Installation and Operation Manual For Models: IH and WC Series Industrial Dehumidifiers PD and PDW Series Residential Dehumidifiers RC Series Remote Condensers CAUTION CAUTION - ONLY TRAINED, QUALIFIED PERSONNEL SHOULD INSTALL AND/OR SERVICE DESERT AIRE EQUIPMENT. SERIOUS INJURY, DEATH AND PROPERTY DAMAGE CAN RESULT FROM IMPROPER INSTALLATION/SERVICE OF THIS EQUIPMENT. HIGH VOLTAGE ELECTRICAL COMPONENTS AND REFRIGERANT UNDER PRESSURE ARE PRESENT. LIMITED WARRANTY. The goods manufactured by seller are warranted to be free from all latent defects in material and workmanship which may be disclosed under normal use and service within two years from date of shipment. In order for warranty to be valid, a START-UP REPORT must be completed and returned to the factory. If the report is not sent back, warranty will be voided on the equipment. If it is found that the goods contained defects at the time such goods were furnished by the seller, seller will either repair or replace the defective part or parts at sellers option. This warranty to repair or replace is the exclusive remedy and is expressly limited to the materials furnished by the seller. All replacements or repairs shall be F.O.B. Milwaukee, WI. The seller shall not be liable for labor cost incurred in diagnosing the problem, in removal or replacement of the part or parts so repaired or replaced. Accordingly, seller shall not be liable for any consequential damages, whether to person or property, caused by defects in goods. This warranty does not apply to any goods which may have been repaired or altered in any way outside of our factory, so as to affect its stability in our judgment, nor does this warranty apply to any goods which have been subjected to misuse, negligence or accident. This warranty is in lieu of all other warranties, expressed or implied, including any implied warranty of merchantability, and extends only to the original purchaser. Additional copies of this manual can be purchased for $5. Contact Desert Aire by mail or phone to order: Desert Aire Corp. c/o Service Department 8300 West Sleske Court Milwaukee, WI 53223 ph: 414-357-7400 fax: 414-357-8501 TABLE OF CONTENTS Installation ..........................................................................................5 1. 1.1. Unpacking and Inspecting ........................................................................................ 5 1.2. Location of Dehumidifier........................................................................................... 5 1.3. High Voltage Electrical Connections......................................................................... 6 1.4. 1.3.1 Wire and Fuse Sizing ...................................................................................... 6 1.3.2 High Voltage Connections ............................................................................... 7 Controls Wiring and Set-up ...................................................................................... 7 1.4.1 CA2300 Controller Package ............................................................................ 7 1.4.2 Johnson Controls UNT Controller Package................................................... 8 1.4.3 Honeywell 1.4.4 Johnson Controls Aquastat........................................................................... 9 1.4.5 Nonstandard Control Package ........................................................................ 9 ® ® Snap Action Humidistat and Thermostat Controller Packages ... 8 ® 1.5. Condensate Drain..................................................................................................... 9 1.6. Duct Installation...................................................................................................... 10 1.7. Outside Air Applications ......................................................................................... 13 1.8. 1.9. 2. 1.7.1 Outdoor Air Option Equipped Units ............................................................... 13 1.7.2 Standard Systems in Conjunction with Outside Air........................................ 15 Water Heating Applications (PDW and WC Models Only) ...................................... 16 1.8.1 Water Piping Connections ............................................................................. 16 1.8.2 Low Water Flow Protection............................................................................ 18 Remote Condenser Installation .............................................................................. 18 1.9.1 Refrigerant Piping of Remote Condensers .................................................... 19 1.9.2 Evacuation and Charging of Remote Condensers ........................................ 20 Start-up Procedures ........................................................................21 2.1. Prior to Start-up ...................................................................................................... 21 2.2. Start-up Procedure ................................................................................................. 22 2.3. System Operation Modes ....................................................................................... 22 2.3.1 Dehumidification / Air Reheat ........................................................................ 23 2.3.2 Dehumidification / Air Cooling ....................................................................... 23 2.3.3 Dehumidification / Water Heating (PDW and WC Models Only)................... 23 2.3.4 Blower Operation........................................................................................... 24 2.3.5 Air Heat (Optional)......................................................................................... 24 2.3.6 Outside Air (Outside Air Equipped Models Only)........................................... 24 3. Service and Maintenance................................................................ 25 3.1. Routine Maintenance..............................................................................................25 3.1.1 Service Every Month .....................................................................................25 3.1.2 Service Every Six Months..............................................................................25 3.1.3 Pool Water Chemistry....................................................................................26 3.2. 4. Compressor Failure ................................................................................................26 3.2.1 Mild Burnouts ................................................................................................26 3.2.2 Severe Burnouts............................................................................................27 Appendix .......................................................................................... 29 4.1. System Rating Plate ...............................................................................................29 4.2. Model Numbering Matrix.........................................................................................30 4.2.1 System Serial Number Code .........................................................................30 4.2.2 Dehumidifier Model Number ..........................................................................31 4.2.3 Remote Condenser Model Number ...............................................................32 4.3. Troubleshooting......................................................................................................33 4.3.1 Supply Blower Will Not Run...........................................................................33 4.3.2 Compressor Will Not Run ..............................................................................33 4.3.3 Evaporator Coil Ices Up (Suction Pressure Below 58 psig) ...........................34 4.3.4 Head Pressure is Too High (Above 270 psig)................................................35 4.3.5 Unit Runs But Walls and Windows Drip.........................................................36 4.3.6 Pool Water Heating Problems (WC and PDW Models Only) .........................36 4.4. System Start Up Report..........................................................................................37 4.5. System Guidelines - Unit Air Flow ..........................................................................39 4.5.1 Determining System Air Flow ........................................................................39 4.5.2 Blower Adjustment Procedure .......................................................................39 4.6. System Guidelines - Unit Operation........................................................................40 4.6.1 Controller Set Points......................................................................................40 4.6.2 Refrigeration System Pressures ....................................................................41 4.6.3 Temperature Rise or Drop Across Unit..........................................................41 4.7. Outside Air Supplemental Information ....................................................................42 4.7.1 PDW and PD Operation Mode .....................................................................42 4.7.2 IH and WC Operation Modes ........................................................................42 4.8. SMACNA Duct Designs ..........................................................................................43 4.9. Determining if Outside Air Pre-Heating is Required................................................44 4.10. Approximating Outside Air Volume .......................................................................45 4.11. Start-up Supervision Supplemental Information (Optional)...................................46 1. Installation 1.1. Unpacking and Inspecting Desert Aire inspects and tests each dehumidifier before it leaves the factory so that you receive a quality piece of equipment. However, the dehumidifier may have been damaged in transit. Check the equipment thoroughly for both visible and concealed damage before you sign the receiving papers. Document any damage in writing on the carrier’s bill of lading to ensure that damage claims are handled promptly. If the unit has been damaged, obtain a claim form from the carrier. Promptly fill out and return the form, and notify Desert Aire of any damage. DAMAGE CLAIMS OR SHORTAGES MUST NORMALLY BE FILED WITH THE FREIGHT CARRIER WITHIN 5 WORKING DAYS AFTER YOU RECEIVE THE EQUIPMENT. 1.2. Location of Dehumidifier Allow a minimum of 36 inches of clearance around all sides of the dehumidifier for piping, duct connections, and service access. Install the unit on a sturdy, level mounting base or a platform that will prevent vibration and sound transmission. Never install the dehumidifier on a wooden platform. Do not install the unit near occupied rooms such as bedrooms. Never suspend the unit above a swimming pool or a spa. Do not attempt to conserve installation space by fabricating restrictive ductwork with abrupt bends. You may reduce the operating efficiency and the moisture removal capacity of the dehumidifier. See Section 1.6 for detailed duct installation instructions. Figure 1. IH/WC/PD/PDW Installation & Operation Manual Typical Floor Installation 5 Figure 2. Typical Suspended Installation YOU MUST NOT INSTALL A STANDARD DEHUMIDIFIER IN AN UNCONDITIONED SPACE OR WHERE AMBIENT TEMPERATURES CAN FALL BELOW 45°F. If you must install the dehumidifier outside or in an unconditioned space, such as an attic, you must use an outdoor-rated dehumidifier. Desert Aire equips outdoor-rated dehumidifiers with weatherproofing and thicker insulation. You can determine whether your dehumidifier is outdoor-rated by inspecting the unit rating plate (see Section 4.1 for details). 1.3. High Voltage Electrical Connections THE INSTALLING CONTRACTOR MUST VERIFY THAT ALL THE ELECTRICAL WIRING TO THE DEHUMIDIFIER AND ITS ACCESSORIES COMPLIES WITH NATIONAL, STATE AND LOCAL CODES. 1.3.1 Wire and Fuse Sizing The field-installed power supply wires and overcurrent devices must be sized to handle the minimum ampacity of the dehumidifier without exceeding the maximum fuse size rating. Both the minimum ampacity and the maximum fuse size are printed on the unit rating plate. FAILURE TO PROPERLY WIRE THE DEHUMIDIFIER WILL CREATE THE POSSIBILITY OF SHOCK AND MAY LEAD TO PREMATURE SYSTEM FAILURE. 6 Desert Aire 1.3.2 High Voltage Connections On single phase units the power supply must have 3 connections (2 power, 1 ground). On three phase units the power supply must have 4 connections (3 power, 1 ground). Connect the power supply wires to the main power block located in the upper section of the electrical compartment. Figure 3. Single-Phase and Three-Phase System Power Connection. 1.4. Controls Wiring and Set-up The optional controls provided with your system are delicate instruments. You must handle them carefully. Installation requirements depend on your controller package. 1.4.1 CA2300 Controller Package The CA2300 controller is a digital controller used with Desert Aire Dehumidifiers. It includes pool water (if applicable) and air sensors which have been factory wired and mounted inside the unit. No sensor field wiring is required and the controller need not be mounted in the conditioned environment. Mount the controller in a convenient place and run the provided ribbon cable back to the unit’s electrical box. NOTE: Do not run the ribbon cable adjacent to or in the same conduit as wires higher than 30 volts. Refer to the CA2300 instruction manual for complete documentation. The CA2300 controller is designed to work with a variety of Desert Aire systems. As part of the installation you must perform a setup procedure so that the controller knows which type of system it is controlling. The INSTALL “AIR HEAT” OR “WATER SENSOR” section of controller manual will show you how to do this. Which steps you install depends upon which system you have: • IH and PD Models: If your application includes the installation of an air heater you can control it with the CA2300 by installing AIR HEAT. Utilize dry contacts H1 and H2 located on the system’s terminal strip for this purpose. IH/WC/PD/PDW Installation & Operation Manual 7 • WC and PDW Models; For these units you must install WATER SENSOR. Once again, install AIR HEAT if your application includes an air heater. See Section 4.6.1 for recommended set points. NOTE: The CA2300 series controller is capable of controlling a field-supplied auxiliary water heater. Utilize dry contacts W1 and W2 located on the system’s terminal strip for this purpose. 1.4.2 ® Johnson Controls UNT Controller Package The Johnson Controls UNT controller is a more powerful digital controller used with Desert Aire dehumidifiers. For maximum flexibility, the air temperature and humidity sensor and the digital display are shipped loose for field-installation. This controller is capable of energizing auxiliary air and water heaters, as well as outdoor intake dampers, depending on the model and options of your dehumidifier. The blowers in dehumidifiers with a UNT controller can operate either continuously or intermittently. With intermittent blower operation, the blower will run only when there is a demand for air heating, air cooling, or dehumidification. You can select the blower operating mode by adding or removing a wire jumper from the terminal strip on the electrical panel of the dehumidifier. Refer to the separate UNT instruction manual for detailed instructions on installing the sensors, using the controller, and choosing the ideal blower mode for your application. 1.4.3 ® Honeywell Snap Action Humidistat and Thermostat Controller Packages These controllers have the sensors built-in. You must mount the controllers in the conditioned environment approximately 5 feet above ground level. Avoid locations where sensor readings may be influenced by sunlight, air vents, stagnant areas, etc. Run standard thermostat wire back to the terminal strip located inside the unit’s electrical box. Refer to your unit’s low voltage diagram located on the inside of the electrical box door for necessary terminal connection points. If you choose to control an air heater with the thermostat, use the isolated contacts provided on the dehumidifier’s terminal strip. Do not connect the heater directly to the thermostat unless you are certain that the heater is equipped with an isolation relay. NOTE: Leave the thermostat set in the ‘AUTO’ position. This will allow automatic cycling of the unit between cooling and heating modes. If you leave the thermostat set to ‘HEAT,’ the air cooling mode will be locked out and vice versa. 8 Desert Aire NOTE: If you control your system with a humidistat only, you will have to add a wire jumper to the unit’s terminal strip. Refer to the electrical diagram for details. 1.4.4 ® Johnson Controls Aquastat If you application includes water heating with snap action controls provided by Desert Aire, the field installation of an aquastat is required. Mount the sensor on the water circuit in an area where continuous water flow will be experienced before any heater. Mount the thermostat in a convenient place assuring that the sensor capillary tube remains protected by wrapping excess length. Run standard thermostat wire back to the terminal strip located inside the unit’s electrical box. Refer to your unit’s low voltage diagram located on the inside of the electrical box door for necessary terminal connection points. The controller is equipped with an isolated contact closure for second stage water heat. Control auxiliary water heaters by connecting them directly to the second stage contacts on the aquastat. NOTE: An aquastat is not used in cooling tower applications where water heating occurs on call for air cooling. 1.4.5 Nonstandard Control Package If your application does not utilize the standard controller, refer to the documentation which accompanied your control package. The low voltage wiring diagram located on the inside of the electrical box door shows how to connect sensors and auxiliary heaters to your non-standard controller. NOTE: If you use a non-standard controller to energize an auxiliary heater, you may need to install one or more isolation relays between the heater and the controller. FAILURE TO ISOLATE ELECTRICAL CIRCUITS CAN RESULT IN DAMAGE TO THE DEHUMIDIFIER AND THE ACCESSORY DEVICE. 1.5. Condensate Drain You must raise the dehumidifier at least 12 inches above the floor to provide clearance for the condensate drain connection. You must supply and install a p-trap on the 1” MPT drain line. Pitch the condensate drain line a minimum of 1/4” per linear foot, and support the pipe with code-approved hangers at least every 5 feet. If the drain runs through an unconditioned space, you must install heat tracing to prevent the moisture in the drain from freezing. When gravity disposal is not possible, you may use a condensate pump. Follow the pump manufacturer’s installation instructions. IH/WC/PD/PDW Installation & Operation Manual 9 NOTE: While its supply blower runs, the inside of the dehumidifier operates at a negative pressure. If you do not trap the drain, condensate will be drawn into the cabinet of the dehumidifier, which may lead to premature corrosion and property damage. Figure 4. Condensate Piping 1.6. Duct Installation Duct design and installations should conform to the latest ASHRAE and SMACNA low velocity duct standards (see Section 4.8 for details). Undersized, restrictive ductwork with abrupt turns or transitions can decrease the efficiency and the moisture removal capacity of your dehumidifier. Size the ductwork for an acceptable air pressure drop at the air flow volume of your dehumidifier. Model Size Air Flow Rate (CFM) 0100/0125 0200 0300 0400 0500 0750 / 0800 0950 / 1000 1200 1500 540 950 1400 1900 2300 3500 4100 5500 6900 External Static Pressure (Resistance of Ductwork and Grilles) 0.5” Water Column (WC) 0.5” WC 0.5” WC 0.5” WC 0.5” WC 0.5” WC 0.5” WC 0.5” WC 0.5” WC Table 1. Standard Unit Air Flow Specifications. Use neoprene flex connectors when you attach ductwork to the dehumidifier to prevent excess vibration noise. Duct the supply air from the dehumidifier to all exterior walls and glass surfaces. Pay particular attention to skylights to avoid air 10 Desert Aire stagnation and condensation on their surfaces. NOTE: Never direct air toward the surface of a pool or spa. Do not install ceiling fans over the water surface. Air movement above a pool can significantly increase its evaporation rate. Figure 5. Basic Pool Room Layout. Install the return air grilles or openings as high as possible in the room. In most cases one centrally-located return air grille will be adequate. To prevent air shortcycling, do not install the return air grille too close to a supply grille. Grille sizing is also important. Select the grilles, registers and diffusers on the basis of low static pressure loss, required throw distance, and the specified CFM rating. You can find this information in most grille manufacturer’s catalogs. If you are installing the grilles in a corrosive environment, such as an indoor swimming pool, choose components made from anodized aluminum. IH/WC/PD/PDW Installation & Operation Manual 11 Figure 6. Soffit Duct Layout. Due to the elevated humidity conditions in a pool or spa enclosure, you should avoid the use of fiberglass duct board or duct liner to prevent mold and bacteria growth. If you must install ductwork in an unconditioned area, use two-inch fiberglass duct wrap with a vapor barrier facing. If you install a below-grade duct system, use PVC or plastic-coated galvanized spiral pipe to avoid deterioration. You can use galvanized sheet metal ducts for most applications. However, you should use aluminum or stainless steel ducts for extreme applications such as chemical laden environments. 12 Desert Aire Figure 7. Under-Floor Duct Layout. 1.7. Outside Air Applications 1.7.1 Outdoor Air Option Equipped Units Construction codes often require you to introduce outdoor air into a commercial building while it is occupied. Desert Aire dehumidifiers can be factory-configured to help you comply with these codes. Several factory-installed options, which are available by special order, can include flanging for an outdoor air duct connection and a fresh air intake box with air filters and a damper. See Section 4.2.2 to determine if your system is equipped with any of these options. The CA2300 Series and the UNT controller have a 7-day programmable timer which can be used to set occupied times on IH and WC model dehumidifiers. These models are built with an electronic evaporator damper. When the occupancy timer opens (or closes) the outdoor air damper, the airflow volume through the evaporator coil changes, affecting the moisture removal rate of the dehumidifier. The internal electronic damper will automatically modulate to maintain the optimum airflow volume across the evaporator. IH/WC/PD/PDW Installation & Operation Manual 13 The Desert Aire PD and PDW Series dehumidifiers are designed for residential swimming pool applications. These dehumidifiers are not provided with an electronic evaporator damper. You must not connect an occupancy-controlled outdoor air damper to a PD or a PDW system. The airflow volume changes which occur can cause condensate carryover and can reduce the service life of the equipment. You must either interlock the outdoor air damper with the blower of the dehumidifier (using contacts provided) or use a separate outdoor air intake and fan which are not physically connected to the ductwork of the dehumidifier. When you interlock the outdoor air damper and the blower, you do not need an occupancy timer. The outside air damper must be open whenever the blower is running. If you use a physically separate outdoor air intake, then you may use the occupancy timer on the CA2300 Series or UNT controller to turn it on and off. NOTE: If your PD or PDW was ordered with an outside air option which will not be utilized in the field, a minor adjustment is necessary to assure proper air flow through the evaporator coil. Call the Desert Aire Service department at 414-357-7400 for further information. Desert Aire dehumidifiers ordered with the outdoor air intake option are built with additional electrical terminals. These terminals should be utilized to control an exhaust fan and outside air duct damper. See the system’s low voltage wiring diagram for details. NOTE: You must provide a transformer or a power source for the outdoor air damper and the exhaust blower contactor. You must install an exhaust blower or “gravity dampers” whenever you bring outdoor air into a dehumidified room. Without the exhaust fan, the room would be at a positive pressure. This increased room pressure can drive moisture and chlorine odors into insulation, building materials, and adjacent rooms. Size the exhaust blower to maintain the dehumidified room at a neutral or slightly negative pressure. If you do not use the exhaust fan dry contacts provided by Desert Aire, you must make sure that the exhaust blower shuts off whenever the outdoor air damper closes. You must install the outdoor air intake away from any sources of airborne contamination such as exhaust fans or plumbing vents. You must also filter the outdoor air before it comes in contact with any coils. Insects and debris in the unfiltered air will rapidly clog the dehumidifier’s reheat condenser coil, which will lead to repeated service calls and eventual equipment damage. If mixed air temperatures in the system’s blower compartment fall below 45°F an internal safety thermostat will de-energize and override a call for outside air on IH 14 Desert Aire and WC models. In PD and PDW models this thermostat will lock out the compressor. This safety mode will remain active until mixed air temperatures in the blower compartment rise above 55°F. IF OUTDOOR TEMPERATURES IN CONJUNCTION WITH YOUR OUTSIDE AIR FLOW RATE ARE CAPABLE OF TRIPPING THE SAFETY THERMOSTAT, YOU MUST INSTALL AN OUTSIDE AIR PREHEATING COIL. Refer to Section 4.9. to determine if the pre-heating of outside air is required for your application. An example of a proper outdoor air installation is shown in Figure 8. Figure 8. Proper Installation for an Outside Air Application. NOTE: Desert Aire systems are designed to handle a range of external static pressures. In applications where strict outside air code compliance is required, proper system airflow must be determined by a professional balancing contractor. When an approximation of outside air volume is all that is necessary, the procedures detailed in Section 4.10. can be used. 1.7.2 Standard Systems in Conjunction with Outside Air THE INTRODUCTION OF OUTSIDE AIR INTO THE RETURN AIR DUCT CAN LEAD TO A HOST OF PROBLEMS. Contact the Desert Aire service department before proceeding with such an installation. If outside air must be added to satisfy code requirements on a non outside air equipped system it is advised that the intake and exhaust be connected directly to the space being conditioned. SYSTEM FAILURES CAUSED BY IMPROPER OUTSIDE AIR INSTALLATIONS ARE NOT COVERED BY WARRANTY. IH/WC/PD/PDW Installation & Operation Manual 15 1.8. Water Heating Applications (PDW and WC Models Only) 1.8.1 Water Piping Connections Desert Aire PDW and WC Series dehumidifiers are equipped with water heating condensers. You must connect pool water circulating lines to these units so that they operate as intended. The dehumidifier water supply circuit must tap into the main pool water line downstream from the main filter. If the main pool circulating pump is large enough, you can use a manual throttling valve to divert a portion of the water to the dehumidifier. Normally, you must size and install an auxiliary water pump which can handle the unit’s required water flow rate, which is listed in Table 2. If you are using a water source other than a pool or a spa (such as a chilled water loop), the required flow rate has been printed on a label affixed near the water line stubs of the dehumidifier. Model Size 0100/0125 0200 0300 0400 0500 0750 / 0800 0950 / 1000 1200 1500 Water Flow Rate and Pressure Drop Pool Application 2 GPM @ 7.8 ft H2O 4 GPM @ 7.8 ft H2O 6 GPM @ 9.2 ft H2O 8 GPM @ 6.1 ft H2O 10 GPM @ 8.0 ft H2O 14 GPM @ 10.6 ft H2O 20 GPM @ 15.7 ft H2O 24 GPM @ 20.1 ft H2O 30 GPM @ 23.1 ft H2O Water Flow Rate and Pressure Drop Spa Application 3 GPM @ 12.9 ft H2O 5 GPM @ 10.2 ft H2O 8 GPM @ 13.6 ft H2O 11 GPM @ 9.1 ft H2O 13 GPM @ 11.5 ft H2O 18 GPM @ 13.1 ft H2O 26 GPM @ 20.1 ft H2O 31 GPM @ 26.3 ft H2O 39 GPM @ 30.0 ft H2O Table 2. Standard Unit Water Flow Rates (PDW/WC models only). A typical water circuit arrangement is shown in Figure 9. To simplify the commissioning and servicing of this job, you should install a flow meter and isolation valves in the pool water lines which feed the dehumidifier. 16 Desert Aire Figure 9. Proper Pool Water Heating Installation. Legend 1 2 3 4 5 6 7 8 9 10 Supply Air Duct Heater (Gas, Electric, Steam, Hot Water) Flex Duct Connector Refrigerant Piping to Remote Condenser Desert Aire Water Cooled Dehumidifier Filter Rack Assembly with Filters Return Air 3 x 3 x 1 Rubber Vibration Isolators P-Trap Base IH/WC/PD/PDW Installation & Operation Manual 11 12 Check Valve Ball Valve 13 14 Flow Meter Main Pool Heater 15 Auxiliary Pump 16 17 18 19 20 Filter Assembly Main Pool Pump Aquastat Sensor (Dry Well) Water Inlet Water Outlet 17 1.8.2 Low Water Flow Protection Desert Aire WC Series dehumidifiers are equipped with a factory-installed water flow switch. This switch prevents the unit from running in the water heating mode if there is a lack of water flow. Desert Aire PDW Series dehumidifiers do not have a water flow switch. The flow switch must be field-supplied and installed. Check the wiring schematic of the dehumidifier for electrical connection details. PDW MODELS WILL NOT RUN IN THE WATER HEATING MODE UNTIL YOU INSTALL THIS FLOW SWITCH. 1.9. Remote Condenser Installation When you add a Desert Aire remote condenser to a “remote-ready” dehumidifier, the dehumidifier can reject unneeded heat to the outdoors. This option allows the dehumidifier to provide space cooling during warm summer months. A “remoteready” dehumidifier has been factory-piped and wired to accept a remote condenser. Not all Desert Aire dehumidifiers are remote-ready. If in doubt, refer to Section 4.2 in the appendix to determine if your dehumidifier is equipped with this option. Install the remote condenser on a level, hard surface. Do not install the condenser directly on soil or within three feet of any major obstructions. If either the air inlet or outlet is blocked by walls, shrubs, or debris; the service life of the equipment will be reduced. CONSULT WITH DESERT AIRE IF YOU MUST INSTALL THE REMOTE CONDENSER MORE THAN 10 FEET BELOW OR 50 FEET AWAY FROM THE DEHUMIDIFIER. NOTE: Pitch refrigerant lines in the direction of flow a minimum of ½” every 5 ft. of horizontal run. Figure 10. Refrigerant Piping Examples, with Remote Condenser Above and Below Dehumidifier. 18 Desert Aire 1.9.1 Refrigerant Piping of Remote Condensers 1. Desert Aire remote condensers and remote-ready dehumidifiers have capped refrigerant pipe stubs for the line set connection. The caps have been softsoldered in place. To remove the caps, heat them with a torch and then twist them loose with a pliers. Do not overheat the caps or pipe stubs. NOTE: The remote condensers are shipped from the factory with a holding charge of dry nitrogen. RELEASE THIS CHARGE BEFORE REMOVING THE CAPS! 2. Remove the caps from the dehumidifier pipe stubs. NOTE: Desert Aire dehumidifiers are equipped with remote condenser service valves located in the blower compartment. The dehumidifier pipe stubs have been pressurized with refrigerant for factory leak-checking. RELIEVE THIS PRESSURE BEFORE REMOVING THE CAPS! 3. Fabricate the refrigeration piping between the dehumidifier and the remote condenser using dehydrated ACR-type copper. Refer to the Table 3 at the end of this section for the proper line sizes for your system. Use standard refrigeration piping practices when you install the remote condenser above the dehumidifier. Install a trap in the hot gas discharge line (labeled “A”) at every 15 feet of vertical lift as shown in Figure 10. Pitch horizontal runs a minimum of 1/2” every 5 feet in the direction of flow. When you install the condenser piping, clean and de-burr all the connection points. Take care to keep copper chips and foreign materials out of the tubing. Solder or braze the joints together with 45%, 15% or Stay-Brite® solder. 4. After you braze the joints, check the lines for leaks by pressurizing the remote condenser and line set with dry nitrogen or refrigerant vapor. CAUTION: Do NOT EXCEED 80 PSIG NITROGEN CHARGE! EXCESSIVE NITROGEN PRESSURE CAN INTRODUCE NONCONDENSABLES INTO THE DEHUMIDIFIER AND CONTAMINATE THE REFRIGERATION SYSTEM. If the piping is free from leaks, release the pressure from the condenser. You may charge and evacuate the lines by using the schrader ports on the remote condenser service valves located in the blower compartment. IH/WC/PD/PDW Installation & Operation Manual 19 LINE SIZE REQUIRED FOR UNITS (INCHES) UNIT SIZE 0100 / 0125 / 0200 0300 / 0400 0500 / 0750 / 0800 0950 / 1000 / 1200 1500 SUPPLY (A) 5/8” OD 5/8” OD 7/8” OD 1-1/8” OD 1-3/8” OD RETURN (B) 3/8” OD 1/2” OD 5/8” OD 7/8” OD 7/8” OD Table 3. Remote Condenser Line Size Summary. 1.9.2 Evacuation and Charging of Remote Condensers 1. Evacuate the condenser and the piping to 400 microns. Isolate the piping for at least ten minutes to verify that the system is free from leaks, moisture, and noncondensables. 2. When you add a remote condenser to a Desert Aire dehumidifier, you must add more refrigerant to the system. The amount you add depends on the size of the condenser and the length of the piping you installed. See Table 4 to determine the necessary charge for your application. You can add this charge rapidly by first heating your refrigerant cylinder, and then charging liquid refrigerant into the condenser. Example: You install an IH0500RR dehumidifier and an RC050 condenser 20 feet apart. The total lineset length is 30 feet. From Table 4, you must add 26 pounds of additional refrigerant to the system. 3. Once you have filled and checked the condenser and lineset for leaks, open the lineset service valves located in the blower compartment of the dehumidifier. 4. Add the remote condenser jumper wire to the terminal contacts provided inside the electrical compartment of the dehumidifier. Refer to the low voltage wiring schematic for details. This dehumidifier will not operate in remote condenser mode until this jumper is added. ADDITIONAL REFRIGERANT CHARGE REQUIRED FOR LINE SETS (R-22) UNIT SIZE (UP TO 25’) (26’ TO 50’) 0100 / 0125 8 LBS 9 LBS 0200 11 LBS 12 LBS 0300 15 LBS 17 LBS 0400 21 LBS 24 LBS 0500 23 LBS 26 LBS 0750 / 0800 / 0950 / 1000 36 LBS 40 LBS 1200 / 1500 30 LBS 38 LBS Table 4. Additional Charge Summary for Remote Condensers 20 Desert Aire 2. Start-up Procedures 2.1. Prior to Start-up A complete startup will minimize operational problems and expensive callbacks. The startup will be quicker and easier if the space to be dehumidified is at its design temperature and humidity. You may need to use auxiliary or portable air heaters to heat the room. Read this section thoroughly before attempting to commission the Desert Aire dehumidifier. Always disconnect the power before servicing the equipment! NOTE: If you purchased a factory supervised start-up with your system, refer to Section 4.11. in the appendix for important information. 1. LEAK TEST ALL FIELD AND FACTORY PIPING. Shipping and handling may have caused refrigerant leaks inside the dehumidifier. Dehumidifiers with a large refrigerant charge are equipped with rotalock shutoff valves on their receivers. Their operating charge is pumped down and locked into the receiver prior to shipping, leaving a residual vapor charge in the system piping. DO NOT OPEN THE RECEIVER ISOLATION VALVES UNTIL THE SYSTEM HAS BEEN LEAK TESTED. DESERT AIRE WILL NOT REIMBURSE YOU FOR REFRIGERANT LOST IN THIS MANNER. 2. Check the rating plate for power requirements. The available power supply voltage must be within ±10% of the voltage printed on the rating plate. 3. Verify that all field wiring matches the Desert Aire wiring schematics. Inspect and tighten all field and factory wiring. 4. Check and adjust the belt tension for 1 inch deflection at the mid-point of the blower belt(s). 5. Check the drain pan and the condensate piping. Test the drain and prime the ptrap by pouring water into the drain pan. 6. If you installed a supplemental air heater, make sure you installed it in the air discharge (or “supply”) duct and not the return duct. IH/WC/PD/PDW Installation & Operation Manual 21 7. If your dehumidifier has a water heating condenser, turn on the circulating pump to run water through the system. Inspect the piping and repair any water leaks you find. If your dehumidifier is a Desert Aire PDW Series, verify that a water flow proving switch has been installed and properly wired to the electrical panel of the dehumidifier. 8. If you installed a remote condenser, verify that a jumper wire has been added to the system’s control circuit. 9. Verify that all service valves in the refrigeration lines are fully open. 10. Inspect the air filters and coils to assure they are clean. If necessary, clean the coils and install new air filters. 11. Make sure that the neoprene blocks (vibration isolators) are placed under the dehumidifier at each corner and that unit is level. 2.2. Start-up Procedure First, read and understand the “Start-Up Report” which was shipped with the dehumidifier. Desert Aire uses the start-up report to verify the integrity of each installation. A thorough start-up can reduce callbacks and can help increase customer satisfaction. Carefully follow the process detailed in the start-up report. Mail or fax the completed start-up report back to Desert Aire to validate your unit’s warranty. Be sure to keep a copy for future reference. If you do not have a start-up report, call the Desert Aire Service Department at (414) 357-7400 for a new copy. Please be prepared with the model and serial number of the dehumidifier. THE START-UP REPORT IS REQUIRED FOR WARRANTY VALIDATION. 2.3. System Operation Modes The standard sequence of operation for a Desert Aire dehumidifier is relatively simple. Whenever the compressor runs, refrigerant flows through the evaporator coil, where it absorbs heat from the warm, humid airstream. This heat must be rejected to one of three heat sinks; room air, pool water (PDW and WC models) or a separate air stream (remote condenser). The dehumidifier will direct the heat where it is needed (or not wanted) as determined by the controller setpoints. 22 Desert Aire In the case of PDW and WC models with remote condensers, if both the water and the air need heat, the dehumidifier heats the air first. If neither the water nor the air need heat, then the dehumidifier rejects the heat to the remote outdoor condenser. PDW and WC models not equipped with remote condensers require a simultaneous call for air cooling before they will heat water. This feature prevents possible air cooling when it is not desired. Whenever a remote condenser is not utilized, the compressor will only run in dehumidification mode if there is not simultaneous call for air cooling. This feature prevents the conditioned room from becoming overheated and creating uncomfortable room conditions. 2.3.1 Dehumidification / Air Reheat When the room air requires dehumidification and heating, the dehumidifier runs in the “reheat” mode. The hot refrigerant is discharged to the reheat condenser, which warms the dehumidified air. The air which is discharged from the unit is drier and about 20° warmer than when it entered. 2.3.2 Dehumidification / Air Cooling When the room air requires cooling; or dehumidification and cooling, the dehumidifier attempts to run in the air cooling mode. The hot refrigerant must be discharged to a condenser other than the reheat coil. The refrigerant can be discharged to an optional pool water condenser (PDW and WC models) or an optional remote outdoor condenser (if so equipped). The air which is discharged from the unit is drier and about 20° cooler than when it entered. 2.3.3 Dehumidification / Water Heating (PDW and WC Models Only) When the pool water requires heating and the room air requires cooling, a dehumidifier equipped with a pool water condenser attempts to run in the air cooling / pool water heating mode. The hot refrigerant will be discharged to the pool water condenser if the water flow proving switch shows that water is flowing through the condenser. The air which is discharged from the unit is drier and about 20° cooler than when it entered. IH/WC/PD/PDW Installation & Operation Manual 23 NOTE: Units equipped with a CA2300W controller, a UNT controller, or a Johnson Controls Aquastat (A28AA-29C) can also energize a field-supplied backup pool water heater. You can find wiring details on the low-voltage wiring schematic affixed to the electrical door of the dehumidifier. 2.3.4 Blower Operation Units equipped with the standard CA2300 controller have been factory wired for continuous blower operation. This helps prevent air stagnation and stratification. Continuous blower operation is also required since the air temperature and humidity sensors are mounted in the airstream inside of the dehumidifier. If the blower shuts off, the sensors cannot read the actual room temperature and humidity. If your unit is not equipped with the standard CA2300 controller, refer to the system wiring diagram and the controller documentation for the possible blower operation options. 2.3.5 Air Heat (Optional) If so equipped (see CONTROLS WIRING Section 1.4), a standard dehumidifier can activate an auxiliary air heater when the room temperature drops below the set point. supply air blower of the dehumidifier must run whenever there is a demand for air heating. You must verify this when installing an auxiliary heater. 2.3.6 Outside Air (Outside Air Equipped Models Only) During the “occupied” mode the dehumidifier will energize the outside air damper and exhaust fan terminal contacts. Desert Aire IH and WC Series dehumidifiers will operate in the occupied mode only if the occupancy timer is set accordingly. Desert Aire PD and PDW models must operate in the occupied mode whenever the supply blower runs. See Section 4.7 in the appendix for further outside air operation mode details. 24 Desert Aire 3. Service and Maintenance You can prevent many future problems by adhering to the recommended maintenance schedule shown. If you do discover a problem with the dehumidifier or the installation, refer to the TROUBLESHOOTING GUIDE in Section 4.3. IF YOU HAVE EXHAUSTED THE TROUBLESHOOTING GUIDE AND HAVE NOT DISCOVERED THE PROBLEM, CALL THE DESERT AIRE SERVICE DEPARTMENT AT (414) 357-7400. BE PREPARED WITH THE MODEL AND SERIAL NUMBER OF YOUR DEHUMIDIFIER. 3.1. Routine Maintenance Desert Aire dehumidifiers are designed for years of reliable service. However, like any piece of machinery they require periodic maintenance. 3.1.1 Service Every Month • Check the air filters and replace them if necessary. • Check the coils in the dehumidifier and the optional remote condenser. Use compressed air or a commercial coil cleanser if they are dirty or plugged. • 3.1.2 Verify that the air flow around the remote condenser remains unobstructed. Service Every Six Months • Tighten all field and factory electrical connections. • Check the blower belts in the dehumidifier and the optional remote condenser for wear, glazing, and proper tension. Replace the belts if necessary. Adjust the belts for approximately one inch deflection at their midpoints. • Conduct a SYSTEM PERFORMANCE AUDIT. A copy of this worksheet is located in Section 4.4 of the appendix. Simply run copies whenever necessary. This form is a valuable maintenance tool which can help you to uncover problems before they get expensive. Compare the values to those documented on the start-up report. If you require interpretation of the results, fax the completed form to the Desert Aire Service Department for a analysis. IH/WC/PD/PDW Installation & Operation Manual 25 3.1.3 Pool Water Chemistry Pool chemistry must be maintained to ensure the proper pH, total alkalinity, calcium hardness, and free chlorine. NSPI recommends the following levels for pool chemistry: pH ................................ 7.4 - 7.6 Total Alkalinity ..............100 - 150 ppm Calcium Hardness ........ 200 - 250 ppm (Plaster Pool) 175 - 225 ppm (Vinyl or Painted Pool) Free Chlorine ................1.0 - 3.0 ppm Excessive chemical levels in the pool can be dangerous to users and can damage pool hardware, including the dehumidification system. SERVICE PROBLEMS CAUSED BY EXCESSIVE CHEMICAL LEVELS ARE NOT COVERED UNDER WARRANTY. 3.2. Compressor Failure Although some compressors fail because they are mechanically flawed, most failures are due to system-related problems. Compressor failure can be caused by liquid floodback, air or moisture in the refrigerant system, solid contaminants, excessive heat or electrical service malfunctions. To avoid repeated callbacks, you must determine the cause of the failure and then correct it. If the compressor has failed because its motor has burned out, the refrigerant, oil, and piping may have become severely contaminated. If a burnout has occurred, use the following procedure to replace the compressor and clean the refrigerant system. YOU MUST CLEAN THE SYSTEM THOROUGHLY TO PREVENT REPEATED COMPRESSOR BURNOUTS! Use an oil test kit to determine the severity of the burnout. Make sure you use rubber gloves and eye protection, as contaminated refrigerant and oil can cause severe burns! 3.2.1 Mild Burnouts • If the burnout is mild, recover the refrigerant charge or transfer it to an unused portion of the refrigeration circuit, such as the receiver or remote condenser. You may need to energize the liquid line solenoid valve to evacuate the circuit completely. On systems equipped with an optional pool water condenser, take care to avoid freezing the condenser during evacuation. • If the compressor is equipped with rotalock valves, you may want to install and evacuate the new compressor, and use it to pump down the charge. 26 Desert Aire CAUTION! DO NOT ATTEMPT THIS WHEN A SEVERE BURNOUT HAS OCCURRED! • Replace the suction filter with a suction line filter-drier. Sporlan manufactures special “HH” filter-driers for cleaning system burnouts. These filters are equipped with a tap for measuring the pressure drop across the filter. If you install a filter without a tap, solder a tap in the suction line immediately upstream of the filter. • Remove the old liquid line filter-drier and replace it with a new “HH” type filter one size larger than the original. • Remove the old compressor if you have not already done so. • Install the new compressor. Be careful not to overheat its pipe stubs if it is not equipped with rotalock connections. • Evacuate the system to purge the moisture and non-condensables from it. You may need to energize the liquid line solenoid to evacuate all portions of the refrigeration circuit. • 3.2.2 Check the piping and joints for leaks, and recharge the system. Severe Burnouts • If the burnout is severe, recover the refrigerant charge or transfer it to an unused portion of the refrigeration circuit, such as the receiver or remote condenser. You may need to energize the liquid line solenoid valve to evacuate the circuit completely. On systems equipped with an optional pool water condenser, take care to avoid freezing the condenser during evacuation. • Verify that the TXV and solenoid valves are not plugged with debris. Clean or replace them if necessary. • Replace the suction filter with a suction line filter-drier. Sporlan manufactures special “HH” filter-driers for cleaning system burnouts. These filters are equipped with a tap for measuring the pressure drop across the filter. If you install a filter without a tap, solder a tap in the suction line immediately upstream of the filter. • Remove the old liquid line filter-drier and replace it with a new “HH” type filter one size larger than the original. • Remove the old compressor if you have not already done so. • Install the new compressor. Be careful not to overheat its pipe stubs if it is not equipped with rotalock connections. • Evacuate the system to purge the moisture and non-condensables from it. IH/WC/PD/PDW Installation & Operation Manual 27 • Check the compressor contactor for damage or pitted contacts. Some compressors are equipped with start capacitors, run capacitors, and starting relays. Check these components and replace them if necessary. • Check the piping and joints for leaks, and recharge the system. • Run the refrigeration system for an hour while you monitor the pressure drop across the suction filter. If the pressure drop is 3 psig or less after one hour, continue to run the system for 24 hours, then take an oil sample. • If the oil sample is dirty or acidic, or if the one-hour pressure drop is greater than 3 psi, then recover the system charge and replace both the suction and liquid filter-dryers. Repeat the previous step until your oil sample tests negative. 28 Desert Aire 4. Appendix 4.1. System Rating Plate The system rating plate is attached to the outside of the electrical box door. You will require the rating plate information when you install and service the dehumidifier. System model and serial numbers System electrical specifications Model No. PD0300RR2S Serial No. 3094D5154 VoltagePhase/Hz Compressor and blower motor electrical specifications Refrigerant type and factory charge System working pressure range System wiring diagrams Control Voltage 208/230-1-60 24 31 Maximum Fuse 45 Compressor RLA 20.0 Blower LRA 103 HP FLA 0.5 4.9 Factory Charge lbs. 18 R22 ONLY Wiring Diagram Numbers HD-100 / LPD-0000 This Unit Is For Indoor Use Indoor or outdoor system rating Figure 11. System rating plate. IH/WC/PD/PDW Installation & Operation Manual 29 4.2. Model Numbering Matrix 4.2.1 System Serial Number Code Figure 12. System serial number code. NOTE: If your dehumidifier is an engineered system, portions of this manual may not apply. 30 Desert Aire 4.2.2 Dehumidifier Model Number Figure 13. Dehumidifier model number matrix. IH/WC/PD/PDW Installation & Operation Manual 31 4.2.3 Remote Condenser Model Number Figure 14. Remote condenser model number matrix. 32 Desert Aire 4.3. Troubleshooting 4.3.1 Supply Blower Will Not Run POSSIBLE CAUSE System terminal switch in open position Loss of main power Blower overload has tripped Faulty control wiring 4.3.2 REMEDY Close system terminal switch. Check for tripped circuit breaker or blown fuses Correct cause and reset overload Check for loose or incorrect wires on system and controller Compressor Will Not Run NOTE: Under some circumstances the compressor will not run even though the humidity in the room may be too high. See Section 2.3 for more information on the control sequence for the dehumidifier. POSSIBLE CAUSE Control logic (see above) Loss of main power Blower overload has tripped Faulty wiring Compressor overload has tripped Comp. failure may have occurred if: A) Comp. draws locked rotor amps B) Comp. starts but does not pump C) Motor windings have shorted Compressor delay-timer IH/WC/PD/PDW Installation & Operation Manual REMEDY A) Adjust controller setpoints B) On RR models with a remote condenser installed: Verify that the RC jumper has been installed in dehumidifier (see Section 1.9). Check for tripped circuit breaker or blown fuses Correct cause and reset overload Check for loose or faulty wiring on system and controller Correct cause and reset overload A) Replace compressor (or check fuses on three-phase units) B) Replace compressor C) Replace compressor Wait 3 minutes for timer 33 4.3.3 Evaporator Coil Ices Up (Suction Pressure Below 58 psig) POSSIBLE CAUSE Entering air is below 70oF (PD/PDW Series only) Faulty or improperly set hot-gas bypass valve (IH/WC Series only) Insufficient evaporator air flow rate Lack of refrigerant Restrictive filter drier Defective expansion valve Restriction in refrigeration piping 34 REMEDY Raise entering air temperature 1) Set hot-gas valve to maintain 32o F suction (58 psig) 2) Replace if defective 3) Open hot-gas isolation valve 1) Evaluate system air flow (see Section 4.6) 2) Check for dirty filters or restricted ductwork 3) Assure coils are clean Reevaluate system charge Evaluate filter pressure drop and replace if necessary Evaluate expansion valve performance and replace if necessary. 1) Check coil for kinks in tubing 2) Evaluate debris in distributor Desert Aire 4.3.4 Head Pressure is Too High (Above 270 psig) POSSIBLE CAUSE Insufficient system air flow Excessive refrigerant charge Non-condensables in system Defective refrigeration valves Restriction in refrigeration piping Refrigeration system is overloaded Low water flow (PDW/WC Series only) REMEDY 1) Evaluate system air flow (see Section 4.5). 2) Check for dirty filters or restricted ductwork 3) Verify that coils are clean Re-evaluate system charge Evacuate or purge system Check 3-way, flooding, solenoid, and check valves for sticking 1) Check coil and tubing for kinks 2) Replace dirty drier filter 1) Reduce entering air temperature or relative humidity 2) Check register locations for shortcycling of air Evaluate water flow rate for your application REMOTE CONDENSER PROBLEMS WHICH CAUSE EXCESSIVE PRESSURES: Lack of air flow Remote cond. blower does not run. A) Overload tripped B) Contactor faulty C) Blower cycling on internal protection D) Remote Cond. jumper missing at dehumidifier Service valves closed or not fully open Excessive pressure drop in line sets Assure coil is clean and no air flow restrictions exist around unit. A) Reduce blower speed and reset overload B) Replace contactor C) Reduce blower speed D) Add necessary jumper in dehumidifier (See Section 1.9) Fully open service valves Re-evaluate remote condenser installation (See Section 1.9 for guidelines) NOTE: When the remote condenser is active and the outdoor temperature is above 95°, normal head pressure can be as high as 300 psig. IH/WC/PD/PDW Installation & Operation Manual 35 4.3.5 Unit Runs But Walls and Windows Drip POSSIBLE CAUSE Air and pool water temperature imbalance Poor air distribution Unit air flow is too high Unit is undersized UNITS NOT EQUIPPED WITH THE CA2300 SERIES CONTROLLER: 1) Controller installation 2) Air stratification 4.3.6 REMEDY Adjust setpoints so that air temperature is 2o F above water temperature. 80o F water and 82o F air recommended for most jobs Evaluate duct design and dehumidifier location (See Sections 1.2 and 1.6) Evaluate system air flow (See Section 4.5) Re-evaluate unit sizing. Check for initially neglected sources of heat or humidity 1) Assure that sensors are NOT located near supply registers, windows, heaters, saunas, etc. 2) Consider continuous blower operation. Pool Water Heating Problems (WC and PDW Models Only) NOTE: 1. PDW models require the installation of a field supplied water proving switch before the water heating mode can be activated. 2. Lack of water heating may be a symptom of another refrigeration or controls problem not related to the water circuit. 3. Under normal conditions the water temperature rise across the dehumidifier should be between 4o and 15o F. • LOW WATER TEMPERATURE INCREASE is a symptom of excessive water flow rate. Excessive water flow can erode the water condenser and cause premature equipment failure. • HIGH WATER TEMPERATURE INCREASE is a symptom of insufficient water flow. This can be caused by an undersized pump, insufficient water diversion or restrictions in the water piping such as dirty filter(s). This would also lead to high operating pressures in the water heating mode. 36 Desert Aire 4.4. System Start Up Report A copy of the system start up report can be found on the following page. This report needs to be filled out thoroughly by a qualified service technician and returned to Desert Aire for warranty validation. Please ensure that the model and serial number of the unit is noted on this form. The model and serial number can be found on the systems rating plate located on or near the electrical compartment service door. Failure to complete and return this form will void the units warranty. These reports are also helpful when trying to correct existing problems. Should you need system diagnosis help, fax the completed worksheet to the Desert Aire Service Department using the number provided. Be sure to include your name and a telephone number where you can be reached. IH/WC/PD/PDW Installation & Operation Manual 37 IH/WC/PD/PDW System Startup Report WARNING — Only trained, qualified personal should service Desert Aire equipment. Serious injury and/or death can result from improper service of this equipment. High voltage electrical components and refrigerant under pressure are present. Note! This Startup Report must be filled out completely and returned to Desert Aire for warranty activation. All readings should be taken when equipment is operating at design conditions. Model Number Serial Number Air Flow Information (see Section 4.5 of the Installation & Operation Manual) Reheat coil static pressure drop: inches WC Evaporator coil static pressure drop: inches WC Electrical & Refrigeration System Readings (as measured by a qualified service technician) Actual Supply Voltage: Control Voltage: °F Return Air Temperature: RH: % Compressor 1 amp draw Line 1 Line 2 Line 3 Compressor 2 amp draw Line 1 Line 2 Line 3 Blower amp draw Line 1 Line 2 Line 3 Air Dehumidification Mode * Air Cooling Mode * Water Heating Mode Compressor discharge pressure: (psig) Compressor suction pressure: (psig) o Dehumidifier leaving air temperature: ( F) Condensate trap installed: Yes Oil Level Sight Glass (if applicable): °F RC elevation is ft. * Water Cooled Installations: * Outside Air (OA ) Installations: ½ ¾ Amp Draw: Full R-22 added: lbs Line set length between RC and dehumidifier: above Water temperature: Water flow rate (measured): (See I&O Manual for details) Less than ½ * Remote Condenser (RC) Installations: Outdoor Ambient: No below In: dehumidifier °F Out: °F GPM Outside Air Flow Rate: OA duct is equipped with (check all that apply): Filters Outside Air Damper Is Controlled by Dehumidifier: Yes CFM Damper Heater No inches WC Activate outside air mode and measure evaporator coil static pressure drop: Evaporator is: Wet ft. Dry CONSULT THE OPERATION MANUAL FOR INSTALLATION INSTRUCTIONS AND SYSTEM OPERATION GUIDELINES * if so equipped Submitted by: Phone No. Please Mail or fax to : Desert Aire Service Department 8300 W. Sleske Ct, Milwaukee, WI 53223-3844 PH: 414/357-7400 FAX: 414/357-8501 38 Date: Desert Aire 4.5. System Guidelines - Unit Air Flow Each Desert Aire Dehumidifier is designed to operate at a specified air flow rate. System air flow must be checked prior to troubleshooting the refrigeration circuit to assure that such problems are not actually caused by improper unit air flow. • • 4.5.1 Problems with excessive air flow: • Reduction in moisture removal capacity. • High amperage draw by the blower motor. • Water carry over from evaporator coil • Excessive unit noise levels. Problems with inadequate air flow: • Can cause excessive discharge (high side) refrigeration pressure. • Increase in system energy consumption. • Can lead to premature compressor failure. Determining System Air Flow Using a manometer or magnehelic pressure differential gauge, determine the static pressure drop in inches water column across the unit's condenser coil. NOTE: Newer units are equipped with pressure tap holes on the side panels just for this purpose. If your unit is not equipped with such taps, simply drill two small holes in the unit’s side panels (one in the blower compartment just downstream from the condenser and one in the section between the evaporator and the condenser). Drill the holes so that they are large enough for your static pressure taps. See Table 5 for the proper pressure drop range for your unit. A low static pressure drop indicates low air flow -- you must speed up the blower. A high pressure drop indicates high air flow -- you must slow down the blower. NOTE: Low system airflow can also be caused by airflow restrictions such as dirty coils, filters, and duct work. Assure that this not the case before you speed up the blower. 4.5.2 Blower Adjustment Procedure WARNING! DISCONNECT POWER TO THE UNIT BEFORE YOU ADJUST THE BLOWER. Change the blower speed by adjusting the motor pulley. To adjust the variable pitch pulley, first loosen the set screw. To slow down the blower, turn the outer pulley face IH/WC/PD/PDW Installation & Operation Manual 39 counterclockwise (to decrease its pitch diameter). To speed up the blower, turn the outer pulley face clockwise (to increase its pitch diameter). AFTER EVERY ADJUSTMENT BE SURE TO: • Tighten the set screw against the flat spot on the pulley hub so you don’t damage any threads. • Adjust the belt tension if needed. • Check to assure that the blower motor current draw does not exceed the rating printed on the rating plate. NOTE: System airflow will tend to decrease over time due to belt wear and dirty filters and ducts. Always adjust the blower speed to the high side of the pressure drop range. If the blower motor current draw exceeds its rating but your airflow is still too low, the static pressure losses in the ductwork and grilles may be higher than the unit was designed for. If this happens, consult the Desert Aire Service Department. Please be prepared with system serial and model number. Model 0100/0125 0200 0300 0400 0500 0750 / 0800 0950 / 1000 1200 1500 Total System CFM 540 950 1400 1900 2300 3500 4100 5500 6900 Condenser Coil Pressure Drop Range (inches WC) 0.19” - 0.21” 0.23” - 0.25” 0.20” - 0.22” 0.14” - 0.16” 0.20” - 0.22” 0.28” - 0.30” 0.25” - 0.27” 0.40” - 0.42” 0.32” - 0.34” Table 5. Standard Reheat Coil Pressure Drops 4.6. System Guidelines - Unit Operation 4.6.1 Controller Set Points It is important to determine your comfortable set points and to avoid further controller adjustments. It takes time for the unit to establish equilibrium at a given setpoint. Therefore, continued setpoint adjustments will lead to high energy consumption and user discomfort. Continuous blower operation is recommended. This will reduce air stratification and assure that the refrigeration circuit is activated only when it is necessary. 40 Desert Aire RECOMMENDED SET POINTS: • Humidity: 50% to 60% RH • Air temperature: 2o to 4o F above the pool water temperature WARNING: Never disable a dehumidifier in a pool room application unless the pool has been drained. Even when not in use, pool water continues to evaporate adding moisture to the air. During these periods of high humidity moisture will seep into walls, ceilings, furniture, etc.. Although the dehumidifier may be capable of regaining control of pool room conditions after re-start, in the long run, moisture damage to the pool room will become apparent. 4.6.2 Refrigeration System Pressures Many factors affect refrigeration pressures on a given day. Such factors include ambient temperature, water temperature, air flow volume, and relative humidity. However, for the sake of troubleshooting: • Normal suction pressure range: 55 to 70 psig • Normal discharge pressure range: 180 to 270 psig NOTE: Always check the system air flow before you troubleshoot the refrigeration circuit (see Section 4.5). 4.6.3 Temperature Rise or Drop Across Unit • Typical air temperature rise across unit (Reheat mode): 10o to 20o F • Typical air temperature drop across unit (Air conditioning or water heating mode): 10o to 20o F NOTE: • If your unit does not meet these temperature ranges, check the system air flow (See Section 4.5). • These guidelines do not apply to dehumidifiers with outdoor air intakes when they are in the “occupied” mode. IH/WC/PD/PDW Installation & Operation Manual 41 4.7. Outside Air Supplemental Information 4.7.1 PDW and PD Operation Mode Figure 15. PD / PDW models, Occupied Mode Operation. 4.7.2 IH and WC Operation Modes Figure 16. IH / WC Models, Unoccupied Mode Operation. Figure 17. IH / WC Models, Occupied Mode Operation. 42 Desert Aire 4.8. SMACNA Duct Designs You must use proper duct design to ensure that the dehumidifier operates efficiently and without problems. Undersized or restrictive ducts reduce the system airflow, which can cause premature compressor failure. Use the following diagrams as a guide when you design the duct system. No! Yes! Figure 18. Recommended Duct Designs for Desert Aire Dehumidifiers. IH/WC/PD/PDW Installation & Operation Manual 43 4.9. Determining if Outside Air Pre-Heating is Required Desert Aire systems require that outside air be pre-heated if mixed air temperatures inside the unit may fall below 45 °F. To determine if an application requires outside air pre-heating, the following study needs to be conducted: 1. Determine the following: • Design return air temperature. For pool rooms typically 82 °F. • Outside air winter design temperature. Use values as specified by design engineer or ASHRAE tables. • 2. Total system CFM and required outside air CFM Determine worst case Mixed Air Temperature using the following equation: MAT = (winter temp °F) x (OA CFM) + (return air temp °F) x (system CFM - OA CFM) (system CFM) (system CFM) 3. If MAT is less than 45 °F, then the pre-heating of outside air is required. NOTE: • Proper system airflow and outside air CFM must be confirmed at the time of installation. • Outside air duct must be equipped with filters and a motorized damper provided by installing contractor or as optional equipment on Desert Aire dehumidifiers. • Outside air duct must be insulated to prevent condensation which may form on the exterior of the duct during winter months. EXAMPLE: PD0500 (2300 system CFM), pool room application, 500 CFM of outside air. Location: Minneapolis, Minnesota. MAT = (-16 °F) x 500 + 82 °F x (2300 - 500) = 60.7 °F 2300 2300 CONCLUSION: No need for outside air pre-heat. 44 Desert Aire 4.10. Approximating Outside Air Volume When servicing or installing a Desert Aire unit, it may be necessary to determine and/or set the amount of outside air CFM entering the unit. Proper outside air CFM settings can be approximated using two simple equations as follows: Figure 19. Approximating Outside Air CFM. OACFM = LACFM x (LATEMP - RATEMP) / (OATEMP - RATEMP) LATEMP = (OACFM x (OATEMP - RATEMP) / LACFM) + RATEMP NOTE: • This method is just an approximation! In applications where strict code compliance is required proper airflow must be determined by a professional testing and balancing contractor. • Refrigeration circuit must remain inactive during this procedure (blower on only). • When measuring air temperatures, several readings must be taken across a duct and averaged. • Proper LACFM (total system airflow) must be confirmed prior to this procedure. This is done by achieving specified air flow pressure drop across the reheat coil. See Section 4.5. for details. EXAMPLE 1: Determine how much OA CFM is entering a PD0500. Measured: LACFM = 2300, LATEMP = 73 °F, RATEMP = 82 °F, OATEMP = 40 °F Solution: OACFM = 2300 x (73 °F - 82 °F) / (40 °F - 82 °F) = 490 CFM EXAMPLE 2: Determine proper outside air damper setting to achieve 900 CFM of OA on an IH0750. Given: Desired OACFM = 900 Measured: LACFM=3500, OATEMP=40 °F, RATEMP=82 °F Solution: LATEMP = (900 x (40 °F - 82 °F) / 3500) + 82 °F = 71 °F i.e. adjust outside air damper until a system leaving air temperature of 71 °F is achieved IH/WC/PD/PDW Installation & Operation Manual 45 4.11. Start-up Supervision Supplemental Information (Optional) A Desert Aire factory start up is an option which can be purchased with the equipment. A factory start up includes several key services: • The expertise of an accomplished, factory-trained mechanic who will supervise the commissioning of the equipment. • This Desert Aire representative will assist the installing contractor with filling out the Start Up Report. • He will also inspect the installation to make sure that the dehumidifier has been properly integrated with the rest of the equipment on the jobsite. • Finally, he can train the maintenance personnel to operate and service the equipment if necessary. A factory start up does not include installation assistance. The installing contractor is responsible for ensuring that the system is ready for start-up when the Desert Aire representative arrives. When the installing contractor is confident the system will be ready, he should contact the Desert Aire Sales representative to schedule the start-up. Please call at least two weeks before the desired start up date to help prevent scheduling conflicts. 46 Desert Aire SERVICE BULLETIN 010 IH / WC / PD / PDW / ND / SA FACTORY START-UP SUPERVISION A Factory Start-Up requires a Desert Aire Service Department Technician to visit the job-site and provide supervisory experience to installing contractors as they perform the required procedures as outlined in our warranty activation start-up report. The company technician will also present an educational review of the dehumidifier’s operating and maintenance requirements. A CST Start-Up is performed by a local Certified Service Technician who has been trained by Desert Aire. The CST performs all duties of commissioning and also trains responsible parties on the proper maintenance and operation of the unit. “Factory Start-Up is not an installation bid & therefore the system must be ready to run before scheduling.” The Desert Aire Service Dept. will advise contractors of their responsibilities and coordinate all site visits. This start-up procedure may be performed by Desert Aire OR an authorized “Certified Service Technician.” This document requires a signature and must be returned to Desert Aire before the Factory- or CST-supervised start-up can be scheduled. Desert Aire will confirm the start-up dates upon receipt of the pre-start-up checklist. If a return trip must be scheduled due to insufficient job-site preparation, a second P.O.# must be issued to Desert Aire for re-scheduling. The following list of items will apply to all start-ups and is the responsibility of the installing contractor. If you are unable to supply any of the following equipment, you must contact Desert Aire before signing this document. You can reach Desert Aire at (800) 443-5276. Items needed for Start-Up: Equipped service vehicle and service technician – Technician will be trained. Refrigerant manifold gauges – 2 sets Air balancing equipment (magnehelic or manometer differential pressure gauge) Volt/Amp/OHM meters in working order. Digital Thermometer w/clamp on sensors OR laser type temperature probe. 50# of R-22 & weigh in scale Hand Pump for adding oil to compressor (Copeland Scroll) 9 ton compressor & larger Items to be completed before Start-Up: Dehumidifier leak checked (with halogen leak detector) and inspected for internal concealed damage – remove access panels and inspect the interior of the unit for transit damage. Contact Desert Aire immediately if damage is noted (800) 443-5276 Dehumidifier leveled and properly supported per the installation manuals recommendations. Outside air duct filters and damper installed (if applicable) – See installation manual. Condensate P Trap installed with heat trace for winter operation. Remote condenser plumbed and inspected for freight damage (If applicable) Remote condenser circuit leak checked, evacuated and charged (if applicable – see installation manual for R-22 weights and condenser locations) All electrical connections terminated and verified for proper voltage at the unit. All field controls and sensors installed and circuits verified that they are wired correctly. If there are any questions, contact Desert Aire (800) 443-5276 Pool filled, water and air temp minimum 80 degrees (if applicable) Pool water heating circuit connected to dehumidifier with flow meter and balancing valves installed in circuit (if applicable) Verify the installation of the booster pool water heating pump and purge air from the water lines (if applicable) Verify that voltage matches nameplate design for the condenser and the dehumidifier. A MINIMUM TWO WEEK LEAD TIME IS NEEDED TO SCHEDULE START UP Desert Aire Corporation • 8300 West Sleske Court • Milwaukee, WI 53223 • (800) 443-5276 • Fax (414) 357-8501 IH/WC/PD/PDW Installation & Operation Manual 47 SERVICE BULLETIN 010 IH / WC / PD / PDW / ND / SA FACTORY START-UP SUPERVISION Desert Aire Corporation • 8300 West Sleske Court • Milwaukee, WI 53223 • (800) 443-5276 • Fax (414) 357-8501 Please complete this two page document, sign and return to Desert Aire for start-up scheduling. Dates will be scheduled after this form is received. Please print clearly. Unit Information Model # ___________________________________________________________ Serial # ___________________________________________________________ Contractor Information Installing Contractor Address ______________________________________________________________________ _______________________________________________________________________________ _______________________________________________________________________________ Phone # _____________________________________ Jobsite Information Jobsite Address __________________________________________________________________________ __________________________________________________________________________ Jobsite Contact ______________________________________ Cell # ______________________________ Jobsite Phone # __________________________________________________________________________ Signature, Jobsite Supervisor ________________________________________ Date __________________ Test & Balance Contractor Name ________________________________________________________________________ Technicians Name __________________________________ Phone # ______________________________ Test & Balance Completion Date ____________________________________________________________ Desert Aire Sales Representative Company Name ___________________________________________________________________________ 48 Desert Aire 8300 West Sleske Court Milwaukee, WI 53223 (414) 357-7400 Fax:(414) 357-8501 31 - 07/05