Facility Planning Data Sheet MGE Galaxy 300 UPS 10 - 40kVA (400V/400V, 400V/230V) UPS AC Input UPS Rating Voltage kVA kW Input V 10 8 400 10 15 15 20 20 30 8 12 12 16 16 24 400 400 400 400 400 400 UPS AC Output Current Full Load A 13.6 13.4 19.1 19.4 25.4 25.1 37.6 Voltage Max. Recommended Cable size (mm2) Recommended Overcurrent ProtectionDevice See note 7 Output V 18.8 10 C60H-C-40H 400 18.5 23.9 24.3 30.3 29.9 47.2 10 10 10 10 35 16 C60H-C-40H C60H-C-40H Compact NS125 Compact NS125 Compact NS125 Compact NS125 230 400 230 400 230 400 Mechanical Data Current @ Full Load Max. See note 2 Overcurrent Protection Device Typical Dimensions HxWxD (mm) Average Weight kg Floor Loading kg/cm2 Heat Loss Watt-hour 15.2 Fast Fuse 63A/690V 1300x400x860 615 0.113 192 45.5 Fast fuse 125A/660V 1300x400x860 615 0.113 207 22.8 Fast Fuse 63A/690V 0.113 274 68.2 Fast fuse 125A/660V 0.113 306 30.4 Fast Fuse 63A/690V 0.113 369 90.9 Fast fuse 250A/660V 0.1433 355 45.6 Fast Fuse 125A/690V 0.1433 528 1300x500x860 0.1433 549 1300x500x860 0.1433 726 30 24 400 38.5 48.3 35 Compact NS125 230 136.4 Fast fuse 250A/660V 40 32 400 50.3 59.9 25 Compact NS125 400 60.8 Fast Fuse 125A/690V 1. Input current based on full rated output load. 2. At <150% for 10seconds. 3. Input and bypass cables must be run in separate conduits from output cables. Not more than three conductors in raceway assumed; ambient temperature of 86°F assumed. 4. If initial load is less than UPS' rated output, it is recommended that AC input, battery, and AC output wiring and overcurrent protection be sized to UPS’ full load rating to accommodate possible future expansion. 5. Only copper cables are considered. 6. DC cables should be sized for a total maximum of less than 1% of CB rating. 7. OCPD = Overcurrent Protection Device. Recommended represents 125% of nominal full load current (continuous). 8. Minimum-sized grounding conductors are recommended. Parity-sized ground conductors are recommended. Neutral conductors to be sized for full capacity. AC Input/Output: 3Ø, 3 or 4 wire + ground, depending on UPS configuration. See Installation Manual and submittal drawings for specific instructions. - DC Input: 2 wire (positive and negative) + ground 9. All wiring to be in accordance with all applicable national and/or local electrical codes. 10. Minimum access clearance per UPS drawings. 1300x400x860 1300x400x860 1300x400x860 1300x500x860 1300x500x860 615 615 615 615 615 615 615 11.The cable sizes are based on an environment with ambient max temperature of 35 degrees C. 12. Control wiring and power wiring must be run in separate conduit. 13. Weights and dimensions shown do not include battery cabinet(s) or other options. 14.Backup emergency generator must be properly sized for UPS application and equipped with an isochronous governor for frequency regulation, and a UPS-compatible voltage regulator for voltage stability. 15. If site configuration requires an external maintenance bypass, phase parity between UPS input and UPS bypass must be ensured. Consult applications engineer. 16. The terminals have minimum size requirements for cables. 17. Note 1: Each PFC or Boost pack contains a 63A fuse per phase. 10-20kVA Ups has one pack and 30-40kVA UPS have two packs. 18. Average weight references installed weight with batteries. 19. Temperature rating of conductors: 90°C (194°F). 75°C (167°F) cable terminal conductors assumed. 20.Battery cabinet floor loading loading = .1087 kg/cm² 21. All Floor loading values are with batteries installed RATINGS OF CABLES AND OVERCURRENT DEVICES SUPPLIED FOR INFORMATION ONLY. USER TO CONSULT WITH THEIR ENGINEERING SERVICES BEFORE ADOPTING. G300FPDS, REV0