BACnet SRCM User Manual

advertisement
BACnet SRCM User Manual
125-1900. Rev AA
2014-02-12
Building Technologies Division
Copyright Notice
Copyright Notice
Notice
Document information is subject to change without notice by Siemens Industry, Inc.
Companies, names, and various data used in examples are fictitious unless otherwise
noted. No part of this document may be reproduced or transmitted in any form or by
any means, electronic or mechanical, for any purpose, without the express written
permission of Siemens Industry, Inc.
All software described in this document is furnished under a license agreement and
may be used or copied only in accordance with license terms.
For further information, contact your nearest Siemens Industry, Inc. representative.
Copyright 2014 by Siemens Industry, Inc.
To the Reader
Your feedback is important to us. If you have comments about this manual, please
submit them to: SBT_technical.editor.us.sbt@siemens.com
Product or company names mentioned herein are the trademarks of their respective
owners.
Printed in USA
2
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Table of contents
Overview .................................................................................................................... 5
Home Screen .................................................................................................................. 5
Condition Banner ............................................................................................................. 6
Condition Banner - Touch Screen Operation .................................................................... 7
Alarms Cause Condition Banner to Turn Red................................................................... 7
Condition Banner Functions............................................................................................. 7
Operating Condition Screen............................................................................................. 8
Pressure Value ................................................................................................................ 9
Slider Bar and Setpoint Values ........................................................................................ 9
Slider Bar On/Off ............................................................................................................. 9
Active and Standby Modes ............................................................................................ 10
Menu Screens ............................................................................................................... 10
Setting the Application.................................................................................................12
Before You Begin .......................................................................................................13
Setup Unit..................................................................................................................14
Room - Primary or Secondary........................................................................................ 14
Primary Room Sensor .............................................................................................. 14
Secondary Room Sensor .......................................................................................... 15
Room Parameters ......................................................................................................... 15
Label ........................................................................................................................ 15
Primary Analog Output ............................................................................................. 15
Engineering Unit ....................................................................................................... 15
Sensor Range .......................................................................................................... 16
Analog Inputs ................................................................................................................ 16
Changing the Room Name ............................................................................................ 17
Setup Display .............................................................................................................19
General Tab - Customizing the Condition Banner .......................................................... 19
Advanced Tab - Customizing the Condition Banner ....................................................... 19
Display Averaging (Tenths of Seconds) ......................................................................... 20
What Pressure to Display .............................................................................................. 20
Pressure Resolution ...................................................................................................... 21
Supervisor and Operator Passwords ............................................................................. 21
Condition Banner Tab - Customizing Blinking Screens ................................................... 22
Full Screen Condition Banner and Active Standby Mode Application .............................. 23
Set Time & Date Screen ................................................................................................ 24
Setup Alarm ...............................................................................................................26
Alarms Disabled When Door is Open and Buzzer for Door Warning ............................... 27
Alarm Setpoint ............................................................................................................... 28
Alarm Matrix .................................................................................................................. 29
3
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Calibration and Self-Test ............................................................................................. 31
System Information..................................................................................................... 33
USB Configuration Cloning .......................................................................................... 34
Network Setup ........................................................................................................... 36
Event Log .................................................................................................................. 38
Controlling Temperature.............................................................................................. 39
French Language Support on Default Screen and Data Entry Screen ............................... 40
Troubleshooting ......................................................................................................... 42
Point Database .......................................................................................................... 43
Notification Class ....................................................................................................... 53
Event Enrollment ........................................................................................................ 54
4
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Overview
Home Screen
Overview
The following pages describe how to use the BACnet SRCM. The screen has two
basic functions. The primary mode of operation displays the Home screen, which
shows the end-user pressure values, messages, text and other data intended for visual
pressure verification in the facility. The secondary mode of operation is the
Administrative Menu screen, which permits set-up and configuration, and changes how
the SRCM operates. After changes have been performed on the Menu screen,
functions are saved and operation returns to the Home screen.
If you do not interact with the touch screen for more than one minute, the screen will
automatically return to the Home screen.
Many administrative settings can be written over the network.
Home Screen
The default screen has two modes. You can switch modes by selecting the SLIDER
ON or SLIDER OFF button on the bottom of the Administrative Menu. The Home
screen is the normal, continuous operating mode of the SRCM.
The Home screen shows a Condition Banner on the left of the screen, and Operating
Conditions on the right of the screen.
5
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Overview
Condition Banner
Figure 1: Alternate Home Screen with Multiple Parameters.
Condition Banner
The Condition Banner, on the left of the screen can be configured by the user or
Facility Manager to display a message to staff on the floor. The Condition Banner can
be Green, Yellow, Red or Blue, depending on the type of message desired outside the
pressurized space. The Condition Banner is set up in the Setup Display-Condition
Banner tab of the Administrative Menu. The Condition Banner also has an option to
display in full screen mode. The Condition Banner will change to Red in alarm state
regardless of the current configuration. You can manually change the banner by
pressing the touch screen anywhere within the banner color region.
Green Condition Banner—shows Entry
Permitted graphic, and user defined text
above and below graphic image. Use the
GREEN banner to indicate room is safe to
enter.
Red Condition Banner—shows Stop
graphic, and user defined text above and
below graphic image. Use the RED banner
to indicate room is under critical use and
entry is not allowed.
Yellow Condition Banner—shows Warning
graphic, and user defined text above and
below graphic image. Use the YELLOW
banner to indicate room is under transient
use and entry is restricted.
BLUE Condition Banner—shows Entry
Permitted graphic, and user defined text
above and below graphic image. Use the
BLUE banner to indicate room is safe to
enter.
6
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Overview
Condition Banner - Touch Screen Operation
Condition Banner - Touch Screen Operation
You can cycle through all four conditions by simply touching the left third of the screen
in any region. If passwords are enabled, you will be prompted to enter their password
before proceeding. Each of the four colored screens can have a unique message
defined.
Alarms Cause Condition Banner to Turn Red
When alarm occurs, the Condition Banner changes as follows:
1. The Condition Banner will turn to Red and will blink irrespective of the color mode
selected by the user. User-configured color mode: “Alarm Blink” and “Blink in Red”
in the Setup Display screen will remain same. The operation field which displays
the alarm state of the system will also blink. When the system returns to normal,
user-configured settings will be retained.
2. The Message text on the bottom of Condition Banner symbol and user-defined text
on top of the Condition Banner symbol will be temporarily displayed as ALARM as
shown.
3. The Condition Banner can now be configured so that any of the Condition Banner
colors can be programmed to blink when that condition occurs. For example, if an
alarm occurs, the Red color can be programmed to blink; similarly, the Yellow
warning, Green, and Blue can be programmed to blink.
Condition Banner Functions
The Condition Banner configuration on the Display screen will have three options:
Active, Standby, and No Action for all four colors (Red, Yellow, Green, and Blue).
When Active is selected, the Occupancy Status object of the SRCM will be active.
When Standby is selected, the unit will go into Standby mode (No alarms will be
generated) when the corresponding color condition is selected.
When No Action mode is selected, no action will be taken other than to display the
Condition Banner screen that has been associated with the No Action mode.
7
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Overview
Operating Condition Screen
Operating Condition Screen
The Operating Condition screen shows the active operating conditions of the
pressurized space.
The Room Label at the top of the screen can be defined to ensure the viewer
understands which room is actively being monitored by the SRCM.
The PRESSURE indication shows the intended direction of airflow for the space:
POSITIVE for airflow out of the space, NEGATIVE for airflow into the space,
NEUTRAL for airflow conditions that may vary, and STANDBY for use when there is no
need to verify the direction of airflow (alarms are disabled).
The OPERATION indication shows whether the pressurized space is within normal
operating parameters (within alarm thresholds), or whether there is an alarm or
warning condition. If operation is within alarm thresholds, a Green NORMAL indication
is shown. If operation is near either high or low alarm threshold limits, a Yellow
WARNING indication is shown.
If operation is at or beyond high or low threshold limits, a Red ALARM indication is
shown. If Audible Alarming is Enabled, a piezo buzzer will sound and a SILENCE
menu button is displayed. Pressing the SILENCE button will shut off the alarm for the
period of time defined in the alarm configuration. Alarm operation can be configured to
blink or sound an audible signal
In addition to pressure indication, OPERATION also displays. If a door switch is
configured, an open door contact will display a Yellow DOOR indication.
8
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Overview
Pressure Value
Pressure Value
A black banner displays the actual pressure reading from the space, in either Water
Column inches (“WC) or Pascals (Pa).
Slider Bar and Setpoint Values
The Blue banner below the pressure value shows where the current pressure reading
is in relation to alarm setpoints. The value at the left of the Blue banner is the low
setpoint value, and the value on the right is the high setpoint value. The middle cursor
represents the current measured pressure value on the setpoint scale.
Slider Bar On/Off
If the you do not wish to see the actual slider bar, it can be turned off using the Menu
screen. Operation of the pressure sensing and alarming is unaffected. See Section,
Menu Screens.
Slider bar is turned off. This displays when four parameters are configured.
9
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Overview
Active and Standby Modes
Slider bar is turn on. This displays when no parameters are configured. Pressure
still displays.
Active and Standby Modes
By pressing the touch-screen directly on the word POSITIVE (NEGATIVE, NEUTRAL,
or STANDBY), you can change the condition of the room between ACTIVE and
STANDBY modes. A pop-up menu appears to enable selection. If passwords are
enabled, you must first enter a password to proceed with the change.
In ACTIVE mode, the full function of the SRCM is active. In STANDBY mode, the
SRCM will perform all functions except that alarming will be disabled (both audible and
visual alarms). The STANDBY mode is designed to put the SRCM into a mode where
room pressurization is not critical, such as cleaning, patient transfer, or longer-term
unoccupied status.
This operation can be password protected so that only an Operator or a Supervisor
can make this change. Passwords are set up in the Setup Display Advanced tab.
Menu Screens
Pressing the MENU button on the Home Screen brings up the Administrative Menu. If
passwords are enabled, you must enter the correct password before being authorized
to make changes.
10
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Overview
Menu Screens
11
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
1
Setting the Application
Setting the Application
The SRCM Room Pressure Monitor is a standard BACnet device; therefore, it does not
contain an application point. The SRCM must be set up at the field panel using
application numbers that are specific for each project, in the range of 10,000 through
11,999. Nothing is required to set up the application number in the SRCM device.
12
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Before You Begin
2
Before You Begin
For proper installation, verify that:
the network wiring is correct.
the IO wiring (pressure, temperature, humidity, user defined) is correct.
the hardware configuration switches are set correctly:
Table 1: Hardware Configuration Switches.
Switch Position
Function
1
Enable Network Setup
2
Not Connected (Not Used)
3
Pull Up Resistor
4
Termination Resistor
5
Pull Down Resistor
The switch to the right is On; otherwise, it is Off.
if the unit is at the end of the line, the termination resistor is enabled (Position 4 is
On-when pushed to the right).
the Network Setup switch is disabled (enabled only during network setup).
13
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Setup Unit
Room - Primary or Secondary
Setup Unit
The SRCM is configured using built-in touchscreen menus.
Select the MENU button on the touchscreen to enter the setup screens.
The SRCM can take as input, the signal from two separate pressure transducers as
well as temperature, humidity, and user-defined (for example CO2) inputs for up to two
rooms. These are configured for either Primary Room or Secondary Room (an
anteroom is an example of a Secondary Room). When two transducers are used, you
can toggle between each room on the Home screen display of the SRCM to view the
status of each room momentarily, cycling from one to the other a few seconds apart, or
the display can be locked on either of the two rooms.
Figure 2: Home Screen Display.
*If CH-1 is selected for the Primary Room, it will not be an available option for the
Secondary Room.
Room - Primary or Secondary
To set up the parameters for a room select either the Primary or Secondary button.
Primary Room Sensor
The Onboard Sensor is the defaultPrimary sensor, which uses the sensor
manufactured on the unit. If the OnBoard Sensor is selected, a box displays showing
the pressure range (SENSOR FS) and engineering unit. Change, if necessary, to
match the sensor being used, if there is one present.
Alternatively, an external sensor (PPRESS.SRC, PTEMP.SRC, PHUM.SRC,
PUD.SRC) (also known as an external transducer) such as Siemens QBM3100 can be
used. If an external sensor is used, change this selection to ADC CH-1 (Analog Input
1) or ADC CH-2 (Analog Input 2). The FS output and range of the external sensor must
be entered.
14
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Setup Unit
Room Parameters
Secondary Room Sensor
None is the default for the Secondary Room sensor. Change, if necessary, to match
the sensor being used, if there is one present. An external sensor (SPRESS.SRC,
STEMP.SRC, SHUM.SRC, SUD.SRC) (also known as an external transducer such as
Siemens QBM3100 Series) can be used for the Secondary Room or anteroom. If an
external sensor is used, change this selection to ADC CH-1 or ADC CH-2, which uses
Analog Input 1 or Analog Input 2, respectively. The FS output and range of the external
sensor must be entered.
Room Parameters
The SRCM can display up to four parameters for each of two rooms. The parameters
are Pressure, Temperature, Humidity, and User-Dfined (for example, CO2). Start with
the Primary Room and set up the parameters to be monitored and displayed on the
default or Home screen. As parameters and inputs are selected, further selection of
parameters and inputs become self-limiting. (For example, if Temperature is selected
in Parameter 2, it is not available for selection in Parameter 3 or 4.)
Start with Parameter 1 (PRIM.PARAM1, SEC.PARAM1), this is the Room
Pressure. Select the Input Source as OnBoard, ADC CH-1 or ADC CH-2.
Parameter 2 (PRIMPARAM2, SEC.PARAM2) - Select None, Temperature
(suggested) or Humidity. Select Source as ADC CH-1, ADC CH-2, or BACnet.
Parameter 3 (PRIM.PARAM3, SEC.PARAM3) – Select None, Temperature or
Humidity (suggested). Select Source as ADC CH-1, ADC CH-2, or BACnet.
Parameter 4 (PRIM.PARAM4, SEC.PARAM4) – Select None, User Defined.
Label
Touch the Label check box and use the data entry keypad to enter the Room Label for
the Primary Room (PRIM LABEL, SEC LABEL). The name displays at the top of the
Home screen and identifies the room that the parameters refer to. Press the
Secondary Room button to select the Secondary Room (generally an anteroom) and
label that room if desired.
Primary Analog Output
This Analog Output (ANALOG OUTPUT) is used to communicate the value of the
differential pressure of the Primary Room to an external source such as a Building
Management System (BMS). The value is scaled as either 4 to 20 mA, 0 to 5 Vdc, or 0
to 10 Vdc (ANALOG TYP). A normalized pressure value is generated once every 100
milliseconds. The Analog Output is only available for the Primary Room.
Engineering Unit
Units of measurement display on the Home screen, and can be either Inches of Water
Column (“WC) or Pascals (Pa). The units are factory-calibrated as “WC. If the unit is
changed to Pa, the range will be changed to Pascals (Pa). This is selected from the
Parameter 1 tab as it is associated with the Primary Room pressure (PRIM.P.UNITS).
15
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Setup Unit
Analog Inputs
Sensor Range
The SRCM is manufactured with an on-board differential pressure transducer. This
transducer is manufactured to specifications for fixed minimum and maximum pressure
measurement, known as the full-scale range of the transducer. When the on-board
transducer is used exclusively, these values cannot be changed. Alarm setpoints
cannot be set above the positive value or below the negative value. If a wider or
narrower sensor range is required for the project, and external pressure transducer can
be chosen to match the requirements. See Primary Room Sensor or Secondary Room
Sensor for additional information.
If an external transducer is used, the full-scale values and other parameters must be
configured into the SRCM so that the unit understands the scale of measurement
being received on the Analog CH-1 or Analog CH-2 inputs.
Analog Inputs
The SRCM has two Analog Input channels (ADC Ch1 and ADC Ch2).
If a 4 to 20 mA transmitter is used as an analog input, then a 250 ohm resistor must
be installed. This will be translated into a 1 to 5 Vdc input at the input terminals.
The unit takes an Analog Input from any transducer or transmitter: pressure
(PRIM.PRESS, SEC.PRESS), temperature (PRIM.TEMP, SEC.TEMP), or humidity
(PRIM.HUM, SEC.HUM). If an external transducer is used, the full scale values and
parameters need to be configured into the SRCM so that the unit understands the
scale of measurement being received on Inputs ADC CH-1 or ADC CH-2.
The following examples uses a pressure transducer to measure Secondary Room
pressure (SEC.PRESS). The pressure transducer has a range of ±1 “WC and an
output of 4 to 20 mA over that range.
Figure 3: Pressure Transducer Measuring Secondary Room Pressure.
The following example uses a temperature sensor to measure the Primary Room
temperature (PRIM.TEMP). The temperature range is ± 50°C with a 1 to 10 Vdc output
over that range.
16
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Setup Unit
Changing the Room Name
Figure 4: Temperature Sensor Measuring Primary Room Temperature.
The following example uses a humidity sensor to measure the Primary Room relative
humidity (PRIM.HUM). The range is 0 to 98% RH with a 0 to 10 Vdc output.
Figure 5: Humidity Sensor Measuring Primary Room Humidity.
Changing the Room Name
The room name shown on the top part of the Home screen is changed by using the
Label check box (see Figure 6). Depending on whether the Primary (PRIM LABEL) or
Secondary Room (SEC LABEL) button is enabled, the corresponding Label check box
displays. A label can contain a maximum of 18 alphanumeric characters.
Press anywhere in the Label check box to open the on-screen keyboard where you
can enter the name of the room label. It is not necessary to touch the white area next
to the Label, simply start entering data using the keyboard. When you are finished,
press ENTER. Press the Save & Exit button to save the configuration and exit.
Figure 6: Changing the Label Name.
17
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Setup Unit
Changing the Room Name
Figure 7: Data Entry Screen.
18
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Setup Display
General Tab - Customizing the Condition Banner
Setup Display
The Setup Display screen permits authorized users (based on password level) to
configure Condition Banner messages and other Home screen options. There are four
tabs for display customization: General, Advanced, Condition Banner, and Set Time &
Date.
General Tab - Customizing the Condition Banner
The General tab allows the user to define messages for each Condition Banner color.
Pressing anywhere in the colored region of the Condition Banner changes each
selection between Green, Yellow, Red, and Blue. By pressing on the colored region of
text, the on-screen keyboard pops up, enabling data entry. If User Defined Text (USER
TEXT) is Disabled, then data entry on the Condition Banner will not be permitted.
Change the User Defined Text to Enabled to change the text of each banner.
There are four Condition Banner colors available: Green, Yellow, Red, and Blue.
Figure 8: General Tab.
In the Setup Display General tab, you can configure the text to be displayed above and
below the center symbol by enabling the User Defined Text (USER TEXT). If you want
the banner to blink, enable the Blink (RED BLINK, GREEN BLINK, YELLOW BLNK,
BLUE BLINK) selection.
If any alarm occurs, the Condition Banner turns to red and the text above and below
the center symbol displays ALARM.
Advanced Tab - Customizing the Condition Banner
The Advanced tab allows you to make refinements in how information is displayed on
the Operating Condition section of the Home screen.The display contrast level is
adjusted using Adjust Contrast Level (CONTRAST), with selections from 1 to 4. After
modifying this parameter, press Save & Exit to view the brightness and contrast on the
Home screen display. Depending on the lighting and viewing conditions in the final
space, different contrast levels can improve readability of the SRCM.
19
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Setup Display
Display Averaging (Tenths of Seconds)
Figure 9: Advanced Tab.
For passwords, the text displayed on the button is the action that takes place when
the button is pushed, not the status of the current setting.
Display Averaging (Tenths of Seconds)
This function helps to improve the stability of the pressure value displayed on the
Home screen, so significant digits do not change rapidly. It is used more often in
environments where you require higher display resolution (four digits) but the ambient
pressure is unstable. By increasing the number (DISPLAY AVG), the effective number
of measured data points is increased and a weighted average is developed. Enter the
number in tenths of a second for the response time of the display to a pressure
change. There is no ratcheting of the display or a deadband. The pressure change is
very smooth. For example, entering 10 equates to the display reaching final value in 1
second, entering 2 equates final value in 2 seconds.
Display Averaging does not affect the Analog Output response time, only the apparent
stability of the pressure display. Display Averaging also does not affect Alarm
Thresholds or Alarm Delay.
What Pressure to Display
This function defines what pressure value (PRESS.TOGGLE) displays on the Home
screen under normal operating conditions. This can be Primary Only, Secondary Only,
or Toggle depending on which room is most important for visual pressure verification.
If this is set to Secondary Only, then the Home screen displays the pressure value
read by the secondary pressure transducer (anteroom for example). In this case, if an
alarm condition occurs in the Primary Room, the display will toggle and remain on the
Primary Room and pressure value as long as the alarm condition is present in that
space. If no Secondary Room is configured on the Setup Unit screen attempts to
choose Secondary Only results in the error “Secondary Room source is NONE”.
If this is set to Toggle, then the Home screen displays the pressure value for both
rooms alternating back and forth momentarily (approximately 10 seconds apart). If an
alarm condition occurs in either room, the display will toggle to the appropriate room
and pressure value and remain on that room as long as the alarm condition is present.
If both rooms are in alarm, then the alarm condition and pressure values will toggle.
20
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Setup Display
Pressure Resolution
Pressure Resolution
This setting (PRESS.RES) shows the number of digits after the decimal point for the
default screen pressure displays. This setting affects the Primary and Secondary
Room settings.
Supervisor and Operator Passwords
The Password function provides security against changed configurations by
unauthorized users. This is accomplished by using two levels of password protection
which can be Enabled or Disabled.
Figure 10: Operator Password.
The Operator level allows access to change between Active and Standby room modes,
but no other changes.
The Operator is the person that has day-to-day interaction with the monitor to change
operating modes (OCC STATUS) from Active to Standby mode (where no alarms are
active). The Operator (Nurse or Lab Technician) can also respond to local audible and
visual alarms. The SRCM was designed to make interaction with the unit as easy as
possible for the Operator. Changes to messages and to the room mode are made by
simply touching active areas of the display. If Operator Password (OPERATOR PSW)
is enabled, then a password will be needed before the change can be made.
Figure 11: Supervisor Password.
The Supervisor (SUPERV PSW) level allows full access to all menus. The Supervisor
has access to all levels of the menu structure. This mode is used during initial
configuration and follow-on reconfiguration.
21
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Setup Display
Condition Banner Tab - Customizing Blinking Screens
The master Supervisor password is 351, and is valid for any condition where a user
may need to reset passwords.
Condition Banner Tab - Customizing Blinking Screens
The Condition Banner can be used for control functions as well as pure
communication. There are three choices for each color: Active, Standby, and No Action
(REDCBMODE, GREENCBMODE, YELLOWCBMODE, BLUECBMODE).
Figure 12: Customizing Blinking Screens.
The Condition Banner tab in the Setup Display allows you to choose whether certain
parts of the screen blink or not. Blinking components on the Home screen are intended
to draw more attention to the Condition Banner or the OPERATION indicators, for the
purpose of making exception conditions more noticeable to staff concerned with room
pressurization status.
Selection
Description
Alarm Blink (ALARM.BLINK)
Defines the behavior of the red ALARM
indicator on the Home screen Normal Blink is
used for the green NORMAL indicator.
Warning Blink (WARN.BLINK)
Applies to the yellow WARNING DOOR
indicator.
Blink in Red/Green/Yellow/Blue (RED BLINK,
GREEN BLINK, YELLOW BLINK, BLUE
BLINK)
Applies to the Condition Banner messages
and icon on the left third of the Home screen.
Full CB Display (FULL CB)
If this is selected, the left third of the Condition
Banner will become full screen after 15
seconds. If an alarm is in progress or occurs
while the Condition Banner is full screen, the
standard default screen will display. Touching
the display will return it to the 1/3, 2/3 standard
display mode. This is useful when users want
a very simple interface. Touching the screen at
any time will momentarily display the Home
screen.
Save & Exit
Saves the selections made on this screen.
22
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Setup Display
Full Screen Condition Banner and Active Standby Mode Application
Full Screen Condition Banner and Active Standby Mode
Application
At times, you may want a minimal User Interface and want to switch between Active
and Standby Modes (FULL CB) and clearly convey the status of the room.
Any color can be associated with any action: Active, Standby, or No Action.
The following example uses Green for Active and Yellow for Standby.
1. On the Setup Display/General tab set User Defined Text (USER TEXT) to Enabled.
2. Tap the Condition Banner screen (COLOR MODE) until the green screen displays.
Setup the desired green screen text message to be displayed in the Active mode.
You can enter text so that it displays in the boxes above and below the center
“Clear to Enter” symbol. Touch the top box and enter the desired text (UD MSG
GREEN) using the Data Entry keypad. Save by pressing ENTER when complete.
Figure 13: Green Screen.
3. Perform the Steps 1 and 2 for the bottom box (MSG GREEN CB).
4. Set up the desired yellow screen text message in the Setup Display/General tab.
Text can be entered so that it displays in the boxes above and below the center
“Warning Triangle” symbol. Touch the top box and enter the desired text (UD MSG
YLLOW) using the Data Entry keypad. Save by pressing ENTER when complete.
Figure 14: Yellow Screen.
5. Perform Steps 1 through 4 for the bottom box (MSG YLLOW CB).
6. Set up the Condition Banner to display Full Screen rather than the 1/3 left of the
screen display that is the default “as shipped” setup. To do this, go to the Setup
23
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Setup Display
Full Screen Condition Banner and Active Standby Mode Application
Display/Condition Banner tab and set the full Condition Banner (FULL CB) Display
to Enabled. Press Save & Exit.
Figure 15: Condition Banner.
With this setup the unit is in Active Mode. The Full Screen display will look like the
following with the text that was specified in Step 2.
Figure 16: Active Mode Display.
If you change the Standby by touching the section to the right of the PRESSURE, then
the display is yellow with the text that was specified in Step 4.
Figure 17: Standby Mode Display.
This feature can be combined with password protection.
24
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Setup Display
Set Time & Date Screen
Set Time & Date Screen
The Set Time & Date tab is used for setting the time and date of the SRCM. This time
and date is used to time stamp the event log. See Event Log.
If power is lost to the unit, the time and date must be reset.
The date format is DD-MM-YYYY.
Figure 18: Set Time & Date Tab.
25
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Setup Alarm
Set Time & Date Screen
Setup Alarm
The Setup Alarm screen permits authorized users (based on password level) to
configure alarm behavior, such as the duration of alarms, methods of clearing alarm
condition, and how alarms are acknowledged. It also sets the room mode (PPRES
MODE, SPRES MODE) to Positive, Negative or Neutral room.
Figure 19: Setup Alarm Screen.
Latch Alarm
(LATCH ALARM)
If enabled, this causes the display of red ALARM on the
Home screen to remain, even if the room pressurization
returns to normal. Latch Alarm Enabled requires that an
alarm event be acknowledged and that the pressure
returns to within the normal range. This is useful
because it forces recognition that an alarm event
occurred. The alarm will still be on even if the pressure
returns to normal range. Only when the alarm is
acknowledged will alarming cease. When Disabled, the
alarm will be silenced when the pressure returns to
normal range without requiring acknowledgement.
When a Latch Alarm occurs, the Home screen displays
a RESET button to the right of the Menu button. Press
the RESET button to acknowledge and reset the Latch
Alarm condition.
Alarm Delay
(ALARM DELAY)
Time between when the pressure exceeding alarm
setpoints and when the unit goes into Alarm mode. This
is useful in preventing false alarms. For example, if
Alarm Delay is set to 20 seconds, the staff has 20
seconds to open a door, enter the room, and close the
door before the alarm sounds (if audible alarms are
enabled). Alarm Delay also applies to alarms
annunciated to a Remote Annunciator via the SRCM
Digital Output (hardware configuration).
26
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Setup Alarm
Set Time & Date Screen
Audible Alarm
(AUD. ALARM)
Enables or disables the audible buzzer. Regardless of
whether audible alarming is enabled or disabled, the red
ALARM condition displays on the Home screen,
annunciate to a Remote Annunciator, and propagate to
a configured Digital Output. If an alarm occurs and the
audible alarm is enabled, a new SILENCE button
displays on the Home screen so that the operator can
silence the audible alarm. The audible alarm is silenced
only for the period of time defined by Mute Time Out.
Mute Time Out
(MUTE T.OUT)
Sets the time (in seconds) that the alarm will remain
silent after pressing the SILENCE button before the
audible alarm resumes again. This assumes that the
room pressure condition is still outside the normal
setpoint operating limits. Mute Time Out can be set from
0 to 9998 seconds. Entering a value of 9999 will silence
the audible alarm “forever”, as long as a new alarm
condition does not occur.
Digital Input (DI) (DI
STATUS)
Used for monitoring the door status—Open or Closed.
The DI is a Normally-Closed dry contact. A door jamb
must be wired to the terminals labeled DOOR in the rear
of the unit. When the door opens the contact will open,
and this will show a yellow DOOR Warning on the
Home screen. The Door Alarm will suppress alarms if
they are generated at the same time that the door is
open.
Deadband (DEAD BAND)
Represents the region within the setpoint range where
yellow WARNING displays on the Home Screen to
indicate that the pressure is near ALARM limits. It is
adjustable from 0 to 10%. If set to 0, no WARNING
occurs, only ALARM when the pressure value reaches
setpoints. If set to any other value, WARNING will be
displayed if the pressure value reaches the percentage
of total pressure setpoint range.
When the unit goes outside of the deadband range, the
alarm occurs. The alarm remains on until the pressure
returns within the alarm limit range (or is
acknowledged—Latch Alarm), minus the setpoint.
Buzzer Volume
(BUZZER VOL.)
The buzzer volume can be adjusted from one to four,
with four being the highest sound level. The alarm
buzzer is disabled using the Audible Alarm Disabled
function.
27
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Setup Alarm
Alarms Disabled When Door is Open and Buzzer for Door Warning
Alarms Disabled When Door is Open and Buzzer for Door
Warning
The SRCM can configure the Room status to disable the Alarms when Door is open.
This function is used when there will be high traffic throughout the area and the User
wants to disable any alarms that are occurring because the Door is open. The alarms
are re-enabled once the Door is closed.
In the Setup Alarm screen, select the Digital Input (MV_11) choice to Door-!=Alarm.
Figure 20: Door Alarm Selection.
As shown in the screen below, DOOR (DI STATUS) is highlighted to indicate that the
door is open. However, the STANDBY (to the right of PRESSURE) indicates that the
room is in STANDBY mode.
Figure 21: Door Status Screen.
If the Door opens when the unit is in alarm, the unit will continue to operate in alarm
state instead of clearing the alarm.
Alarm Setpoint
For each space, Primary Room (PPRES.LO.RNG, PPRES.HI.RNG, PPRES.NEU.LO,
PPRES NEU.HI, PPRES.NEG.LO, PPRES.NEG.HI) or Secondary Room
(SPRES.LO.RNG, SPRES.HI.RNG, SPRES.NEU.LO.SPRES.NEU.HI,
SPRES.NEG.LO, SPRES.NEG.HI) is used to define the alarm setpoints. When the
room is set to Positive, Neutral, or Negative, the setpoints and conditions configured
here are in effect for alarm and warning conditions.
28
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Setup Alarm
Alarm Matrix
Figure 22: Setup Alarm Setpoint.
Alarm Matrix
The SRCM offers plenty of flexibility to define alarm conditions. Alarms and warnings
can be configured for Primary and Secondary Rooms, and for the Door. Room display
can toggle between Primary and Secondary. The following table outlines what occurs
in terms of priority and display under Normal and Alarm conditions.
N = Normal; A = Alarm
Table 2: Alarm Matrix
Toggle
High Priority
Background
Remarks
Primary
Pressure
Secondary
Pressure
Display Text
(Maximum
Eight
Characters)
Disabled
N
N
Normal
Green
Displays Primary
pressure or Secondary
pressure based on the
selection in the setup
display screen.
Disabled
N
A
Alarm
Red
Displays Alarm for
Secondary Room if
Secondary Room is
selected. If the pressure
to display is selected as
Primary, the display
switches to the
Secondary Room and
displays the alarm.
Disabled
A
N
Alarm
Red
Displays Alarm for
Primary Room if Primary
Room is selected for
display. If the pressure to
display is selected as
Secondary, the display
switches to the Primary
Room and displays the
alarm.
Disabled
A
A
Alarm
Red
Toggles between Primary
and Secondary Room.
29
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Setup Alarm
Alarm Matrix
Toggle
High Priority
Background
Remarks
Toggles between Primary
and Secondary Room.
Primary
Pressure
Secondary
Pressure
Display Text
(Maximum
Eight
Characters)
Enabled
N
N
Normal
Green
Enabled
N
A
Alarm
Red
Displays Secondary
alarm. Display stops
toggling.
Enabled
A
N
Alarm
Red
Displays Primary alarm.
Display stops toggling.
Enabled
A
A
Alarm
Red
Toggles between Primary
and Secondary Room.
30
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Calibration and Self-Test
Calibration and Self-Test
This procedure is used for calibration of the internal pressure transducer sensor and
testing operation of hardware circuitry. Calibration is only required for highly accurate
measurement needs such as those needed to comply with federally mandated
regulations. Calibration must only be performed by qualified personnel. See SRCM
Room Pressure Monitor Technical Specification Sheet (149-211) for more information.
1. Select Primary or Secondary Room. When selected, the gray box to the right
indicates if the calibration will be applied to the on-board sensor or the external
sensor (Analog CH-1 or Analog CH-2). The indicated pressure is shown.
Figure 23: Calibration & Self Test Screen.
2. Calibration of the on-board sensor requires that the faceplate be removed and the
captive screw holding the display cover must be loosened (at the bottom-center of
the display bracket).
3. Lift the cover to expose the clear and red tubing connecting the on-board sensor to
the pressure fittings in the rear of the unit.
4. Remove the tubing from the high and low ports (red and clear tubing). This
disconnects the sensor from the room pressure.
Figure 24: Pressure Fitting Tubing.
31
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Calibration and Self-Test
5. After calibration, replace the red and clear tubing.
Table 3: Calibration & Self-Test Screen
Display
Description
Zero Adjust
Pressing the Zero Adjust button displays the message Is zero
pressure applied?. If yes, press OK. If the zero measurement
is within 10% of the factory zero measurement stored in the unit,
the zero value will be reset.
NOTE: Zero Adjust should only be performed after the unit has
been operating for 30 minutes in the installed location.
Span Adjust
This requires the use of a Pressure Calibrator, such as a Setra
Model 869 or equivalent. Connect the tubing from the Calibrator to
the low and high ports identified near the PCBA markings. Apply
Full Range pressure, for example ± 0.1” WC range, use 0.1” WC.
When pressure reaches Full Range pressure, press OK. The
output at Full Range must be within 10% of the factory calibration
to allow re-adjustment.
Restore Factory User Zero If the unit has been miscalibrated in the field, the factory zero and
and User Span
span settings can be restored.
Test
The Buzzer, Relay, and Internal Memory checksum can be tested
and verified.
32
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
System Information
System Information
The System Information screen reports the Model Number, Serial Number, Firmware
Revision, Network Status, Last (Factory) Calibration Date, and Technical Support
Contact.
Figure 25: System Information Screen.
Table 4: System Information Screen
Display
Description
Technical Support (TECH ID)
A maximum of 30 alphanumeric characters
can be entered in this field by pressing
anywhere in the white text entry box to enable
the pop-up keyboard.
Enter an email address, name, or phone
number, as needed.
Restore Factory Default
Restores the default settings for all
configuration and setup screens. All
configured settings, including alarm thresholds
and audible alarming, that were modified after
installation are lost if this function is used.
Normal operation of pressure measurement is
not affected.
33
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
USB Configuration Cloning
USB Configuration Cloning
The SRCM has a USB port built in for the purpose of duplicating configurations when
multiple units are being set up with similar configurations. To use this function, a USB
2.0 thumb drive with a capacity 256 megabytes or larger must be used. The thumb
drive must have at least 100K of free memory available. The USB port should only be
accessed by qualified personnel.
Use Kingston DataTraveler 112, 4GB (minimum) flash drive along with the aid of a
short mini-USB adapter cable from Tensility International Corporation (Part Number
10-00003), or equivalent. No computer is required.
Table 5: Configuration.
Manufacturer
Kingston
Sandisk
Model
DataTraveler
Size (GB)
Comment
1
No issue
256 MB
No issue
DataTraveler
4
DataTraveler
8
To make Kingston work, format as:
* Fat 32
* Must have volume label
* Do not use quick format
DataTraveler 112
4
Passes out of the box without
formatting.
Cruzer
2
To make Sandisk work, format as:
* Fat 32
* Must have volume label
* Do not use quick format
4
16
To access the USB port, do the following:
1. Remove the faceplate cover and set it aside.
2. The USB port is located on the right side of the touchscreen display driver board,
and is accessed by removing the security screw and flipping up the display
housing.
A Micro USB Host Mode OTG cable (from T&S Electronics, Part Number OTG-SBK6,
or from SonoXY, Part Number USB_MIC-OTG) is required to connect a standard
USB 2.0 compliant thumb-drive to the SRCM USB port.
To use of the cloning feature, do the following:
1. Set up one SRCM with a configuration that represents most other SRCM units that
will be used during installation. Configure the “master” unit with all parameters
needed, including alarm thresholds, Condition Banners, blinking operations, I/O
configuration and so on.
34
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
USB Configuration Cloning
2. Press Save & Exit to properly save your configuration. This “master” setup is then
downloaded to the thumb drive and can be uploaded to other units.
Figure 26: USB Port and Connected Thumb Drive.
As soon as the thumb drive is connected to the SRCM, it will be recognized and the
Drive Connected menu will display.
1. Select Configuration Write to transfer the master SRCM configuration from the unit
to the thumb drive.
Figure 27: Transfer Configuration from Unit to Thumb Drive.
2. Select START to initiate the copy operation.
3. Remove the thumb drive and cable, and move the first slave unit to be configured.
Figure 28: Transfer Configuration from Thumb Drive to Slave Unit.
4. With power applied to the unit, connect the thumb drive and cable.
5. Select Read and START to write the master configuration to the new slave unit.
A Write Process Successful message displays if the configuration has been
written to memory. Review the various Menu screens of the slave unit and subsequent
units to confirm that the proper configuration is stored. In most cases the only change
that will be required to clone SRCM units is Primary and Secondary Room labels that
match the location of installation.
35
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Network Setup
Network Setup
The BACnet setup screen is enabled by pushing the position 1 switch (labeled MAC) to
the ON (right) position. After configuration, the switch must be moved to the OFF (left)
position.
Figure 29: DIP Switch Location with Switch ON.
The Network Setup screen gives you the option to configure the Network and other
parameters which must be read from the network.
Figure 30: Network Setup Screen.
1. BACnet configuration requires that you configure the following parameters:
-
Baud Rate – Press the Change button and select any one of the four standard
Baud rates for RS485 communication: 9600, 19200, 38400 and 76800. Auto
baud features are not supported.
-
MAC Address – Enter the Medium Access Control address specific to this
device by touching this field. Valid values are 0 to 127. Since this unit is a
BACnet master, address 128 through 254 are reserved for 254, and 255 is
reserved for Broadcast.
-
Device Instance – The Device Instance number must be unique within a
BACnet internetwork since it identifies each device. Instance numbers are
defined as 22 bits long; in decimal instance, number ranges from 0 through
4194,3,03.
36
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Network Setup
-
APDU Timeout – Indicates the amount of time in milliseconds between
retransmissions of the APDU requiring acknowledgement for which no
acknowledgement has been received. The default value for this property is
3,000 ms; the maximum can be 65535.
2. Press Save & Exit to save settings or cancel to cancel setting changes.
3. Once this is complete disable the BACnet setup by moving the DIP switch position
1 to the OFF (left) position.
Figure 31: DIP Switch Location with Switch OFF.
4. Press Save & Exit.
5. After the unit returns to the Main Menu screen, disconnect the power to the unit
and reconnect to boot up with the proper MAC address and Device Instance. The
power can also be cycled by removing Jumper JP1 and then reconnecting.
Figure 32: Jumper Location.
The unit can also be configured through the BACnet interface as well as through the
touchscreen user interface.
37
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Event Log
Event Log
The SRCM can be enabled with an audit trail of changes made to the
configurations/modes of the system by the Supervisor and Operator. When the
Supervisor or Operator changes any configuration using the menu, the action is
captured and stored in a string that includes the User Profile, Screen name where the
parameter was changed, Parameter name, and Value to which it was changed. There
are five such instances stored in non-volatile memory of the unit. Any power failure in
the unit will lose the data and it will be the responsibility of the BMS system to log
these strings after polling from the SRCM unit through BACnet. The SRCM unit will
store these strings as different instances of the Character String Object.
The value to which the parameter is changed is not logged for parameters such as
User-Defined Condition Banner Text, Room Label, Message Text, and so on, which
needs more memory. Other parameters whose variables are enumerated, real and
integer, are logged until the value is changed.
The string length of each instance of configuration change will be 50 Bytes in the data
memory area of the controller.
Figure 33: Event Log.
38
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Controlling Temperature
Controlling Temperature
The SRCM can be used for controlling the temperature of the Primary and Secondary
Rooms. Each room that will be controlled must have the Temperature Parameter set
up for each of the rooms with the source as BACnet. Enter the Object Instance and
Device Instance so that the SRCM can map to the temperature Present Value.
To verify the correct mapping, press Read to see the Present Value.
Figure 34: Verify Mapping.
39
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
French Language Support on Default Screen and Data Entry Screen
French Language Support on Default Screen
and Data Entry Screen
The Home screen can be set up to show French language (LANGUAGE) words using
the Setup Display Menu.
Figure 35: English/French Language Selection.
The following screens show the difference between the English and French Home
screens:
Figure 36: English Default Screen.
Figure 37: French Default Screen.
40
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
French Language Support on Default Screen and Data Entry Screen
On the default screen, the following changes will be made for the French version:
Table 6: English/French Translations.
English
French
PRESSURE
PRESSION
OPERATION
OPÉRATION
NEGATIVE
NÉGATIVE
NEUTRAL
NEUTRE
STANDBY
ATTENTE
DOOR
PORTE
WARNING
ALERTE
ALARM
ALARME
TEMPERATURE
TÉMPERATURE
SILENCE, NORMAL, HUMIDITY, and RESET do not change
When the language is selected as French in the Setup Display screen, French
character entry in the data screen is enabled. Whenever you press N (same for all
French characters like A, E, I, O, U, C) a child screen will pop up which will contain all
corresponding French characters. In this case, the child screen will contain French
characters corresponding to N. When you press any of these characters, that character
will be taken as input, and the child screen will disappear. If you do not want to enter
any character, the child screen will disappear when you press N in the Main screen.
41
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
3
Troubleshooting
Troubleshooting
Error/Trouble Condition
Possible Cause
Solution
Display shows: Factory
Calibration has been
lost. Return to
Factory for
Calibration.
Non-recoverable EEPROM
checksum error of factory
calibration data, ER01.
Return unit to Factory for
calibration.
Display shows: Setup
information has been
lost. Loading Default
Values. Please Wait...
Recoverable EEPROM
checksum error of unit setup
configuration, ER02.
Unit will auto recover by
rebooting and then displaying
message: Setup
information has been
lost, default
configuration loaded.
User should
reconfigure. You should
press OK/Cancel (User
Acknowledgement) so that the
device enters into default
screen.
You cannot enter into menus
because of password
protection.
You have lost your password.
Use default password: 351.
SRCM does not come online.
Two or more controllers have
the same MAC address.
Modify each duplicate address
to a unique number.
The MS/TP network has too
many devices.
Do not exceed the maximum
number of devices and
maximum length allowed by
the EIA-485 specifications.
Too many devices were
installed without any
repeaters.
Repeaters must be installed
as specified in this document.
The MS/TP cable runs are
broken.
Locate the break and correct
the wiring.
MS/TP connections at the
module were reversed.
Respect polarity of the wires
on an MS/TP network.
The SRCM does not have
power.
Apply power to teh SRCM.
42
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Point Database
Point Database
Instances
Point
Number
AI1
1
AI2
Object Name
Units
(SI Units)
Object Description
Value
PRIM. PRESS.
in H2O
(PASCAL)
Indicates the Primary
Room Pressure
2
SEC. PRESS.
in H2O
(PASCAL)
Indicates the Secondary Value
Room Pressure
AI3
3
PRIM. TEMP.
DEG F
(DEG C)
Indicates the Primary
Room Temperature
AI4
4
SEC. TEMP.
DEG F
(DEG C)
Indicates the Secondary Value
Room Temperature
AI5
5
PRIM. HUM.
Rh
Indicates the Primary
Room Humidity
AI6
6
SEC. HUM.
Rh
Indicates the Secondary Value
Room Humidity
AI7
7
PRIM. UD
Indicates the Primary
Room User Defined
Parameter
AI8
8
SEC. UD
Indicates the Secondary Value
Room User Defined
Parameter
AV1
9
ANALOG OUT
mA
Indicates Analog Output Value
corresponding to
Primary Room Pressure
AV2
10
PPRES.LO.RNG
in H2O
(PASCAL)
Primary Room Pressure Value
Low range when
Primary Room is
configured to Read
Pressure from External
Transducer through
ADC
AV3
11
PPRES.POS.LO
in H2O
(PASCAL)
Value
Alarm low limit for
Primary Room Pressure
when Pressure mode
Positive
AV4
12
PPRES.POS.HI
in H2O
(PASCAL)
Value
Alarm High limit for
Primary Room Pressure
when Pressure mode
Positive
Value
Value
Value
Value
43
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Point Database
Instances
Point
Number
Object Name
Units
(SI Units)
AV5
Object Description
Value
13
SPRES.LO.RNG
in H2O
(PASCAL)
Secondary Room
Pressure Low Range
when Primary Room is
configured to Read
Pressure from External
Transducer through
ADC
AV6
14
SPRES.POS.LO
in H2O
(PASCAL)
Value
Alarm low limit for
Secondary Room
Pressure when
Pressure mode Positive
AV7
15
SPRES.POS.HI
in H2O
(PASCAL)
Alarm High limit for
Secondary Room
Pressure when
Pressure mode
Negative
Value
AV8
16
ALARM DELAY
secs
Alarm Delay for
Pressure, Valve Alarms
0 to 9999
AV9
17
MUTE T. OUT
secs
Buzzer Volume Mute
Time Out
0 to 9999
99999 = Mute
Forever
AV10
18
BUZZER VOL.
AV11
19
DEAD BAND
AV12
20
AV13
Value
0 to 40
Pressure Alarm
Deadband
1 to 10%
CONTRAST
TFT Contrast Level
1 to 4
21
PRESS. RES
Pressure Display
Resolution
2 to 4
AV14
22
DISPLAY AVG
Display Averaging
Window Size
0 to 40
AV15
23
PTEMP.LO.RNG
DEG F
(DEG C)
Primary Room
Temperature Low
Range when
Temperature is
configured to read
through ADC
Value
AV16
24
PTEMP.HI.RNG
DEG F
(DEG C)
Primary Room
Temperature High
Range when
Temperature is
configured to read
through ADC
Value
PCT
44
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Point Database
Instances
Point
Number
Object Name
AV27
25
PUD.LO.RNG
Low Range for Primary
Room User Defined
Parameter when
Humidity is configured
to read through ADC
Value
AV28
26
PUD.HI.RNG
High Range for Primary
Room User Defined
Parameter when
Humidity is configured
to read through ADC
Value
AV29
27
PHUM.LO.RNG
Rh
Primary Room Humidity Value
Low Range when
Humidity is configured
to read through ADC
AV30
28
PHUM.HI.RNG
Rh
Primary Room Humidity Value
High Range when
Humidity is configured
to read through ADC
AV31
29
PPRES.NEG.LO
in H2O
(PASCAL)
Value
Alarm low limit for
Primary Room Pressure
when Pressure mode
Negative
AV32
30
PPRES.NEG.HI
in H2O
(PASCAL)
Value
Alarm High limit for
Primary Room Pressure
when Pressure mode
Negative
AV33
31
PPRES.NEU.LO
in H2O
(PASCAL)
Value
Alarm low limit for
Primary Room Pressure
when Pressure mode
Neutral
AV34
32
PPRES.NEU.HI
in H2O
(PASCAL)
Value
Alarm High limit for
Primary Room Pressure
when Pressure mode
Neutral
AV35
33
WINDOW SIZE
in H2O
(PASCAL)
Moving Average
Window Size
1 to 40
AV36
34
SPRES.NEG.LO
in H2O
(PASCAL)
Alarm low limit for
Secondary Room
Pressure when
Pressure mode
Negative
Value
AV37
35
SPRES.NEG.HI
in H2O
(PASCAL)
Alarm low limit for
Secondary Room
Pressure when
Pressure mode
Negative
Value
Units
(SI Units)
Object Description
Value
45
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Point Database
Instances
Point
Number
Object Name
Units
(SI Units)
AV38
Object Description
Value
36
SPRES.NEU.LO
in H2O
(PASCAL)
Alarm low limit for
Secondary Room
Pressure when
Pressure mode Neutral
Value
AV39
37
SPRES.NEU.HI
in H2O
(PASCAL)
Alarm low limit for
Secondary Room
Pressure when
Pressure mode Neutral
Value
AV40
38
STEMP.LO.RNG
DEG F
(DEG C)
Secondary Room
Temperature Low
Range when
Temperature is
configured to read
through ADC
Value
AV41
39
STEMP.HI.RNG
DEG F
(DEG C)
Secondary Room
Temperature High
Range when
Temperature is
configured to read
through ADC
Value
AV42
40
SHUM.LO.RNG
rh
Secondary Room
Humidity Low Range
when Humidity is
configured to read
through ADC
Value
AV43
41
SHUM.HI.RNG
rh
Secondary Room
Humidity High Range
when Humidity is
configured to read
through ADC
Value
AV44
42
SUD.LO.RNG
Low Range for
Secondary Room User
Defined Parameter
when Humidity is
configured to read
through ADC
Value
AV45
43
SUD.HI.RNG
High Range for
Secondary Room User
Defined Parameter
when Humidity is
configured to read
through ADC
Value
AV46
44
SENSOR FS
in H2O
(PASCAL)
Full Scale Range of On
Board Sensor
Value
AV49
45
ADC1.IN.LO.V
V
Indicates ADC Ch1
Input Low voltage
Value
AV50
46
ADC1.IN.HI.V
V
Indicates ADC Ch1
Input High voltage
Value
46
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Point Database
Instances
Point
Number
Object Name
AV51
47
ADC2.IN.LO.V
V
Indicates ADC Ch2
Input Low voltage
Value
AV52
48
ADC2.IN.HI.V
V
Indicates ADC Ch2
Input High voltage
Value
AV53
49
PPRES.HI.RNG
in H2O
(PASCAL)
Primary Room Pressure Value
High range when
Primary Room is
configured to Read
Pressure from External
Transducer through
ADC
AV54
50
SPRES.HI.RNG
in H2O
(PASCAL)
Secondary Room
Pressure High Range
when Primary Room is
configured to Read
Pressure from External
Transducer through
ADC
Value
BI1
51
DI STATUS
Digital Input Status
0 - Input Closed
1 - Input Open
BV1
52
RELAY ON.OFF
Relay Status
1 - Relay On
0- Relay Off
BV2
53
PRIM.P.UNITS
Primary Room Pressure 0 - "WC
Engineering Unit
1 - Pa
BV3
54
SEC.P.UNITS
Secondary Room
Pressure Engineering
Unit
0- "WC
1 - Pa
BV04
55
PRIM.T.UNITS
Primary Room
Temperature
Engineering Unit
0 - Fahrenheit
1- Celsius
BV6
56
LATCH ALARM
Alarm Latch Status
1 - Enabled
0 - Disabled
BV8
57
SUPERV PSW
Supervisory Password
Status
1 - Enabled
0 - Disabled
BV9
58
OPERATOR PSW
Operator Password
Status
1 - Enabled
0 - Disabled
BV10
59
SEC.T.UNITS
Secondary Room
Temperature
Engineering Unit
0 - Fahrenheit
1 - Celsius
BV11
60
USER TEXT
User Define Text Status 1 - Enabled
0 - Disabled
BV12
61
SLIDER
Slider Status
Units
(SI Units)
Object Description
Value
1 - Slider On
0 - Slider Off
47
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Point Database
Instances
Point
Number
Object Name
BV14
62
LANGUAGE
Language support
1 - English
0 - French
BV15
63
ALARM BLINK
Blink Status Alarm
Condition
1 - Enabled
0 - Disabled
BV16
64
NORMAL BLINK
Blink Status Normal
Condition
1 - Enabled
0 - Disabled
BV17
65
WARN. BLINK
Blink Status Warning
Condition
1 - Enabled
0 - Disabled
BV18
66
RED BLINK
Blink Status for
Condition Banner Red
1 - Enabled
0 - Disabled
BV19
67
GREEN BLINK
1 - Enabled
Blink Status for
Condition Banner Green 0 - Disabled
BV20
68
YELLOW BLINK
Blink Status for
Condition Banner
Yellow
1 - Enabled
0 - Disabled
BV22
70
FULL CB
Full Screen Condition
Banner feature
1 - Enabled
0 - Disabled
BV23
71
BLUE BLINK
Blink Status for
Condition Banner Blue
1 - Enabled
0 - Disabled
BV26
69
AUD. ALARM
Audible Alarm Status
1 - Enabled
0 - Disabled
MSI1
-
SYS. STATUS
System Operation
Status
1 - NORMAL
2 - DOOR
3 - WARNING
5 - ALARM
MSV1
72
ANALOG TYP
Primary Room Analog
Output Type
1 - 4-20mA
2 - 0- 5V
3 - 0- 10V
MSV2
73
PPRES MODE
Primary Room Pressure 1 - Positive
Mode
2 - Negative
3 – Neutral
MSV3
74
COLOR MODE
Condition Banner Color
Mode
1 - Green
2 - Red
3 – Yellow
4 - Blue
MSV5
75
PRESS.TOGGLE
Room to be displayed
on Home screen
1 - Primary Only
2 - Secondary
Only
3 - Toggle
between the two
Units
(SI Units)
Object Description
Value
48
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Point Database
Instances
Point
Number
Object Name
MSV6
76
PRIM.PARAM1
Primary Parameter 1
MSV7
77
SEC.PARAM1
Secondary Parameter 1 1 - Pressure
2 - Temperature
3 - Humidity
4 - User defined
5 - None
MSV8
78
PRES.ALRM
Pressure Alarm status
1 - Primary
alarm active
2- Secondary
alarm active
3 - Both active
4 - Both normal
MSV9
79
SPRESS.SRC
Secondary Room
Pressure Input Source
1 - Analog Ch1
2- Analog Ch2
3 - None
MSV10
80
PPRESS.SRC
Primary Room Pressure 1 - Onboard
Input Source
Sensor
2 - Analog CH1
3 - Analog CH2
MSV11
81
MV_11
Digital Input
Configuration
1 - Door
3 - Disabled
4 - Door !=
Alarm
MSV13
82
SPRES MODE
Secondary Room
Pressure Mode
1 - Positive
2 - Negative
3 - Neutral
MSV14
83
RED CB MODE
Red Condition Banner
Mode
1 -Active
2 - Standby
3 - No Action
MSV15
84
GREENCBMODE
Green Condition Banner 1 -Active
Mode
2 - Standby
3 - No Action
MSV16
85
YELLOWCBMODE
Yellow Condition
Banner Mode
1 - Active
2 - Standby
3 - No Action
MSV17
86
PTEMP.SRC
Primary Room
Temperature Input
Source
1 - ADC CH-1
2 - ADC CH-2
3 - BACnet
4 – None
Units
(SI Units)
Object Description
Value
1 - Pressure
2 - Temperature
3 - Humidity
4 - User defined
5 - None
49
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Point Database
Instances
Point
Number
Object Name
MSV18
87
PRIM.PARAM2
Primary Parameter 2
MSV19
88
PHUM.SRC
Primary Room Humidity 1 - ADC CH-1
Input Source
2 - ADC CH-2
3 - BACnet
4 - None
MSV20
89
PRIM.PARAM3
Primary Parameter 3
1 - Pressure
2 - Temperature
3 - Humidity
4 - User defined
5 - None
MSV21
90
PUD.SRC
Primary Room User
Defined Parameter
Input Source
1 - ADC CH-1
2 - ADC CH-2
3 - BACnet
4 - None
MSV22
91
PRIM.PARAM4
Primary Parameter 4
1 - Pressure
2 - Temperature
3 - Humidity
4 - User defined
5 - None
MSV23
92
STEMP.SRC
Secondary Room
Temperature Input
Source
1 - ADC CH-1
2 - ADC CH-2
3 - BACnet
4 - None
MSV24
93
SEC.PARAM2
Secondary Parameter 2 1 - Pressure
2 - Temperature
3 - Humidity
4 - User defined
5 - None
MSV25
94
SHUM.SRC
Secondary Room
Humidity Input Source
MSV26
95
SEC.PARAM3
Secondary Parameter 3 1 - Pressure
2 - Temperature
3 - Humidity
4 - User defined
5 - None
MSV27
96
SUD.SRC
Secondary Room User
Defined Parameter
Input Source
Units
(SI Units)
Object Description
Value
1 - Pressure
2 - Temperature
3 - Humidity
4 - User defined
5 - None
1 - ADC CH-1
2 - ADC CH-2
3 - BACnet
4 – None
1 - ADC CH-1
2 - ADC CH-2
3 - BACnet
4 – None
50
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Point Database
Instances
Point
Number
Object Name
MSV28
97
SEC.PARAM4
Secondary Parameter 4 1 - Pressure
2 - Temperature
3 - Humidity
4 - User defined
5 - None
MSV29
98
OCC STATUS
Room Occupancy
Status
1 - Active
2 - Standby
MSV31
99
BLUE CB MODE
Blue Condition Banner
Mode
1 -Active
2 - Standby
3 - No Action
PCV1
PRIM LABEL
Primary Room Label
PCV2
SEC LABEL
Secondary Room Label
PCV3
PRIM UD NAME
Primary Room User
Defined Parameter
Name
PCV4
SEC UD NAME
Secondary Room User
Defined Parameter
Name
PCV5
PRIM UD UNIT
Primary Room User
Defined Parameter
Engineering Unit
PCV6
SEC UD UNIT
Secondary Room User
Defined Parameter
Engineering Unit
PCV7
AUDIT.T.STR1
Audit Trail String 1
PCV8
AUDIT.T.STR2
Audit Trail String 2
PCV9
AUDIT.T.STR3
Audit Trail String 3
PCV10
AUDIT.T.STR4
Audit Trail String 4
PCV11
AUDIT.T.STR5
Audit Trail String 5
PCV12
TECH ID
Technical Support ID
PCV13
MSG RED CB
Statutory Message for
Red Color Mode
PCV14
MSG YLLOW CB
Statutory Message for
Yellow Color Mode
PCV15
MSG GREEN CB
Statutory Message for
Green Color Mode
PCV19
MSG BLUE CB
Statutory Message for
Blue Color Mode
Units
(SI Units)
Object Description
Value
51
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Point Database
Instances
Point
Number
Object Name
Units
(SI Units)
Object Description
PCV16
UD MSG RED
User Defined Text for
Red Color Mode
PCV17
UD MSG GREEN
User Defined Text for
Yellow Color Mode
PCV18
UD MSG YLLOW
User Defined Text for
Green Color Mode
PCV20
UD MSG BLUE
User Defined Text for
Blue Color Mode
Value
Points without a point number are only available via BACnet Browser.
SI Units can be selected for specific points.
52
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Notification Class
4
Notification Class
Instances
Object Name
Description
NC1
PPRES WARN
Primary Room Pressure Warning
NC2
SPRES ALRMNC
Primary Room Pressure Alarm
NC3
SPRES WARNNC
Secondary Room Pressure
Warning
NC4
SPRES ALRMNC
Secondary Room Pressure Alarm
NC5
DIGITAL INPUT STATUS
Digital Input Status
53
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
5
Event Enrollment
Event Enrollment
Instances
Object Name
Description
EE1
PPRES WARNEE
Primary Room Pressure Warning
EE2
SPRES ALRMEE
Primary Room Pressure Alarm
EE3
SPRES WARNEE
Secondary Room Pressure
Warning
EE4
SPRES ALRMEE
Secondary Room Pressure Alarm
EE5
DIGITAL INPUT STATUS
Digital Input Status
54
Siemens Industry, Inc.
125-1900. Rev AA
2014-02-12
Issued by
Siemens Industry, Inc.
Building Technologies Division
1000 Deerfield Pkwy
Buffalo Grove IL 60089
Tel. +1 847-215-1000
Document ID
125-1900. Rev AA
Edition
2014-02-12
© 2014 Copyright Siemens Industry, Inc.
Technical specifications and availability subject to change without notice.
125-1900 (AA)
BACnet SRCM User Manual
Download