OccuSwitch Classic LRL2380 LRL2385 Installation and Programming Guide Product Description Important Safety Information The Philips OccuSwitch Classic On/Off Photocell Sensors provide the industry’s most intelligent control of lighting for daylight harvesting applications. Ideal for public spaces with windows like vestibules, corridors, or bathrooms; the sensors work by monitoring daylight conditions in a room, then controlling the lighting so as to insure that adequate lighting levels are maintained. They have on/off lighting control; they turn off the lights when sufficient daylight is present and turn them on when additional lighting is necessary. These sensors are ceiling mounted, line powered and can switch loads directly without the need for a power pack. Parts of the sensor carry line power, which is a potential lethal voltage. This product was designed and manufactured to ensure maximum safety during operation and service. Always read these safety instructions before installing, maintaining or servicing the product, and strictly comply with these instructions. - Whenever it is suspected that an unsafe condition exists, switch off power at the circuit breaker and replace the device. Safety is likely to be impaired if, for example, the equipment fails to perform the intended functions or if the equipment shows visible damage. Do not paint the device. - This product should be installed by a qualified electrician. - Use only a soft damp cloth to clean, never use any abrasive or chemical cleaner. - This device is designed for indoor use only. - Disconnect power at circuit breaker or fuse when servicing, installing or removing. - Only use with copper or copper clad wire. - Wire sensor to the line power according to the wiring scheme in this guide. - To avoid short circuits, do not expose this product to rain or condensing moisture. Short circuit may cause fire or electric shock hazard. Operate the devices between 14°F to 160°F (-10°C to 71°C) ambient temperature. Mounting Daylight Harvesting The sensor enclosure accommodates mounting to a variety of junction boxes ranging in size from a single gang mud ring at a 3.28” spacing, up to a round fixture box spacing of 3.5”. Warning It is the installer’s responsibility to ensure that the equipment being controlled is visible from every control location and that only suitable equipment is connected to these controls. Failure to do so could result in serious injury or death. The product is intended to control lighting loads. Do NOT use to control equipment that could create hazardous situations, like entrapment. For examples, do NOT install this product to control motorized gates, garage doors, industrial doors, microwave ovens, heating devices, etc. Dual Zone (LRL2385) Provides second output that can control an additional zone of lighting Two Operational Modes: Stepped Dimming (Duo): Determines the ideal On/Off combination of the two poles to achieve adequate lighting; best for A/B (also called inboard/outboard) switching applications As daylight increases and decreases throughout the day, the connected loads are switched off and on based on the programmed set-point. When sufficient daylight is present to maintain a level of light equal to or above the set-point level, the sensor will switch off the ballast completely. Percentage Offset: A percentage higher than the primary pole’s set-point is used as a relative set-point for the second pole; best for rooms with separately controlled parallel rows of lights Wiring Danger Turn OFF breaker of all circuits involved. Wiring the device with power ON could result in serious injury or death. LRL2380 Wiring LRL2385 Wiring Note Once installed, the sensor may take a few minutes to become active. Additionally, there is a 45 second delay before switching from “Off” to “On” (this delay is 55 seconds when connected to 50 Hz). Specifications* Function Definitions Input Voltage: 120-277 VAC 4 100 Hour Burn-In / Auto Set-Point 100 Hour Burn-In Overrides relay on and/or dimming output to full bright (typically for lamp seasoning) Operational Frequencies: 50/60Hz Load Rating: 800W @ 120VAC; 1200W @ 277VAC; Motor: 1/4 HP Load; No minimum load; Environmental Conditions: Operating Temp: 14 to 160°F (-10 to 71°C) Storage Temp: -14 to 160°F (-26 to 71°C) 20% to 90% non-condensing, relative humidity. For indoor use only. Size: Diameter: 4.55” (11.56cm); Depth: 1.55” (3.94cm) Weight: 5oz (0.14kg) Regulatory compliance: UL, cUL, and Title 24. *Subject to change without notice. Auto Set-Point Photocell calibration procedure for detecting optimum lighting control level 5 Ten’s Digit of Holdback SetPoint The ten’s digit of the target light level for daylight holdback in foot-candles. 6 One’s Digit of Holdback SetPoint The one’s digit of the target light level for daylight holdback in foot-candles. 18 Second Zone Off-Point 7 Sunlight Discount Factor Value used to improve the tracking accuracy of a photocell during periods of high daylight. Decreasing the value will lower the controlled level of the lights. Zone 2 set-point is selected as a percentage of Zone 1 set-point (Only available when Percentage Offset Mode is selected for function 11 Dual Zone Mode) 8 Incremental Holdback Set-Point Adjustment Alters the target light level for daylight holdback in foot-candles. 11 Dual Zone Mode Stepped Dimming (DUO) Determines the ideal On/Off combination of the two poles to achieve adequate lighting Percentage Offset Allows Zone 2 set-point to be set as a percentage of Zone 1 set-point Note For information on additional advanced settings, including resetting unit to factory defaults, contact: Technical Support: 1.800.372.3331 Programming Functons Programming Please read all 3 steps before programming 1. Enter a programming function by pressing button, on side of device, the number of times as the desired function number from the tables below (e.g., press twice for function 2, occupancy time delay). Function 2. LED will flash back the selected function's current setting (e.g., 5 flashes for 10 minute time delay). To change setting, proceed to step 3 before flash back sequence repeats 3 times. To exit the current function or to change to a different function, wait for sequence to repeat 3 times then return to step 1. 3. Press button the number of times indicated in the particular function's detailed table for the NEW desired setting (e.g., press 3 times for 5 min). As confirmation of setting change, LED flashes back the NEW setting 3 times before exiting. 4 100 hr Burn-In / Auto Set-Point Selection Description LRL2385 2 Occupancy Time Delay 3 Dim to Off Time Delay 4 100 hr Burn-In / Auto Set-Point • • 5 Ten’s Digit of Set-Point • • 6 One’s Digit of Set-Point • • 7 Sunlight Discount Factor • • 8 Incremental Set-Point Adjustment • • 10 Minimum On Time 11 Dual Zone Mode 14 Lamp Information 15 Dimming Range (High) 16 Dimming Range (Low) 18 Second Zone Off-Point 5 Ten’s Digit of Holdback Set-Point Operation LRL2380 Selection • • 6 One’s Digit of Holdback Set-Point Selection Light Level (foot-candles) Light Level (foot-candles) 7 Sunlight Discount Factor Selection Factor 1 Normal* 1 10 fc 1 1 fc 1 1x 2 Run 100 hr Burn-In 2 20 fc 2 2 fc 2 2x 3 Run 100 hr Burn-In then Auto Set-Point 3 30 fc 3 3 fc 3 3x 40 fc 4 fc 4 4 x* Run Auto Set-Point 4 4 4 50 fc 5 fc* Blink back Set-Point2 5 5 5 5x 5 6 100 fc 6 6 fc 6 6x 7 200 fc 7 7 fc 7 7x 8 Disable (LRL2380 ONLY) 8 8 fc 8 8x 10 0 fc* 9 9 fc 10 0 fc 2 The LED will blink back the ten’s digit, then pause, then blink back the one’s digit. For a “0” the LED will blink very rapidly. The sequence is repeated three times. * default setting * default setting * default setting 8 Incremental Holdback Set-Point Adjustment Selection 11 Dual Zone Mode (LRL2385) Selection Change (foot-candles) 1 Decrease 1 fc 2 Increase 1 fc 18 Second Zone Off-Point1 (LRL2385) Mode Selection % of Zone 1 Set-Point Stepped Dimming (DUO) Mode* 1 110% 2 120% Stepped Dimming (DUO) Mode - Never Off 3 130% 4 140% 3 Percentage Offset Mode 5 150%* Fan Mode (Zone 2’s Photocell Control Disabled 6 160% 4 7 170% 8 180% 9 190% 10 200% 1 2 * default setting 1 Only available when Percentage Offset Mode is selected for function 11 Dual Zone Mode * default setting Warranty Statement Contact Information The Philips OccuSwitch products, when properly installed and under normal conditions of use (without overload, abuse or alteration), is warranted to you, the original user, for a period of two (2) years from the date of original purchase, to be free from defects in materials and workmanship. If during the warranty period you believe the purchased product or any part thereof has such a defect, you must return the product (or part) at your cost during such period, with proof of purchase (or if installed by a third party a written explanation of installation transaction with proof of date), to Philips Lighting Electronics N.A (1-800-3723331 / www.philips.com/advance), for repair or replacement (or to an authorized Philips Lighting Electronics N.A. supplier which agrees in advance to handle the return and replacement by factory authorization). If the product or part is found by Philips to have been defective in material or workmanship it will be repaired or replaced (as deemed necessary by Philips Lighting Electronics N.A.), and the replacement will be returned to you free of charge. The original user is solely responsible for any costs associated with removal and reinstallation of the product and shipping to Philips Lighting Electronics N.A. or its authorized supplier. Philips Lighting 10275 West Higgins Road Rosemont, IL 60018 Customer Care/Technical Service: 800-372-3331 Email: tech.service.rosemont@philips.com Website: www.philips.com ©2012 Philips Lighting Electronics North America. A Division of Philips Electronics North America Corporation. All rights reserved. Printed in the USA Published 6/12 Part No. 12NC 4435 290 60651 Version 1 * default setting