Installation LT-0180 (4/94) 881 Expansion Interface Card For Use with DMP 1912XR Command Processor Panels Description The 881 Expansion Interface Card allows you to connect additional 714 and 715 Loop Expander Modules to the 1912XR Command Processor panel. Loop expanders connect in parallel to a 4-wire bus consisting of two data wires, auxiliary power, and a panel common wire. See Figure 1. Installing the 881 module The 881 card plugs onto the J9 connector of the 1912XR panel and uses an adhesive backed plastic standoff mounted in the center to hold securely in place. 1912XR Panel J9 Expansion Connector Adhesive backed standoff attaches to microprocessor. J3 Loop Expansion Connector LPX Red Black Red - To terminal 7 Black - To terminal 10 Loop Expander Harness { Bk - Aux. Common Gr - Serial Data Out Yl - Serial Data In Rd - Aux. Positive Figure 1: Installing the 881 on the 1912XR panel Follow the instructions below when installing the 881 card: 1. Remove AC and battery power from the 1912XR panel before installing the 881. 2. Remove the paper strip from the base of the plastic standoff. 3. Hold the 881 card on the upper left and right corners using the thumb and index finger of each hand and carefully align the 40 pin connector of the 881 with the J9 connector on the 1912XR panel. 4. Gently press the 881 into the J9 connector while applying even pressure on both sides. 5. Connect the loop expander bus to the J3 Loop Expansion Connector. 6. Connect the Black wire from the 881 card to terminal 10 on the 1912XR panel. 7. Connect the Red wire from the 881 card to terminal 7 on the 1912XR panel. 8. Power for devices connected to the 881 card is provided by the panel's auxiliary power terminals 7 and 10. You can also add a regulated auxiliary power supply. When using a separate power supply, connect a wire from the negative terminal of the power supply to terminal 10 of the 1912XR panel. 9. Restore AC and battery power to the 1912XR. 881 Installation 2500 N. Partnership Boulevard Springfield, MO 65803 www.dmpnet.com Digital Monitoring Products Installing Multiple Expansion Devices 1912XR Command Processor 881 Expansion Interface DMP 714 and 715 Loop Expanders can be used together on the same 1 2 3 4 5 6 7 AC AC B + B - BELLGND 8 YEL9 GRN 14 L115GND 19 L4 10 BLK1SMK 12 L5+ 13 L516L2 17L3 18GND expansion wiring. Red Yellow Terminal 7 Auxiliary Power Green Black Terminal 10 Panel Common. Terminal 1 1 Switched MODEL 715 LOOP EXP ANDER MODEL 714 LOOP EXP ANDER Aux. Power MODEL 715 LOOP EXP ANDER Always connect a wire from the negative of the power supply to An auxiliary UL listed power supply can be used to extend terminal 10 of the 1912XR Command Processor panel. device mounting distances. MODEL 714 LOOP EXP ANDER 12 VDC Auxiliary Power Supply AC T o AC transformer Do NOT use the 1912XR AC transformer Figure 2: Device and power supply connection to the 881 card. Wiring Distances for Multiple Expansion Devices # of expansion devices on 881 Distance when powered from panel Distance when powered from auxiliary power supply * 22 AWG 18 AWG 22 AWG 18 AWG 1 3940' 9875' 7500' 9375' 2 2735' 6855' 7500' 9375' 3 1925' 4830' 7500' 9375' 4 1420' 3565' 7500' 9375' 5 1140' 2855' 7500' 9375' 6 900' 2250' 7500' 9375' 8 700' 1755' 7500' 9375' 10 550' 1370' 7500' 9375' 15 370' 930' 7500' 9375' 20 265' 660' 7500' 9375' 25 200' 495' 7500' 9375' Figure 3: Expansion device wiring distances. * Locate auxiliary power supplies at the far end of the wire run. Digital Monitoring Products 2500 N. Partnership Boulevard Springfield, MO 65803 800-641-4282 MODEL 714 LOOP EXP ANDER