Multi Parameter
Environmental Logging
FLOW MEASUREMENT
DATA LOGGING
LEAK DETECTION
PRESSURE CONTROL
ENVIRONMENTAL MONITORING
Waste, Drainage, Ground Water, Surface Water
and more data from Octopus/Vista
INTRODUCTION
Halma Water Management has introduced two data loggers
specifically designed for Multi -Parameter Environmental
Logging Applications. Both units combine 20 years of
application experience at Hydreka S.A. with the unique data
logging hardware experience of Radcom Technologies.
DRINKING WATER
SURFACE WATER
GROUND WATER
WASTE WATER
The
water
cycle
KEY BENEFITS
•
Rugged and fully submersible unit
•
Five year battery life
•
Dedicated “Winfluid” software
•
Switch output
•
PDA and PC software compatibility
•
Multiple telemetry options
•
Local display (Vista+ only)
•
GSM and Landline Outputs
(Octopus only)
•
Remote programming
•
Multi-sensor compatibility
MULTIPLE
APPLICATIONS
•
Level Monitoring of rivers, tanks,
reservoirs, open channels etc;
•
Open channel flow monitoring
•
Overflow monitoring
•
Rainfall monitoring
•
Pump usage monitoring
•
Multi-sensor compatibility
•
Network Pressure monitoring
•
Rain Gauge
•
Driving and Logging Samplers
When deployed with 'Winfluid'
Software the loggers offer
ease of use whilst providing
results across a wide
range of applications.
The power and simplicity
of the software enables
easy configuration of
multiple sensors and
automatic conversion
algorithms to give immediate
usable data.
The Vista Plus is a manual download logger with advanced
specification and a local display to give multiple input
compatibility and PDA and PC software compatibility. It also
features a local display and can be programmed with
conversion tables via Winfluid to show conversion data, for
example from depth to flow.
The Octopus logger additionally features multiple telemetry
options with GSM and PSTN Landline, together with a switch
output to drive additional equipment such as samplers to
extend applications.
5 YEAR
BATTERY
LIFE
WINFLUID
SOFTWARE
MULTI
INPUT
HWM
EXPERTISE
All of this is supported by HWM’s unrivalled reputation for
customer support by highly experienced personnel and fully
trained, supported representatives world-wide.
Halma Water Management
Call +44 (0) 1633 489479
or visit www.hwm-water.com
Company is ISO 9001 Registered No.06134A
A H A L M A C O M PA N Y
Flow Measurement
Unique Processing Power with Winfluid
Almost all bulk or domestic meters can be read allowing applications in
zonal or DMA measurement, network testing or modelling, DMA reporting
or customer usage monitoring. Advanced alarm features are available which,
together with telemetry provide immediate exception warnings.
HWM Octopus
Data Logger
with Multiple
Telemetry Options
Ultrasonic Level Monitoring
Ultrasonic sensors (e.g. ‘SonicSens‘) are mounted above liquids and used for
a range of purposes, including open channel, level and flow measurement,
river, tank or reservoir level monitoring or sewer overflow reporting. The
sensor is never in contact with the fluid, thereby minimising maintenance.
Intrinsically safe versions are available.
GSM
Rain Gauge
The event logging facility and advanced processing of Winfluid enables rain
gauges to accurately report rainfall. This can be combined with other input
data to measure the impact of rainfall on sewer or drainage levels. Samplers
can also be driven by the logger to monitor quality parameter variation
against precipitation.
Landline/PSTN
Winfluid is a powerful yet easily used software package for the
full range of HWM sensors and applications. It is available for
local PC and PDA download together with full telemetry
programming, reporting and alarm options. Ease of use is
maintained by the use of consistent programming screens no
matter what the application.
Level Monitoring, Pressure Transducer
Accurate submerged sensors monitor levels by measuring the liquid pressure
above for applications such as river level, borehole, reservoir or tank level
monitoring. It can be used where limited overhead mounting prevents use of
ultrasonic sensors. Winfluid allows easy calibration without the need for
factory ‘pairing’ loggers and sensors.
Open Channel Flow Monitoring
PC
Using accepted function sets programmed in Winfluid and civil
constructions (flumes, weirs) level measurements from pressure or Ultrasonic
sensors can be converted into accurate flow readings. This can be displayed
on the logger or software, for local or telemetry monitoring.
The true power of the software is seen in its ability to make
conversions based on established function sets (Kindsvater
Carter, Kindsvater Shen, Manning-Strickler), and in its ability to
input specific tables and conversions.
Overflow Monitoring
Simple overflow measurement can be achieved with HWM overflow
sensors and event logging. The overflow event shorts contacts in the
sensor and the start duration and finish of the overflow is accurately
recorded in Winfluid. This provides a highly cost effective solution for
recording and alarming spill activity.
Laptop
Insertion Probe, Flow Measurement
The HydrINS electromagnetic insertion probe provides highly accurate flow
monitoring without the need to cut the pipe. Installation is done through a
‘hot tap’ and flow is not interrupted. It’s the ideal solution for network
investigation and zoning and all programming and reporting is done through
HWM loggers and Winfluid software.
Pump Usage
Pump activity can be monitored and reported using current clamps which
detect when a pump is active. Pump run times can be recorded for diagnostic
and flow approximation, allowing associated consumption, volume and
potential network problems to be identified. Multi-pump calculation for
accurate multiple pump flow-measurement.
Network Pressure Monitoring
Loggers can use internal or external pressure sensors to accurately record
network pressure through available connections such as consumer meters,
hydrants and other ‘wet’ fittings. Typical applications are network
diagnostics, network model verification, compliance (minimum pressure)
monitoring and network optimisation.
Multi-sensor
compatibility
Loggers are available with
multiple (digital, 4-20ma,
voltage, serial) input options
to interface with third party
sensors for additional
applications such as water
quality, PH, conductivity etc
or new specific requirements
where rugged remote logging
with telemetry options would
be of benefit (e.g. weather
parameters)
Sampler
Octopus loggers have a
switch output available
to drive samplers
triggered by other inputs
such as flow or level.
PDA
The data base facility is flexible with numerous search, listing
and sort options. Full graphical visualisations and reporting
facilities are available, together with exporting in standard
formats and specific interface to third party management
software packages.
Specific tools are available to treat and combine data. Examples
include linear interpolation, height to velocity/flow and multiple
pump usage analysis. Winfluid is continually evolving but
maintains it's ease of use to ensure that its full functionality can
be exploited
Winfluid is available in a number of language options.
.
Multi Parameter
Environmental Logging
LoLog Vista Plus
Digital
Inputs
Two
Channels
Logging
Features
Communication
Physical
Analogue
Memory
Logging Modes
Display
Local
Software
Dimensions
Material/Protection
Temperature
Power
Unidirectional Count: 60Hz maximum
Event (rain gauge)
State (overflow, pump clamps)
Internal Pressure Sensor 10-20 Bar
External Pressure Sensor 150mB to 20 Bars
0-20 mA, 4-20 mA
0-1v, 0-5v
49152 readings based on start/stop threshold
1 second to 24 hours. Instantaneous or average/delayed start.
Real time display of flow, pressure, level, state, event, level to flow conversions
Infra Red 9600 bauds
Winfluid
160 L X 108 W X 45 H / 0.8 kg
Die cast aluminum / IP 68 submersible
-20°C with + 70°C
5 year ion lithium internal batteries. Minimum 5 years battery life at 1 minute logging
HWM reserve the right to change the specification of any product without prior notice.
Octopus
Direct Link Land Line GSM
Digital
(1 or 2 options)
Inputs
Outputs
Logger
Details
Communication
Physical
Analogue
(1 option)
Contact
Memory
Logging Period
Alarms
Room
Landline
GSM
Software
Dimensions
Material/Protection
Operating Temp
Battery
Count single or bidirectional (500 Hz max)
Compatible with all flow meters
State, Event, Frequency
Pressure sensor for level (25, 50, 100 mV). Internal pressure:
10, 16, 20 Bars. External pressure: 150 mbar, 350 mbar, 1Bar
20 my, 4-20 passive or active (powered by logger)
Input signal tension (2.5, 5, 10V)
2 relay outputs (1 A at 30 V). Driving samplers
65.536 samples by channel, start/stop or barrel memory
Instantaneous or averaging, differed start programmed stop
1 second to 24 hours
Autocall alarm by single exception or profile
RS232. 19.200 bauds
Internal Modem
Internal Dual or Quad bands
Winfluid
195 L X 120 W X 70 H / 1.6 kg
235 L X 145 W X 80 H / 2.4 kg
Die cast aluminum / IP68 submersible
-20°C with + 70°C
Internal lithium ion batteries, giving 5 years typical life at 15
minute logging. Optional external power through RS232 port.
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
HWM reserve the right to change the specification of any product without prior notice.
Halma Water Management
a Division of Palmer Environmental
Ty Coch House Llantarnam Park Way
Cwmbran Gwent NP44 3AW United Kingdom
Tel: +44 (0) 1633 489479 Fax: +44 (0) 1633 877857
sales@hwm-water.com www.hwm-water.com
HWM Multi Parameter Logging 11/2008
FLOW MEASUREMENT
DATA LOGGING
LEAK DETECTION
PRESSURE CONTROL
ENVIRONMENTAL MONITORING
Specification