Phoenix Contact CLIPLINE Special Terminal Blocks

advertisement
454
PHOENIX CONTACT
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370
Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Special terminal blocks
Circuit breakers and feed-through terminal blocks
The more varied the tasks in electrical
engineering, the more varied the
components for the solution have to be.
The industrial connection technology from
Phoenix Contact hence contains more than
just modular terminal blocks.
Circuit breakers
For the optimum protection of your
systems, Phoenix Contact offers highquality circuit breakers in the following
versions:
– Thermal circuit breakers TCP
They are ideally suited as device
protection for AC and DC loads, e.g. to
protect motors, transformers and
actuators against overloads
– Thermomagnetic circuit breakers TMC
They combine the advantages of thermal
and magnetic trigger mechanisms and are
typically used in information and
communication technology as well as in
process control
– Electronic circuit breakers ECP
They are designed specifically for selective
protection of all load circuits that are fed
by a 24 V DC power supply unit. They
respond to overload or short-circuit
faster than the power supply unit, and
they selectively switch off the faulty load
circuit before the power supply unit
switches off all connected loads to
protect itself
Program overview
Circuit breakers
456
Thermal circuit breakers
Thermomagnetic circuit breakers
Electronic circuit breakers
458
460
464
Feed-through terminal blocks
470
Feed-through terminal blocks
The feed-through terminal blocks from
Phoenix Contact are always used when
currents of different magnitudes have to be
guided through a panel. They are available in
three designs:
– For snapping into the housing panel
– For molding for fully-insulated
transformers and filter modules and
– As feed-through terminal blocks for high
currents
Detailed information on the feedthrough terminal blocks can be found
in the "COMBICON device
connection technology" catalog or at
www.phoenixcontact.net/eshop
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370
Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
PHOENIX CONTACT
455
Special terminal blocks
Circuit breakers
Thermal circuit breakers
The TCP thermal circuit breakers
protect inductive consumers against
overloads in distribution systems in the
control cabinet and plant engineering.
456
PHOENIX CONTACT
Thermomagnetic circuit breakers
TMC thermomagnetic circuit breakers
provide protection against overloads and
short-circuits in the field of information and
communication technology, in process
control as well as in devices and systems.
Electronic circuit breakers
The ECP and ECP-E electronic circuit
breakers have been developed to provide
distinct protection even in 24 V DC load
circuits. They protect all loads that are fed
by a switched-mode power supply unit.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370
Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Special terminal blocks
Circuit breakers
The TCP .../DC 32V pluggable thermal
miniature circuit breakers combine the
protective mechanism of an auto flat-type
fuse with the advantages of an automatic
device. Potential distribution is carried out
through the basic terminal blocks.
The TCP pluggable thermal circuit
breakers with an integrated ON/OFF
switching function are available in compact
sizes between 0.25 and 10 A. Potential
distribution is carried out through the basic
terminal blocks.
The UT 6-TMC thermomagnetic circuit
breakers are characterized by their compact
design and large-surface labeling options.
They are integrated into the CLIPLINE
complete system using the plug-in bridge
shaft.
The TMC thermomagnetic circuit
breakers have signal contacts and are
available with two different trigger
characteristics and as 1-, 2- and 3-pos.
versions from 0.2 A to 16 A.
The TMCP pluggable thermomagnetic
circuit breaker has single and group signal
contacts. The signal contacts and supply
potentials are simply cabled using plug-in
bridges.
The EC-E electronic circuit breakers
offer an additional bridgeable terminal point
for the load return conductor in addition to
fault current limitation and bridgeable signal
contacts for single, group or reset function.
The ECP-E electronic circuit breakers
differ from the EC-E versions in their
pluggable modularity as a result of the
TMCP-SOCKET-M base.
The ECP circuit breakers are a
combination of electronic and thermal
circuit breakers; in the event of an error,
they interrupt the load circuit electrically.
The TMCP, EC-E and ECP pluggable
circuit breakers are characterized by their
modular design.
Thanks to this modular structure, they
can be customized according to the
application and can always be expanded or
replaced.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370
Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
PHOENIX CONTACT
457
Special terminal blocks
Circuit breakers
Thermal circuit breaker TCP ...
20,3
6
2,7
24
4
3,4
6,4
TCP ...DC32V
Dimensions
Length
20
Umax. [V]
32
Height
31.2
Max. Ø [mm²]
-
IEC
UL / CUL
CSA
[V]
32
-
-
[A]
32 V AC/DC
Dependent on the article variant selected
[mm]
Width
6
Max. electrical data
The pluggable thermal circuit breaker
TCP .../DC32V combines the protective
mechanism of an automobile flat-type fuse
with the advantages of a circuit breaker.
The switching back on function of the
TCP .../DC32V eliminates the timeintensive search for a suitable replacement
fuse.
The TCP .../DC32V can be used to
protect integrated circuits in all battery and
on-board systems in the DC voltage range
up to 32 V.
The thermal circuit breaker fits in all fuse
holders designed for flat-type fuse inserts in
acc. with ISO 8820-3 (DIN 72581-3).
The basic terminal block is available in a
screw version (UK 6-FSI/C) and a springcage version (ST 4-FSI/C).
Rated data
Rated voltage
Operating data
Nominal voltage
Nominal current
Disconnection
Switch-off time
Typical behavior
Switching capacity ICN
TCP 5/DC32V- TCP 30/DC32V
Life
Cycles with approx. 50 A
General data
Height
Weight
Temperature range
AWG
IEC/
EN 60079-7
-
Refer to the time/current characteristic curve
Slow-blow
[A]
150
300
[mm]
[g]
[°C]
17
5
-30 ... 60
-
Nominal
current
Color
Type
Order No.
Pcs. /
Pkt.
5A
Light brown
TCP 5/DC32V
0700005
50
7.5 A
10 A
15 A
20 A
25 A
30 A
Brown
Red
Blue
Yellow
White
Light Green
TCP 7,5/DC32V
TCP 10/DC32V
TCP 15/DC32V
TCP 20/DC32V
TCP 25/DC32V
TCP 30/DC32V
0700007
0700010
0700015
0700020
0700025
0700030
50
50
50
50
50
50
Ordering data
Description
One-pos., thermal circuit breaker, for
fuse holders in acc. with ISO 8820-3
Attention: The reset button must not be obstructed. During
installation, please leave enough room for using button.
For more technical data, drawings and accessories, visit
www.phoenixcontact.net/eshop.
1) If the fuse is faulty, the downstream circuit is not off load.
Accessories
Fuse terminal block, with spring-cage
connection, for mounting on NS 35...
With light indicator for 12 V DC, 1.7 mA
Black
Black
ST 4-FSI/C
ST 4-FSI/C-LED 12
3036372
3036495
50
50
With light indicator for 24 V DC, 1.9 mA
Black
ST 4-FSI/C-LED 24
3036505
50
Black
Black
Black
UK 6-FSI/C
UK 6-FSI/C-LED12
UK 6-FSI/C-LED24
3118203
3001925
3001938
50
50
50
Fuse terminal block, for mounting on NS 32... or NS 35...
Response time [s]
With LED for 12 V DC
With light indicator for 24 V DC, 1.9 mA1)
10
4
TCP/DC32V
5A
10
4
TCP/DC32V
7,5 A - 30 A
3
10
102
10
10
-40°C
10
3
2
-40°C
10
+23°C
+23°C
1
+85°C
0,1
0,4 1 2
1
4
10
20
+85°C
0,1
0,4 1 2
4
10 20
Current [A]
458
PHOENIX CONTACT
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370
Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Special terminal blocks
Circuit breakers
Thermal Circuit Breaker TCP
Note:
When mounted in rows, the nominal current of the devices can be
transmitted only at 80% or must be correspondingly
overdimensioned.
For more technical data, drawings and accessories, visit
www.phoenixcontact.net/eshop.
TCP ...
uJP
Dimensions
Length
24.5
Umax. [V]
250
Height
55
Max. Ø [mm²]
-
IEC
UL / CUL
CSA
[V]
[V]
250
65
-
-
[A]
250 V AC
Dependent on the article variant selected
[mm]
Width
8.2
Max. electrical data
The thermal miniature circuit breaker can
be switched back on again, has a compact
design, and is available in 9 fine nominal
current gradations from 0.25 to 10 A.
The integrated switching function makes
it possible to switch the circuit breaker back
on immediately, thus guaranteeing the
availability of the system.
Potential distribution can be conveniently
implemented using bridges.
A complete data sheet is available for
the relevant item at
www.phoenixcontact.net/eshop for
downloading.
Rated data
Rated voltage
Rated voltage DC
Operating data
Nominal voltage
Nominal current
Disconnection
Switch-off time
Typical behavior
Switching capacity ICN
TCP 0.25 A - TCP 4 A
TCP 6 A - TCP 10 A
Life
Cycles with 1 x IN
Cycles with 2 x IN
General data
Weight
Temperature range
Insulating material
Inflammability class acc. to UL 94
AWG
IEC/
EN 60079-7
-
Refer to the time/current characteristic curve
Slow-blow
6 x IN
8 x IN
3000
500
[g]
[°C]
15
-20 ... 60
PA
V0
Ordering data
Description
Thermal miniature circuit breaker,
can be plugged into UK 6 FSI/C or ST 4FSI/C fuse terminal block
Nominal
current
Color
Type
Order No.
Pcs. /
Pkt.
0.25 A
Black
TCP 0,25A
0712123
20
0.5 A
1A
2A
3A
4A
6A
8A
10 A
Black
Black
Black
Black
Black
Black
Black
Black
TCP 0,5A
TCP 1A
TCP 2A
TCP 3A
TCP 4A
TCP 6A
TCP 8A
TCP 10A
0712152
0712194
0712217
0712233
0712259
0712275
0712291
0712314
20
20
20
20
20
20
20
20
UK 6-FSI/C
3118203
50
ST 4-FSI/C
3036372
50
Accessories
Response [s]
Fuse terminal block, for mounting on NS 32... or
Black
NS 35...
Fuse terminal block, with spring-cage
Black
connection, for mounting on NS 35...
Zack marker strip, flat, for labeling in the outer marker grooves,
White
10
4
10
10
ZB 5 (see page 487)
0,25 - 4 A
6 - 10 A
3
2
10
1
0,1
0,8 1
2
4
6
8 10
20
30
Multiples of IN
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370
Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
PHOENIX CONTACT
459
Special terminal blocks
Circuit breakers
Thermomagnetic circuit breaker
UT 6-TMC ...
For more technical data, drawings and accessories, visit
www.phoenixcontact.net/eshop.
Dimensions
[mm]
Max. electrical data
Switching time [s]
The UT 6-TMC thermomagnetic circuit
breakers are impressive due to their
compact design, large-surface labeling
options and the double plug-in bridge shafts.
They are integrated into the CLIPLINE
complete system via the plug-in bridge
shaft.
10000
< 7,0A
> 7,0A
1000
100
Thanks to their restartability and clear
status display, the device protection
switches ensure high system availability.
Eleven nominal current levels from 0.5 A to
16 A are available.
The large-surface center labeling enables
a clear allocation of the relevant circuit
breaker.
Rated data
Rated voltage
Nominal current / cross-section
Rated cross-section
Cross-section range
Connection capacity
Color
Gray
1A
2A
4A
5A
6A
8A
10 A
12 A
15 A
16 A
Gray
Gray
Gray
Gray
Gray
Gray
Gray
Gray
Gray
Gray
Plug-in bridge for cross connections in the bridge
shaft
2
3
4
5
10
20
Warning sign for UT series
Screwdriver
UniCard sheet, for labeling the lateral groove
Red
Red
Red
Red
Red
Red
Yellow
0,01
6 8 10
20
40 60 100
Multiples of IN
Trigger characteristic
A complete data sheet is available for
the relevant item at
www.phoenixcontact.net/eshop for
downloading.
[g]
[°C]
0.5 A
0,1
2 3 4
[A]
[A]
Nominal
current
Thermomagnetic circuit breaker, for
mounting on NS 35...
1
[A]
Ordering data
1
0,001
[mm2]
[mm2]
[mm2]
One conductor
Two conductors (of the same type)
Two stranded conductors with a TWIN ferrule
Operating data
Nominal voltage
Nominal voltage
Nominal current
Switch-off time
Switching capacity ICN
UT 6-TMC ... 0.5 A - UT 6-TMC ... 5 A
UT 6-TMC ... 6 A - UT 6-TMC ... 16 A
Life
Cycles with 1 x IN
General data
Weight
Temperature range
Insulating material
Inflammability class acc. to UL 94
Description
10
[V]
[A] / [mm²]
[mm2]
AWG
Accessories
Zack marker strip, for labeling the lateral groove
460
PHOENIX CONTACT
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370
Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Special terminal blocks
Circuit breakers
UT 6-TMC M ...
Width
12.3
Length
86
Umax. [V]
240
Height NS 35/7,5
88.5
Max. Ø [mm²] AWG
0.2 - 10
24 - 8
IEC
UL / CUL
CSA
240
0.5 / 6
6
24 - 8
Solid
-/Stranded
0.2 - 10
0.2 - 2.5
0.2 - 10
0.2 - 2.5
IEC/
EN 60079-7
-/-/Ferrule
without / with plastic sleeve
0.25 - 6
0.25 - 6
0.25 - 1.5
0.5 - 4
240 V AC
28 V DC
Dependent on the article variant selected
Refer to the time/current characteristic curve
200 AC / 400 DC
200 AC / 400 DC
5000
50
-5 ... 60
PA
V0
Type
Imax
Order No.
Pcs. /
Pkt.
UT 6-TMC M 0,5A
0916603
6
UT 6-TMC M 1A
UT 6-TMC M 2A
UT 6-TMC M 4A
UT 6-TMC M 5A
UT 6-TMC M 6A
UT 6-TMC M 8A
UT 6-TMC M 10A
UT 6-TMC M 12A
UT 6-TMC M 15A
UT 6-TMC M 16A
0916604
0916605
0916606
0916607
0916608
0916609
0916610
0916611
0916612
0916613
6
6
6
6
6
6
6
6
6
6
3030336
3030242
3030255
3030349
3030271
3030365
3047345
1205066
50
50
50
50
10
10
10
10
FBS 2-6
FBS 3-6
FBS 4-6
FBS 5-6
FBS 10-6
FBS 20-6
WS UT 6
SZS 1,0X4,0
UC-TM 12 (see page 481)
32 A
32 A
32 A
32 A
32 A
32 A
ZB 12 (see page 490)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370
Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
PHOENIX CONTACT
461
Special terminal blocks
Circuit breakers
Thermomagnetic Circuit Protector
TMC
The TMC circuit breaker is available for
different nominal current values, with a fast
or normal blow characteristic curve and a
one, two or three-pos. main current path.
All types of the pluggable device circuit
breaker TMCP have integrated signal
contacts as well.
For more technical data, drawings and accessories, visit
www.phoenixcontact.net/eshop.
1) Please observe the type key on the right side.
2) DC
3) Main contact
4) Auxiliary contact
TMC ...
TMCP ...
ACJP
Dimensions
[mm]
Dimensions
[mm]
Dimensions
[mm]
Width
12.5
Width
12.5
Width
12.5
Length
83.5
Length
83.5
Length
83.5
Umax. [V]
250
Height NS 35/7,5
96
Height NS 32
100.5
Height
Max. Ø [mm²] AWG
0.2 - 63)
24 - 10
Width
12.5
Width
12.5
Width
12.5
-/-
250
652)
0.2 / -
24 - 10
Solid
-/Stranded
Max. electrical data
Rated data
Rated voltage
Rated voltage DC
Nominal current / cross-section
Rated cross-section
Cross-section range
Connection capacity
[V]
[V]
[A] / [mm²]
[mm2]
AWG
AP
250
652)
0.2 / -
One conductor
Two conductors (of the same type)
Two stranded conductors with a TWIN ferrule
[mm2]
[mm2]
[mm2]
0.2 - 63)
0.2 - 0.75
0.2 - 4
0.2 - 0.75
One conductor
Two conductors (of the same type)
Two stranded conductors with a TWIN ferrule
Operating data
Nominal voltage
Nominal current
Disconnection
Switch-off time
Typical behavior
Switching capacity ICN
TMC ... 0.2 A - TMC ... 5 A
TMC ... 6 A - TMC ... 16 A
Life
Cycles with 1 x IN
General data
Temperature range
Insulating material
Inflammability class acc. to UL 94
[mm2]
[mm2]
[mm2]
0.2 - 2.54)
0.2 - 0.75
0.2 - 1.5
0.2 - 0.75
[A]
[A]
[A]
[°C]
-/Ferrule
without / with plastic sleeve
0.25 - 4
0.25 - 2.5
0.25 - 1
0.5 - 2.5
without / with plastic sleeve
0.25 - 2.5
0.25 - 1.5
0.25 - 0.5
0.5 - 0.75
Length
50
Length
50
Length
50
Umax. [V]
250
Height NS 35/7,5
Height NS 32
Height
96
Max. Ø [mm²]
-
AWG
-
Solid
-/Stranded
-/-
-
-
-/Ferrule
without / with plastic sleeve
-
-
-
without / with plastic sleeve
-
250 V AC
Dependent on the article variant selected
250 V AC
Dependent on the article variant selected
Refer to the time/current characteristic curve
Fast or normal blow
Refer to the time/current characteristic curve
Fast or normal blow
400
800
400
800
10000
10000
-30 ... 60
PA-F
V0
-30 ... 60
PA-F
V0
Ordering data
Nominal
current
Color
Type
Order No.
0.2 A
Black
TMC 1 F1 100 0,2A
0914015
Thermomagnetic circuit breaker,
0.2 A
pluggable, one, two or three-position1)
Spring lock, for mechanical locking in the case of
overhead mounting, 1-pos.
Black
Description
Thermomagnetic circuit breaker,
with universal foot for mounting on
NS 32... or NS 35...1)
Pcs. /
Pkt.
Type
Imax
Order No.
Pcs. /
Pkt.
6
TMCP 1 F1 300 0,2A
0915506
6
SPRING-LOCK
0713009
10
Accessories
Modular socket, 2-position, for holding two circuit
breakers, each with a single position
Black
TMCP SOCKET M
0916589
10
Socket termination elements, can be plugged in
both left and right, contain the connections for the
reset inputs/group query
Black
TMCP CONNECT LR
0916592
3
1A
0916602
6
50 A
0916615
20
Signal bridge, pluggable, for bridging group signaling when there
is a free slot on the TMCP-SOCKET-M socket
Red
Fixed bridge, pluggable, 500 mm long, can be cut to length, for
distribution of the input potential in the socket
Silver
462
PHOENIX CONTACT
TMCP SB
FBST 500 TMCP
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370
Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Special terminal blocks
Circuit breakers
Drilling diagram for the TMCP front
plate mounting
32
Note:
A mutual thermal effect occurs in the case of an assembly in rows
with concurrent load. This is equivalent to an increase in the ambient
temperature. It depends on the nominal current, the ambient
temperature, the number of devices and the distance between the
devices. The nominal current of the devices can either be overdimensioned (see multiplication factor for temperature response) or
can only be led to > 80%. Please ask for the maximum permissible
current for the assembly in rows that you plan.
16
3)
12,5 12,5
Multiplication factor for higher
ambient temperatures for TCP...,
UT 6-TMC..., TMC... and TMCP...
30
46
2)
4
1)
1,5
11,5
Multiplication factor
- 30
- 20
- 10
0
+ 10
+ 23
+ 30
+ 40
+ 50
+ 60
S
Ambient temperature °C
0.76
0.79
0.83
0.93
0.93
1.00
1.04
1.11
1.19
1.29
90°
S > 1,5 mm
1)
1-pos.
2)
2-pos.
3)
3-pos.
TMC and TMCP trigger
characteristics
Normal blow (M1): nominal value 0.2-6 A
Normal blow (M1): nominal value 8-16 A
Lower trigger limit: 1.05 IN
Upper trigger limit: 1.4 IN
Lower trigger limit: 1.05 IN
Upper trigger limit: 1.4 IN
Lower trigger limit: 1.05 IN
Upper trigger limit: 1.4 IN
-30°C
1000
+23°C
100
+50°C
10
1
0,1
DC
AC
10000
-30°C
1000
+23°C
100
+55°C
10
1
0,1
0,01
Switching time in seconds [s]
10000
Switching time in seconds [s]
Switching time in seconds [s]
10000
0,001
Fast blow (F1): nominal value 0.2-16 A
only for DC applications
DC
AC
2
3 4
6 8 10
0,001
20 30 40 60 100
The type key is used to identify the exact
structure of the item.
+55°C
10
1
0,01
1
2
3 4
6 8 10
20 30 40 60 100
Multiples of IN
TMC and TMCP type keys
+23°C
100
0,1
0,01
1
-30°C
1000
0,001
1
2
3 4
6 8 10
Multiples of IN
Type
Main current paths
Characteristic curve
Auxiliary contact versions
Nominal current
TMC
or TMCP
1 = single-pos.
2 = two-pos.
3 = three-pos.
F1 = therm. 1.05-1.4 IN,
magn. 2-4 IN DC (fast blow),
only for DC applications
M1= therm. 1.05-1.4 IN,
magn. 6-12 IN AC,
7.8-15.6 IN DC
(normal blow)
100 = single-pos.: 1 N/O contact,
200 = single-pos.: 1 N/C contact
120 = two-pos.: 1 N/O contact,
1 N/C contact
122 = three-pos.: 1 N/O contact,
2 N/C contacts
0.2 A
0.3 A
0.4 A
0.5 A
0.6 A
0.8 A
1A
1.5 A
2A
3004) = 1 N/O and 1 N/C contact
per position
Ordering example:
20 30 40 60 100
Multiples of IN
2.5 A
3A
4A
5A
6A
8A
10 A
12 A
16 A
A TMC with single-pos. main current path, one N/O contact, normal blow characteristic curve and a nominal current of 2 A.
TMC
4)
1
M1
100
2A
The only version for TMCP, not possible for TMC.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370
Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
PHOENIX CONTACT
463
Special terminal blocks
Circuit breakers
EC-E1 and EC-E4 electronic circuit
breakers
Line+
1
Line+
14
12
13
11
2
2
LOAD+
1
LOAD+
EC-E1 ...
0V
0V
3
EC-E 1 ...
3
EC-E 4 ...
A
Dimensions
[mm]
Width
12.5
Length
80
Umax. [V]
24
Height NS 35/7,5
83
Max. Ø [mm²] AWG
0.5 - 16
20 - 6
IEC
UL / CUL
CSA
24
1 / 16
16
20 - 6
Solid
0.5 - 16
0.5 - 4
-/Stranded
0.5 - 16
0.5 - 4
Max. electrical data
The EC-E... electronic circuit breaker
selectively protects all DC 24 V load
circuits on power supply units. A
combination of active electronic current
limitation for short-circuit and an overload
shutdown from 1.1 x IN onwards ensures
that the circuit breaker can react to
overloads faster than the power supply unit.
In this case, the fault current is constantly
restricted to 1.3 to 1.8 times the nominal
current.
A complete data sheet is available for
the relevant item at
www.phoenixcontact.net/eshop for
downloading.
For more technical data, drawings and accessories, visit
www.phoenixcontact.net/eshop.
Rated data
Rated voltage
Nominal current / cross-section
Rated cross-section
Cross-section range
Connection capacity
One conductor
Two conductors (of the same type)
Two stranded conductors with a TWIN ferrule
Operating data
Nominal voltage
Nominal current
Disconnection
Switch-off time
Typical behavior
[V]
[A] / [mm²]
[mm2]
AWG
[mm2]
[mm2]
[mm2]
[A]
IEC/
EN 60079-7
-/-/Ferrule
0.5 - 10
0.5 - 10
0.5 - 2.5
0.5 - 6
24 V
Dependent on the article variant selected
Refer to the time/current characteristic curve
3 s If 1.1 x IN
0.1 s If > 1.8 x IN
Switching capacity ICN
EC-E1 1A - EC-E1 12A
Life
Cycles with 1 x IN
General data
Temperature range
Insulating material
Inflammability class acc. to UL 94
Active current limitation
10000
[°C]
0 ... 50
PA-F
V0
Ordering data
Description
Electronic circuit breaker, signal
contact: 1 N/O contact
Electronic circuit breaker, signal
contact: 1 N/C contact
Stop point
typ. 1,1 x l N
Switching time [s]
10
10
1,8 x l N
4
Nominal
current
Color
Type
Order No.
Pcs. /
Pkt.
1A
Black
EC-E1 1A
0903023
6
2A
3A
4A
6A
8A
10 A
12 A
1A
Black
Black
Black
Black
Black
Black
Black
Black
EC-E1 2A
EC-E1 3A
EC-E1 4A
EC-E1 6A
EC-E1 8A
EC-E1 10A
EC-E1 12A
EC-E4 1A
0903024
0903025
0903026
0903028
0903029
0903030
0903031
0903032
6
6
6
6
6
6
6
6
2A
3A
4A
6A
8A
10 A
12 A
Black
Black
Black
Black
Black
Black
Black
EC-E4 2A
EC-E4 3A
EC-E4 4A
EC-E4 6A
EC-E4 8A
EC-E4 10A
EC-E4 12A
0903033
0903034
0903035
0903036
0903037
0903038
0903039
6
6
6
6
6
6
6
FBST 500-PLC BU
FBST 500-PLC RD
FBST 500 TMC-N GY
SZS 0,6X3,5
ZBF 12 (see page 494)
2966692
2966786
0901028
1205053
20
20
10
10
Accessories
3
Cont. plug-in bridge, 500 mm long, isolated, can
be cut to length, for potential distribution
2
10
Blue
Red
Gray
10
5
Screwdriver
Zack marker strip, flat, 10-section
1
0,1
0,01
0
1
2
IK
3
Multiples of IN
464
PHOENIX CONTACT
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370
Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Special terminal blocks
Circuit breakers
EC-E electronic circuit breakers
Line+
1
Status 23
Reset 22
2
LOAD+
EC-E ...
0V
3
EC-E ...
Dimensions
[mm]
Width
12.5
Length
80
Umax. [V]
24
Height NS 35/7,5
83
Max. Ø [mm²] AWG
0.5 - 16
26 - 6
IEC
UL / CUL
CSA
24
0.5 / 16
16
26 - 6
Solid
0.5 - 16
0.5 - 4
-/Stranded
0.5 - 16
0.5 - 4
Max. electrical data
The EC-E electronic circuit breaker
selectively protects all DC 24 V load
circuits on the power supply units. A
combination of active electronic current
limiting in the case of a short-circuit and an
overload shutdown from 1.1 x IN ensures
that the circuit breaker can react to
overloads faster than the power supply
unit.In this case, the fault current is always
restricted to 1.3 to 1.8 times the nominal
current.
A complete data sheet is available for
the relevant item at
www.phoenixcontact.net/eshop for
downloading.
For more technical data, drawings and accessories, visit
www.phoenixcontact.net/eshop.
Rated data
Rated voltage
Nominal current / cross-section
Rated cross-section
Cross-section range
Connection capacity
One conductor
Two conductors (of the same type)
Two stranded conductors with a TWIN ferrule
Operating data
Nominal voltage
Nominal current
Disconnection
Switch-off time
Typical behavior
[V]
[A] / [mm²]
[mm2]
AWG
[mm2]
[mm2]
[mm2]
[A]
IEC/
EN 60079-7
-/-/Ferrule
0.5 - 10
0.5 - 10
0.5 - 2.5
0.5 - 6
24 V
Dependent on the article variant selected
Refer to the time/current characteristic curve
5 s If 1.1 x IN
0.1 s If > 1.8 x IN
Switching capacity ICN
EC-E 0,5A DC24V - EC-E 12A DC24V
Life
Cycles with 1 x IN
General data
Temperature range
Insulating material
Inflammability class acc. to UL 94
Active current limitation
10000
[°C]
0 ... 50
PA-F
V0
Ordering data
Description
Electronic circuit breaker, with reset
input
Nominal
current
Color
Type
Order No.
Pcs. /
Pkt.
0.5 A
Black
EC-E 0,5A DC24V
0903041
6
1A
2A
3A
4A
6A
8A
10 A
12 A
Black
Black
Black
Black
Black
Black
Black
Black
EC-E 1A DC24V
EC-E 2A DC24V
EC-E 3A DC24V
EC-E 4A DC24V
EC-E 6A DC24V
EC-E 8A DC24V
EC-E 10A DC24V
EC-E 12A DC24V
0903042
0903043
0903044
0903045
0903046
0903047
0903048
0903049
6
6
6
6
6
6
6
6
FBST 500-PLC BU
FBST 500-PLC RD
FBST 500 TMC-N GY
SZS 0,6X3,5
ZBF 12 (see page 494)
2966692
2966786
0901028
1205053
20
20
10
10
Accessories
Cont. plug-in bridge, 500 mm long, isolated, can
be cut to length, for potential distribution
Switching time [s]
Stop point
typ. 1,1 x l N
10
10
Blue
Red
Gray
1,8 x l N
Screwdriver
Zack marker strip, flat, 10-section
4
3
2
10
10
5
1
0,1
0,01
0
1
2
IK
3
Multiples of IN
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370
Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
PHOENIX CONTACT
465
Special terminal blocks
Circuit breakers
Electronic circuit breaker ECP-E with
reset input and status output
GND (-)
13
Reset
14
Reset
12
Status
2
LOAD (L+)
On/Off
Control Unit
LINE (+)
11
For more technical data, drawings and accessories, visit
www.phoenixcontact.net/eshop.
1
The area of application for the electronic
circuit breaker ECP-E extends to all aspects
connected with the power supply unit. In
the event of an overload, power supply units
reduce their output voltage and all the
connected loads are no longer supplied with
sufficient power, e.g. in the case of shortcircuit at the load.
This is remedied here by the electronic
circuit breaker ECP-E that protects all DC
24 volt load circuits selectively. The ECP-E
constantly limits the fault current at 1.8
times the protected nominal current.
Capacitive loads can thus be switched on
and loads are only switched off in the case
of an overload or short-circuit.
After detecting overload or short-circuit
in the load circuit, the load output of the
ECP-E is locked. The current flow is
interrupted in the faulty current circuit.
The ECP-E and subsequently the current
circuit can be activated again through the
electronic reset input (13;14) or manually at
the device through the slide-type switch.
A multi-color LED as well as the
integrated status output (12) display the
operating and error status. Due to its
plugging capacity and narrow width of
12.5 mm, the ECP-E offers time and space
saving mounting on the TMCP SOCKET M.
More versions of the auxiliary contacts
and a complete data sheet are provided
for the relevant item at
www.phoenixcontact.net/eshop for
downloading.
ECP-E ...
A
Dimensions
[mm]
Width
12.5
Length
60
Umax. [V]
24
Height
70
Max. Ø [mm²]
-
IEC
UL / CUL
CSA
24
1/-
-/-
-/-
Max. electrical data
Rated data
Rated voltage
Nominal current / cross-section
Operating data
Nominal voltage
Nominal current
Auxiliary contacts
Disconnection
Switch-off time
Typical behavior
[V]
[A] / [mm²]
[A]
[A]
AWG
IEC/
EN 60079-7
-/-
24 V
Dependent on the article variant selected
Refer to the time/current characteristic curve
5 s If 1.1 x IN
0.1 s If > 1.8 x IN
Auxiliary contacts
Pin 11
Pin 12
Pin 13/14
Switching capacity ICN
ECP-E 1A - ECP-E 12A
Life
Cycles with 1 x IN
General data
Weight
Temperature range
Insulating material
Inflammability class acc. to UL 94
Gnd (-)
Individual signaling
Group query
Active current limiting 180%
10000
[g]
[°C]
50
0 ... 50
PA-F
V0
Ordering data
Description
Electronic circuit breaker, standard
variant with status output and reset
input, can be plugged into TMCP
socket, signaling through three-color
LED
Nominal
current
Color
Type
Order No.
Pcs. /
Pkt.
1A
Black
ECP-E 1A
0900113
5
2A
3A
4A
6A
8A
10 A
12 A
Black
Black
Black
Black
Black
Black
Black
ECP-E 2A
ECP-E 3A
ECP-E 4A
ECP-E 6A
ECP-E 8A
ECP-E 10A
ECP-E-12A
0900210
0900317
0900414
0900618
0900812
0901002
0900126
5
5
5
5
5
5
5
Black
Black
TMCP SOCKET M
TMCP CONNECT LR
0916589
0916592
10
3
Accessories
Modular socket, 2-position, for holding two circuit
breakers, each with a single position
Stop point
typ. 1,1 x l N
Switching time [s]
10
10
Socket termination elements, can be plugged in
both left and right, contain the connections for the
reset inputs/group query
1,8 x l N
4
3
Zack marker strip, 10-section
ZB 6 (see page 487)
2
10
10
5
1
0,1
0,01
0
1
2
IK
3
Multiples of IN
466
PHOENIX CONTACT
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370
Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Special terminal blocks
Circuit breakers
LINE (+)
11
GND (-)
13
LINE
1
SC
On/Off
14
SI
2
LOAD
SO
12
The electronic circuit breaker ECP 3-6
with a width of only 12.5 mm selectively
protects all 24 V DC load circuits. With a
combination of active electronic current
limitation and proven circuit breaker
technology including electrical isolation.
The ECP 3-6 can be plugged onto the
proven TMCP-SOCKET-M base, which also
guarantees fast and easy mounting and a
reduction in the logistics costs.
The area of application for the ECP 3-6
extends to all aspects connected with the
power supply unit. Because in the case of an
overload, power supply units reduce the
output voltage. As a consequence, the
connected loads would no longer be
sufficiently supplied. This means that if a
fault occurs in one consumer of a system,
the voltage will break down in all load
circuits.
The ECP 3-6 solves this problem by
always limiting the maximum possible
current to 1.8 times the value of the set
nominal current. Capacitive loads can thus
be switched on, loads, however, are only
switched off in the case of an overload or
short-circuit.
An LED and integrated signal contacts
indicate the operating and error states.
A complete data sheet is available for
the relevant item at
www.phoenixcontact.net/eshop for
downloading.
Control Unit
Selective circuit breaker ECP
LOAD (L+)
ECP ...
Dimensions
[mm]
Width
12.5
Length
60
Umax. [V]
24
Height
70
Max. Ø [mm²]
-
IEC
UL / CUL
CSA
24
2/-
-/-
-/-
Max. electrical data
Rated data
Rated voltage
Nominal current / cross-section
Operating data
Nominal voltage
Nominal current
Auxiliary contacts
Disconnection
Switch-off time
Typical behavior
[V]
[A] / [mm²]
[A]
[A]
AWG
IEC/
EN 60079-7
-/-
24 V DC
Dependent on the article variant selected
Refer to the time/current characteristic curve
5 s If 1.1 x IN
0.1 s If > 1.8 x IN
Auxiliary contacts
Pin 11
Pin 12
Pin 13/14
Switching capacity ICN
ECP 1-2 - ECP 10
Life
Cycles with 1 x IN
General data
Weight
Temperature range
Insulating material
Inflammability class acc. to UL 94
Gnd (-)
Individual signaling
Group query
Active current limitation
10000
[g]
[°C]
65
0 ... 50
PA-F
V0
Ordering data
Description
Selective circuit breaker, can be
plugged into TMCP base, signaling
using two-color LED, floating signal
contact, on/off push button
Nominal
current
Color
Type
Order No.
Pcs. /
Pkt.
2A
Black
ECP 1-2
0912018
5
6A
4A
8A
10 A
Black
Black
Black
Black
ECP 3-6
ECP 4
ECP 8
ECP 10
0916536
0912034
0912019
0912020
5
5
5
5
Black
Black
TMCP SOCKET M
TMCP CONNECT LR
0916589
0916592
10
3
ECP-LOCK
ZB 6 (see page 487)
0912021
10
Accessories
Modular socket, 2-position, for holding two circuit
breakers, each with a single position
Socket termination elements, can be plugged in
both left and right, contain the connections for the
reset inputs/group query
Switching time [s]
Stop point
typ. 1,1 x l N
10
10
1,8 x l N
Spring lock, for mechanical locking in the case of overhead
mounting, 1-pos.
4
3
Zack marker strip, 10-section, for labeling in the terminal center
2
10
10
5
1
0,1
0,01
0
1
2
IK
3
Multiples of IN
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370
Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
PHOENIX CONTACT
467
Special terminal blocks
Circuit breakers
Base for ECP and TMCP
For more technical data, drawings and accessories, visit
www.phoenixcontact.net/eshop.
TMCP ...
P
Dimensions
[mm]
The TMCP SOCKET M socket is used for
rail-mounting of pluggable TMCP and ECP
circuit breakers. This can lead to a flexible
design with any desired number of
positions. A free combination of both types
of circuit breakers on one module also
enables individual protection.
The TMCP CONNECT LR termination
elements are plugged in on both ends of the
construction of the modules. The supply
can be signaled using connections 11 and 12.
The signal can be requested separately for
each circuit breaker. Using connections 13
and 14 in the termination elements, a signal
loop can be set up over all circuit breakers
quickly and without the need for additional
wiring. All electrical connections of the
main contacts and signal contacts are
located in the base.
The spring-cage connection and the
bridge shaft for potential distribution
facilitate wiring. Generous labeling options
facilitate the allocation of circuit breakers to
the modules.
468
PHOENIX CONTACT
General data
Insulating material
Inflammability class acc. to UL 94
Width
25
Length
115
Height NS 35/7,5
110.5
PA-F
V0
Ordering data
Order No.
Pcs. /
Pkt.
TMCP SOCKET M
0916589
10
Black
Signal bridge, pluggable, for bridging group signaling when there
is a free slot on the TMCP-SOCKET-M socket
TMCP CONNECT LR
0916592
3
Red
Fixed bridge, pluggable, 500 mm long, can be cut to length, for
distribution of the input potential in the socket
TMCP SB
1A
0916602
6
Silver
Cont. plug-in bridge, 500 mm long, isolated, can be cut to length,
for potential distribution
Blue
Cont. plug-in bridge, 500 mm long, isolated, can be cut to length,
for potential distribution
Red
Zack marker strip, 10-section
FBST 500 TMCP
50 A
0916615
20
FBST 500-PLC BU
32 A
2966692
20
FBST 500-PLC RD
ZB 6 (see page 487)
32 A
2966786
20
Description
Color
Type
Modular socket, 2-position, for holding
two circuit breakers, each with a single
position
Black
Imax
Accessories
Socket termination elements, can be plugged in
both left and right, contain the connections for the
reset inputs/group query
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370
Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Special terminal blocks
Circuit breakers
Backup fuse
A back-up fuse together with a circuit
breaker must always be used if there is a risk
of the maximum switching capacity being
exceeded in the event of a fault. The
adjacent table specifies the maximum
switching current, the respective internal
resistance and the resulting backup fuse.
TMCP circuit diagram
Device 1
Device 2
1
1
11
13
11
2
12
2
12
14
Display and definitions in the switched-off, zero-current state.
TMCP and TMC nominal currents, internal resistances and backup fuses
Nominal
current
Maximum
backup fuse
[A]
0.2
0.3
0.4
0.5
0.6
0.8
1
1.5
2
2.5
3
4
5
6
8
10
12
16
[A]
Any
Any
Any
Any
Any
Any
Any
25
25
25
25
25
25
50
50
50
50
50
Internal resistance [Ω]
F1 (fast blow)
for DC
39.3
17.5
9.2
6.8
4.2
2.8
1.6
0.78
0.42
0.26
0.18
0.12
0.092
0.054
0.025
0.022
≤ 0.02
≤ 0.02
M1 (normal blow)
for DC/AC
26.1
11.6
6.6
4.1
3
1.65
1.10
0.47
0.28
0.183
0.124
0.077
0.063
0.045
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370
Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Switching capacity
as per EN 60934
[A]
400
400
400
400
400
400
400
400
400
400
400
400
400
800
800
800
800
800
PHOENIX CONTACT
469
Special terminal blocks
Feed-through terminal blocks
General
Frequency converters, inverters, power
supply units and filter modules are only
some of the applications that have a
modular design and small compact housings.
Despite having different fields of application
and use, they all have one thing in common:
currents of different magnitudes have to be
led through the housing panel. A conductor
connection that can be released, is touch
proof and easy to install is nowadays
considered the most satisfactory
connection method for wiring these system
components.
470
PHOENIX CONTACT
The various feed-through terminal
blocks satisfy these requirements. Three
different designs are available:
– The DFK terminal blocks which are
snapped into sheet metal cutouts
– The VDFK molded feed-through
terminal blocks, which are made specially
for fully insulated transformers and coils
– The HDFK high-current feed-through
terminal blocks, whose clamping parts
are safely interlocked in the housing
All feed-through terminal blocks have a
touch-proof insulating housing which can be
labeled with various marking materials.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370
Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Special terminal blocks
Feed-through terminal blocks
Feed-through terminal blocks
DFK
– Housing panel thickness: 1.5 - 2.5 mm
– Rated voltage: 400 - 690 V
– Nominal current: 6.3 - 17.5 A
– Cross-section range: 0.2 - 6 mm2
VDFK molded feed-through terminal
blocks
– Housing panel thickness: 1.0 - 8.0 mm
– Rated voltage: 500 V
– Nominal current: 32 - 57 A
– Cross-section range: 0.2 - 10 mm2
HDFK high-current feed-through
terminal blocks
– Housing panel thickness: 1.0 - 6.0 mm
– Rated voltage: 250 - 1000 V
– Nominal current: 41 - 232 A
– Cross-section range: 0.2 - 95 mm2
HDFKV high-current feed-through
terminal blocks
– Housing panel thickness: 1.0 - 6.0 mm
– Rated voltage: 250 - 1000 V
– Nominal current: 41 - 232 A
– Cross-section range: 0.2 - 95 mm2
HDFK and HDFKV molded
high-current feed-through terminal
blocks
– Housing panel thickness: 1.0 - 6.0 mm
– Rated voltage: 250 - 1000 V
– Nominal current: 63 - 232 A
– Cross-section range: 0.5 - 95 mm2
HDFK...-TWIN high-current
feed-through terminal blocks
– Housing panel thickness: 1.0 - 6.0 mm
– Rated voltage: 250 - 500 V
– Nominal current: 70 - 125 A
– Cross-section range: 0.5 - 35 mm2
Detailed information on the
feed-through terminal blocks can be
found in the "COMBICON device
connection technology" catalog or at
www.phoenixcontact.net/eshop
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370
Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
PHOENIX CONTACT
471
Related documents