Isolated safety barrier

advertisement
Isolated safety barrier
TSFx02W-EX Series
12.5mm ultra-thin switch output isolated safety barrier
FEATURES
z
Input, output are mutually isolated from each other
z
12.5mm ultra-thin case
z
Isolation voltage (Intrinsically safe and
no-intrinsically safe:2KVAC/60S)
PART NUMBER SYSTEM
TSFx02W-EX
z
Protect: power reverse protect
z
Operating temperature range:-25 ~ +71℃
z
Excellent EMC performance
z
High reliability(MTBF>500,000 hours)
Safety barrier mark
Slim case
Channel configurat ion
Channel number
Signal flow
Signal style
Isolation t ransducer
TSFx02W-EX series ultra-thin switch output isolated safety barrier, the product can drive equipment in hazardous area by controlling the
switch of power supply in safe area. Driving power is 12V/44mA. Products are suitable for drivers, such as solenoid valves, audible and visual
alarm, and other intrinsically safe end equipment. The product’s shell is as thin as 12.5mm.
Connection of field devices and the regions: switch; zone 0,zone 1,zone 2; IIA,IIB,IIC,T4~T6 hazardous area.
Industries applications: intrinsically safe explosion protection systems of chemical engineering, petroleum, metallurgy, mining, pharmacy,
natural gas, electric power, etc.
Selection Guide
Part No.
Isolation voltage
Description
TSF102W-EX
2KVAC
1 input 1 output
TSF202W-EX
2KVAC
2 input 2 output
Input Specifications
Item
Operating Conditions
Value
Power supply
Power Supply Input
Safe Zone
18-30VDC (Typical value 24VDC)
Input power
When the output current is in its max. value
About 2.4W
Power supply protection
Anti-reverse protection
Input signal
Dry contact input
Output Specifications
Item
Operating Conditions
Open status voltage
Hazardous Zone
Output voltage
Value
24VDC±5%
Current 44mA
≥12VDC
Driving capability
12VDC/44mA
Recovery time
≤5ms
General Specifications & Explosion Protection Certification parameter
Item
Operating Conditions
Value
Electric Isolation
1Min, humidity < 70%, leakage
current ≤1mA
Intrinsically safe and no-intrinsically safe:2KVAC/60s
Isolation Resistance
Intrinsically safe and no-intrinsically safe:≥100MΩ,500VDC
MTBF
>50,0000 h
Explosion Protection Certification Mark
[Exia Ga]IIC
Explosion Protection Certification
Parameter
Pin(6+,5-);
Uo:26.3VDC
Um:250VAC/DC
Co:0.08uF
(2+,1-)
Io:130mA
Po:0.85W
Lo:1.5mH
2015.02.27-A/1
Page 1 of 4
MORNSUN Guangzhou Science & Technology Co., Ltd. reserves the copyright and right of final interpretation
Isolated safety barrier
TSFx02W-EX Series
CQST (China National Quality Supervision and Test Centre for
Explosion Protected Electrical Products)
Explosion Protection Certification Body
Explosion Protection Certificate No.
CNEx13.3056
Operating Temperature
-25 ~ +71℃
Transportation and Storage
Temperature
-40~+85℃
Physical Specifications
Casing Material
Retardant material UL94-V0
Protection Class
IP20 (IEC60529 / EN60529)
Dimension
35mm DIN-rail package:T-rail card package (DIN50022), pluggable
connection terminal, 107.00mm*108.50mm*12.50mm.
Weight
1 input 1 output about 100g, 2 input 2 output about 128g (Typ.)
Cooling Method
Free convection
EMC Specifications
EMS
ESD
IEC/EN61000-4-2
Contact ±4KV/Air ±8KV
perf. Criteria B
RS
IEC/EN61000-4-3
10V/m
perf. Criteria A
IEC/EN61000-4-4
power supply port ±2KV
perf. Criteria A
IEC/EN61000-4-4
signal port ±1KV
perf. Criteria A
IEC/EN61000-4-5
power supply port ±1KV
perf. Criteria B
IEC/EN61000-4-5
signal port ±1KV (line-to-ground)
perf. Criteria B
IEC/EN61000-4-6
3 Vr.m.s
perf. Criteria A
EFT
Surge
CS
Application Precautions
1.
2.
3.
4.
Please read the instructions carefully before use; contact our technical directly if you have any problem;
Do not use the product in hazardous zones;
Use DC power supply for the product, and 220V AC power supply is prohibited;
Do not disassemble or assemble the product without permission to avoid explosion protection failure or malfunction of product.
Design Reference
1. Wiring diagram for product application
2 inpu t 2 o utpu t
Safe A rea
Hazar dous
Ar ea
+
+
6
8
_
5
_ 7
Power
Electr omagn etism valv e/Alar m
2
12 _ 1 1
cha nnel 2
_
Power
+
+
cha nnel 1
1
Note:This diagram is for 2 input & 2 output model only, 1 input & 1 output model connect channel 1 only.
2. Output typical curve
Vo(VDC)
24
12
0
44
Io(mA)
① Use dismountable ports for instrument wiring, easy to operate;
② The sectional area of conductor is 0.5mm2-2.5 mm2;
③ The length of conductor exposed is 8mm and is fastened by M3 bolts.
2015.02.27-A/1
Page 2 of 4
MORNSUN Guangzhou Science & Technology Co., Ltd. reserves the copyright and right of final interpretation
Isolated safety barrier
TSFx02W-EX Series
3. Application in the intrinsically safe explosion protection system
In the intrinsically safe explosion protection system, the isolated safety barrier belongs to related equipment and is installed in a safe location
for connecting the intrinsically safe equipment in hazardous location and non-intrinsically safe equipment in safe location, which is capable
of limiting the energy entering into the site in safe value, so as to ensure the safety of site equipment, personnel and production.
The selection principles for the safety barrier in the intrinsically safe explosion protection system:
1) The grade of the explosion-proof marker of safety barrier must be not less than that of the intrinsically safe site equipment.
2) The port resistor and loop resistance of safety barrier should be taken into consideration so as to ensure the output voltage of safety
barrier can meet the requirements of the min. operating voltage of the intrinsically safe site equipment.
3) The safety parameters of the intrinsically safe port of safety barrier can meet:
Uo ≤ UI, Io ≤ Iin, Po ≤ Pin
Cc≤ Co-Ci, Lc ≤Lo-Li
4) Select the matched safety barrier according to the power supply polarity and signal type of intrinsically safe site equipment as well as its
transmission mode.
5) The wires leading to the dangerous places should use the blue safety wire, wire soft copper area must be greater than 0.5mm2,
dielectric strength should be greater than 500VDC.
4. For more information please find the application notes on www.mornsun-power.com
Installation & disassembly
Installation
Disassembly
DIN35mm standard rail installation
1. Insert the top of the instrument card in the rail;
2. Push the bottom of the instrument into the rail.
1. Insert to the clamp on the lower end of instrument with a screw
driver (tool edge width≤6mm);
2. Push the screw driver up, and pry the clamp down;
3. Pull the instrument up out of the guide rail.
1
3
2
1
2
Dimensions
2015.02.27-A/1
Page 3 of 4
MORNSUN Guangzhou Science & Technology Co., Ltd. reserves the copyright and right of final interpretation
Isolated safety barrier
TSFx02W-EX Series
Notes:
1.
Packing information please refer to Product Packing Information which can be downloaded from www.mornsun-power.com. Packing
bag number: 58040010;
2.
Unless otherwise specified, parameters in this datasheet were measured under the conditions of Ta=25℃, humidity<75% with nominal
input voltage and rated output load;
3.
All index testing methods in this datasheet are based on our Company’s corporate standards;
4.
The performance parameters of the product models listed in this manual are as above, but some parameters of non-standard model
products may exceed the requirements mentioned above. Please contact our technicians directly for specific information;
5.
We can provide product customization service;
6.
Specifications are subject to changes without prior notice.
Mornsun Guangzhou Science & Technology Co., Ltd.
Address: No. 5, Kehui St. 1, Kehui Development Center, Science Ave., Guangzhou Science City, Luogang District, Guangzhou, P. R. China
Tel: 86-20-38601850-8801
Fax: 86-20-38601272
E-mail: info@mornsun.cn
2015.02.27-A/1
Page 4 of 4
MORNSUN Guangzhou Science & Technology Co., Ltd. reserves the copyright and right of final interpretation
Download