PerfectSense ® Intelligent Building Occupancy Sensors PS-HC24-R: 1000 sq ft 360° Sensor High Definition Infrared Technology Ceiling Mount | Low Voltage Description: The PS-HC24-R is a low voltage High Definition Infrared (HDIR) Presence Sensor designed to work with any PerfectSense power pack, to automatically control lighting in standard and cold weather applications. This sensor utilizes an industry leading 8-Element Infrared detector for superior minor motion detection. The sensor operates in climates down to -40° Fahrenheit or Celsius. Dual Form C Relays are present on the sensor to allow for integration to NexLight’s 2-wire system and HVAC/BMS Systems. The sensor turns the lights on and keeps them on while occupancy is detected and will turn the lights off after the delayedOFF time has expired. Operation of Sensor: Features: • 1000 sq ft Range • 300 sq ft minor motion detection range • Patented HDIR 8-element Sensor • 864 Optical Field-of View Pattern • 360° Coverage Pattern • Adjustable Time Delay (30 sec – 30 min) • Walk-Through Mode • Daylight Override Mode • Mounts in drop ceilings and solid ceilings • LED indication of occupancy sensing Motion detection by the HDIR sensor will turn ON the lights as well as keep them ON. When motion is not detected, the lights will turn OFF after the delayed-OFF time. Walk-Through Mode: The walk-through feature is useful when a room is momentarily occupied, such as a storage room. When a person enters the room, the lights will turn on and stay on for 2.5 minutes. After 2.5 minutes the lights will shut off. Scenario A: If motion is detected within 10 seconds of the lights shutting off, the sensor will proceed to standard operation (5s to 30m). After the lights shut off, the sensor will revert back to walk-through mode. Scenario B: If no motion is detected within 10 seconds of the lights shutting off, the sensor will stay in walk through mode and the next time it sees detection the lights will turn on for 2.5 minutes. Daylight Sensor: To enable daylight sensor operation, set Dip Switch 1 in Bank B to OFF. This puts the sensor in a stand-by mode when the natural light level exceeds the selected Foot Candles (FC) level inhibiting the lights from turning ON. LED Operation: The Sensor has two LED indicators that, when enabled, will flash when motion is detected. These LEDs are Enabled/Disabled via DIP switch 2 in Bank B. When enabled, a red flash indicates that motion has been detected by Infrared Technology. Electrical: Power Requirements: 24VDC, from powerpack Current Consumption: 15mA Output: 24VDC active high logic control signal with short circuit protection Isolated Relays: 2 SPDT 1 Amp, 30 VDC Form C Wiring Diagram: See Fig. 2 Controls: HDIR Sensitivity: 0-100% (Factory Set 50%) Daylight Sensor: 20-320 FC (Factory Disabled) Detection Range: See Fig. 1 Load Rating: Controls Class 2 Power Pack Housing Material: High-Impact ABS Color: White Environment Temperature: -40ºF to 122ºF Humidity: 0-95% Non Condensing Installation: See Install Instructions Dimensions: Diameter 4.33 in Height 2.2 in Supported with limited 5-year warranty Title 24 Compliant Meets ASHRAE 90.1 requirements © 2015 NexLight Lighting Controls, All Rights Reserved. Phone: 218.828.3700 www.nexlight.com 1 Fax: 218.824.1568 Sensor Adjustments Console: All aspects of sensor operation can be adjusted here. View of adjustments when cover is removed. Dip Switch setting table below illustrates how to enable and disable sensor functions. DIP SWITCH SETTINGS SWITCH A1 A2 A3 A4 B1 B2 B3 B4 SWITCH FUNCTIONS Bank A N/A N/A N/A Walk- Through Mode Bank B Daylight Mode LEDs Mode Test Mode N/A SWITCH SETTINGS OFF ON N/A N/A N/A N/A N/A N/A Walk-Through Enable Walk- Through Disable Daylight Mode Enable Daylight Mode Disable LEDs Enabled LEDs Disable OFF ON OFF = Enter/Exit Test Mode N/A N/A Daylight Sensor Adjustment Factory default setting is disabled. If installed location calls for the use of daylight sensor this is the adjustment for control of required ambient light levels necessary to disable the automatic ON control of the sensor when detecting occu pancy. NOTE: The daylight sensor function is not applicable in rooms using manual ON control. Note: Gray indicated factory default settings Passive Infrared Adjustment PIR sensitivity can be dialed up or down to meet the exact needs of anyspace. This adjustment is helpful to ensure detection in all areas during a walk test. Sets the infrared range Each time motion is detected, the lights remain activated for a pre-set time, which is set by the Off-time adjustment. The fully counter-clockwise setting (30seconds) can be used for testing. If motion is detected during the ON time, the timer resets and lights will remain on until the full Range setting Full CCW = min.(OFF) Full CW = max. Delayed-OFF time © 2015 NexLight Lighting Controls, All Rights Reserved. Phone: 218.828.3700 www.nexlight.com 2 Fax: 218.824.1568