Single Phase Harmonic Filters

advertisement
Single Phase Harmonic Filters
Table of Contents
3rd Harmonic Filters
Delivery / Lead Time
PB-1400-2
Product Description
PB-1400-3
Catalog Numbering System
PB-1400-4
Selection Guide
PB-1400-5
Pricing
3rd Harmonic Filters
3rd Harmonic Inductors Only
PB-1400-6
PB-1400-6
PB-1400-7
Product Specification
PB-1400-8
Product Characteristics
PB-1400-10
Data subject to change without notice. Effective 01/18/10
PB-1400-1
TYPICAL DELIVERY SCHEDULE
3rd HARMONIC FILTER
Panel Mounted Style
All Filters Built to Order
TYPE
SHIPMENT
120V, 60 HZ Filter
1 - 3 Weeks
240V, 60 HZ Filter
2 - 4 Weeks
240V, 50 HZ Filter
2 - 4 Weeks
Inductors Only
1 - 4 Weeks
Data subject to change without notice. Effective 01/18/10
PB-1400-2
3rd HARMONIC FILTERS
MTE 3rd Harmonic Filters are designed to be used on single phase branch
circuits with a high number of triplen harmonic producing loads attached. The
filter typically reduces triplen harmonics (3rd, 9th, 15th) caused by switch mode
power supplies, electronic ballasts, light dimmer controls, and single phase motor
drives. This filter reduces triplen harmonic currents in the neutral of the upstream
three phase distribution system.
Features
• Open panel construction
• Single phase
• 5, 10, and 15 Amp versions
• 120V 60 HZ, 240V 50 HZ or 60 HZ
• Hardwired terminal block supplied
• Typical 80 – 90% reduction in each individual harmonic from the 3rd
through the 9th.
• Reduce triplen harmonics in three phase neutrals.
Data subject to change without notice. Effective 01/18/10
PB-1400-3
3rd Harmonic Filter
Catalog Numbering System
X X HF X X
FREQUENCY
BLANK = 60 HZ
X = 50 HZ
VOLTAGE
BLANK = 120V
2 = 240V
PRODUCT TYPE - HF
ENCLOSURE TYPE
P = OPEN PANEL
FILTER RATING (Amps)
Data subject to change without notice. Effective 01/18/10
PB-1400-4
Catalog Number Selection Procedure:
1. Identify the following
a. Identify the maximum current draw of the device (5, 10, or 15
Amps).
b. The enclosure type required. (P=Open unit in all cases.)
c. Product type is HF in all cases.
d. Line voltage (Blank=120V, 2=240V)
e. Line frequency (Blank = 60 Hz, X = 50 Hz)
2. Create the part number
a. Start with 5, 10, or 15 identified in item (1.a.)
b. Append a “P”, the results of item (1.b)
c. Append a “HF”, the results of (1.c)
d. Append the results of (1.d)
e. Append the results of (1.e)
3. Look up the created catalog number in the following tables to determine
list price. (Note: The ‘X’ is a place holder and will be substituted with a ‘D’
or an ‘F’ in the tables depending on the series.)
4. Check with the factory if you can not find the part in the table.
5. For example a 10 AMP, 120V - 60 Hz unit’s part number would be:
From 2.a From 2.b
From 2.c From 2.d From 2.e
10
P
HF
Blank
Blank
Another example is a 5 AMP, 240V - 50 Hz unit’s part number would be:
From 2.a From 2.b
From 2.c From 2.d From 2.e
5
P
HF
2
X
The list price for the 10PHF and 5PHF2X can be found on the next page..
Data subject to change without notice. Effective 01/18/10
PB-1400-5
PRICE LIST
3rd Harmonic Filters
OPEN PANEL
Model
Amps Volts
5PHF
5
120
10PHF
10
120
15PHF
15
120
5PHF2
5
240
10PHF2
10
240
15PHF2
15
240
5PHF2X
5
240
10PHF2X
10
240
15PHF2X
15
240
VA
600
1200
1800
1200
2400
3600
1200
2400
3600
Frequency
(HZ)
60
60
60
60
60
60
50
50
50
Weight
(LB)
(KG)
6
2.2
7
2.6
12
4.5
6
2.2
7
2.6
12
4.5
6
2.2
7
2.6
12
4.5
Price
$
310
$
379
$
459
$
310
$
379
$
459
$
330
$
395
$
465
Includes inductor, capacitors, terminal block and panel only.
Inductors only for 3rd Harmonic Filters
600 Volts max, 50/60 HZ
Rating
(Amps)
5
10
15
Cat. No.
L-11614
L-11615
L-11616
Price
$ 89
$ 102
$ 132
Data subject to change without notice. Effective 01/18/10
Weight
(LB) (KG)
4
1.5
5
1.9
10
3.7
PB-1400-6
3rd Harmonic Filter
Responsibility: Engineering
Approved By:
ISO Section:
7.3.3
SCOPE:
ES-006
Rev 000
10/28/03
3rd Harmonic Filter Specification
1.0 General
This 3rd Harmonic filter is intended to reduce triplen harmonics generated by
voltage switching loads.
1.1
The 3rd Harmonic filter incorporates UL recognized inductor, capacitors, wires,
and terminal block but is not UL component recognized as an assembly.
1.2
These filters reduce triplen (3rd and 9th ) current harmonics produced by personal
computers, electronic ballasts, lighting dimmer controls, uninterruptible power
supplies, or 1-Phase Motor Drives/Inverters.,
1.3
The 3rd Harmonic Filters are used to reduce neutral currents, reduce transformer
loading, protect electrical systems, reduce fire hazards, and improve power
factor.
2.0 Electrical Ratings:
2.1
Filters can be selected for 120V – 60 Hz, 240V – 60Hz, and 240V – 50 Hz single
phase supply sources with 5, 10, or 15 Amp ratings..
3.0 Applicable Standards
3.1
CUL Recognized inductors, UL component categories NMTR2 and NMTR8
3.2
UL recognized capacitors, UL component category CYWT2.
3.3
UL recognized wiring, UL component category AVLV2
3.4
UL recognized terminal block, UL component category XCFR2
Data subject to change without notice. Effective 01/18/10
PB-1400-7
4.0 Standard Features
4.1
UL Recognized components only. Assembled filter is not UL recognized.
4.2
Open panel construction
4.3
Terminal block supplied for hard wiring.
4.4
Ground stud provided on the panel
5.0 Optional Features
5.1
5A, 10A, 15A 50/60 Hz, 600V, UL Recognized inductors sold stand-alone
6.0 Documentation
6.1
Typical dimensional data shall be supplied by MTE upon request.
Data subject to change without notice. Effective 01/18/10
PB-1400-8
3rd Harmonic Filter
Product Specification
Open Panel Construction
Inductors only for 3rd Harmonic Filters
600 Volts max, 50/60 HZ
Cat. No.
L-11614
L-11615
L-11616
L (mH)
9.77/8.8
4.89
4.89
Height (H)
Width (W)
(in.) (mm) (in.) (mm)
2.80
71
3.00
76
2.80
71
3.00
76
3.20
81
3.75
95
Depth (D)
(in.) (mm)
3.50
89
3.69
94
5.09
129
Mounting
Width (E)
Depth (F)
Weight
(in.) (mm) (in.) (mm) (LB) (KG)
2.50
64
1.44
37
4
1.5
2.50
64
3.13
79
5
1.9
3.13
79
4.07 103
10
3.7
Note: L-11614 has three leads, Common (Red), 50 HZ (Yellow) , and 60 HZ
(Blue) leads. L-11615 and L-11616 connect to the same two leads for 50
HZ or 60 Hz operation.
Data subject to change without notice. Effective 01/18/10
PB-1400-9
PRICE LIST
3rd Harmonic Filter
Product Specification
Technical Data
Data subject to change without notice. Effective 01/18/10
PB-1400-10
ISO 7.2.3
Responsibility:
Approved by:
File Location:
Single Phase Harmonic Filters
PB-1400
Corporate
Karl Hink
J:\Public\Controlled Documents\Sales\PRICE BOOK
Revision
---
Date
10/15/03
001
10/28/03
002
11/14/03
003
9/29/05
004
1/18/10
IMPORTANT!
Revision History (recorded by date on document)
New document written by Karl Hink
Revised by Hank Nechvatal – ES-004 R--- 3rd Harmonic Filter was changed
to ES-006 R--- 3rd Harmonic Filter
Revised by Bruce Schram – Corrected Part number on PB-1400-15.
ZDG036A was incorrectly indicated as ZDG063A.
Rev WRW: price adjustments pages 6 and 15 effective 11/1/05.
Rev WRW: price adjustments page 6 removed zero sequence and zigzag
transformers products effective 1/18/10
Make sure ES-005 Zero Sequence Harmonic Filter
and ES-006 3rd Harmonic Filter revisions agree
with those in PB-1400.
Data subject to change without notice. Effective 01/18/10
PB-1400-11