CH90 Series Multi-candela Chime Strobes

advertisement
Fire Alarm Systems | CH90 Series Multi-candela Chime Strobes
CH90 Series Multi-candela Chime Strobes
▶ Low current draw with temperature compensation to
reduce power consumption and wiring costs
▶ 24 VDC, filtered or FWR
▶ Adjustable volume and tone
▶ Single‑stroke or vibrating tone
▶ Selectable strobe intensities of 15 cd, 30 cd, 75 cd,
or 95 cd
▶ Strobes flash once per second over the regulated
voltage range
These Wheelock CH90 Multi-candela, Ceiling-mount
Chime Strobes provide low current draw, choice of
single-strike or vibrating operation, adjustable sound
level, chime tone adjustable from 800 Hz to 1200 Hz, and
choice of four light output intensities (15 cd, 30 cd,
75 cd, or 95 cd) in one unit. The strobes can be
synchronized using SM (single) or DSM (dual) modules.
They also have an attached mounting plate for easy
indoor installation on a variety of electrical boxes.
Functions
Strobe Settings
The unit comes set at 15 cd. Change the setting using a
screwdriver in the slot in the unit's base (setting is
visible on indicator plate within the lens).
Volume and Tone Settings
The volume and tone controls are factory set to ensure
maximum dBA output; however, the volume and tone
can be tuned to suit a particular application. Take
appropriate measurements to ensure the volume meets
the listing requirements for private mode fire protective
service per UL464.
Sound Mode Settings
The chimes are factory set in single-stroke mode. They
can be changed to vibrating mode before wiring by
moving a jumper.
Single-Stroke Mode
The minimum input pulse duration must be at least
160 ms on and 160 ms off. The chime only operates once
each time it is pulsed. Use this mode for coded systems.
Vibrating Mode
Apply continuous input voltage to the chime to activate
the chime at 1 sec intervals.
Certifications and Approvals
Wheelock, Inc. holds these Listings and Approvals:
Listings and
Approvals
UL UCST: Audible Signal Appliances, General Signal
(UL464)
UL ULSZ: Audible Signal Appliances (UL464)
UL UUKC: Signaling Appliances and Equipment for the Hearing Impaired (UL1971)
CSFM 7125-0785: 151
NYC/MEA (151‑92‑E, Vol. 40; 151‑93‑e, Vol. 40)
Complies with:
Americans with Disabilities Act (ADA)
American National Standards Institute (ANSI), International
Standards Organization (ISO), and National Fire Protection
Association (NFPA) temporal pattern
www.boschsecurity.com
2 | CH90 Series Multi-candela Chime Strobes
Federal Communications Commission (FCC Part 15, Class B
RFI limits)
Technical Specifications
Occupational Safety and Health Administration
(OSHA 29 Part 1910.165
Environmental Considerations
Installation/Configuration Notes
Relative Humidity:
Up to 85%, non‑condensing
Temperature (Operating):
+32°F to +120°F (0°C to +49°C)
Chime Ratings at 24 VDC
Compatible Products
The following products are compatible with the CH90
Series Chime Strobes:
Reverberant dBA at 10 ft (3 m) per
UL464:
Maximum: 58 dBA
Minimum: 52 dBA
Mechanical Properties
Category
Product ID
Product Description
D70221
Conventional FACP
Dimensions
(diameter x D):
7.25 in. x 2.9375 in. (18.4 cm x 7.5 cm)
Control
Panels
D70242
Addressable FACP
Material:
D7024
Conventional FACP
Molded plastic enclosure with Xenon flashtube and Lexan®
lens
D80241
Analog FACP
Power Requirements
D91241
Addressable FACP
D10024A1
Analog FACP
Chime Current (maximum):
22 mA
SM-12/24-R
Synchronization module (red)
Voltage (input)
24 VDC nominal, filtered or FWR
DSM-12/24-R
Dual synchronization module (red)
Modules
For synchronization, use the SM or DSM modules with
these control panels. The synchronization module must
be set for 24 V operation. When used, the D7022 must
be set for 24 VDC operation.
2
When used with a D7039 Multiplex Expansion Module,
the D7024 becomes an addressable fire alarm control
panel (FACP).
Strobe Current (maximum):
15 cd:
VDC: 65 mA
FWR: 110 mA
30 cd:
VDC: 105 mA
FWR: 170 mA
75 cd:
VDC: 189 mA
FWR: 280 mA
95 cd:
VDC: 249 mA
FWR: 375 mA
1
Trademarks
Mounting Considerations
Mount these chime strobes on the indicated back boxes
for the indicated applications:
Conduit
Applications
Surface
Mounted
Four-inch square*
SBB Back Box
Flush Mounted
•
•
* Requires a four-inch square back box that is 2.125 in
(5.4 cm) deep with a 1.5 in. (3.8 cm) deep extension
ring.
Lexan® is a registered trademark of General Electric Corporation, USA, in the
United States and other countries.
Ordering Information
CH90-24MCC-FR Multi-Candela Chime Strobe (red) CH90-24MCC-FR
CH90-24MCC-FW Multi-Candela Chime Strobe
(white)
CH90-24MCC-FW
Hardware Accessories
ISP2-R Surface Adapter (red)
ISP2-R
ISP2-W Surface Adapter (white)
ISP2-W
Wiring
RP-R Retrofit Plate (red)
RP-R
The input terminals accept wires with diameters
between 18 AWG (1.2 mm) and 12 AWG (2.3 mm).
SBB-R Surface-mount Back Box (red)
SBB-R
SBB-W Surface-mount Back Box (white)
SBB-W
SBL2-R Retrofit Device Back Box (red)
SBL2-R
SER-R Square Semi-flush Extension Ring (red)
SER-R
SER-W Square Semi-flush Extension Ring (white)
SER-W
Parts Included
Quant.
Component
SFP-R Semi-flush Plate (red)
SFP-R
1
Chime Strobe
SSB-4 Ceiling Support Bridge
SSB-4
1
Hardware pack
1
Literature pack
CH90 Series Multi-candela Chime Strobes | 3
Americas:
Bosch Security Systems
130 Perinton Parkway
Fairport, New York, 14450, USA
Phone: +1 585 223 4060
Fax: +1 800 289 0096
security.sales@us.bosch.com
www.boschsecurity.us
Europe, Middle East, Africa:
Bosch Security Systems B.V.
P.O. Box 80002
5600 JB Eindhoven, The Netherlands
Phone: +31 40 27 83955
Fax: +31 40 27 86668
emea.securitysystems@bosch.com
www.boschsecurity.com
© Bosch Security Systems 2006 | Data subject to change without notice
F1584560779 | Cur: en-US, V2, 9 Feb 2006
Asia-Pacific:
Bosch Security Systems Pte Ltd
38C Jalan Pemimpin
Singapore 577180
Phone: +65 6319 3450
Fax: +65 6319 3499
apr.securitysystems@bosch.com
www.boschsecurity.com
Represented by