3-Phase UPS International 380V Site Planning Data

advertisement
International 380V Site Planning Data Sheet
UPS 10,20,40, 60, & 80kVA, 50/60Hz, 220/380VAC (also 400/230V or 415/240V)
UPS Rating
kVA
10
30
Voltage
AC input
Battery
Current A
Rec. Ext.
Min.
Float
kW Input
Output
Nom.
Max
OCPD
input mm2 VDC
8
380/50Hz 220 1ph 14/45 A 16/47A 32/63A
6/14
274
24 380/50Hz 380/220
43A
45A
63A
14-Jan
274
20
16 380/ 50Hz 220/380
40
32 380/ 50Hz 220/380
60
48 380/ 50Hz 220/380
80
64 380/ 50Hz 220/380
See Notes for Table Below:
26A
53A
79A
105A
1
30A
60A
91A
121A
2,3,4,5
50A
75A
125A
150A
6
14
14
22
38
3,4
AC Output
Max.
KW
Discharge Nom.
OCPD
9.1
45.5A
45A
N/A
27.3
136.5
46A
63A
Modular Series
+/- 274 17
43
30A
50
+/- 274 34
85
61A
75
+/- 274 51.1
128
91A
125
+/- 274 68.1
170
121A
150
7
1,3,4,5
1,3,4,5
6
Mechanical Data
Dimensions
Weight
(WDH cm)
(Kg)
28 x 63 x 56.5
46
49 x 91.4 x 89.66
300
52 x 85.5 x 116
52 x 85.5 x 116
52 x 85.5 x 116
52 x 85.5 x 116
8
245
412
210
244
8
Heat Dis.
BTU/Hr
3034
10115
Cooling Air
CFM (m3/Hr)
327(557)
587 (998)
3843
7685
11528
15371
767(1304)
1247(2120)
1728(2937)
2208(3753)
Notes For Table
1) Nominal (Nom) current is based on full rated output load.
2) Maximum (Max) current is of short duration for battery recharge.
3) Input, Bypass and output cables to be run in separate conduit. Not more than 3 conductors in raceway assumed; ambient temperature of 86F.
4) Wiring Requirements: (Copper conductors. Consult NEC handbook and local codes)
AC input: 3-phase 4 wire, Plus Ground
AC output: 3-phase 4 wire, Plus Ground
AC output: 1-phase 2 wire, Plus Ground (for N-series 3/1 model)
5) Control and power wiring must be run in separae conduit.
6) Over Current Protection Device (OCPD) recommended represents 125% of nominal full load current (continuous) per NEC 215.
7) Nominal battery voltage is shown at 2.0 volts/cell per NEC 480-2
8) Dimensions and weight do not include battery module.
9) All wiring is to be in accordance with national and local electric codes.
10) Minimum access clearance is 3ft. front, 1in. Sides, 12in. Rear, and 24 in. top.
11) It is recommended that 5 ft. of flex cable be installed for AC input and output for ease of access and maintenance.
12) Minimum sized grounding conductors to per per NEC 250-122. Parity-Sized ground conductors are recommended. Neutral conductors to be sized for full
capacity per NEC 310-15(b)(4). References are per NEC 1999.
13) Cable entry from lower rear or lower front of UPS.
14) If site conditions include a generator consult generator manufacturer for required generator options and sizing.
15) If site configuration requires an external maintenance bypass care must be taken to ensure phase parity between UPS input and UPS bypass. Consult Tripp
Lite applications engineer.
16) RATINGS FOR OVERCURRENT DEVICES AND CABLES SUPPLIED IN THIS DOCUMENT IS FOR INFORMATIONAL PURPOSES ONLY. USER SHOULD
CONSULT WITH ITS ENGINEERING SERVICES BEFORE ADOPTING.