PowerLogic Knowledge Base Procedure Phasor Diagram Verification - 4 wire system Safety Precautions • • • Work on De-Energized Gear NEVER short circuit the secondary of a PT NEVER open circuit a CT Use the shorting block to short circuit the leads of the CT before removing the connection from the CM. Procedure 1. Follow Phasor Diagram Data Reading procedure 2. Draw each of the vectors in the diagram or complete the Phasor Diagram Creator spreadsheet, 4-wire Tab Example: 200 4-Wire Current Phase A Phase B Phase C Neutral Voltage Phase A-B Phase B-C Phase C-A Phase A-N Phase B-N Phase C-N 150 Magnitud Register Angle 1078 79 1079 327.8 1080 81 1081 90.6 1082 72 1083 207.9 1084 1085 Register 100 50 0 1094 1096 1098 1088 1090 1092 210 207 207 1095 1097 1099 1089 1091 1093 -150 -100 -50 0 50 100 150 200 250 -50 0 120.8 240.1 -100 -150 Ia Ib Ic Van Vbn Vcn -200 3. Compare your diagram with the possible cases Note • • • Voltage between Va and Vn is the 0 degree reference ALL other phasors are referenced from these phasors Examples shown are with ABC or positive phasor sequence convention. To use negative sequence convention or ACB replace B by C and C by B in all diagrams. Phasor_Diagram_Verification_4_wire.doc 1999 Square D Company, All Rights Reserved Rev:05/22/99 1 of 3 PowerLogic Knowledge Base Procedure Possible Cases Vcn Vcn (120) ABC or Positive Sequence Ic Van (0) Van n Ia Ib Vbn (240) CCW Phasor Sequence Convention Vcn Vbn Unity PF Vcn Ic Ic Ia Van Ib Van Ia Vbn 0.5 Lag PF Inductive Load Phasor_Diagram_Verification_4_wire.doc 1999 Square D Company, All Rights Reserved Ib Vbn 0.87 Lead PF Capacitive Load Rev:05/22/99 2 of 3 PowerLogic Knowledge Base Procedure 4. Use the following rules to match your system to one of the possible cases • To change phasor direction: revert polarity of PT/CT Example: 200 The polarity of CT phase b is reversed 150 Reversing the polarity of the CT will correct the phasor with a shift of 180 degrees 100 50 0 -150 -100 -50 0 50 100 150 200 250 -50 Ia Ib Ic Vab Vbc Vca -100 -150 -200 • To change phases: swap CT/PT Example: 200 150 The leads from the CTs for B and C phases were swapped on the input terminals of the circuit monitor 100 50 0 -200 -100 0 100 200 300 -50 Swapping the phase B&C CT leads on the current input terminal of the circuit monitor will correct this condition -100 -150 -200 • • Ia Ib Ic Vab Vbc Vca Do one change at a time Repeat Checking Meter Readings procedure after you finish changing connections Phasor_Diagram_Verification_4_wire.doc 1999 Square D Company, All Rights Reserved Rev:05/22/99 3 of 3