ADVANCE GRP Series 125A

advertisement
ADVANCE GRP Series 125A
Switched Interlocked socket outlets
ADVANCE GRP Series 125A
> SWITCHED INTERLOCKED SOCKET OUTLETS
> REFERENCE STANDARDS
EN 60309-1
Plugs, socket outlets and couples for industrial purposes.
Part 1: general requirements.
EN 60309-2
Plugs, socket outlets and couples for industrial purposes.
Part 2: dimensional interchangeability requirements for pin
and contact-tube accessories of harmonised configurations.
EN 60309-4
Plugs, socket-outlets and couplers for industrial purposes.
Part 4: Switched socket-outlets
and connectors with or without interlock.
> VERSIONS WITH MECHANICAL INTERLOCK
With switch-disconnector
IEC 61241-0 / EN 61241-0
Electrical apparatus for use
in the presence of combustible dust.
Part 0: General requirements.
With switch-disconnector and fuse
IEC 61241-1 / EN 61241-1
Electrical apparatus for use
in the presence of combustible dust.
Part 1: Protection by enclosures 'tD'.
With fuse and switch
> PRODUCTS FOR USE IN A POTENTIALY
EXPLOSIVE ENVIRONMENT
With molded case circuit breaker with
thermal magnetic trip unit
With molded case circuit breaker with
thermal magnetic and residual current
release trip units
> VERSIONS WITH ELECTRICAL INTERLOCK
With contactor
2
Scame offers products suitable for installation into
environments under potential risk of explosion identified as
Zone 22 and that enter into the field of application for the
ATEX Directive (European Directive 94/9/CE).
Saline
solution
Resistant
Bases
Acids
Solvents
Concentrated
Diluted
Concentrated
Diluted
Hexane
Benzol
Acetone
Alcohol
Limited
Resistance
Resistant
Not
Resistant
Resistant
Limited
Resistance
Limited
Resistance
Limited
Resistance
Limited
Resistance
Mineral
oil
UV
rays
Resistant
Resistant
ADVANCE GRP Series 125A
> BEHAVIOUR WITH CHEMICAL AND ATMOSPHERIC AGENTS
For specific substances please contact our technical service
> TECHNICAL CHARACTERISTICS
Rated current:
Rated voltage:
Frequency:
Insulating voltage:
Protection degree:
Operating temperature
according to the
reference standard:
Max. operating
temperature:
Self-extinguishing GW test:
Self-extinguishing UL94:
Material:
IK degree at 20°C:
Cable inlets:
125A
100÷690V~
50÷60Hz
500/690V~
IP66
-25°C+40°C
60°C
850°C/960°C
V0
Thermoset
IK10
Top side max 3xM63
Bottom side max 2xM63
Switch-disconnectors:
ABB OT 160
Fuse:
NH00
Thermal magnetic protection: Molded case circuit breaker
ABB Tmax T1B (16kA) with
thermal magnetic trip unit
TMD (adjustable thermal
threshold 0,7…1 x In fixed
magnetic threshold 10 x In)
Thermal-magnetic and
Molded case circuit breaker
residual current protection: ABB Tmax T1B (16kA) with
thermal magnetic trip unit
TMD (adjustable thermal
threshold 0,7…1 x In fixed
magnetic threshold 10 x In) +
residual current release trip
units RC221/1 (adjustable
residual current trip 0,03 - 0,1
- 3A and time limit for non-trip
instantaneous)
Version with contactor:
Contactor CL09 GE POWER
CONTROL
Colour:
Grey RAL7037
> EX CLASSIFICATION
Atex Code:
II 3D
Ex Protection type:
Ex tD A22 IP66 T90°C
Operating Temperature
Range:
-25°C +60°C
Maximum permissible
surface temperature:
T90°C
Switched socket outlets with
interlock degree of Protection: IP66
Plugs - degree of Protection: IP66/IP67
Impact Resistance:
7J
Switched socket outlets with
interlock material:
Thermoset
Plugs material:
Thermoplastic
Interlocked switch sockets
outlets CE certificate:
SCAME ATEX 02
Plugs CE certificate:
SCAME ATEX 03
Via Costa Erta 15 Parre BG ITALY
3P+N+
- 125A - 6h / 346-415V~
Cod. 503.12587-F
SCAME ATEX 02
Ex tD A22
IP66 T90°C
II 3D
DO NOT OPEN WHEN ENERGIZED
IN PRESENCE OF EXPLOSIVE ATMOSPHERE
> WIRING OPERATIONS
Wiring capacity of the terminals (mm2)
Socket outlets
Plugs
Rated current
(A)
Min
Max
Min
Max
125A
25
70
16
50
3
ADVANCE GRP Series 125A
> APPLICATION EXAMPLES
4
ADVANCE GRP Series 125A
> TECHNICAL DATA SWITCH DISCONNECTORS
125A
Vac
750
Vdc
750
Rated impulse withstand voltage Uimp
kV
12
Thermal current Ith
A
200
Thermal current Ithe
A
-
400V
A
200
500V
A
-
690V
A
160
400V
A
200
500V
A
-
690V
A
160
400V
A
135
500V
A
125
690V
A
80
400V
A
-
690V
A
-
300V
A
160(*)
250V
A
160(*)
600V
A
-
A
4000
kA
24
kA
30
kA
1200
600V
A
125
120V
Hp
7,5
240V
Hp
20
240V
480V
600V
Hp
Hp
Hp
40
75
100
Rated insulation voltage Ui
AC21A Resistite loads, inluding
moderate overloads
Nominal current rating Ie
Mixed resistite and inductive loads,
AC22A
including moderate overloads
Switching off motor loads or other
AC23A highly inductive loads
(3 phase/3 pole)
AC3
Squirrel-cage motor: starting,
switching off motor during running (3 phase/ 3 pole)
DC21A
Resistite loads, including
Moderate overloads
DC22A
Mixed resistite and inductive loads,
including moderate overloads
Short-circuit
protection
Rated short-time withstand current Icw (s)
Conditional short-circuit current
Associate fuse size for conditional
short-circuit current - Type gG
Rated short-circuit making capacity Icm
Rated current UL
General applications - Single-phase and Three-phase
AC motor, all-pole interruption - Single-phase
AC motor, B, C, D, all-pole interruption - Three-phase
Permissible wire
range
500V
mm2
10-70
AWG
8-1/10
Wire
(*) 2+2 poles in series
5
ADVANCE GRP Series 125A
Outdoor wall
fastening
Ample space for
easy wiring
Under-plate cable
runway
Switchdisconnector with
mechanical lock
that can be
accessorized with
auxiliary contacts
Threaded metal
inserts
Punched marks for
easy closure of the
cover
Easily extractable
bottom plate
Possibility to
assemble
microswitch
BOTTOM VIEW
TOP VIEW
Module in hightemperature glassfibre filled
engineering
polymer
Possible entry from
bottom side (input-output also)
6
Self-centering punch
marks to facilitate drilling
ADVANCE GRP Series 125A
Single-piece
waterproof gasket
Rating on metal
plate
Captive stainless
steel closing
screws
Lockable
Switch
in position 0
and 1
High-strength
material with
superior UV and
chemical
resistance
Double mechanical
lock and metal
levers
Residual current
release trip units
test push button
Cover entirely
separate from the
base for easy
installation
An electronic device controls the status of the interlocked socket, monitoring the electrical
functionality:
- operation of the signalling and control card is guaranteed even when the load is not
connected;
- indicates that the fuses are not open and all the phases are present (indicator light on);
- indicates that the socket outlet is powered correctly (indicator light on);
- signals the interruption of one or more fuses (indicator light flashing);
- signals the absence of a phase (indicator light flashing)*;
- indicates that the socket outlet is not powered (indicator light off).
* for single-phase products in the event of phase/ neutral loss LED signaling appears off.
7
ADVANCE GRP Series 125A
> MECHANICALLY INTERLOCKED SOCKET OUTLETS - IP66
Description
Switchdisconnector
Description
Switchdisconnector
and fuse (*)
Description
Fuse (*)
and switch
Description
Plug
Volt
2P+E 125A
50/60
200-250V
6
1
503.12583
3P+E 125A
50/60
380-415V
6
1
503.12586
3P+N+E 125A 50/60
346-415V
6
1
503.12587
Hz
Volt
2P+E 125A
50/60
200-205V
6
1
503.12583-F
3P+E 125A
50/60
380-415V
6
1
503.12586-F
3P+N+E 125A 50/60
346-415V
6
1
503.12587-F
Plug
2P+E 125A
50/60
200-205V
6
1
503.12583-FS
3P+E 125A
50/60
380-415V
6
1
503.12586-FS
3P+N+E 125A 50/60
346-415V
6
1
503.12587-FS
Plug
Hz
Plug
Hz
(*) Fuses not included
Volt
Colour
h
Volt
Molded case
2P+E 125A
50/60
circuit breaker with
thermal magnetic 3P+E 125A
50/60
and residual current
release trip units 3P+N+E 125A 50/60
8
Colour
Hz
Plug
Molded case
2P+E 125A
50/60
circuit breaker
3P+E 125A
50/60
with thermal
magnetic trip unit 3P+N+E 125A 50/60
Description
Colour
h
Hz
Colour
h
h
200-205V
6
1
503.12583-M
380-415V
6
1
503.12586-M
346-415V
6
1
503.12587-M
Volt
Colour
h
200-205V
6
1
503.12583-RM
380-415V
6
1
503.12586-RM
346-415V
6
1
503.12587-RM
Pack Quantity.
Description
Contactor (*)
Hz
Volt
2P+E 125A
50/60
200-205V
6
1
503.12583-T
3P+E 125A
50/60
380-415V
6
1
503.12586-T
3P+N+E 125A 50/60
346-415V
6
1
503.12587-T
Plug
Colour
ADVANCE GRP Series 125A
> ELECTRICALLY INTERLOCKED SOCKET OUTLETS - IP66
h
(*) Microswitch already provided.
Contactor operated by microswitch.
> ACCESSORIES
Description
Terminals
Contacts
Microswitch kit 400V 10A
1NO+1NC
(microswitch + terminal block)
4x4 mm2
579.0125
For products with mechanical interlock.
> COMPLEMENTARY PRODUCTS - OPTIMA-EX SERIES - PLUGS IP66/IP67
Description
Plugs
Plug
Hz
Volt
Colour
h
2P+E 125A
50/60
200-250V
6
1
218.EX12533
3P+E 125A
50/60
380-415V
6
1
218.EX12536
3P+N+E 125A 50/60
346-415V
6
1
218.EX12537
9
ADVANCE GRP Series 125A
> DIMENSIONS
(Dimensions in mm)
10
Switch-disconnector and fuse
Fuse and switch
Molded case circuit breaker with
thermal magnetic trip unit
Molded case circuit breaker with
thermal magnetic and residual
current release trip units
Contactor
ADVANCE GRP Series 125A
Switch-disconnector
(Dimensions in mm)
11
ZP00738-GB-2
ScameOnLine
www.scame.com
export@scame.com
SCAME PARRE S.p.A.
VIA COSTA ERTA, 15
24020 PARRE (BG) ITALY
TEL. +39 035 705000
FAX +39 035 703122
Download