CIRED 17th International Conference on Electricity Distribution Barcelona, 12-15 May 2003 TRANSFORMERS FOR WIND TURBINES NEED FOR NEW DESIGNS OR BUSINESS AS USUAL Jan DECLERCQ Pauwels International - Belgium jan.declercq@pauwels.com INTRODUCTION The wind energy industry is booming at European and international level with annual growth levels reaching up to 30%. The liberalisation of the electricity market, the need for more generating power, the concept of decentralized generation and distribution, the acceptance of wind turbines in the landscape and the awareness of environmental constraints were the major drivers. However, due to the sharp increase in demand, the technology development efforts increased and came out with new techniques leading to estimated cost reductions of 5 % per year. The major technology changes lead to an increased reliability, reduced maintenance as well as an increased efficiency and power output. This power output per tower has gone up from 400 kW over 1.2 MW to 2.5 MW nowadays and prototypes for 3 and 4 MW are being tested. The eye-catchers of the technology are the wind blades and towers but inside and also indispensable, the gearbox, the generator and the link to the grid. This latter role is carried out by switchgear and the transformer stepping up the voltage from the generator (400-690 V) to a medium voltage level for the distribution grid (10 000 – 33 000 V). This paper will present an overview of technologies suitable for step up transformers that can be used in wind turbines. Dry type transformer, conventional transformers based on the cellulose mineral oil insulation system and new insulation systems will be discussed. Secondly, it will highlight on the potential problems that can occur when installing distribution transformers close to windturbine generators. Numerous failures have already been reported in Europe and this needs attention, especially when the transformer goes off shore. TRANSFORMER TECHNOLOGIES For the transformer, the wind turbine industry has the choice between dry-type transformers and liquid immersed transformers. The fundamental difference is the electrical insulation medium namely air and resin for dry type transformers and an insulation paper and liquid for the liquid immersed transformers. The conventional liquid immersed transformer uses cellulose and mineral oil, an advanced technology referred as SLIM® uses a high temperature aramid insulation NOMEX® and silicone liquid. The insulation structure is also needed for the heat management and mechanical integrity. The functional specifications for both technologies are the same, and both technologies meet the requirements as shown in table 1. Power MVA High Voltage kV Low Voltage V Impedance % FIGURE 1. Typical windfarm with step up- transformer inside These step up transformers are subject over longer periods to higher loads when the wind speed reaches more than 10 m/sec. The generator causes also more voltage and power fluctuations stressing the integrity of the transformer. Harmonics, fast transients and vibrations makes it even harder. PAU_Declercq_A1 Session 4 Paper No 25 Mineral oil cellulose 0.5 – 10 … 1000 10 – 36 …. 750 400–3000 4 – 10 Cast resin and air SLIM® 0.5 – 5 1 – 10 10 – 33 10 – 36 400 – 3000 400 – 3000 4 – 10 5 - 10 TABLE 1. Specifications for transformer technologies. The specifications are generalised and every technology has exceptions. The liquid immersed transformer with the mineral oil and cellulose technology is the only technology nowadays that allows voltages above 500 kV and power ratings above 500 MVA. So any transformer technology is allowed for its use in the wind turbine. But what about the other specifications such as -1- CIRED 17th International Conference on Electricity Distribution no load losses and load losses, dimensions, harmonics and loading, fire behavior and last but not least the environmental issues. LOSSES AND DIMENSIONS A comparative study is done in table 2 for SLIM® and conventional transformers from 1 to 2 MVA. No load losses The levels of no load losses have a direct financial impact on the transformer design and its operational use. Lower no load losses require a larger magnetic circuit increasing the dimensions and cost of the transformer. The liquid immersed transformers have usually up to 50 % lower no load losses for the same dimensions leading to an attractive operational financial benefit. The annual savings of for example 1900 W (the difference between 2 transformers of 2 MVA ) is 1.9 kW x 8760 h/y x 0.05 €/kWh which equals 832 € for one turbine in service for one year. Barcelona, 12-15 May 2003 Dimensions can be crucial for wind turbines. In towers nowadays of 100 m height and a small door of 780 mm, the electrical components have to fit in easily and perform their job of delivering high power at severe operating conditions for the expected life. Conventional mineral oil transformers tend to become bulky because of their cooling equipment. For outdoor installations and substations is this no problem. Cast resin transformers can be made more compact but enclosures are needed to respect the safety clearances for the high voltage equipment. Consequently larger dimensions are needed. The new technology SLIM has been special designed for wind turbines, with more power for less space and increased reliability. It can be designed with the smallest dimensions and lowest mass. This allows flexibility for tower and nacelle installations and has to option to be replaced in case of an emergency or fault as can be seen in figure 2. Load losses The three technologies can deliver the same load loss performance e.g. high or low load losses. These losses are proportional to the power squared and are only applicable when the transformer is loaded. Note that the losses must be specified at the expected operating temperature of the transformer. In addition, the heat generated by the transformer losses has to be evacuated from the turbine. This can impose an extra requirement for lower load losses in specific wind turbine designs. . FIGURE 2. Compact transformer for in tower installation Dimensions POWER Pnll Pll @ 75°C Pll @ 125°C Uk Temperature rise Length Width Height Height cover Mass Liquid Mass Total W W W % K mm mm mm mm kg kg 1000kVA Conv SLIM 1450 1450 13000 11300 13000 6 6 60/65 80/120 1840 1640 1000 940 1805 1775 1305 1275 535 510 2415 2250 1250kVA Conv SLIM 1650 1550 16000 14500 16500 6 6 60/65 80/120 1860 1670 1000 970 1865 1880 1365 1380 620 620 2800 2700 1600kVA Conv SLIM 2000 1700 20000 17500 20000 6 6 60/65 80/120 2100 1900 1000 1000 2200 2000 1600 1500 825 715 3600 3250 2000kVA Conv SLIM 2650 1850 25500 22000 25000 6 6 60/65 80/120 2160 1900 1410 1230 2500 2200 1900 1600 1035 780 4440 4030 TABLE 2. Losses and dimensions of step up transformers, convetional versus SLIM design. LOAD, AMBIENT AND HARMONICS PAU_Declercq_A1 Session 4 Paper No 25 -2- CIRED 17th International Conference on Electricity Distribution As mentioned before, the high load will lead to an increase of the losses and an increase of the transformer temperature. This temperature rise is limited to 60 K for mineral oil and 65 K for cellulose-designed transformers. According IEC standards, the maximum average monthly temperature for a FIGURE 3 : Current I __ __ __ , losses ……., transformer temperature -.-.-. and lifetime ______ in function of load. Barcelona, 12-15 May 2003 100.0 1600 90.0 1400 80.0 1200 70.0 1000 60.0 50.0 800 40.0 600 30.0 400 20.0 Temp geno 1 Temp geno 2 T bearing A T bearing B Gearbox Nacelle Geno coll air Gearb. Bearing shaft bearing Trafo 1 Trafo 2 Trafo 3 Outside door Power 200 10.0 0.0 22:34:14 21:34:14 20:34:14 19:34:14 18:34:14 17:34:14 16:34:14 15:34:14 14:34:14 13:34:14 12:34:14 9:34:14 11:34:14 8:34:14 10:34:14 7:34:14 6:34:14 5:34:14 4:34:14 3:34:14 2:34:14 1:34:14 0:34:14 23:34:14 22:34:14 21:34:14 20:34:14 19:34:14 18:34:14 17:34:14 16:34:14 15:34:14 14:34:14 13:34:14 0 Time Load P transformer is 30ºC with a maximum daily temperature 40ºC so the maximum temperature of the transformer is 40ºC + 60 K which totals to 100ºC. Above 100ºC, the insulation materials start to age very fast according the Montsigner relation. L In a wind turbine, transformers do operate in the vicinity of this ageing point due to the higher air temperatures in the tower or nacelle, the full load for several days and the content of current harmonics. A power derating is usually advised e.g a 1000 kVA transformer for a 900 kW turbine. The SLIM® transformer has different insulation materials that can withstand temperatures up to 200ºC without accelerated loss of life. On site temperature measurements have been performed on a 2 MVA 20 kV transformer to verify the 1600 40 1400 35 1200 30 1000 25 Po we r 800 20 600 15 400 10 200 5 0 10 :3 4: 14 14 :3 4: 14 18 22 2: 6: :3 :3 34 34 4: 4: :1 :1 14 14 4 4 10 :3 4: 14 14 :3 4: 14 18 22 :3 :3 4: 4: 14 14 2: 6: 34 34 :1 :1 4 4 10 :3 4: 14 14 :3 4: 14 18 :3 4: 14 22 2: 6: 10 14 18 22 2: :3 34 34 :3 :3 :3 :3 34 4: :1 :1 4: 4: 4: 4: :1 14 4 4 14 14 14 14 4 Time 6: 34 :1 4 10 :3 4: 14 14 18 22 2: :3 :3 :3 34 4: 4: 4: :1 14 14 14 4 6: 10 34 :3 :1 4: 4 14 14 18 22 2: :3 :3 :3 34 4: 4: 4: :1 14 14 14 4 6: 0 34 :1 4 FIGURE 4 : Loading of a 1600 kVA transformer at different windspeeds compatibility of a transformer in a tower. Typical loading profiles and corresponding temperatures are shown in figures 4 and 5 and are meant for illustration of the correlation between temperatures and loading in turbines. PAU_Declercq_A1 Session 4 Paper No 25 FIGURE 5. Transformer and air temperatures in ºC in a windturbine FIRE BEHAVIOUR The Materials and the Transformer The fire behaviour of the transformer depends on the materials used inside the transformer. Conventional mineral oil filled transformer contain mineral oil, which is a class O product and has a fire point of 150ºC. A silicone filled transformer has class K3 meaning a fire point above 300ºC namely 360ºC. It is difficult to compare with the dry type transformer technology but the fire properties are comparable to a silicone oil filled transformer for a F0 cast resin transformers and slightly better for a F1 cast resin transformer. In addition to the ignition values, smoke, heat release, toxic gasses can also be important but in general, the silicone oil filled transformers and cast resin transformer can be treated as good fire retarding products. Standards, Laws and Policies All transformer are treated as passive to fire e.g. they will very unlikely start the fire themselves. If an external fire reaches the products, both will burn. A lot of good information is available in the Standards such as Cenelec standard HD637 S1:1999 on "Installation of electric equipment" and IEC 60695-1-40,TS,Ed1 : Fire hazard testing - Part1-40,"Guidance for assessing the fire hazard of electro technical products - Insulating liquids". In general, no formal guidelines do exist for installation of electrical products in wind turbines, the three transformer technologies are allowed. Class O filled transformers can always be used but some countries could require fireretarding walls. Class K and cast resin transformers do not need special equipment. It will therefore depend on the local policies and laws. -3- CIRED 17th International Conference on Electricity Distribution ENVIRONMENTAL IMPACT Barcelona, 12-15 May 2003 Point 12 tank long side Silicone liquid will degenerate slowly into natural existing products and shows no harmful or contamination effects. If silicone liquid is spoiled in water (salt or not salt) it will not react with the water and sink to the bottom and degenerate slowly into carbondioxide, water and other natural products. The liquid will not take oxygen out of the water. Mineral oil will react with the environment and oxidize. It has to be mentioned that transformers can be considered as leak free. They leave the factory leak free and can only be damaged during transport or installation. Once in service, they remain closed for their lifetime. ENCLOSURES AND CABLE BOXES Hermetic sealed transformers are considered as maintenance free. Hermetic sealed transformers are IP55 and are treated as EMC-passive elements. This is valuable for off shore or aggressive environment applications where moisture and salt contaminate the air. Cast resin type transformers should be cleaned and checked yearly since the air is the insulation medium. Cast resin types are IP00 so ‘live’ surfaces and have higher EM values, thus need additional protection such as an enclosure. The connections of all transformers can be protected with shielded connectors and cable boxes. 1 XFRfunc Mag What about the end-of-life of the transformer. The copper and steel can be recycled for 100 %. For the moment, silicone oil is burned in incinerators at the same cost as mineral oil. However, an European recycling business for silicone liquid is already active since 2001. Mineral oil can also be recycled but is usually burned and used for production of electricity. The windings of the cast resin transformer have to be treated as waste or need energy and high temperature burning. A recycling company with factories in 4 European countries, recycles oil filled transformers at 75 – 100 EUR/ton. PCB contaminated transformers at 1200 EUR/ton and dry type transformers at 150-160 EUR/ton. 0.6 0.4 0.2 0 0 25 50 75 100 125 150 175 200 Hz FIGURE 4 Frequency response of a finned tank for frequencies up to 200 Hz. The resonance frequencies of 5 Hz and 100 Hz are not harmful since their amplitude is lower than 1. ON SITE EXPERIENCE AND RELIABILITY The windturbine industry started with distribution transformer with conventional insulation system and dry type and these transformers were designed according the practices for step down grids. Thousands of transformers were successful designed, manufactured and tested according IEC standards. Many of them are successful in operation but several transformers in Europe failed. This was applicable for different manufactures, power ratings and voltages. An increased failure rate of factor 3 is seen compared to a step down grid. The major reasons for failures are mentioned below : • • • • VIBRATIONS A few cases have been reported where heavy vibrations occurred in the nacelle leading to damages in the transformer. Vibrations have been reported from 5 Hz to 100 Hz and accelerations up to 1 m/s2 or 0.1 g. These vibrations can lead to fatigues of the material. Normally, transformers are designed up to 3 g shock for transport reasons. Additional tests can be carried out as shown in figure 4 to verify if resonances are present in the frequency domain of interest. 0.8 • • Voltage fluctuations due to generator and step up function causes frequent saturation of magnetic circuit Very sharp load fluctuations (from 10 % to 100 % load in less a minute) causing thermal stresses in mainly the solid insulation Average loading of transformer is mainly 50 % but loading reaches 100 % for several days. This causes accelerated ageing of insulation if designs are not optimised. Proximity of low voltage and high voltage circuit breakers and frequent switching causing additional switching electrical stresses. Failures have been reported for more than 50 transformers. Vibrations for nacelle installations causing weakening of solid insulation, reduced connection contacts and failures with even fires. Moisture and reduced maintenance leading to start up problems. In some of the cases, the failures lead to fires causing a burned out wind turbine. In other cases, it lead to a 50 % failure rate for an off shore wind park where due to bad weather conditions, some turbines could not be energized again for 3 months. Contractors and wind turbine manufactures must be aware that although a transformer has its outstanding reputation in reliability, it still can fail. When transformers are installed PAU_Declercq_A1 Session 4 Paper No 25 -4- CIRED 17th International Conference on Electricity Distribution inside turbine towers and due to transformer dimensions and door restrictions cannot be taken out in case of failure, serious problems can arise. Worse case scenarios such as lifting of tower in order to replace a transformer will lead to enormous costs. Some wind turbine manufactures take therefore very compact transformers for. Barcelona, 12-15 May 2003 Transformers are treated passive to fire and otherwise; precautions or selection of materials can be made in order to be in line with the local policy and laws. The transformer is very recyclable up to 98 % for liquid filled transformers and up to 85 % for dry type transformers. Enclosures and cable boxes can be installed in order to protect the transformer or its live contacts from the environment. In order to make a choice between different technologies, the Total Cost of Ownership can be computed where all aspects are taken into account and not just the purchase price. The capitalization of losses and the extra costs in case of a replacement need to be considered. FIGURE 6 : Typical tower installation over a substation containing a compact SLIM® transformer. Consequently, various fine tuning in design, manufacturing and testing is needed for a successful operation and acceptable maintenance. The new generation of conventional transformers as well as the SLIM® transformer has met several of those new criteria. CONCLUSIONS Three transformer technologies have been presented which can be used for step up transformers in the wind turbines. Next to power, high voltage and low voltage specifications, several additional features are highlighted. Load losses and especially no-load losses have a direct impact on the transformer design and its operational cost during its lifetime. Dimensions can be critical if in tower or nacelle applications are required. The SLIM® transformer with advanced materials can be made very compact. PAU_Declercq_A1 Session 4 Paper No 25 -5-