHTING.com