G59/3 TYPE TEST VERIFICATION REPORT Type Tested reference number M250-60-230-S22 Generating Unit technology Photovoltaic Microinverter System supplier name Enphase Energy Inc. Address 1420 North McDowell Blvd. Petaluma, CA USA Tel +1-707-763-4784 Fax +1-707-763-0784 E:mail ptarver@enphaseenergy.com Web site http://www.enphase.com Maximum export capacity, use separate sheet if more than one connection option. 0.250 per PCU kW single phase, single, split or three phase system kW three phase kW two phases in three phase system kW two phases split phase system System supplier declaration. - I certify on behalf of the company named above as a supplier of a Generating Unit, that all products supplied by the company with the above Type Test reference number will be manufactured and tested to ensure that they perform as stated in this document, prior to shipment to site and that no site modifications are required to ensure that the product meets all the requirements of G59/3. Signed On behalf of Enphase Energy Inc. Peter L. Tarver enphase.com Doc # HPV-00150-1.0 G59/3 TYPE TEST VERIFICATION REPORT Power Quality - Harmonic Generation Generating Unit tested to BS EN 61000-3-12 Generating Unit rating per phase (rpp) Harmonic 7.0* At 45-55% of rated output Measured Value MV in Amps 100% of rated output Measured Value MV in Amps % kVA % Harmonic % =Measured Value (Amps) x 23/rating per phase (kVA) Limit in BS EN 61000-3-12 1 phase 3 phase 2 0.003 0.023 0.006 0.01 8% 8% 3 0.039 0.298 0.283 0.62 21.6% Not stated 4 0.006 0.046 0.003 0.01 4% 4% 5 0.009 0.069 0.19 0.42 10.7% 10.7% 6 0.006 0.046 0.002 0.00 2.67% 2.67% 7 0.04 0.306 0.26 0.57 7.2% 7.2% 8 0.02 0.153 0.006 0.01 2% 2% 9 0.027 0.207 0.231 0.51 3.8% Not stated 10 0.004 0.031 0.004 0.01 1.6% 1.6% 11 0.048 0.367 0.197 0.43 3.1% 3.1% 12 0.004 0.031 0.006 0.01 1.33% 1.33% 13 0.08 0.612 0.259 0.57 2% 2% THD 0.013 1.3 0.00095 0.095 23% 13% PWHD 0.034 3.4 0.02575 2.575 23% 22% * system size is scalable; this is the system size tested (28 PCUs) enphase.com Doc # HPV-00150-1.0 G59/3 TYPE TEST VERIFICATION REPORT Power Quality - Harmonic Generation Generating Unit tested to BS EN 61000-3-2 Generator Unit rating per phase (rpp) At 45-55% of rated output Harmonic Measured Value MV in Amps 3.5 kW 100% of rated output Measured Value MV in Amps Limit in BS EN 61000-3-2 in Amps 2 0.003 0.003 1.080 3 0.047 0.039 2.300 4 0.002 0.006 0.430 5 0.045 0.009 1.140 6 0.002 0.006 0.300 7 0.018 0.04 0.770 8 0.006 0.02 0.230 9 0.012 0.027 0.400 10 0.003 0.004 0.184 11 0.02 0.048 0.330 12 0.001 0.004 0.153 13 0.042 0.08 0.210 14 0.004 0.005 0.131 15 0.064 0.075 0.150 16 0.004 0.004 0.115 17 0.06 0.064 0.132 18 0.003 0.004 0.102 19 0.056 0.06 0.118 20 0.003 0.005 0.092 21 0.028 0.014 0.107 enphase.com Higher limit for odd harmonics 21 and above 0.160 Doc # HPV-00150-1.0 G59/3 TYPE TEST VERIFICATION REPORT Power Quality - Harmonic Generation Generating Unit tested to BS EN 61000-3-2 Generator Unit rating per phase (rpp) At 45-55% of rated output Harmonic Measured Value MV in Amps 3.5 kW 100% of rated output Measured Value MV in Amps Limit in BS EN 61000-3-2 in Amps 22 0.004 0.004 0.084 23 0.027 0.027 0.098 24 0.004 0.004 0.077 25 0.038 0.026 0.090 26 0.004 0.002 0.071 27 0.028 0.013 0.083 28 0.005 0.002 0.066 29 0.027 0.024 0.078 30 0.005 0.004 0.061 31 0.024 0.009 0.073 32 0.003 0.003 0.058 33 0.016 0.028 0.068 34 0.004 0.007 0.054 35 0.002 0.016 0.064 36 0.005 0.008 0.051 37 0.008 0.022 0.061 38 0.003 0.007 0.048 39 0.013 0.012 0.058 40 0.004 0.006 0.046 enphase.com Higher limit for odd harmonics 21 and above 0.147 0.135 0.124 0.117 0.109 0.102 0.096 0.091 0.087 Doc # HPV-00150-1.0 G59/3 TYPE TEST VERIFICATION REPORT Power Quality. Voltage fluctuations and Flicker Tested to BS EN 61000-3-11 Starting Stopping Running dmax dc d(t) dmax dc d(t) Pst Plt 2 hours Measured Values at test impedance 0% 0% 0% 0.62% 0% 0% 0.07 0.08 Normalised to standard impedance 0% 0% 0% 0.62% 0% 0% 0.07 0.08 Normalised to required maximum impedance 0% 0% 0% 0% 0% 0% 0.07 0.08 Limits set under BS EN 61000-3-11 4% 3.3% 3.3% 4% 3.3% 3.3% 1.0 0.65 Test Impedance R 0.4 Ω XL 0.25 Ω Standard Impedance R 0.24 * 0.4 ^ Ω XL 0.15 * 0.25 ^ Ω Maximum Impedance R 0.4 Ω XL 0.25 Ω Test start date 31JUL2014 Test end date Test location Enphase Energy Inc. 1400 North McDowell Blvd., Petaluma, CA enphase.com 31JUL2014 Doc # HPV-00150-1.0 G59/3 TYPE TEST VERIFICATION REPORT Power quality - DC injection. Test power level 10% 55% 100% Recorded value in Amps 0.0 A 0.0 A 0.0 A as % of rated AC current 0% 0% 0% 0.25% 0.25% 0.25% Limit Power Quality - Power factor Measured value Limit 216.2 V 230 V 253 V 0.99 0.99 0.99 >0.95 >0.95 >0.95 Measured at three voltage levels and at full output. Voltage to be maintained within ±1.5% of the stated level during the test. Protection - Frequency tests Setting “No-trip tests” Trip test Function Frequency Time delay Frequency Time delay O/F stage 1 51. 5 Hz 90 s 51.55 Hz O/F stage 2 52 Hz 0.5 s 51.95 Hz Frequency /time Confirm no trip 90.00 s 51.3 Hz 95 s Confirmed 0.74 s 51.8 Hz 89.98 s Confirmed 52.2 Hz 0.48 s Confirmed U/F stage 1 47.5 Hz 20 s 47.5 Hz 20.3 s 47.7 Hz 25 s Confirmed U/F stage 2 47 Hz 0.5 s 47.05 Hz 0.73 s 47.2 Hz 19.98 s Confirmed 46.8 Hz 0.48s Confirmed enphase.com Doc # HPV-00150-1.0 G59/3 TYPE TEST VERIFICATION REPORT Protection - Voltage tests Setting “No trip-tests” All phases at same voltage Trip test Function Voltage Time delay Voltage Time delay O/V stage 1 262.2 V 1.0 s 261.3 V O/V stage 2 273.7 V 0.5 s 273.8 V Voltage /time Confirm no trip 1.09 s 258.2 V 2.0 s Confirmed 0.79 s 269.7 V 0.98 s Confirmed 277.7 V 0.48 s Confirmed U/V stage 1 200.1 V 2.5 s 198.1 V 2.65 s 204.1 V 3.5 s Confirmed U/V stage 2 184 V 0.5 s 181.3 V 0.79 s 188 V 2.48 s Confirmed 180 V 0.48 s Confirmed enphase.com Doc # HPV-00150-1.0 G59/3 TYPE TEST VERIFICATION REPORT Protection - Loss of Mains test and single phase test To be carried out at three output power levels plus or minus 5%, an alternative for inverter connected Generating Units can be used instead. Test Power Balancing load on islanded network Trip time. Limit is 0.5 s 10% 55% 100% 10% 55% 100% 95% of 95% of 95% of 105% of 105% of 105% of Generating Unit output Generating Unit output Generating Unit output Generating Unit output Generating Unit output Generating Unit output 0.152 s 0.048 s 0.416 s 0.168 s 0.032 s 0.448 s Note as an alternative, inverters can be tested to BS EN 62116. The following sub set of tests should be recorded in the following table. Protection - Frequency change, Stability test Start Frequency Change End Frequency Confirm no trip Positive Vector Shift 49.5Hz +9 degrees Confirmed Negative Vector Shift 50.5Hz - 9 degrees Confirmed Positive Frequency drift 49.5Hz +0.19Hzs Negative Frequency drift 50.5Hz -0.19Hzs -1 51.5Hz Confirmed -1 47.5Hz Confirmed Protection - Re-connection timer Time delay setting (s) Measured delay (s) 20 s 24 s Confirmation that the Generating Unit does not re-connect Checks on no reconnection when voltage or frequency is brought to just outside stage 1 limits of table 10.5.7.1. At 266.2 V At 196.1 V At 47.4 Hz At 51.6 Hz Confirmed Confirmed Confirmed Confirmed enphase.com Doc # HPV-00150-1.0 G59/3 TYPE TEST VERIFICATION REPORT Fault level contribution. For machines with electro-magnetic output Parameter For Inverter output Time after fault Symbol Value Peak Short Circuit current ip 15 20 ms Initial Value of aperiodic current A 15 100 ms Initial symmetrical short-circuit current* Ik 17.9 250 ms Decaying (aperiodic) component of short circuit current* iDC 0 500 ms Reactance/Resistance Ratio of source* X /R 2.5 Time to trip Volts Amps 0 0 0 0 0 0 0 0 0.014 In seconds Yes/NA Self Monitoring solid state switching It has been verified that in the event of the solid state switching device failing to disconnect the Generating Unit, the voltage on the output side of the switching device is reduced to a value below 50 Volts within 0.5 seconds NA Additional comments enphase.com Doc # HPV-00150-1.0