Data Sheet - Proton Motor Fuel Cell GmbH

advertisement
we do more for security
PII 1000 - 10000 VA
Multi functional Tower UPS with LCD operating panel
Double conversion
Tower UPS
Secure power for
workstations, servers, small
network and telecom applications
With true double-conversion design, the UPS provides powerful and overall protection
to your sensitive devices. It can accept wider input voltage for harsh environment. It‘s
perfect protection for your precisous servers and workstations.
Features:
• True double-conversion
• 6/10 k Tower Version N+X parallel redundancy
• Wide input voltage range (110-300 VAC)
• Input power factor correction 0.99
• Output Power Factor 0.8
• 50Hz/60Hz frequency converter mode
• Programmable power management outlets
• Emergency power off function (EPO)
• Eco mode operation for energy saving (ECO)
• Generator compatible
• SNMP+USB+RS-232 multiple communications
• Smart battery charger design for optimized battery performance
• Selectable output voltage: 208-240VAC
• Accessory: External maintenance bypass switch & SNMP card
MODEL
OUTPUT
Capacity
Voltage
AC Voltage Regulation
(Batt. Mode)
Frequency Range
(Synchronized Range)
Frequency Range (Batt. Mode)
Current Crest Ratio
Harmonic Distortion (THD)
(Linear Load / Non-linear Load)
EFFICIENCY
BATTERY
INDICATORS
High Line Transfer
High Line Comeback
Frequency Range
Phase
Power Factor
AC Mode
Battery Mode
Standard Battery Type
Model
Qty.
Typical Recharge Time
Charging Current (max.)
Charging Voltage
LCDPanel
LED Panel
ALARM
Battery Mode
Low Battery
Overload
Fault
Tower
Dimension, D X W X H
PHYSICAL
Case,
(mm)
Standard
Net Weight (kgs)
Model
ENVIRONMENT Operation Humidity
Noise Level @ 1 Meter
MANAGEMENT Smart RS-232/USB
Optional SNMP
Paralell Capapility
Battery Type
EXTERNAL
BATTERY
Qty.
PACK
Charger
PII 2K
PII 3K
PII 6K
PII 10K
2000 VA / 1600 W 3000 VA / 2400 W 6000 VA / 4800 W 10000 VA / 8000 W
208V / 220 V / 230 V / 240 V or 110 V / 120 V
± 3%
± 1%
47 ~ 53 Hz or 57 ~ 63 Hz
46 ~ 54Hz or 56 ~ 64 Hz
50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
3:1
<3% /<6%
Transfer
Time
INPUT
AC Mode to Batt. Mode
Inverter to Bypass
Waveform (Batt. Mode)
Voltage
Low Line Transfer
Range
Low Line Comeback
PII 1K
1000 VA / 800 W
<4%/<7%
<3%/<6%
Zero
4 ms (Typical)
Zero
Pure Sinewave
160 VAC ± 5% or 80 VAC ± 5% @ 100% load
110 VAC ± 5% or 50 VAC ± 5% @ 50% load
175 VAC ± 5% or 85 VAC ± 5% @ 100% load
176 VAC @ 100% load
186 VAC @ 100% load
300 VAC ± 5 % or 150 VAC ± 5 %
300 VAC
290 VAC ± 5 % or 145 VAC ± 5 %
290 VAC
40 Hz ~ 70 Hz
46 ~ 54 Hz or 56 ~ 64 Hz
Single phase with ground
≥ 0.99 @ nominal voltage (100% load)
85%
88%
89%
83%
88%
12 V / 7 Ah
12 V / 7 Ah
12 V / 9 Ah
12 V / 7 Ah
12 V / 9 Ah
3
6
6
20
20
4 hours recover to 90% capacity
7 h / 90%
9 h / 90%
1.0 A
41.0 VDC ± 1%
82.1 VDC ±1%
273 VDC
273 VDC
UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions
Sixteen LEDs indicating UPS status, Load level, Battery level, overload,
fault, and programmable outlet information
Sounding every 4 seconds
Sounding every second
Sounding twice every second
Continuously sounding
397 X 145 X 220
13
421 X 190 X 318
26
592 X 250 X 576
28
81
83
20-90 % RH @ 0- 40°C (non-condensing)
< 45dB
< 55dB
< 58dB
Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix, and MAC
Power management from SNMP manager and web browser
No
YES
12 V / 9 Ah
12 V / 9 Ah
12 V / 9 Ah
12 V / 9 Ah
12 V / 9 Ah
6
12
12
40
40
No
Battery Type
Qty.
Charger
(100% Load)
12 V / 9 Ah
40
12 V / 9 Ah
40
YES
5 min
5 min
5 min
5 min
3 min
BACKUP TIME
If the UPS is installed or used in a place where the altitude is above than 1000m, the ouput power must be derated one percent per 100m
SP_PII_1000_10000_V003E_Mar15
Proton Motor Fuel Cell GmbH, SPower UPS/Battery Storage Systems, Office Schallershofer Str. 141, D-91056 Erlangen,
Tel. +49 89 127626577, www.spower.de - info@spower.de - Specifications are subject to change without notice
Download