R H 4 1 2 3 D E S I G N 1 2 3 4 G U I D E HWAT-Plus System Design Guide Contents Introduction 4 How to use this design guide 6 System description Application information 7 Design steps Plumbing design sheet instructions 8 Design Sheet A: Plumbing Design 9 Electrical design sheet instructions 10 Design Sheet B: Electrical Design 11 60-bed nursing home 12 250-bed medium-security prison 14 35-story apartment building 16 500-room hotel 18 Specification CSI Model Specification 20 Installation Installation details 22 Design examples 3 HWAT-Plus System Design Guide Introduction This manual presents Raychem’s recommendations for designing an HWAT-Plus hot water temperature maintenance system. Following these guidelines will result in a reliable, efficient system. For information regarding other Raychem heat-tracing applications, consult your Raychem representative. 4 HWAT-Plus System Design Guide Introduction Scope The design information provided is applicable to the majority of domestic hot water temperature maintenance applications, but certain conditions apply. The heater must be installed on copper tubes beneath fiberglass insulation. It must be powered at 208 volts, and the design must fall within the temperature requirements for one of the typical applications outlined below: Typical application Ambient temperature Nominal pipe temperature Hospitals, nursing homes Schools, prisons, some hospitals General domestic (e.g., offices, hotels, apartments) Kitchens, laundries 74°F to 79°F (23°C to 26°C) 105°F (40°C) 70°F to 78°F (21°C to 26°C) 115°F (45°C) 70°F to 78°F (21°C to 26°C) 125°F (50°C) 70°F to 78°F (21°C to 26°C) 140°F (60°C) Pipe temperatures indicated are nominal, and variations will occur. If any of the following conditions exist, consult your Raychem representative: • different nominal pipe temperature • insulation is not fiberglass • insulation differs from Plumbing Design Sheet, Step 6 • ambient temperature range is not as indicated or may change seasonally • voltage is different These nonstandard applications can be handled with factory assistance. Approvals and Code Compliance • UL System Listing • BOCA • Uniform Plumbing Code • National Standard Plumbing Code • Southern Building Code Congress • National Electrical Code Additionally, the HWAT-Plus system is approved by numerous other state and local codes and approval agencies. Contact your Raychem representative for more information. 5 HWAT-Plus System Design Guide How to use this design guide General Recommended Procedure This manual provides instructions for all engineering disciplines involved in the design of an HWAT-Plus system. For clarity, the procedure has been divided into plumbing design and electrical design. This design guide provides design and performance data, recommended design steps, sample design sheets, and examples that show typical designs. 1. System description (page 7). Review the system illustrations to understand how a typical HWAT-Plus system operates. 2. Design steps (pages 8 - 11). Review the design steps to gain a general understanding of the design principles. 3. Design examples (pages 12 - 18). Study the design example which is similar to your project. Use the example to gain understanding of the best design approach for your project. 4. Design sheets (pages 9, 11). Using the design steps as a guide, fill in the design sheets located in this manual. Copies of the original design sheet may be made for large projects or for multiple project use. 5. Specification (pages 20, 21). Use the enclosed sample specification to specify the HWAT-Plus system you have designed. 6. Installation details (pages 22, 23). Include the typical installation details on your drawings. 6 HWAT-Plus System Design Guide System description The HWAT-Plus system provides temperature maintenance of domestic hot water lines by tracing the supply pipes with the HWAT-Plus heating cable. Because the water in the supply pipe is directly maintained at temperature, return lines, pumps, and balancing valves are all unnecessary. The selfregulating electric heating cable replaces the small amount of heat which pipes lose to the environment through the thermal insulation. The heating cable automatically compensates for temperature variations. By changing its power output in response to the pipe temperature, the HWATPlus heating cable will produce more power where needed and compensate for temperature differences automatically. Heating cable and glass tape “Electric traced” label End seal Heating cable splice Heating cable tee HWATTM Note: Pipe insulation shown is incomplete. Required items not supplied by Raychem: • Fiberglass pipe insulation • 30-mA trip ground-fault protection device Power connection 7 HWAT-Plus System Design Guide Plumbing design sheet instructions Note: Follow these design steps when filling in copies of the adjacent design sheet. The design sheet shown on page 9 is available in tablet form. Contact your Raychem representative. 1. Select the appropriate HWAT-Plus heating cable for your application. Verify that ambient temperatures will be in the range indicated. Pipe temperatures indicated are nominal, and variations will occur. If the application requirements are not as indicated, consult your Raychem representative. 2. Obtain from the electrical department the maximum available 208-V circuit breaker size: 15, 20, or 30 amps. 3. Determine the maximum circuit length. Maximum circuit lengths are based on system start-up at minimum 60°F (15°C) water temperature. 4. Lay out the circuits in segments (floors, risers, zones, wings, etc.), staying within the maximum circuit length. Identify each circuit and measure the circuit length. See examples on pages 12-19 for additional circuit layout advice. Note on the drawings the pipes to be traced, and show the circuits using the following symbols (include circuit no. within symbol): 3 Circuit continued on another sheet 3 End of circuit Hot water supply pipe traced with HWAT-Plus heating cable 3 Power connection 5. Provide equipment to allow for thermal expansion in all closed sections of piping downstream of check or pressure-reducing valves. For example, in a high-rise building use an expansion tank or pressure relief valve at each pressure zone. 6. Specify the correct thicknesses and diameters of fiberglass insulation for each copper pipe size. Pipe sizes up to 11/4 inch require insulation that is oversized in diameter by 1/4 inch to allow for installation over the heating cable. For example, a 1-inch diameter pipe requires 1-inch thick insulation, with a 11/4-inch inside diameter. 7. Include clauses in the project specification to provide, install, and test the HWAT-Plus system. State the appropriate insulation thicknesses. A CSI format specification is located on page 20. 8. 8 Transmit copies of the plumbing design sheets to the electrical engineer. HWAT-Plus System Design Sheet R Project name: Part A: Plumbing Design Project No.: Prepared by: Area of building: Checked by: 1. Select the HWAT-Plus heating cable for the application. Date: Page no. of Application Ambient temperature Nominal pipe temperature Heating cable type Hospitals, nursing homes Schools, prisons, some hospitals General domestic (offices, hotels) Kitchens, laundries 74°F to 79°F 70°F to 78°F 70°F to 78°F 70°F to 78°F 105°F (40°C) 115°F (45°C) 125°F (50°C) 140°F (60°C) HWAT-B2 HWAT-G2 HWAT-Y2 HWAT-R2 Use HWAT- 2. Maximum 208-V circuit breaker size: 15 amp 20 amp 30 amp Maximum circuit 3. Determine the maximum circuit length. Maximum circuit length in feet (meters) 4. Lay out the HWAT-Plus circuits. Identify and measure each circuit. 5. Provide for thermal expansion. 6. Specify the following thicknesses of fiberglass insulation: breaker: Circuit HWAT-B2 Breaker HWAT-G2 HWAT-Y2 HWAT-R2 30 amp 20 amp 15 amp 800 (240) 700 (210) 520 (155) 500 (150) 330 (120) 250 (75) 800 (240) 800 (240) 800 (240) A Maximum circuit length: 800 (240) 500 (150) 350 (105) Circuit Heating Risers, zones Drwg. Approx. no. cable type or floors served no. length Equipment to allow for thermal expansion should be provided in all closed sections of piping downstream of check or pressure-reducing valves. Pipe size (inches) Fiberglass insulation thickness (inches) 1⁄ " - 1" 2 11⁄4" - 2" 21⁄2" - 6" 1" 11⁄2" 2" Transmit this table to the electrical engineer. Provide in pipe sections Note: for pipe sizes 11/4" and smaller, use 1/4" larger diameter insulation to allow room for installation over cable. 7. Include clauses in the project specification to provide, install, and test the HWAT-Plus system. State appropriate fiberglass insulation thicknesses. 9 HWAT-Plus System Design Guide Electrical design sheet instructions Note: Follow these design steps when filling in copies of the adjacent electrical design sheet. The design sheet shown on page 11 is available in tablet form. Contact your Raychem representative. 1. Based on the information on the plumbing design sheets, note the HWAT-Plus cable type and fill in the electrical design table. Use Table 1 to determine breaker size and steady-state current draw. Choose the smallest circuit breaker size which can accommodate the circuit length. Junction box and panel locations should be based on circuit layouts provided by the plumbing engineer. If desired, steady-state current may be calculated to determine transformer sizing. Please note that the steady-state current table chart is used to estimate steady-state current only. Current draw at start-up on a cold pipe will be higher. The HWAT-Plus system design is based on operation at 208 volts. If different conditions occur, consult the factory for assistance. 2. Include the finished table on the electrical drawings. 3. Call out 30-mA ground-fault protection device in Division 16 of the specification and on the drawings. These ground fault breakers are a system requirement. Suitable circuit breakers are available from Westinghouse (types QPGFEP and QBGFEP) and Square D (types QOEPD and QOBEPD). 10 HWAT-Plus System Design Sheet R Project name: Part B: Electrical Design Project No.: Prepared by: Area of building: Checked by: 1. Fill in the electrical design table below, using the information provided on the plumbing design sheet. Date: Page no. of Electrical Design Table HWAT-Plus cable type: Circuit Approx. Voltage Breaker no. length Ground fault protection 208 30 mA 208 30 mA 208 30 mA 208 30 mA 208 30 mA Size (Table 1) Steadystate current (Table 1) J-box Panel location no. for power connection Include the electrical design table in the electrical drawings. Table 1 Heating cable type Circuit length in feet (meters) Circuit breaker* Steady-state current draw HWAT-B2 800 (240) 15 amp .006 amp / ft @ 105°F 800 (240) 20 amp (.020 amp / m @ 40°C) 800 (240) 30 amp 520 (155) 15 amp .008 amp / ft @ 115°F 700 (210) 20 amp (.026 amp / m @ 45°C) HWAT-G2 HWAT-Y2 HWAT-R2 800 (240) 30 amp 350 (105) 15 amp .010 amp / ft @ 125°F 500 (150) 20 amp (.033 amp / m @ 50°C) 800 (240) 30 amp 250 (75) 15 amp .015 amp / ft @ 140°F 330 (100) 20 amp (.049 amp / m @ 60°C) 500 (150) 30 amp 2. Include the finished electrical design table on the electrical drawings. *Use a ground-fault protection device with a nominal 30-mA trip level in each circuit. 3. Call out 30-mA ground-fault protection device in Division 16 of the specification and on the drawings. 11 HWAT-Plus System Design Guide Design example: 60-bed nursing home* *Design example has been simplified for clarity. The Decision The plumbing engineer was laying out the piping for the domestic hot water system for St. Mary’s Nursing Home, a three-story, sixty-bed, long-term health care facility. The engineer did not believe it necessary to recirculate the risers and was going to run two recirculation loops, one for each wing, in the ground floor ceiling space. However, the engineer decided that the return lines would have to take the same route as the supply lines. In this situation, the engineer knew the HWAT-Plus system would provide the more economical design. Furthermore, the client had indicated the possibility of extending either wing at some time in the future. The engineer knew that by using HWAT-Plus products, the system could be easily expanded if and when the client decided to do so. Plumbing Design The plumbing engineer began to fill in an “HWAT-Plus System Design Sheet, Part A: Plumbing Design.” The nursing home required a nominal temperature of 105°F, and HWAT-B2 was chosen. The engineer thought it would be useful to be able to isolate either wing for maintenance, so it was decided to run two separate circuits. Using 15amp circuit breakers, a maximum circuit length of 800 feet could be run, which was sufficient for either wing. Alternatively, just one circuit could have been run, with a tee connection at the intersection of the pipes from the two wings. The plumbing engineer filled in the table on the design sheet and handed it over to the electrical engineer. HWAT-Plus System Design Sheet R Refer to the HWAT-Plus Design Guide for complete design instructions. Project name: Area of building: St. Mary's Nursing Home All Project No.: E10 Prepared by: Checked by: Date: 1. Select the HWAT-Plus heating cable for the application. DG KC 11/4/90 80 Page no. 23 of Application Ambient temperature Nominal pipe temperature Heating cable type Hospitals, nursing homes Schools, prisons, some hospitals General domestic (offices, hotels) Kitchens, laundries 74°F to 79°F 70°F to 78°F 70°F to 78°F 70°F to 78°F 105°F (40°C) 115°F (45°C) 125°F (50°C) 140°F (60°C) HWAT-B2 HWAT-G2 HWAT-Y2 HWAT-R2 Use HWAT- 15 amp 20 amp 30 amp Maximum circuit 2. Maximum 208-V circuit breaker size: 3. Determine the maximum circuit length. 4. Lay out the HWAT-Plus circuits. Identify and measure each circuit. breaker: B2 15 A Maximum circuit length in feet (meters) Circuit HWAT-B2 breaker HWAT-G2 HWAT-Y2 HWAT-R2 30 amp 20 amp 15 amp 800 (240) 700 (210) 520 (155) 500 (150) 330 (120) 250 (75) 800 (240) 800 (240) 800 (240) 800 (240) 500 (150) 350 (105) Circuit Heating Risers, zones, Drwg. Approx. no. cable type or floors served no. length 1 2 See reverse to make additional Circuit Design Table entries. B2 B2 EW Wing NS Wing 13 13 280' 180' 5. Provide for thermal expansion. Equipment to allow for thermal expansion should be provided in all closed sections of piping downstream of check or pressure-reducing valves. 6. Specify the following thicknesses of fiberglass insulation: Pipe size (inches) Fiberglass insulation thickness (inches) 1⁄2" 1" - 1" 11⁄4" - 2" 11⁄2" 21⁄2" - 6" 2" Maximum circuit length: 800 ft Transmit this table to the electrical engineer. Check here if additional circuits are listed on reverse. Provide in pipe sections Note: for pipe sizes 11/4" and smaller, use 1/4" larger diameter insulation to allow room for installation over cable. 7. Include clauses in the project specification to provide, install, and test the HWAT-Plus system. State appropriate fiberglass insulation thicknesses. Completed HWAT-Plus System Design Sheet, Part A: Plumbing Design The plumbing engineer noted the pipes to be traced with HWAT-Plus heating cables on the drawings. He then inserted the standard clauses to provide, install and test the HWATPlus system, and called out the correct thicknesses of fiberglass insulation, in Division 15 of the specification. 12 Part A: Plumbing Design Isometric of building HWAT-Plus System Design Guide Design example: 60-bed nursing home* *Design example has been simplified for clarity. Electrical Design Upon receiving the HWAT-Plus Plumbing Design Sheet, the electrical engineer took out an “HWAT-Plus System Design Sheet, Part B: Electrical Design.” In the electrical drawings, junction boxes were located near each power connection. It was decided to power both circuits from the same panel. Circuit breaker sizes and steady-state current were calculated and included on a table in the electrical drawings. The need for a ground-fault protection device in each circuit was noted on the electrical drawings. HWAT-Plus System Design Sheet R Part B: Electrical Design Refer to the HWAT-Plus Design Guide for complete design instructions. Project name: Area of building: St. Mary's Nursing Home All Project No.: E10 Prepared by: Checked by: Date: 1. Fill in the electrical design table below, using the information provided on the plumbing design sheet. BW JJ 11/5/90 83 Page no. 13 of Electrical Design Table HWAT-Plus cable type: HWAT-B2 Circuit Approx. Voltage Breaker no. length Groundfault protection 1 2 280' 180' 208 30 mA 208 30 mA 208 30 mA 208 30 mA 208 30 mA Size (Table 1) 15 15 Steadystate current (Table 1) 1.7 A 1 A J-box Panel location no. for power connection J-17 J-21 Include the electrical design table in the electrical drawings. Check here if additional circuits are listed on reverse. P-3 P-3 Completed See HWAT-Plus System reverse for additional circuit entries Design Sheet, Part B: Electrical Design 2 1 H 1 PLAN OF GROUND FLOOR HOT WATER PIPING NOTE LEGEND 1 1 H Beginning and end of HWATPlus heat-tracing circuit 2 All heat-tracing cable to be HWAT-B2 Water heater Riser up HWAT-Plus heat-tracing layout shown on plumbing drawing 13 HWAT-Plus System Design Guide Design example: 250-bed, mediumsecurity prison* *Design example has been simplified for clarity. The Decision Reviewing the architectural drawings, the plumbing engineer observed that the design consisted of about a dozen two-story “pods” arranged around an expanse of open space. For security reasons, the County had requested that mechanical equipment and piping, and the associated pipe openings, be kept to an absolute minimum. The layout of the cells in each pod did not allow any “shortcut” for return piping for a recirculation loop; it would have to follow the same corridor as the supply piping. The plumbing engineer knew from experience that in these kinds of situations, the HWAT-Plus system would be more economical than recirculation. Plumbing Design For the prison application, HWAT-G2 was selected to maintain nominal temperature of 115°F. Each pod would be provided with a separate water heater and it was not considered necessary to heat trace the risers. Upon measuring the length of the ground floor piping, the plumbing engineer found it was possible to trace the entire piping in each pod with a single HWAT-G2 circuit and stay within the capacity of a 15-amp ground-fault circuit breaker. This would allow the heating cable to be conveniently powered from the electrical panel in the mechanical room. The plumbing engineer decided that the situation was sufficiently simple to ignore marking on the plumbing drawing the lines to be heat traced. Instead, the extent of the heat tracing could be called out in the notes. The plumbing engineer filled in the table on the design sheet and faxed it to the electrical engineer. The plumbing engineer then inserted the standard clauses to provide, install, and test the HWAT-Plus system, and called out the correct thicknesses of fiberglass insulation, in Division 15 of the specification. 14 HWAT-Plus System Design Sheet R Part A: Plumbing Design Refer to the HWAT-Plus Design Guide for complete design instructions. Project name: Area of building: Sherwood County Prison Typical Pod Project No.: C-15 Prepared by: Checked by: Date: 1. Select the HWAT-Plus heating cable for the application. MW AJ 4/30/91 34 Page no. 12 of Application Ambient temperature Nominal pipe temperature Heating cable type Hospitals, nursing homes Schools, prisons, some hospitals General domestic (offices, hotels) Kitchens, laundries 74°F to 79°F 70°F to 78°F 70°F to 78°F 70°F to 78°F 105°F (40°C) 115°F (45°C) 125°F (50°C) 140°F (60°C) HWAT-B2 HWAT-G2 HWAT-Y2 HWAT-R2 Use HWAT- 15 amp 20 amp 30 amp Maximum circuit 2. Maximum 208-V circuit breaker size: 3. Determine the maximum circuit length. 4. Lay out the HWAT-Plus circuits. Identify and measure each circuit. breaker: HWAT-G2 HWAT-Y2 HWAT-R2 30 amp 20 amp 15 amp 800 (240) 700 (210) 520 (155) 500 (150) 330 (120) 250 (75) 800 (240) 800 (240) 800 (240) A G2 All h.w. piping P5 270' Equipment to allow for thermal expansion should be provided in all closed sections of piping downstream of check or pressure-reducing valves. Pipe size (inches) Fiberglass insulation thickness (inches) 1⁄2" 1" - 1" 11⁄4" - 2" 11⁄2" 21⁄2" - 6" 2" Maximum circuit length: 800 (240) 500 (150) 350 (105) Circuit Heating Risers, zones, Drwg. Approx. no. cable type or floors served no. length 1 6. Specify the following thicknesses of fiberglass insulation: 15 Maximum circuit length in feet (meters) Circuit HWAT-B2 breaker See reverse to make additional Circuit Design Table entries. 5. Provide for thermal expansion. G2 520 ft Transmit this table to the electrical engineer. Check here if additional circuits are listed on reverse. Provide None required in pipe sections Note: for pipe sizes 11/4" and smaller, use 1/4" larger diameter insulation to allow room for installation over cable. 7. Include clauses in the project specification to provide, install, and test the HWAT-Plus system. State appropriate fiberglass insulation thicknesses. Completed HWAT-Plus System Design Sheet, Part A: Plumbing Design HWAT-Plus System Design Guide Design example: 250-bed, mediumsecurity prison* *Design example has been simplified for clarity. Electrical Design The electrical engineer took out the “HWAT-Plus System Design Sheet, Part B: Electrical Design” and filled in the table from the data on the plumbing engineer’s transmittal.The electrical engineer confirmed that a 15-amp breaker was adequate, and calculated the steady-state current. A junction box was located adjacent to the beginning of the heating cable circuit, and its number and the number of the electrical panel in the table were noted. A draftsperson copied the table onto the electrical drawings, along with a note calling out the need for a ground-fault protection device in each circuit. HWAT-Plus System Design Sheet R Part B: Electrical Design Refer to the HWAT-Plus Design Guide for complete design instructions. Project name: Area of building: Sherwood County Prison Typical Pod Project No.: C-15 Prepared by: Checked by: 1. Fill in the electrical design table below, using the information provided on the plumbing design sheet. Date: HB BF 5/4/1 40 Page no. 14 of Electrical Design Table HWAT-Plus cable type: HWAT-G2 Circuit Approx. Voltage Breaker no. length Groundfault protection 1 270' 208 30 mA 208 30 mA 208 30 mA 208 30 mA 208 30 mA Size (Table 1) 15 A Steadystate current (Table 1) 2.2 A J-box Panel location no. for power connection A-5 Include the electrical design table in the electrical drawings. Check here if additional circuits are listed on reverse. P-1 Completed See HWAT-Plus System reverse for additional circuit entries Design Sheet, Part B: Electrical Design H LEGEND H Water heater Riser up HW supply piping NOTE Heat-trace all HW distribution piping with HWAT-G2 heating cable. Do not trace branches or risers. Ground floor hot water piping diagram 15 HWAT-Plus System Design Guide Design example: 35-story apartment building* *Design example has been simplified for clarity. horizontal supply and return lines necessary in each zone, given the very limited space provided above the dropped ceilings. And there was not any room for the booster heaters and pumps for the recirculation system. The Decision The plumbing engineer was faced with laying out the hot water piping for the 35-story Washington Towers. The piping was relatively complex, making it especially important to balance the system adequately. As requested by the developer, the architect had squeezed in the maximum number of residential floors by working to the minimum headroom allowed by code. The plumbing engineer was required by code to divide the building into three pressure zones. However, there would be great difficulty in running the HWAT-Plus System Design Sheet R The plumbing engineer decided that an HWAT-Plus system would eliminate the need for horizontal piping and additional heaters or pumps. The risers could run continuously from top to bottom, broken only by pressurereducing valves at the 11th and 23rd floors. The plumbing engineer noted that the need for flow balancing was completely eliminated by using the HWAT-Plus system. Plumbing Design Following the plumbing design sheet, the plumbing engineer selected HWAT-Y2. Having estimated that a single circuit length on a 20-amp circuit breaker could run the complete height of the building, the engineer marked an HWAT-Plus circuit on each of the four risers and sent copies of the plumbing drawing and the design sheet to the electrical engineer. Standard clauses to provide, install, and test the HWAT-Plus system were included in Division 15 of the specification. To provide pressure relief in the piping during system startup, an expansion tank was indicated on each riser at each PRV. Part A: Plumbing Design H Refer to the HWAT-Plus Design Guide for complete design instructions. Project name: Area of building: Washington Towers Block A Project No.: F21 Prepared by: Checked by: Date: 1. Select the HWAT-Plus heating cable for the application. Page no. JB MP Application Ambient temperature Nominal pipe temperature Heating cable type Hospitals, nursing homes Schools, prisons, some hospitals General domestic (offices, hotels) Kitchens, laundries 74°F to 79°F 70°F to 78°F 70°F to 78°F 70°F to 78°F 105°F (40°C) 115°F (45°C) 125°F (50°C) 140°F (60°C) HWAT-B2 HWAT-G2 HWAT-Y2 HWAT-R2 Use HWAT- 15 amp 20 amp 30 amp Maximum circuit 2. Maximum 208-V circuit breaker size: 3. Determine the maximum circuit length. 4. Lay out the HWAT-Plus circuits. Identify and measure each circuit. See reverse to make additional Circuit Design Table entries. 5. Provide for thermal expansion. 6. Specify the following thicknesses of fiberglass insulation: LEGEND 1/10/91 41 of 80 H breaker: Water heater 20 Pressurereducing valve A Maximum circuit length in feet (meters) Circuit HWAT-B2 breaker HWAT-G2 HWAT-Y2 HWAT-R2 30 amp 20 amp 15 amp 800 (240) 700 (210) 520 (155) 500 (150) 330 (120) 250 (75) 800 (240) 800 (240) 800 (240) Circuit Heating Risers, zones, Drwg. Approx. no. cable type or floors served no. length 1 P5 2 HWAT-Y2 370' HWAT-Y2 P5 370' riser 1 Pipe size (inches) Fiberglass insulation thickness (inches) 1⁄2" 1" - 1" 11⁄2" 21⁄2" - 6" 2" Balancing valve 500 ft Transmit this table to the electrical engineer. Check here if additional circuits are listed on reverse. riser 2 Equipment to allow for thermal expansion should be provided in all closed sections of piping downstream of check or pressure-reducing valves. 11⁄4" - 2" Maximum circuit length: 800 (240) 500 (150) 350 (105) Provide Expansion tank in pipe sections All risers at floors 11 and 23 BH Booster heater Supply piping Return piping 7. Include clauses in the project specification to provide, install, and test the HWAT-Plus system. State appropriate fiberglass insulation thicknesses. Completed HWAT-Plus System Design Sheet, Part A: Plumbing Design BH Recirc. pump Note: for pipe sizes 11/4" and smaller, use 1/4" larger diameter insulation to allow room for installation over cable. 16 BH Y2 Riser diagram showing originally proposed recirculation system BH HWAT-Plus System Design Guide Design example: 35-story apartment building* *Design example has been simplified for clarity. Electrical Design HWAT-Plus System Design Sheet R The electrical engineer looked at the plumbing drawing, and at the “HWATPlus System Design Sheet, Part A: Plumbing Design,” and determined that it was most convenient to power all the circuits from the penthouse mechanical room. Junction boxes would be located at the beginning of each circuit and power run from a single panel. The electrical engineer completed the “HWAT-Plus System Design Sheet, Part B: Electrical Design” by calculating the breaker sizes and the steady-state currents. The finished table was included in the electrical drawings, along with a note calling for a ground-fault protection device in each circuit. Part B: Electrical Design Refer to the HWAT-Plus Design Guide for complete design instructions. Project name: Area of building: Washington Towers Block A Project No.: F21 Prepared by: Checked by: 1. Fill in the electrical design table below, using the information provided on the plumbing design sheet. Date: VL PB 1/20/92 40 Page no. 26 of Electrical Design Table HWAT-Plus cable type: HWAT-Y2 Circuit Approx. Voltage Breaker no. length Groundfault protection 1 2 3 370' 370' 370' 208 30 mA 208 30 mA 208 30 mA 208 30 mA 208 30 mA Size (Table 1) 20 20 20 20 A A A A Steadystate current (Table 1) 4 A 4 A 4 A 4.3 A J-box Panel location no. for power connection A-5 A-8 A-18 A-19 Include the electrical design table in the electrical drawings. Check here if additional circuits are listed on reverse. R2-4 R2-4 R2-4 R2-4 See reverse for additional circuit entries. Completed HWAT-Plus System Design Sheet, Part B: Electrical Design H 4 LEGEND H 1 2 3 1 2 3 Water heater Pressurereducing valve Expansion tank Riser diagram using HWATPlus system 3 3 Beginning and end of HWATPlus heating cable installed on supply piping NOTE All heat-tracing to be HWAT-Y2 4 17 HWAT-Plus System Design Guide Design example: 500-room hotel* *Design example has been simplified for clarity. The Decision The plumbing engineer reviewed the architectural drawings for a new hotel planned by National Resorts. The building consisted of six floors of guest rooms over a commercial area containing a health club, restaurants, conference rooms, shops, offices, and a laundry. The plumbing engineer decided to deliver water from the boiler at 140°F directly to the kitchens and laundry, and to mix to 125°F for domestic hot water. The HWAT-Plus system was chosen rather than recirculation because National Resorts insisted that there be no delay in getting hot water from any fixture. An HWAT-Plus system was chosen to accommodate all the architectural and construction changes that were bound to occur before the system was operating. Plumbing Design Following the “HWAT-Plus System Design Sheet, Part A: Plumbing Design,” HWAT-R2 was selected for the 140°F line running out of the boiler to the kitchens and laundry, and HWAT-Y2 for the domestic hot water system. Separate design sheets were used for each HWAT-Plus cable type. After reviewing the circuit length table, it was determined that the entire domestic hot water piping could be traced with only two HWAT-Y2 circuits by utilizing a 30-amp circuit breaker. However, the plumbing engineer decided to lay out the heating cable in smaller discrete zones to facilitate partial shutdown of the system for maintenance. Circuits staying within the maximum length for a 15-amp breaker were indicated on the drawing, and the table in the design sheets was completed. A copy of the drawing and the design sheets were sent to the electrical engineer. Division 15 of the specification for the domestic hot water lines called out standard clauses to provide, install, and test the HWAT-Plus system. 18 HWAT-Plus System Design Sheet R Part A: Plumbing Design Refer to the HWAT-Plus Design Guide for complete design instructions. Project name: Area of building: National Resorts Hotel Tower 1 Project No.: P19 Prepared by: Checked by: Date: 1. Select the HWAT-Plus heating cable for the application. SK JS 7/21/90 60 Page no. 42 of Application Ambient temperature Nominal pipe temperature Heating cable type Hospitals, nursing homes Schools, prisons, some hospitals General domestic (offices, hotels) Kitchens, laundries 74°F to 79°F 70°F to 78°F 70°F to 78°F 70°F to 78°F 105°F (40°C) 115°F (45°C) 125°F (50°C) 140°F (60°C) HWAT-B2 HWAT-G2 HWAT-Y2 HWAT-R2 Use HWAT- 15 amp 20 amp 30 amp Maximum circuit 2. Maximum 208-V circuit breaker size: 3. Determine the maximum circuit length. 4. Lay out the HWAT-Plus circuits. Identify and measure each circuit. breaker: 6. Specify the following thicknesses of fiberglass insulation: 15 A Maximum circuit length in feet (meters) Circuit HWAT-B2 breaker HWAT-G2 HWAT-Y2 HWAT-R2 30 amp 20 amp 15 amp 800 (240) 700 (210) 520 (155) 500 (150) 330 (120) 250 (75) 800 (240) 800 (240) 800 (240) 1 2 3 4 horiz. dist main riser risers B,C,D risers F,G,H Y2 Y2 Y2 Y2 H3 H3 H3 H3 95' 110' 240' 230' Equipment to allow for thermal expansion should be provided in all closed sections of piping downstream of check or pressure-reducing valves. Pipe size (inches) Fiberglass insulation thickness (inches) 1⁄2" 1" - 1" 11⁄4" - 2" 11⁄2" 21⁄2" - 6" 2" Maximum circuit length: 800 (240) 500 (150) 350 (105) Circuit Heating Risers, zones, Drwg. Approx. no. cable type or floors served no. length See reverse to make additional Circuit Design Table entries. 5. Provide for thermal expansion. Y2 350 ft Transmit this table to the electrical engineer. ✓ Check here if additional circuits are listed on reverse. Provide None required in pipe sections Note: for pipe sizes 11/4" and smaller, use 1/4" larger diameter insulation to allow room for installation over cable. 7. Include clauses in the project specification to provide, install, and test the HWAT-Plus system. State appropriate fiberglass insulation thicknesses. Completed HWAT-Plus System Design Sheet, Part A: Plumbing Design (for HWAT-Y2 only; design sheet for HWAT-R2 not shown) HWAT-Plus System Design Guide Design example: 500-room hotel* *Design example has been simplified for clarity. Electrical Design HWAT-Plus System Design Sheet R The electrical engineer looked at the layout of the circuits and assigned junction-box and panel locations for each circuit according to the electrical drawings. Filling in the information on the “HWAT-Plus System Design Sheet, Part B: Electrical Design,” the engineer calculated the breaker size and the steady-state current for each circuit. The completed table, with a note that the circuit breakers would incorporate 30-mA ground-fault protection, was then transferred to the electrical drawing. Part B: Electrical Design Refer to the HWAT-Plus Design Guide for complete design instructions. Project name: Area of building: National Resorts Hotel 1 P19 Project No.: Prepared by: Checked by: Date: 1. Fill in the electrical design table below, using the information provided on the plumbing design sheet. GL BF 7/25/90 45 Page no. 18 of Electrical Design Table HWAT-Plus cable type: HWAT-Y2 Circuit Approx. Voltage Breaker no. length Groundfault protection 1 2 3 4 5 95' 110' 240' 230' 260' 208 30 mA 208 30 mA 208 30 mA 208 30 mA 208 30 mA Size (Table 1) 15 15 15 15 15 A A A A A Steadystate current (Table 1) 1 1.1 2.4 2.3 2.6 A A A A A Include the electrical design table in the electrical drawings. J-box Panel location no. for power connection CF-3 J-21 T-6 T-32 CR-6 ✓ Check here if additional circuits are listed on reverse. R-3 M-4 S-8 S-14 R-6 See reverse for additional circuit entries. Table 1 Completed Heating HWAT-PLUS Circuit length cable type feet (meters) System Design Sheet,inPart B: Electrical Design 2 3 3 4 3 4 Circuit breaker* Steady-state current draw 4 *Use a ground-fault protection device with a nominal 30-mA trip level in each circuit. LEGEND H 2 2 4 3 6 6 Beginning and end of HWATPlus heating cable circuit installed on supply piping 5 NOTE 5 6 5 6 1 Water heater 2 5 1 5 5 All heating cables to be HWAT-Y2 except circuit no. 1 which shall be HWAT-R2 H HWAT-Plus heat-tracing layout shown on plumbing drawing 19 HWAT-Plus System Design Guide CSI Model Specification Raychem HWAT-Plus Hot Water Temperature Maintenance System Part 1 - General 2. Mechanical: The cable shall have a minimum cut-through resistance of 600 lb per CSA 22.2 0.3 Cutting Test 4.14. The cable shall have a minimum impact resistance of 25 ft•lb per UL 1588.11. The cable shall withstand a glancing impact of 22 ft•lb per UL 1581.590. The cable shall have a minimum abrasion resistance of 7000 cycles per UL 719.19. The cable shall withstand a crush resistance of 4500 N per IEEE 515 Deformation Test 5.1.5. 1. Furnish and install a UL-listed system of electric self-regulating heating cable and components for maintaining the water temperature in the hot water lines as indicated on the drawings. The cable shall utilize a radiation-crosslinked conductive polymer as the heating element, and the cable shall be specifically designed, manufactured, and UL listed for domestic hot water temperature maintenance. Part 3 - Performance 2. Submittals: i) Copy of UL file indicating the heating cable is specifically listed to provide supplementary heating to hot water service supply systems utilizing thermally insulated metal or plastic pipe. ii) Manufacturer’s catalog cuts showing materials and performance data. iii) Project list of at least 20 projects, installed for at least 5 years, with at least 2000 ft (600 m) of heating cable in each project. Part 2 - Materials 1. Construction: The self-regulating heating cable shall consist of two (2) 16-AWG (1.2-mm2) nickel-coated copper bus wires embedded in a radiationcrosslinked conductive polymer core. It shall be covered by a radiation-crosslinked, polyolefin, dielectric jacket surrounded by a polymer-coated aluminum wrap, and enclosed in a tinned copper braid of 14 AWG (2.5 mm2) equivalent wire size. The braid shall be covered with a (nominal) 40-mil (1mm) polyolefin outer jacket, color coded for easy identification. 20 1. Operating temperatures: The system shall maintain a nominal temperature of [105°F (40°C), 115°F (45°C), 125°F (50°C), 140°F (60°C)] as noted on the drawings, at 208 V. 2. Maintenance temperature: Each hot water system temperature shall be maintained using only one product. Temperatures shall be maintained with straight runs of heating cable on the pipe. 3. Power control (self-regulating index): The slope of the power/temperature curve shall be such that the power of the heating cable shall increase with decreasing temperature at a rate of at least 0.028 W/ft•°F (0.16 W/m•°C) from 50°F (10°C) to 100°F (38°C). 4. Long-term thermal stability (as determined by accelerated testing): The power retention of the heating cable shall be at least 90% after 300 cycles between 50°F (10°C) and 212°F (100°C). 5. High temperature withstand: The heater shall not decrease in resistance, overheat, or burn when powered at 208 V and exposed to 400°F (205°C) in an oven for 30 minutes. HWAT-Plus System Design Guide CSI Model Specification Raychem HWAT-Plus Hot Water Temperature Maintenance System Part 4 - Manufacturer 1. Experience: The manufacturer shall have more than ten years experience with selfregulating heating cables for temperature maintenance of domestic hot water. 2. Acceptable manufacturer: Raychem Corporation Part 5 - Execution 1. Installation: The system shall be installed according to the drawings and the manufacturer’s instructions. The installer shall be responsible for providing a functional system, installed in accordance with applicable national and local code requirements. Each circuit shall be protected with a 30-mA groundfault protection device. 2. Testing i) Procedure: Measure the heater circuit continuity and the insulation resistance between the braid and bus wires with a 2500Vdc megohmmeter (megger). ii) Timing: The tests should be performed after the pipe insulation has been installed and prior to installation of wall or ceiling panels, and shall be witnessed by the Construction Manager and the manufacturer or the manufacturer’s representative. iii) Acceptable results: The heater circuit shall be continuous and megger readings shall be at least 20 megohms regardless of heater length. Circuits yielding unacceptable readings must be repaired or replaced. iv) Submittal of results: Submit records of the test data to the Construction Manager. 21 HWAT-Plus System Design Guide Installation details HWK-XE end seal. Use one per circuit plus one per tee. No service loop required. ETL “electric traced” label. Place at 10-ft (3-m) intervals on alternating sides of insulation. GT-66 glass tape. Use tape to attach heating cable to pipe every 2 ft (.6 m). One roll will handle approximately 50 ft (15 m). ELECTRIC TRACED HWK-XP power connection kit (junction box not included). Use one per circuit. Allow for a 2-ft (.6-m) service loop.* HWK-XS splice kit. Use as needed. Allow for a 2- ft (.6-m) service loop. HWK-XT tee kit. Use at tees in traced piping. Allow for a 3-ft (1-m) service loop. Note: Required items not supplied by Raychem: • Fiberglass pipe insulation • 30-mA ground-fault protection device Component Usage Heater Allowance* Power Connection Kit Splice Connection Kit Tee Connection Kit End Seal Kit Glass Tape One per circuit As required At tees in traced piping One per circuit and one per tee Use tape to attach heating cable to pipe every 2 ft (.6 m) Place at 10-ft (3-m) intervals on alternating sides of insulation 2 ft (.6 m) 2 ft (.6 m) 3 ft (1 m) – – “Electric Traced” Labels 22 – *Raychem recommends a “service loop” (not shown) in the HWAT-Plus heating cables at connections or places in the piping where future service is expected. This extra length of cable will make any maintenance easier to accomplish. Be sure to consider service loops when calculating the total length required for an HWAT-Plus system. HWAT-Plus System Design Guide Installation details HWATTM Power connection Heating cable splice Heating cable tee End seal Heating cable and glass tape “Electric traced” label 23 Raychem Corporation Construction Products Group 300 Constitution Drive Menlo Park, California 94025-1164 (800) 542-8936 Fax (650) 361-6036 Raychem Canada Ltd. 3245 American Drive Mississauga Ontario, Canada LV4 1N4 (800) 387-3993 Fax (416) 671-0972 6/92 H54227 (Y8645) 1992 Raychem Corporation Printed in USA All of the information in this booklet, including illustrations, is believed to be reliable. Users, however, should independently evaluate the suitability of each product for their application. Raychem makes no warranties as to the accuracy or completeness of the information, and disclaims any liability regarding its use. Raychem’s only obligations are those in the Standard Terms and Conditions of Sale for this product, and in no case will Raychem be liable for any incidental, indirect, or consequential damages from the sale, resale, use, or misuse of the product.