SEMINOLE ELECTRIC COOPERATIVE, INC. BULK ELECTRIC SYSTEM FACILITY RATING METHODOLOGY 2009-FAC-008-1-MTD-1-4 CONTENTS 1 INTRODUCTION - R1.1, R1.2.2, R1.3* ................................................................... 2 2 TRANSMISSION LINES (TRANSMISSION CONDUCTORS) - R1.2, R1.3* ....... 3 3 TRANSFORMERS - R1.2, R1.3*............................................................................... 4 4 INSTRUMENT TRANSFORMERS - R1.2, R1.3* .................................................... 5 5 RELAY PROTECTIVE DEVICES (RELAYS) - R1.2, R1.3* .................................. 6 6 LINE TRAPS - R1.2, R1.3* ........................................................................................ 7 7 SERIES REACTORS - R1.2, R1.3* ........................................................................... 8 8 CIRCUIT BREAKERS - R1.2, R1.3* ........................................................................ 9 9 CIRCUIT SWITCHERS - R1.2, R1.3* ..................................................................... 11 10 SWITCHES - R1.2, R1.3* ........................................................................................ 12 11 BUS - R1.2, R1.3*..................................................................................................... 13 12 SHUNT COMPENSATION DEVICES (SHUNT CAPACITORS) - R1.2, R1.3* .. 14 13 GENERATORS - R1.2, R1.3* .................................................................................. 15 14 DISTRIBUTION OF FACILITY RATING METHODOLOGY - R2, R3* ............. 16 15 REVIEW OF SEMINOLE FACILITY RATINGS - R3*......................................... 16 * NERC Reliability Standard FAC-008-1 Requirement(s) covered by this section of the Seminole Bulk Electric System Facility Rating Methodology. 1 SEMINOLE ELECTRIC COOPERATIVE, INC. BULK ELECTRIC SYSTEM FACILITY RATING METHODOLOGY 2009-FAC-008-1-MTD-1-4 1 INTRODUCTION This document describes the methodology used to develop ratings for the Bulk Electric System (BES) Facilities that are solely and jointly owned by Seminole Electric Cooperative, Inc. (Seminole). Furthermore, it is the intent of this document to demonstrate Seminole’s compliance with NERC Reliability Standard FAC-008-1. This document describes the Seminole Facility Rating Methodology for the following BES equipment (100 kV and above): 1 2 3 4 5 6 7 Transmission Lines (Transmission Conductors) Transformers Instrument Transformers Relay Protective Devices (Relays) Terminal Equipment (Line Traps, Series Reactors, Circuit Breakers, Circuit Switchers, Switches & Bus) Shunt Compensation Devices (Shunt Capacitors). Generators NOTE: Seminole does not own, jointly own or maintain any High Voltage Direct Current equipment, Series Compensation Devices or shunt reactors (a type of Shunt Compensation Device). Seminole does not operate any Facility beyond its Normal Rating. The Emergency Rating is equivalent to the Normal Rating for all Seminole Facilities. Additionally, the Seminole Facility Rating is derived from the most limiting applicable Equipment Rating of the individual equipment that comprises the Facility. Seminole’s Facility Rating Methodology and Equipment Ratings consider the following: Ratings and warranties provided by equipment manufacturers IEEE, ANSI, ASTM, NESC, RUS and other standards and rules as applicable Ambient conditions Operating limitations Other assumptions, as appropriate to the facility equipment. 2 SEMINOLE ELECTRIC COOPERATIVE, INC. BULK ELECTRIC SYSTEM FACILITY RATING METHODOLOGY 2009-FAC-008-1-MTD-1-4 2 TRANSMISSION LINES (TRANSMISSION CONDUCTORS) Transmission Lines1 are specified, designed and operated as per the following: IEEE C2 - National Electric Safety Code® (NESC®) IEEE 1312.1 - IEEE Standard for Insulation Coordination—Definitions, Principles, and Rules (as per validity date) IEEE 1312.2 - IEEE Guide for the Application of Insulation Coordination (as per validity date) IEEE 738 - IEEE Standard for Calculating the Current-Temperature of Bare Overhead Conductors Transmission Line design documentation and drawings Operating limits specified by Transmission Line equipment manufacturer(s) Nameplate ratings do not exist for Transmission Lines. Therefore, the Normal Rating of a Transmission Line shall be defined by the following: The rated system voltage of a Transmission Line shall be determined based on the clearances specified in the above standards (IEEE C2 - NESC® shall have the overriding authority in the selection of all clearances) Transmission conductors2 shall have a steady-state thermal rating and transient thermal rating based on the below design parameters (Calculated using Southwire’s SWRate (IEEE 738) program or by Alcan for ACSR/SD) Design Parameters Wind Speed Latitude Time Environmental Conditions Ambient Temperature Total Irradiation (Sun & Atmosphere) Value 3.0 ft / s perpendicular to the conductor 30° 12:00 PM Clear Summer - 35°C Winter - 0°C 2 96.14 W / ft Coefficient of Emissivity 0.9 Coefficient of Solar Absorption Maximum Steady-State Conductor Temperature 0.9 NOTE: The Normal Rating of a conductor may be specified at a lower allowable temperature to meet NESC® and other requirements. Maximum Transient Conductor Temperature (Maximum Duration = 13 cycles = 0.217 s) AAC - 85°C ACSR or ACSR/SD - 100°C ACSS - 200°C AAC - 340°C ACSR, ACSR/SD, ACSS 645°C Seminole’s Emergency Rating is equivalent to the Normal Rating for Transmission Lines 1 2 This section shall also apply to strain bus and jumpers (see Section 10 - Bus). Conductor hardware is considered part of the conductor and rated equivalently. 3 SEMINOLE ELECTRIC COOPERATIVE, INC. BULK ELECTRIC SYSTEM FACILITY RATING METHODOLOGY 2009-FAC-008-1-MTD-1-4 3 TRANSFORMERS Transformers (liquid-immersed power and regulating transformers) are specified, designed1 and operated as per the following: IEEE C57.12.00 - IEEE Standard for Standard General Requirements for LiquidImmersed Distribution, Power, and Regulating Transformers IEEE C57.12.70 - IEEE Standard Terminal Markings and Connections for Distribution and Power Transformers IEEE C57.12.80 - IEEE Standard Terminology for Power and Distribution Transformers IEEE C57.12.90 - IEEE Standard Test Code for Liquid-Immersed Distribution, Power, and Regulating Transformers IEEE C57.19.00 - IEEE Standard General Requirements and Test Procedure for Power Apparatus Bushings IEEE C57.19.01 - IEEE Standard Performance Characteristics and Dimensions for Outdoor Apparatus Bushings IEEE C57.19.100 - IEEE Guide for Application of Power Apparatus Bushings IEEE C57.100 - IEEE Standard Test Procedure for Thermal Evaluation of LiquidImmersed Distribution and Power Transformers IEEE C57.116 - IEEE Guide for Transformers Directly Connected to Generators IEEE C57.131 - IEEE Standard Requirements for Load Tap Changers IEEE C37.91 - IEEE Guide for Protecting Power Transformers (as applicable) IEEE 1276 - IEEE Guide for the Application of High-Temperature Insulation Materials in Liquid-Immersed Power Transformers (as applicable) IEEE 1538 - IEEE Guide for Determination of Maximum Winding Temperature Rise in Liquid-Filled Transformers Operating limits specified by the manufacturer Transformers shall have a Normal Rating that is equivalent to the manufacturer’s nameplate ratings except as follows: For any tap position specified on the manufacturer’s nameplate, the Normal Rating for voltage and frequency shall be defined by IEEE C57.12.00, Section 4.1.6.1 Seminole’s Emergency Rating is equivalent to the Normal Rating for Transformers 1 Seminole shall specify that manufacturers design transformers to conform with the standards listed in this section. 4 SEMINOLE ELECTRIC COOPERATIVE, INC. BULK ELECTRIC SYSTEM FACILITY RATING METHODOLOGY 2009-FAC-008-1-MTD-1-4 4 INSTRUMENT TRANSFORMERS Instrument Transformers are specified, designed1 and operated as per the following: IEEE C57.13 - IEEE Standard Requirements for Instrument Transformers ANSI C93.1 - Requirements for Power-Line Carrier Coupling Capacitors and Coupling Capacitor Voltage Transformers (CCVT) IEEE C57.13.1 - IEEE Guide for Field Testing of Relaying Current Transformers IEEE C57.13.2 - IEEE Standard Conformance Test Procedure for Instrument Transformers IEEE C57.13.3 - IEEE Guide for Grounding of Instrument Transformer Secondary Circuits and Cases IEEE C57.13.5 - IEEE Standard of Performance and Test Requirements for Instrument Transformers of a Nominal System Voltage of 115 kV and Above IEEE C57.13.6 - IEEE Standard for High-Accuracy Instrument Transformers (as applicable) IEEE C57.19.00 - IEEE Standard General Requirements and Test Procedure for Power Apparatus Bushings IEEE C57.19.01 - IEEE Standard Performance Characteristics and Dimensions for Outdoor Apparatus Bushings IEEE C57.19.100 - IEEE Guide for Application of Power Apparatus Bushings IEEE C37.110 - IEEE Guide for the Application of Current Transformers Used for Protective Relaying Purposes Operating limits specified by the manufacturer Instrument Transformers shall have a Normal Rating that is equivalent to the nameplate ratings and/or documented ratings provided by the manufacturer (as specified by the above IEEE standards) NOTE: Seminole utilizes instrument transformers with a variety of thermal rating factors. Instrument transformer ratings are considered when establishing a Facility Rating Seminole’s Emergency Rating is equivalent to the Normal Rating for Instrument Transformers 1 Seminole shall specify that manufacturers design instrument transformers to conform with the standards listed in this section. 5 SEMINOLE ELECTRIC COOPERATIVE, INC. BULK ELECTRIC SYSTEM FACILITY RATING METHODOLOGY 2009-FAC-008-1-MTD-1-4 5 RELAY PROTECTIVE DEVICES (RELAYS) The term “relay protective devices” is not defined in the NERC Glossary of Terms Used in Reliability Standards. Therefore, “Relay protective devices” shall be recognized by Seminole as equivalent to the term “relay” as defined by IEEE 100 – The Authoritative Dictionary of IEEE Standards Terms. Relay protective devices are specified, designed1 and operated as per the following: IEEE C37.90 - IEEE Standard for Relays and Relay Systems Associated with Electric Power Apparatus IEEE C37.90.1 - IEEE Standard for Surge Withstand Capability (SWC) Tests for Relays and Relay Systems Associated with Electric Power Apparatus (as applicable) IEEE C37.90.2 - IEEE Standard for Withstand Capability of Relay Systems to Radiated Electromagnetic Interference from Transceivers (as applicable) IEEE C37.90.3 - IEEE Standard Electrostatic Discharge Tests for Protective Relays (as applicable) Relay protective devices are not directly connected to BES Elements but are connected indirectly through instrument transformers Relay protective devices have a Normal Rating that is specified, designed and applied for the full range of system conditions to which they will be subjected on a given BES Element Seminole’s Emergency Rating is equivalent to the Normal Rating for relay protective devices 1 Seminole shall specify that manufacturers design relay protective devices to conform with the standards listed in this section. 6 SEMINOLE ELECTRIC COOPERATIVE, INC. BULK ELECTRIC SYSTEM FACILITY RATING METHODOLOGY 2009-FAC-008-1-MTD-1-4 6 LINE TRAPS Line Traps are specified, designed1 and operated as per the following: ANSI C93.3 - ANSI Requirements for Power-Line Carrier Line Traps Operating limits specified by the manufacturer Line Traps have a Normal Rating that is equivalent to the nameplate ratings and/or documented ratings provided by the manufacturer (as specified by the above ANSI standard) Seminole’s Emergency Rating is equivalent to the Normal Rating for Line Traps Line Traps are considered terminal equipment. The term “terminal equipment” is not defined in the NERC Glossary of Terms Used in Reliability Standards. Therefore, Seminole shall define “terminal equipment” to include, but not be limited to line traps, series reactors, breakers, circuit switchers, switches, bus and jumpers. 1 Seminole shall specify that manufacturers design line traps to conform with the standards listed in this section. 7 SEMINOLE ELECTRIC COOPERATIVE, INC. BULK ELECTRIC SYSTEM FACILITY RATING METHODOLOGY 2009-FAC-008-1-MTD-1-4 7 SERIES REACTORS Series Reactors are specified, designed1 and operated as per the following: IEEE C57.16 - IEEE Standard Requirements, Terminology, and Test Code for Dry-Type Air-Core Series-Connected Reactors Operating limits specified by the manufacturer Series Reactors have a Normal Rating that is equivalent to the nameplate ratings and/or documented ratings provided by the manufacturer (as specified by the above IEEE standard) Seminole’s Emergency Rating is equivalent to the Normal Rating for Series Reactors Series reactors are classified as terminal equipment since they are utilized on Seminole’s BES as current limiting elements, when supplied with shunt compensation devices (shunt capacitors). The term “terminal equipment” is not defined in the NERC Glossary of Terms Used in Reliability Standards. Therefore, Seminole shall define “terminal equipment” to include, but not be limited to line traps, series reactors, breakers, circuit switchers, switches, bus and jumpers. 1 Seminole shall specify that manufacturers design series reactors to conform with the standards listed in this section. 8 SEMINOLE ELECTRIC COOPERATIVE, INC. BULK ELECTRIC SYSTEM FACILITY RATING METHODOLOGY 2009-FAC-008-1-MTD-1-4 8 CIRCUIT BREAKERS Circuit Breakers are specified, designed1 and operated as per the following: IEEE C37.010 - IEEE Application Guide for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis IEEE C37.011 - IEEE Application Guide for Transient Recovery Voltage for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis IEEE C37.012 - IEEE Application Guide for Capacitance Current Switching for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis IEEE C37.013 - IEEE Standard for AC High-Voltage Generator Circuit Breakers Rated on a Symmetrical Current Basis IEEE C37.04 - IEEE Standard Rating Structure for AC High-Voltage Circuit Breakers IEEE C37.04a/b - IEEE Standard Rating Structure for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis — (as applicable) Amendment 1: Capacitance Current Switching Amendment 2: To Change the Description of Transient Recovery Voltage for Harmonization with IEC 62271-100 IEEE C37.06 - AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis – Preferred Ratings and Related Required Capabilities IEEE C37.06.1 - Guide for High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis Designated “Definite Purpose for Fast Transient Recovery Voltage Rise Times” IEEE C37.09 - IEEE Standard Test Procedure for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis IEEE C37.09a - IEEE Standard Test Procedure for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis — Amendment 1: Capacitance Current Switching IEEE C37.09 / Cor 1 - IEEE Standard Test Procedure for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis— Corrigendum 1 IEEE C37.11 - IEEE Standard Requirements for Electrical Control for AC HighVoltage Circuit Breakers Rated on a Symmetrical Current Basis IEEE C57.19.00 - IEEE Standard General Requirements and Test Procedure for Power Apparatus Bushings IEEE C57.19.01 - IEEE Standard Performance Characteristics and Dimensions for Outdoor Apparatus Bushings 1 Seminole shall specify that manufacturers design circuit breakers to conform with the standards listed in this section. 9 SEMINOLE ELECTRIC COOPERATIVE, INC. BULK ELECTRIC SYSTEM FACILITY RATING METHODOLOGY 2009-FAC-008-1-MTD-1-4 IEEE C57.19.100 - IEEE Guide for Application of Power Apparatus Bushings Operating limits specified by the manufacturer Circuit Breakers have a Normal Rating that is equivalent to the nameplate ratings and/or documented ratings provided by the manufacturer (as specified in the above IEEE standards) Seminole’s Emergency Rating is equivalent to the Normal Rating for Circuit Breakers Circuit Breakers are considered terminal equipment. The term “terminal equipment” is not defined in the NERC Glossary of Terms Used in Reliability Standards. Therefore, Seminole shall define “terminal equipment” to include, but not be limited to line traps, series reactors, breakers, circuit switchers, switches, bus and jumpers. 10 SEMINOLE ELECTRIC COOPERATIVE, INC. BULK ELECTRIC SYSTEM FACILITY RATING METHODOLOGY 2009-FAC-008-1-MTD-1-4 9 CIRCUIT SWITCHERS Circuit Switchers are specified, designed1 and operated as per the following: IEEE C37.016 - IEEE Standard for AC High-Voltage Circuit Switchers rated 15.5 kV through 245 kV IEEE 1247 - IEEE Standard for Interrupter Switches for Alternating Current, Rated Above 1000 V IEEE C37.04 - IEEE Standard Rating Structure for AC High-Voltage Circuit Breakers IEEE C37.06 - AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis – Preferred Ratings and Related Required Capabilities IEEE C37.09 - IEEE Standard Test Procedure for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis Operating limits specified by the manufacturer Circuit Switchers have a Normal Rating that is equivalent to the nameplate ratings and/or documented ratings provided by the manufacturer (as specified in the above IEEE standards) Seminole’s Emergency Rating is equivalent to the Normal Rating for Circuit Switchers Circuit Switchers are considered terminal equipment. The term “terminal equipment” is not defined in the NERC Glossary of Terms Used in Reliability Standards. Therefore, Seminole shall define “terminal equipment” to include, but not be limited to line traps, series reactors, breakers, circuit switchers, switches, bus and jumpers. 1 Seminole shall specify that manufacturers design circuit switchers to conform with the standards listed in this section. 11 SEMINOLE ELECTRIC COOPERATIVE, INC. BULK ELECTRIC SYSTEM FACILITY RATING METHODOLOGY 2009-FAC-008-1-MTD-1-4 10 SWITCHES Switches are specified, designed1 and operated as per the following: IEEE C37.30 - IEEE Standard Requirements for High-Voltage Switches IEEE C37.32 - IEEE / American National Standard for High Voltage Switches, Bus Supports, and Accessories Schedules of Preferred Ratings, Construction Guidelines, and Specifications IEEE C37.34 - IEEE Standard Test Code for High-Voltage Air Switches IEEE C37.35 - IEEE Guide for the Application, Installation, Operation, and Maintenance of High-Voltage Air Disconnecting and Interrupter Switches IEEE C37.36b - IEEE Guide to Current Interruption with Horn-Gap Air Switches IEEE C37.37 - IEEE Loading Guide for AC High-Voltage Air Switches (in Excess of 1000 V) Operating limits specified by the manufacturer Switches have a Normal Rating that is equivalent to the nameplate ratings and/or documented ratings provided by the manufacturer (as specified by the above IEEE standards) Seminole’s Emergency Rating is equivalent to the Normal Rating for switches Switches are considered terminal equipment. The term “terminal equipment” is not defined in the NERC Glossary of Terms Used in Reliability Standards. Therefore, Seminole shall define “terminal equipment” to include, but not be limited to line traps, series reactors, breakers, circuit switchers, switches, bus and jumpers. 1 Seminole shall specify that manufacturers design switches to conform with the standards listed in this section. 12 SEMINOLE ELECTRIC COOPERATIVE, INC. BULK ELECTRIC SYSTEM FACILITY RATING METHODOLOGY 2009-FAC-008-1-MTD-1-4 11 BUS A rigid-bus structure (rigid bus) is specified, designed and operated as per the following: IEEE 605 - IEEE Guide for Design of Substation Rigid-Bus Structures IEEE 1427 - IEEE Guide for Recommended Electrical Clearances and Insulation Levels in Air-Insulated Electrical Power Substations Aluminum Electrical Conductor Handbook, Third Edition, Chapter 13, The Aluminum Association, 1989 (as applicable) Operating limits specified by the manufacturer Nameplate ratings do not exist for rigid bus. Therefore, the Normal Rating of rigid bus shall be defined as follows: The rated system voltage of rigid bus shall be determined based on the clearances specified in the above standards (as applicable) Rigid bus conductor shall have a continuous current rating that is achieved at the maximum allowable bus temperature specified below Design Parameters Value Wind Speed NOTE: Actual wind speed is 3.0 ft/s. Since IEEE 605 ampacity calculations are based on documented testing at a more conservative wind speed of 2.0 ft/s, this was the wind speed chosen for calculations. Latitude Time Environmental Conditions Ambient Temperature Total Irradiation (Sun & Atmosphere) Coefficient of Emissivity Maximum Allowable Steady-State Rigid Bus Temperature Maximum Short-Circuit Rigid Bus Temperature (Maximum Duration = 13 cycles = 0.217 s) 2.0 ft / s perpendicular to the bus 30° 12:00 PM Clear Summer - 35°C Winter - 0°C 96.4 W/ft2 0.5 Aluminum - 90°C Aluminum - 100°C Seminole’s Emergency Rating is equivalent to the Normal Rating for rigid bus Strain bus and jumpers are specified, designed and operated as per the requirements for Transmission Lines (see Section 2 - Transmission Lines). Strain bus and jumpers are rated for operation at the maximum allowable conductor temperature specified in Section 2 for each type of conductor. Rigid bus, strain bus, and jumpers are considered terminal equipment. The term “terminal equipment” is not defined in the NERC Glossary of Terms Used in Reliability Standards. Therefore, Seminole shall define “terminal equipment” to include, but not be limited to line traps, series reactors, breakers, circuit switchers, switches, bus and jumpers. 13 SEMINOLE ELECTRIC COOPERATIVE, INC. BULK ELECTRIC SYSTEM FACILITY RATING METHODOLOGY 2009-FAC-008-1-MTD-1-4 12 SHUNT COMPENSATION DEVICES (SHUNT CAPACITORS) Seminole installs shunt compensation devices (shunt capacitors) to deliver reactive power as specified by the manufacturer’s nameplate rating when the substation bus operates at 1.0 per unit voltage. Shunt capacitors are specified, designed1 and operated as per the following: IEEE 18 - IEEE Standard for Shunt Power Capacitors IEEE 1036 - IEEE Guide for Application of Shunt Power Capacitors IEEE C37.40 - IEEE Standard Service Conditions and Definitions for High-Voltage Fuses, Distribution Enclosed Single-Pole Air Switches, Fuse Disconnecting Switches, and Accessories IEEE C37.41 - IEEE Standard Design Tests for High-Voltage (>1000 V) Fuses, Fuse and Disconnecting Cutouts, Distribution Enclosed Single-Pole Air Switches, Fuse Disconnecting Switches, and Fuse Links and Accessories Used with These Devices IEEE C37.43 - IEEE Standard Specifications for High-Voltage Expulsion, CurrentLimiting, and Combination-Type Distribution and Power Class External Fuses, with Rated Voltages from 1 kV through 38 kV, Used for the Protection of Shunt Capacitors IEEE C37.46 - American National Standard for High Voltage Expulsion and CurrentLimiting Type Power Class Fuses and Fuse Disconnecting Switches IEEE C37.48 - IEEE Guide for the Application, Operation, and Maintenance of HighVoltage Fuses, Distribution Enclosed Single-Pole Air Switches, Fuse Disconnecting Switches, and Accessories IEEE C37.48.1 - IEEE Guide for the Operation, Classification, Application, and Coordination of Current-Limiting Fuses with Rated Voltages 1 – 38 kV IEEE C37.99 - IEEE Guide for the Protection of Shunt Capacitor Banks (as applicable) IEEE C57.19.00 - IEEE Standard General Requirements and Test Procedure for Power Apparatus Bushings IEEE C57.19.01 - IEEE Standard Performance Characteristics and Dimensions for Outdoor Apparatus Bushings IEEE C57.19.100 - IEEE Guide for Application of Power Apparatus Bushings Shunt capacitors shall be capable of operating continuously over the full range of normal system voltage conditions and ranges to which these shunt compensation devices will be subjected. Operating limits specified by the manufacturer Shunt capacitors have a Normal Rating that is equivalent to the nameplate ratings and/or documented ratings provided by the manufacturer (as specified by the above IEEE standards) Seminole’s Emergency Rating is equivalent to the Normal Rating for shunt capacitors 1 Seminole shall specify that manufacturers design shunt capacitors to conform with the standards listed in this section. 14 SEMINOLE ELECTRIC COOPERATIVE, INC. BULK ELECTRIC SYSTEM FACILITY RATING METHODOLOGY 2009-FAC-008-1-MTD-1-4 13 GENERATORS Seminole Generating Station (SGS) SGS is comprised of two coal fired boilers that each provides steam separately to two steam turbine driven generators. The generators are referred to as #1 and #2. The generators are hydrogen cooled. Midulla Generating Station (MGS) MGS is comprised of a combined cycle gas turbine(s) and set of simple cycle peaking gas turbines. The combined cycle plant is fueled by natural gas or #2 fuel oil and consists of two combustion turbine driven generators and one steam turbine driven generator. The combined cycle combustion turbine driven generators are referred to as #1 and #2. The steam turbine generator is referred to as #3. The peaking plant consists of five simple cycle, aero derivative combustion turbine driven generators fueled by natural gas or #2 fuel oil. The peaking unit generators are referred to as generators #4, #5, #6, #7 & #8. All of the generators at MGS are air cooled. The normal continuous rating of the generation facility is based on manufacturer’s nameplate rating and the associated capability curves specific to a given generator. The rating for the entire generation facility is based on the most limiting rating for all of the equipment that comprises the facility. Seminole’s generation facilities are limited to the manufacturer’s nameplate rating which are subject to ambient conditions. The generation facilities’ power output is limited to the manufacturer’s normal nameplate rating; i.e., no emergency output rating, beyond normal, is allowed. 15 SEMINOLE ELECTRIC COOPERATIVE, INC. BULK ELECTRIC SYSTEM FACILITY RATING METHODOLOGY 2009-FAC-008-1-MTD-1-4 14 DISTRIBUTION OF FACILITY RATING METHODOLOGY Seminole posts its Bulk Electric System (BES) Facility Rating Methodology document on the Seminole OASIS node. The Seminole BES Facility Rating Methodology is available for inspection and technical review by those entities that have responsibility for the area in which, Seminole Facilities are located. Those entities may include, but are not limited to: Reliability Coordinators Transmission Operators Transmission Planners Planning Authorities For immediate access to Seminole’s BES Facility Rating Methodology, please download the document from Seminole’s OASIS node (to be posted by 09-10-2009). Seminole’s BES Facility Rating Methodology is directly available from Seminole within 15 business days of receipt of a request. Any entity who wishes to provide written comments on the Seminole BES Facility Rating Methodology, may send those comments to the Manager – Transmission and Substation Engineering. Seminole shall provide a written response to that commenting entity within 45 calendar days of receipt of those comments. The response shall indicate whether a change(s) will be made to the Seminole BES Facility Rating Methodology. If no change(s) will be made to the BES Facility Rating Methodology, Seminole shall state the reason for its disposition. If modifications to the Seminole BES Facility Rating Methodology document are required based on the submitted comments, Seminole will make the appropriate modifications and repost the document on Seminole’s OASIS node with a new document revision number and date. 15 REVIEW OF SEMINOLE FACILITY RATINGS Seminole will review its Facility Ratings for all facilities on an annual basis. To the extent that any facility ratings have been modified, those new ratings will be communicated to the FRCC as part of the Load Flow Databank Process. 16