ACA-10N - PW Maines

advertisement
ACA-10N
02/Eng/01-2012
Instruction manual
1. General
The ACA-10N is an alarm device with 10 alarm inputs, allowing
connection of signallers like a horn, a flashing light, HBA (Interior
Alarm) and a telephone selector contact. Setting an alarm delay
and suppression time is possible as well as continuous monitoring
of charge and discharge current. Every 24 hours the battery
capacity is checked and an alarm is released at capacity drop
below a set value.
• Optional: ACA-OM8 module for 8 outputs.
These outputs can be used as additional telephone selector
contacts.
2. Mounting
The ACA-10N is mounted by 4 screws. Ensure that no moisture can penetrate through the screws.
The cabling must be entered through the couplings and should be kitted properly.
3. Technical specifications
Electrical
Power supply (F1)
Power consumption
Ambient temperature
Alarm input
Telephone selector contact
Flashing light (F2)
Horn (F3)
HBA
:
:
:
:
:
:
:
:
Battery
Deviation battery test timer
Battery voltage indication
:
:
:
Battery current indication
:
Option ACA-OM8
8x Telephone selector contact
:
dead contact breaker, 24 Vac/dc 0,5 A max.
via ACA10N_REL pcb
Mechanical
Dimensions
Encasing
Weight
Noise production
:
:
:
:
243 x 192 x 117 mm
IP 54
about 3 kg
< 70 dB(A)
02/Eng/01-2012/HA90110202
230 Vac ±10%, 50/60 Hz (T 0,5 A)
40 VA
-10 °C ... +40 °C
24 Vdc / 14 mA circuit breaker, R max. 100 Ω
dead contact breaker, 24 Vac/dc 0,5 A max.
Voltage 12 Vdc (T 1,6 A)
Voltage 12 Vdc (T 1,6 A)
Voltage 12 Vdc
Current 60 mA max.
12 Vdc / 2 Ah
25 ppm
U > 11,5 V ; green
U < 11,5 V ; yellow
U < 10,5 V ; red
I > 1 mA ; green
I < 1 mA ; yellow
I < -1 mA ; red
1
Initial operation - Instruction manual ACA-10N
4. Initial operation
Before starting up the ACA-10N, the positive
connector of the battery should be placed
(See 8. Wiring diagram).
The jumper on the bottom PCB makes it
possible to set the alarm at alternately horn
and flashing light (position
) or at
).
continuous horn alarm (position
Also the alarm delay and the alarm
suppression must be set by the two setting
potentiometers on the cover PCB (see figure).
The alarm delay can be set from 0-120 seconds. The alarm suppression can be set from 0-30
minutes. 24 hours after initial operation of the ACA-10N the battery will be subjected to a test. In
order to change the moment of the battery check you will have to start up the battery test by
pressing the
key for 3 seconds just at the moment the test ought to start.
The cover of the ACA-10N contains a form for completion (see figure).
The form can be used to enter one’s own alarm input designations. All
the possible signalisations of the pilot lamps also are indicated near
ON
1
OFF
6
ON
OFF
ALARM
2
7
ON
OFF
NO ALARM
ON
the buttons
.
3
OFF
ALARM OFF
8
ON
OFF
4
9
ON
OFF
ON
5. Operation
Symbol
5
10
OFF
Explanation
HORN OFF: The key switch allows you to switch off the horn or flashing light for
good. The HBA and the telephone selector contact remain being activated.
ALARM SUPPRESSION: an alarm can be suppressed by pressing this key for a
while. Suppressed are: horn, flashing light, HBA and telephone selector contact. The
suppression time can be set from 0-30 minutes.
ALARM TEST: This key can be used to activate alarm signallers such as horn,
flashing light, HBA and telephone selector contact. Pressing this key the alarm test is
switched on. Pressing the key once more the alarm test is switched off. It is
impossible, however, to switch off the alarm in this way.
BATTERY TEST: Use this button to test the battery (test takes about 1.5 minutes).
To stop the battery test the button must be pressed a second time. Should the test
result of the battery be that its condition is below standard, an alarm signal is
activated immediately afterwards. The alarm can be removed by pressing the battery
test button again. Holding the button down for 3 seconds also resets the 24-hour
timer to 0 and ensures the battery to be tested automatically again after 24 hours. So
it is important to execute the test at the right time.
SWITCHING ON and OFF: Inputs are disconnected by turning a key and holding
down the alarm suppression button at the same time. The input is then disconnected.
The alarm remains switched off, when turning the key back after that.
The inputs are disconnected in the same way as they are connected or by holding
down the alarm suppression button for a period of 3 seconds.
2
02/Eng/01-2012
Alarm signalling - Instruction manual ACA-10N
6. Alarm signalling
Symbol
Explanation
ALARM!!!!: A continuously burning pilot lamp
indicates an alarm situation (its alarm input is
interrupted).
ALARM
ON
NO ALARM: A pilot lamp that does not burn
indicates that there is no alarm (the alarm input has
OFF
not been interrupted).
NO ALARM
ON
DISCONNECTION OF ALARM: An LED blinking in
indicates that the alarm is
longer intervals
OFF
switched
off.
The
disconnected
output cannot cause
ALARM OFF
alarm anymore.
ALARM SWITCHED OFF + ALARM INPUT
ON
INTERRUPTED: When the pilot lamp blinks twice in
OFF
long intervals
, the alarm is switched off
and its input is interrupted. A disconnected alarm
input does not release any alarm.
SUPPRESSION OF ALARM: An LED blinking in
ON
short intervals
indicates that the alarm is
OFF
suppressed allowing one to rectify the disturbance. If
the cause of the alarm is not solved within the time
setting, the alarm will be activated again.
ALARM PASSED: When the pilot lamp burns for a
ON
longer period alternated by short blinks
,
OFF
the alarm input was interrupted before. The time of
interruption must at least have been as long as the
‘alarm delay time’.
HORN OFF: A flashing LED indicates that the horn and flashing light
signallers are switched off by the key switch. The HBA and the
telephone selector contact remain being activated.
ALARM or ALARM TEST: A flashing LED indicates activation of the
alarm test and enables you to check the signallers. A continuous lighting
up of the LED indicates that the alarm input is interrupted and releases
an alarm. (at once or after an alarm delay time).
BATTERY PICTURE:
• In normal operation the charging current is indicated. There are three
stages, viz. discharging (red), condition of rest (yellow) and charging
(green).
• During the battery test one of the three LED’s blinks. At the same
time the battery voltage is measured indicating three stages:
insufficient (red), poor (yellow) and good (green). The battery test
lasts 1.5 minutes. In case the battery voltage is below average at the
time of testing, an alarm will be released (all LED battery indications
start blinking).
ON
ON
OFF
OFF
02/Eng/01-2012
3
Functioning - Instruction manual ACA-10N
7. Functioning
Normal operation does not release an alarm. The signallers can be tested by pressing
.
Pressing the key once more stops the testing procedure.
The battery can be tested by pressing
. Holding it down for 3 seconds sets the 24-hour-timer
at 0 and ensures an automatic battery test after 24 hours. All alarm situations offer the possibility
to switch off horn and flashing light permanently by means of the key switch.
The ACA-10N signals alarm at:
+
+
+
One or more alarm inputs are interrupted.
•
Interrupted alarm input:
at insufficient battery voltage when testing the battery.
at lack of power.
Made visible by continuous lighting up of the
LED. From that moment onwards the alarm
delay time is also started. After elapse of the delay time the signallers are activated. Switching off
the signallers immediately interrupts the alarm for a while, which makes it possible to repair the
technical failure. When an alarm signalisation at the alarm input disappears after a while, the pilot
lamp will start burning in long intervals and short blinks indicating that not long ago there was an
alarm. The message can be undone by pressing its button.
During an alarm the battery cannot be tested. The signallers are supplied by the main power,
which avoids discharge of battery.
•
Battery alarm:
Made visible by the three blinking LED’s of the battery indication
passed on without delay. To remove the alarm the
. A battery alarm will be
key should be pressed (the 24-hour-timer
will continue operating without being modified). A poor battery capacity releases an alarm at a next
battery test.
• No main supply:
The lack of main voltage is indicated by a combined red LED (discharging) of the battery indicator
, an active ALARM LED
and suppressed ALARM buttons
that light up
continuously.
The ACA-10N and the signallers are supplied by the battery power. The battery power will last for
at least 1 hours (battery empty). After restoring the main power, it will take about 12 hours to
recharge the battery. An empty battery resets the 24-hour-timer.
Attention: in case all alarm inputs are suppressed / disconnected, there will be no main voltage
alarm.
4
02/Eng/01-2012
Wiring diagram - Instruction manual ACA-10N
8. Wiring diagram
- battery connection (black)
+ battery connection (red)
ATTENTION:
Connect
battery
Power supply
Option pcb ACA10N_REL
5* 6 * 7 * 8 *
F3
1 2 3
PHASE
EARTH
9 10
NEUTR.
7 8
LAMP_+
D
HORN_+
3 4 5 6
HBA_-
TELF
TELF
INPUT 10
INPUT 9
1 2
INPUT 8
9 10
INPUT 8
7 8
INPUT 7
3 4 5 6
INPUT 6
1 2
INPUT 5
9 10
INPUT 4
7 8
INPUT 3
5 6
INPUT 2
3 4
INPUT 1
1 2
INPUT 10
C
INPUT 9
B
LAMP_-
F
7 8
INPUT 7
5 6
INPUT 6
3 4
INPUT 5
1 2
INPUT 4
7 8
INPUT 3
5 6
INPUT 2
3 4
INPUT 1
1 2
HBA_+
E
A
F1
F2
HORN_-
1* 2 * 3 * 4 *
N
L1
12V
Power supply
230 Vac
50/60Hz
Flashing light
12V
Alarm-input
1
2
3
4
5
6
7
8
9
10
Telselector
12V
Horn
Attention: For the ACA10N_REL option PCB applies the following:
Alarm input 1 to 7 activates
output 1* to 7*
Alarm input 8 to 10 activates
output 8*
Symbol
02/Eng/01-2012
Explanation
HORN / FLASHING LIGHT: This jumper makes it possible to change the
alarm setting from horn and flashing light (position
) to permanently
horn (position
).
5
Download