SYLVANIA Emergency Lighting

advertisement
www.sylvania.com/sentrylight
SYLVANIA Emergency Lighting
Key Features & Benefits
•Provides illumination during a
power failure by detecting the AC
voltage loss
•Compact and concealed
– Virtually invisible until activated
– Vandal-resistant
•Meets most interior emergency
lighting codes
•Quick and easy recessed
installation for new construction
and retrofit applications
•Front cover plate is customizable
and can be painted or wall­
papered to blend with decor
Compact, concealed, aesthetically pleasing and vandal-resistant,
SYLVANIA emergency lighting equipment provides bright illumination
during any power failure situation. Upon activation, the internal
rechargeable battery automatically deploys the durable lamp
housing from behind the wall or ceiling and the dual xenon lamps
brightly illuminate a path to safety. These fixtures are virtually
invisible until activated and meet most interior emergency lighting
code requirements. Quick and easy to install in the wall or ceiling,
these reliable emergency lighting fixtures are perfect for retrofit and
new construction applications and have been listed by UL and CSA.
•Self-contained battery and
remote options
•Vandal-resistant and ADA
compliant enabling installation at
any height
•120 and 277 VAC input options
•Green LED push test switch
allows for maintenance and
battery checks
•Illumination duration of 120
minutes on battery power
•UL and CSA listed
Product Offering
Ordering Abbreviation
SC11/INTBAT/120277V/WHITE/BOX
SC36/INTBAT/120277V/WHITE/BOX
RM36/EXTBAT/12V/WHITE/BOX
Wattage
11
36
36
Input Voltage
120/277
120/277
12Vdc
Application Information
Applications
Application Notes
• Education
• Egress lighting
• Healthcare
• Hospitality
• Office
LED166R1
1/12
• Property management
• Residential
• Retail
1. Replace internal battery every three years or according to ambient temperature
guidelines provided by battery unit manufacturer (sold separately), to ensure
proper operation.
2. NOTE: Servicing of parts should be performed by qualified service personnel.
For replacement lamps or batteries, contact your local SYLVANIA representative.
3. This self-contained (SC) series Emergency Light is furnished with a sophisticated low voltage battery dropout circuit to protect the battery from over discharge
after the useful output has been reached. Allow 24 hour recharge time after
installation or power failure for full load testing.
Specification Data
Catalog #
Type
Project
Comments
Prepared by
Date
Ordering Information
Item Number
70661
70660
70662
Ordering
Abbreviation
SC11/INTBAT/120277V/WHITE/BOX
SC36/INTBAT/120277V/WHITE/BOX
RM36/EXTBAT/12V/WHITE/BOX
# of Lamps
2
2
2
Lamp
Wattage (W)
11
36
36
Input
Voltage
120/277VAC
120/277VAC
12VDC
Output
Voltage (VDC)
6
12
12
Rechargeable
Battery
Integrated
Integrated
Remote
Ordering Guide
SC
36
/
SC=Self contained battery
Wattage
RM= Unit with remote
battery backup unit
INTBAT
/
With INTernal or
EXternal battery
backup
120277V
/
WHITE
/
Dedicated Finish
Voltage:
12V, 120V or 277V
BOX
Packaging
configuration
Accessories
Item Number
70665
70666
70667
Ordering
Abbreviation
SM/SC36/WHITE/BOX
SM/SC11/WHITE/BOX
SM/RM36/WHITE/BOX
Description
Surface mount back box (see diagram below)
Surface mount back box (see diagram below)
Surface mount back box (see diagram below)
Construction
Steel-back box – powder coated
Steel-back box – powder coated
Steel-back box – powder coated
Color
White
White
White
Accessory Diagram
Front View
L1
Side View
Dimension Comparison Chart
8 5/8”
L3
[219mm]
8 5/8”
[219mm]
7”
[177.8mm]
3 1/4”
[82.5mm]
L2
L4
Dimensions: inches [mm]
L1
L2
L3
L4
SM-SC11 8.63"
9.94"
8.63"
3.25"
SM-SC36
8.63"
14.25"
8.63"
3.25"
SM-RM36
8.63"
7"
8.63"
3.25"
Mechanical Diagram
Front View
Dimension Comparison Chart
5-7/16
[138.1mm]
L1
L2
L3
L4
Push to test
SM-SC11 5.44"
9.94"1
2.75"
3.25"
SM-SC36
5.44"
4.25"
2.75"
3.25"
SM-RM36
5.44"
7.13"
2.75"
3.25"
14 -1/4
[362mm]
Top View
2 - 3/4
[70mm]
3 - 1/4
[82.6mm]
Dimensions: inches [mm]
Photometric Information
120
135
150
165
180
165
150
135
120
Zonal Lumen Summary
105
105
90
90
75
75
20
60
60
40
60
45
45
30
180 Deg. Plane
15
0
270 Deg. Plane
Note: Photometric information is for the SC36 fixture only.
15
0 Deg. Plane
30
90 Deg. Plane
Zone
0-30
0-40
0-60
0-90
90-120
90-130
90-150
90-180
0-180
Lumens
34
55
111
215
63
67
70
71
286
% Lamp
6.8
11.0
22.2
43.0
12.6
13.4
14.0
14.1
57.1
% Fixture
11.8
19.3
38.8
75.3
22.0
23.4
24.5
24.7
100.0
Application Notes
1. Servicing of parts should be performed by qualified service personnel. For replacement lamps or
batteries see fixture labels.
2. Emergency units can be painted or wallpapered.
3. To test existing unit when fully installed in wall or ceiling, depress and hold LED/AC test switch
located on: front cover panel (green LED light on the SC11 and SC36 models) and on the central
battery unit (RM36 model). Lamp housing will automatically extend outward and lamps will
illuminate. After test, release the LED/AC test switch to return housing to original position.
4. The emergency light is furnished with a sophisticated low voltage battery dropout circuit to
protect the battery from over discharge after the useful output has been reached. Allow 24 hour
recharge time after installation or power failure for full load testing.
Sample Specifications
SentryLight SC36
SentryLight SC11
12 Volt Battery, 36 Watt Xenon emergency light
6 Volt Battery, 11 Watt Xenon emergency light
Automatically powered ON/OFF by Precision Lens Drive
Size: 14.3"L x 3.3"W x 5.4"H
Use: Retrofit and New Construction
Battery: Maintenance-free 12 Volt sealed lead calcium
Battery Charger: Solid state trickle charger
Illumination Duration: 120 minutes
Approvals: UL-924, CSA, NYC, ADA-Compliant
Installation Height: UL-approved for any height
Weight: 10.6 lbs.
AC Voltage: 120 or 277 VAC input (field selectable)
Application: All spaces requiring emergency lighting
Illumination: Two bright 18 Watt Xenon lamps (36 Watt total)
Coverplate: Impact resistant polycarbonate
Color: White. Customizable with paint or wallpaper
Testing: Recessed AC on/push-to-test LED
Accessory: Surface Mount Back Box: SentryLight item SM-SC36
Warranty: 3 year limited warranty (battery excluded)
Automatically powered ON/OFF by Precision Lens Drive
Size: 9.8"L x 3.3"W x 5.4"H
Use: Light commercial/residential; Retrofit and New Construction
Battery: Maintenance-free 12 Volt sealed lead calcium
Battery Charger: Solid state trickle charger
Illumination Duration: 120 minutes
Approvals: UL-924, CSA, NYC, ADA-Compliant
Installation Height: UL-approved for any height
Weight: 5.5 lbs.
AC Voltage: 120 or 277 VAC (field selectable)
Application: All spaces where emergency lighting is desired
Illumination: Two 5.5 Watt Xenon lamps (11 Watt total)
Coverplate: Impact resistant polycarbonate
Color: White. Customizable with paint or wallpaper
Testing: Recessed AC on/push-to-test LED
Accessory: Surface Mount Back Box: SentryLight item SM-SC11
Warranty: 3 year limited warranty (battery excluded)
Powered by an internal 6V battery, two 5.5 Watt Xenon lamps
(11 Watts) are perfect for residences, inside hotel and dorm
rooms, and anywhere you need emergency lighting.
Powered by a remote battery unit, this remote head has two
18 Watt Xenon lamps (36 Watts).
Remote Head, 36 Watt Xenon emergency light
Automatically powered ON/OFF by Precision Lens Drive
Size: 7"L x 3.3"W x 5.4"H
Use: New Construction; Easily retrofit in false ceiling
Battery: Requires external 12 Volt battery (SentryLight RBU unit)
Battery Charger: None; must be incorporated in external unit
Illumination Duration: 120 minutes
Approvals: UL-924, CSA, NYC, ADA-Compliant
Installation Height: UL-approved for any height
Weight: 3.3 lbs
AC Voltage: N/A; attach to remote battery using low-voltage wiring
Application: All spaces requiring emergency lighting
Illumination: Two bright 18 Watt Xenon lamps (36 Watt total)
Coverplate: Impact resistant polycarbonate
Color: White. Customizable with paint or wallpaper
Testing: N/A; testing occurs at Central Battery Unit
Accessory: Surface Mount Back Box: SentryLight item SM-RM36
Accessory: Central Battery Unit: RBU-18A or RBU-36A
Warranty: 3 year limited warranty (battery excluded)
SYLVANIA is a registered trademark of OSRAM SYLVANIA Inc.
SEE THE WORLD IN A NEW LIGHT is a registered trademark of OSRAM SYLVANIA Inc.
All other trademarks are property of their respective owners.
Specifications subject to change without notice.
LED166R1
Trade
Phone:
Fax:
1-800-255-5042
1-800-255-5043
National Accounts
Phone:
1-800-562-4671
Fax:
1-800-562-4674
OEM/Special Markets
Phone:
1-800-762-7191
Fax:
1-800-762-7192
Display/Optic
Phone:
1-888-677-2627
Fax:
1-800-762-7192
SYLVANIA Lighting Services
Phone:
1-800-323-0572
Fax:
1-800-537-0784
Canada
OSRAM SYLVANIA LTD.
2001 Drew Road
Mississauga, ON L5S 1S4
Trade
Phone:
Fax:
1-800-263-2852
1-800-667-6772
OEM/Special Markets/Display/Optic
Phone:
1-800-265-2852
Fax:
1-800-667-6772
SYLVANIA Lighting Services
Phone:
1-800-663-4268
Fax:
1-866-239-1278
Mexico
OSRAM MEXICO
Headquarters
Tultitlan/Edo de Mexico
011-52-55-58-99-18-50
www.sylvania.com
1/12
SentryLight RM36
United States
OSRAM SYLVANIA
100 Endicott Street
Danvers, MA 01923
© 2012 OSRAM SYLVANIA
Powered by an internal 12V battery, two 18 Watt Xenon
lamps (36 Watts) provide bright illumination for the most
critical applications.
Download