EC Type Examination Certificate Number: 0120/ SGS0006
Janz-Contadores de Energia,SA
Av.Infante D. Henrique 328
1800-223 Lisboa
Portugal
Instrument Identification:
C2##
Single Phase, Credit, Active Import kWh, Single & Multi-rate, Electricity Meter
Instrument Traceable Number
0120/ SGS0006
has been assessed and certified as meeting the requirements of
EC Directive 2004/22/EC
on Measuring Instruments Annex B
It is certified that the manufacturer’s technical design and specimen for the above instrument has been examined and, based on the
evidence submitted, it is considered that the instrument conforms to the requirements of
MI-003 of EC Directive 2004/22/EC
This certificate must be used in conjunction with a certificate covering the product verification as required in Annex D or Annex F.
This certificate is valid from 4th June 2007 until 3rd June 2017
Issue 12
Certification is based on report number(s)
DUR44640/1/PF/EMA/06 dated19th June 2006
EMA107891 dated 1st June 2007
EMA186674/1 dated 24th February 2014
Authorised Signature
Jan Saunders
SGS United Kingdom Limited, Notified Body 0120
Unit 202B Worle Parkway, Weston-super-Mare, BS22 6WA□UK
t +44 (0)1934 522917 f +44 (0)1934 522137 www.sgs.com
Contact Address
SGS United Kingdom Ltd, Unit 12, South Industrial Estate, Bowburn, Durham, DH6 5AD□UK
t +44 (0)191 377 2000 f +44 (0)191 377 2020 www.sgs.com
MID-B06E Rev 5
EC Type Examination Cert.
Page 1 of 7
EC-Type Examination Certificate Number:
0120/ SGS0006
Issue Number: 12
1.
Dated: 24th February 2014
Technical Data
Manufacturer
Janz-Contadores de Energia, SA.
Meter Type
C2##
Voltage Rating (Un)
220-240V
Current Rating (Imin – Iref (Imax))
0,25-5(80)A or 0,5-10(60)A
Frequency (Fn)
50Hz
Active Accuracy Class (kWh)
A or B (kWh)
Type of circuit
1p2w
o
Temperature Range
o
-25 C to +60 C
V02.10 or V02.11
V03.12 (Anti Fraud Version)
V04.00.0; V04.01.0; V04.02.0
LCD & Nameplate
PCB BOM No:
9 1300 9001 f5h
Mechanical BOM No:
9 1300 9001 f4h
Assembly Drawing No:
9 1300 9001 f2h
Software/ Firmware Version No.’s
Identification Location
Bill Of Materials Number
IP Rating
IP51
Insulation Protective Class
Class II
LED Pulse Constant
3200 imp/ kWh
Impulse Voltage Rating
6kV
AC Voltage Rating
4kV
Main Cover Sealing Type
Wire & Crimp
or
Tamper proof sealing tape
concealing main cover screw
Integrity of meter
Inaccessible without breaking seals
under terminal cover
Intended Location of the Meter
Indoor
Type of Register
LCD & Nameplate
Terminal Arrangement(s)
DIN
MID-B-06E Rev 5
EC Type Examination Cert.
Page 2 of 7
EC-Type Examination Certificate Number:
0120/ SGS0006
Issue Number: 12
2.
Dated: 24th February 2014
Photograph of Meter & Sealing Plan
Wire & Crimp
Main Seal
Utility Seal
Tamper Proof Sealing Tape
Main Seal
Utility Seal
MID-B-06E Rev 5
EC Type Examination Cert.
Page 3 of 7
EC-Type Examination Certificate Number:
0120/ SGS0006
Dated: 24th February 2014
Issue Number: 12
3.
Calculation of the composite error/ MPE
In addition to the accuracy requirements the composite error ec of the meter is shown below
The composite error at a certain load is calculated from the following formula:
2
2
2
2
ec = √ e (I.cosθ) + e (T.I.cosθ) + e (U.I.cosθ) + e (f.I.cosθ)
where
2
e (I.cosθ)
2
e (T.I.cosθ)
2
e (U.I.cosθ)
2
e (f.I.cosθ)
=
=
=
=
Intrinsic error of meter at a certain load
Additional error due to variation of the temperature at the same load
Additional error due to variation of the voltage at the same load
Additional error due to variation of the frequency at the same load
Current
Ambient Temperature Range 5 to 30 Degrees C
PF Cos e(Icos) e(TIcos) e(UIcos) e(fIcos)
Imin
Itr
10Itr
Imax
1.0
1.0
1.0
1.0
-0.22
-0.21
-0.18
-0.15
-0.11
0.00
-0.04
0.00
-0.15
0.07
0.13
0.13
-0.25
-0.17
-0.21
-0.20
0.38
0.28
0.31
0.28
Itr
10Itr
Imax
0.5ind
0.5ind
0.5ind
-0.20
-0.17
-0.19
0.05
0.01
0.07
-0.11
0.19
0.26
-0.06
-0.20
-0.20
0.24
0.32
0.39
Itr
10Itr
Imax
0.8cap
0.8cap
0.8cap
-0.17
-0.16
-0.13
0.01
-0.05
-0.08
-0.04
0.11
0.15
-0.19
-0.23
-0.26
0.26
0.31
0.34
Current
Ambient Temperature Range -10 to 40 Degrees C
PF Cos e(Icos) e(TIcos) e(UIcos) e(fIcos)
Imin
Itr
10Itr
Imax
1.0
1.0
1.0
1.0
-0.22
-0.21
-0.18
-0.15
-0.16
-0.15
-0.16
0.09
-0.15
0.07
0.13
0.13
-0.25
-0.17
-0.21
-0.20
0.40
0.32
0.34
0.30
Itr
10Itr
Imax
0.5ind
0.5ind
0.5ind
-0.20
-0.17
-0.19
-0.06
-0.11
-0.03
-0.11
0.19
0.26
-0.06
-0.20
-0.20
0.24
0.34
0.38
Itr
10Itr
Imax
0.8cap
0.8cap
0.8cap
-0.17
-0.16
-0.13
-0.18
-0.16
-0.10
-0.04
0.11
0.15
-0.19
-0.23
-0.26
0.31
0.34
0.34
MID-B-06E Rev 5
%MPE
%MPE
EC Type Examination Cert.
Page 4 of 7
EC-Type Examination Certificate Number:
0120/ SGS0006
Dated: 24th February 2014
Issue Number: 12
Current
Ambient Temperature Range -25 to 55 Degrees C
PF Cos e(Icos) e(TIcos) e(UIcos) e(fIcos)
Imin
Itr
10Itr
Imax
1.0
1.0
1.0
1.0
-0.22
-0.21
-0.18
-0.15
-0.08
-0.13
-0.23
-0.15
-0.15
0.07
0.13
0.13
-0.25
-0.17
-0.21
-0.20
0.37
0.31
0.38
0.32
Itr
10Itr
Imax
0.5ind
0.5ind
0.5ind
-0.20
-0.17
-0.19
-0.07
-0.21
-0.12
-0.11
0.19
0.26
-0.06
-0.20
-0.20
0.25
0.39
0.40
Itr
10Itr
Imax
0.8cap
0.8cap
0.8cap
-0.17
-0.16
-0.13
-0.12
-0.25
-0.18
-0.04
0.11
0.15
-0.19
-0.23
-0.26
0.28
0.39
0.37
MID-B-06E Rev 5
%MPE
EC Type Examination Cert.
Page 5 of 7
EC-Type Examination Certificate Number:
0120/ SGS0006
Dated: 24th February 2014
Issue Number: 12
4.
Annex of Variants
Product Variant Identification Details:
Type Designation
Description of meter
CONNECTION
MODE
C
Single phase meter for direct connection (2 wires)
SERIES
2
The concept of series is related with the physical aspect of meter (meter case), seven series
remain available
10
Single rate (electromechanical register), kWh
11
Single rate (LCD), kWh
22
Double rate (LCD), kWh, with internal tariff switch
31
Triple rate (LCD), kWh, with internal tariff switch
40
Programmable Multirate, kWh (maximum demand registers, no load profile)
TARIFF
INTERFACE TO THE
USER
-
Without push buttons (LCD scrolls the programmed data)
-
No pulse output
PULSE OUTPUT
E1
One pulse output (through terminals 21/22)
E2
Two pulse outputs (through terminals 23/24)
-
No pulse input for tariff switch
-
No auxiliary communications
PULSE INPUT
AUXILIARY
COMMUNICATIONS
ANTI-TAMPER
VERSION
R2
With RS232 port
R4
With RS485 port
-
Without external cover opening detection device
-
The initial version is not identified
.A
.B
The concept of version is related to hardware changes or significant firmware modifications,
but always within the same "series" (see above)
...
Modifications to the meter(s) described according to approval No.0120/ SGS0006 must be notified to the
issuing body to confirm the meter(s) continuing compliance to the relevant pattern approval standard(s).
MID-B-06E Rev 5
EC Type Examination Cert.
Page 6 of 7
EC-Type Examination Certificate Number:
0120/ SGS0006
Issue Number: 12
5.
Issue
1
2
3
4
5
6
7
8
9
10
11
12
Dated: 24th February 2014
Document Revision History
Date
Comments
04/06/2007
04//06/2007
04/06/2007
04/06/2007
04/06/2007
14/11/2008
17/01/2012
19/04/2012
09/05/2012
15/03/2013
03/04/2013
24/02/2014
Initial Issue
Certificate corrected and Sealing Type Photo’s Added
Certificate corrected
Certificate corrected
Certificate corrected
Major Firmware Update to Version v03.12 (anti fraud version)
Major Firmware Update to Version v04.00.0
Minor Firmware Update to Version v04.01.0. Migrated to new certificate template
Corrected Terminal Arrangement to DIN Only
BOM & Minor Firmware Update to Version v04.02.0
Certificate corrected
Component & BOM change
MID-B-06E Rev 5