Product Description Alarm Panels Electric Fire Pump Controllers • FTA200-A FTA200-B Type B - Type B panels provide the same alarm indication as the Type A except that SUPERVISORY POWER FAILURE does not have the audible alarm feature. Only a visible alarm indication is provided. Description—Firetrol® FTA200 alarm panels are designed to meet the NPFA 20 specifications requiring a remote alarm panel when the pump house or pump room is not constantly attended. The alarm panel must be installed in a location that is under supervision at all times. Approvals—These alarm panels are listed by Underwriter’s Laboratories, Inc., in accordance with UL508, Standard for Industrial Controls, certified by CSA, Standard for Industrial Control Equipment (cUL), approved by the New York City Bureau of Electrical Control and Board of Standards and Appeals and Factory Mutual. They are designed to meet or exceed the requirements of the approving authorities listed above as well as NFPA 20, Installation of Centrifugal Fire Pumps. Standard Features—The following are included as standard with each controller: Type A - Type A panels provide audible and visible alarm indication for the following conditions: n Supervisory Voltage Normal n Pump Operating n Pump Phase Failure n Pump Phase Reversal Construction - FTA200 alarm panels make use of printed circuit boards which provide reliable and trouble free service. The enclosures are NEMA Type 2 (IEC IP11) drip-proof for indoor wall mounting. The standard enclosure color is red. Mounted on the enclosure door are the pilot lights for visible alarm indication, the audible device for audible alarm indication, the SILENCE ALARM pushbutton and the PUSH-TO-TEST pushbutton. Each pilot light will illuminate to indicate its alarm condition and will remain lighted until the abnormal condition has been corrected. The audible alarm will sound when the alarm conditions occur and will continue to sound until the abnormal condition has been corrected or the SILENCE ALARM pushbutton has been pressed. Pressing the SILENCE ALARM pushbutton will silence the audible alarm but will not extinguish the pilot light. If another alarm condition occurs the audible alarm will again sound until silenced by the SILENCE ALARM pushbutton or until the abnormal condition has been corrected. The PUSH-TO-TEST pushbutton is supplied for manually testing the pilot lights, audible alarm and output circuits. Modifications—The following are available as modifications to the controllers: Special Enclosures -F NEMA Type 4X, 304 stainless (IEC IP56) -Y NEMA Type 1 (IEC IP10) Flush Mount, Painted Steel Consult Factory for other style enclosures. Additional Alarm Functions Each additional alarm function ordered will include a control relay and pilot light and will provide audible and visible alarm. There is no limit as to the number of additional alarm functions that can be supplied, however, enclosure size and weight may be affected. Consult the Factory for dimensions and shipping weights when ordering more than 2 additional alarms. Standard remote alarms may be ordered by using the Suffix Letters indicated for the corresponding alarm function on the Electric Fire Pump Controller. Alarm functions must exist in the controller to be ordered as remote alarms. Standard Remote Alarms -AM Pump Fail To Start -BY Pump Overload -EG Relief Valve Discharge -EJ Flow Meter On Non-Standard Remote Alarms -BT When ordering, specify the number of alarms required, the function of each and the nameplate marking of each. Substitute Amber for Red Pilot Lights -LA To meet local code requirements. Dimensions and Shipping Weight Explanation of Catalog Number FTA200-A-Y Approx. Shipping Weight 18 lbs (8kg) Alarm Panel Type Modification Code(s) Example - FTA200-A-Y Type A Alarm Panel with Nema Type 1, Flush Mount Enclosure. Information Required With Orders n Catalog number of alarm panel n Catalog number of controller to be used with alarm panel n Modifications if any (give complete description) Note—Due to continual product enhancements, dimensions and specifications may change at any time without notice. Contact the factory or local representative for current specifications. (919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27512 USA PD200-01(B) Product Description Alarm Panels Diesel Engine Fire Pump Controllers • FTA200-F FTA200-G Type G - Type G panels provide alarm indication for the following conditions: n Supervisory Voltage Normal (Visible Only) n Engine Trouble (Audible and Visible n Engine Running (Audible and Visible) n Main Switch Mis-Set (Audible and Visible) n Pump Room Trouble (Audible and Visible) Description—Firetrol® FTA200 alarm panels are designed to meet the NPFA 20 specifications requiring a remote alarm panel when the pump house or pump room is not constantly attended. The alarm panel must be installed in a location that is under supervision at all times. Approvals—These alarm panels are listed by Underwriter’s Laboratories, Inc., in accordance with UL508, Standard for Industrial Controls, certified by CSA, Standard for Industrial Control Equipment (cUL), approved by the New York City Bureau of Electrical Control and board of Standards and Appeals and Factory Mutual. They are designed to meet or exceed the requirements of the approving authorities listed above as well as NFPA 20, Installation of Centrifugal Fire Pumps. Standard Features—The following are included as standard with each controller: Type F - Type F panels provide alarm indication for the following conditions: n Supervisory Voltage Normal (Visible Only) n Engine Trouble (Audible and Visible) n Engine Running (Audible and Visible) n Main Switch Mis-Set (Audible and Visible) Construction - FTA200 alarm panels make use of printed circuit boards which provide reliable and trouble free service. The enclosures are NEMA Type 2 (IEC IP11) drip-proof for indoor wall mounting. The standard enclosure color is red. Mounted on the enclosure door are the pilot lights for visible alarm indication, the audible device for audible alarm indication, the SILENCE ALARM pushbutton and the PUSH-TO-TEST pushbutton. Each pilot light will illuminate to indicate its alarm condition and will remain lighted until the abnormal condition has been corrected. The audible alarm will sound when the alarm conditions occur and will continue to sound until the abnormal condition has been corrected or the SILENCE ALARM pushbutton has been pressed. Pressing the SILENCE ALARM pushbutton will silence the audible alarm but will not extinguish the pilot light. If another alarm condition occurs the audible alarm will again sound until silenced by the SILENCE ALARM pushbutton or until the abnormal condition has been corrected. The PUSH-TO-TEST pushbutton is supplied for manually testing the pilot lights, audible alarm and output circuits. Modifications—The following are available as modifications to the controllers: Special Enclosures -F NEMA Type 4X, 304 stainless (IEC IP56) -Y NEMA Type 1 (IEC IP10) Flush Mount, Painted Steel Consult Factory for other style enclosures. Additional Alarm Functions Each Additional alarm function ordered will include a control relay and pilot light and will provide audible and visible alarm. There is no limit as to the number of additional alarm functions that can be supplied, however, enclosure size and weight may be affected. Consult the Factory for dimensions and shipping weights when ordering more than 2 additional alarms. Standard remote alarms may be ordered by using the Suffix Letters indicated for the corresponding alarm function on the Diesel Engine Fire Pump Controller. Alarm functions must exist in the controller to be ordered as remote alarms. Standard Remote Alarms -AU Low Fuel Level -AV Low Pump Room Temperature -AW Reservoir Low -AY Low Suction Pressure -AJ Engine Overspeed -AK Low Oil Pressure -AL High Water Temperature -AM Engine Failed To Start -AN Battery/Charger Failure -AP Main Switch In Manual -AR Main Switch In Off -AS Main Switch In Auto -LC High Fuel Level -LE Fuel Spill -EG Relief Valve Discharge -EJ Flow Meter On Non-Standard Remote Alarms -BT When ordering, specify the number of alarms required, the function of each and the nameplate marking of each. Substitute Amber for Red Pilot Lights -LA To meet local code requirements. Operation on 220-240 Volts -BA Panel is supplied as standard for operation on 110-120 volts. Dimensions and Shipping Weight Approx. Shipping Weight 18 lbs. (8kg) Note—Due to continual product enhancements, dimensions and specifications may change at any time without notice. Contact the factory or local representative for current specifications. Explanation of Catalog Number FTA200-G-AU-LE Alarm Panel Type Modification Code(s) Example - FTA200-G-AU-LE Type G Alarm Panel with remote alarms for Low Fuel Level and Fuel Spill. Information Required With Orders n Catalog number of alarm panel n Catalog number of controller to be used with alarm panel n Modifications if any (give complete description) (919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27512 USA PD200-02(B) Product Description Low Suction Pressure Shutdown Alarm Panels Fire Pump Controllers • FTA200-D FTA200-E Mounted on the enclosure door are the pilot lights for visible alarm indication, the audible device for audible alarm indication and the SILENCE ALARM push-button. Each pilot light will illuminate to indicate its alarm condition and will remain lighted until the abnormal condition has been corrected. The audible alarm will sound when the alarm conditions occur and will continue to sound until the abnormal condition has been corrected or the SILENCE ALARM push-button has been pressed. Pressing the SILENCE ALARM push-button will silence the audible alarm but will not extinguish the pilot light. If another alarm condition occurs the audible alarm will again sound until silenced by the SILENCE ALARM push-button or until the abnormal condition has been corrected. A pressure switch for monitoring the suction pressure is mounted on the side of the enclosure. Description—Firetrol® FTA200 low suction pressure alarm and shutdown panels are designed to be used with electric and diesel engine driven fire pump controllers. They are intended for use where a local authority mandates pump shutdown in the event of low suction pressure. Approvals—These alarm panels have been approved by Factory Mutual. Standard Features—The following are included as standard with each controller: Type D - Type D panels provide audible and visible alarm indication for the following conditions: Supervisory Voltage Normal Pump Controller Voltage Failure Low Suction Pressure (Automatic Reset) Type E - Type E panels provide the same alarm indication as the Type D except that LOW SUCTION PRESSURE shutdown and alarm must be manually RESET when suction pressure is restored. Construction - FTA200 alarm panels make use of printed circuit boards which provide reliable and trouble free service. The enclosures are NEMA Type 2 (IEC IP11) drip-proof for indoor wall mounting. The standard enclosure color is red. APPROVED Modifications—The following are available as modifications to the controllers: Special Enclosures -F NEMA Type 4X, 304 stainless (IEC IP56) Consult Factory for other style enclosures. Substitute Amber for Red Pilot Lights -LA To meet local code requirements. Operation on 220-240 Volts -BA Panel is supplied as standard for operation on 110-120 volts. 50 HZ Operation -GZ Controller is supplied to operate on 50 HZ incoming power. Dimensions and Shipping Weight Explanation of Catalog Number FTA200-D-GZ Alarm Panel Type Modification Code(s) Example - FTA200-D-GZ Type D Alarm Panel with modification to operate on 50 HZ incoming power. Information Required With Orders Catalog number of shutdown panel Catalog number of controller to be used with shutdown panel Modifications if any (give complete description) WARNING- Because NFPA 20 specifically prohibits the installation of any device in the suction piping which will restrict starting or stopping of the fire pump (See NFPA 20 (2007), Paragraph 5.14.9.1), ASCO Power Technologies, LP assumes no liability when Type D or E Shutdown Panels are used in connection with fire pump control equipment. Approx. Shipping Weight 20 lbs (9 kg) Note—Due to continual product enhancements, dimensions and specifications may change at any time without notice. Contact the factory or local representative for current specifications. (919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27512 USA PD200-03 (04-02-07)