Auxiliary Electric Heater Interface kit ASKHTR

advertisement
Auxiliary Electric
Heater Interface kit
ASKHTR
Table of Contents
General Information
2
INSTRUCTIONS for 1: Boilerless
Installation, Operation
& Maintenance
97B0012N07
Revised: 14 July, 2016
2
INSTRUCTIONS for 2: Supplemental3
Typical Wiring Diagram
4
Typical Wiring Diagram
5
Revision History
8
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Aux Electric Heater Interface Kit
Rev: 14 July , 2016
General Information
Safety
Warnings, cautions, and notices appear throughout this
manual. Read these items carefully before attempting any
installation, service, or troubleshooting of the equipment.
All work to be performed by qualified service contractor.
DANGER: Indicates an immediate hazardous situation,
which if not avoided will result in death or serious injury.
DANGER labels on unit access panels must be observed.
WARNING: Indicates a potentially hazardous situation,
which if not avoided could result in death or serious injury.
CAUTION: Indicates a potentially hazardous situation or
an unsafe practice, which if not avoided could result in
minor or moderate injury or product or property damage.
NOTICE: Notification of installation, operation, or
maintenance information, which is important, but which is
not hazard-related.
� WARNING! �
WARNING! The installation of water-source heat pumps and
all associated components, parts, and accessories which
make up the installation shall be in accordance with the
regulations of ALL authorities having jurisdiction and MUST
conform to all applicable codes. It is the responsibility of
the installing contractor to determine and comply with ALL
applicable codes and regulations.
� WARNING! �
WARNING! To avoid possible injury or death due to electrical
shock, open the power supply disconnect switch and secure
it in an open position during installation.
� CAUTION! �
CAUTION! Use only copper conductors for field installed
electrical wiring. Unit terminals are not designed to accept
other types of conductors.
DESCRIPTION: Kit contains 24 VDC relay, wires and
harness.
APPLICATION: This kit can be used for two applications:
1) For automatic changeover from heat pump heat
to electric heat for boilerless applications. Also
required AH Accessory Heater and unit must have
DXM. Controller can be heat pump thermostat, MPC,
or LON. Controller Y is connected to DXM Y, DXMLT1 sensor in unit determines if unit will operate as
compressor heat or electric heat.
2
2) For supplemental electric heat when using MPC.
Also required AH Accessory Heater and unit must have
MPC and either CXM or DXM. W signal from MPC is
connected to W on CXM/DXM.
INSTRUCTIONS for 1: boilerless - use wire diagram
96B0006N39
Connect the harness to DXM-P6 (lower right corner).
Note- For MPC controller- the heater relay uses the same
DXM output (EH) as pulsing fault code. This feature
will not be available and pulsing fault code can only be
viewed at the DXM.
Locate the relay within the reach of the harness wires,
mark and drill two 7/64” (2.8 mm) diameter holes.
Securely attach relay with two #6 screws.
Connect one black and the white harness wire to each side
of relay coil. Securely tape off the 2 unused harness wire
terminals (red and 1 black) to prevent electrical short.
Connect supplied red wire from relay - COM and to any R
connection on DXM.
Connect supplied white wire from relay - N.O. to AH
heater – W1
Connect supplied brown wire from DXM-C to AH
heater-C
Connect supplied yellow wire from DXM-R to AH
heater - R
Remove DXM - G wire (disconnect on both ends).
Connect supplied Black wire from AH heater GT to
controller G output. Connect supplied gray wire from
DXM-G to AH heater GU
Configuring the DXM; Set dip switch S1.7 to enable (off).
Set S1.8 to desired changeover 40F (off) or 50F (on). Set
S1.6 and configure JW4 for your controller (see table 1).
Blue wire is not used.
Table 1
DXM
Controller
Dip Switch
S1.6
S1.7
Clip Jumper
JW4
Thermostat
On
Off
No
MPC
Off
Off
Yes
LON
Off
Off
Yes
C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Aux Electric Heater Interface Kit
R e v : 1 4 J u l y, 2 0 1 6
General Information
INSTRUCTIONS for 2: supplemental electric heat when
using MPC. Use wire diagram 96B0006N82
Connect the harness to CXM/DXM-P6 (lower right
corner). Note- For MPC controller- the heater relay uses
the same CXM/DXM output (EH) as pulsing fault code.
This feature will not be available and pulsing fault code
can only be viewed at the CXM/DXM.
Remove CXM/DXM G wire (disconnect on both ends).
Connect supplied Black wire from AH heater GT to
controller G output. Connect supplied gray wire from
CXM/DXM-G to AH heater GU.
For DXM- Set dip switch S1.6 to normal (on) and JW4
must be clipped. For CXM- Set dip switch 4 to normal
(on) and JW1 must be clipped.
Locate the relay within the reach of the harness wires,
mark and drill two 7/64” (2.8 mm) diameter holes. Securely
attach relay with two #6 screws.
Connect one black and the white harness wire to each
side of relay coil. Securely tape off the 2 unused harness
wire terminals (red and 1 black) to prevent electrical
short.
Connect supplied blue wire from MPC-W to CXM/
DXM-W.
Connect supplied red wire from relay- COM and to any R
connection on CXM/DXM.
Connect supplied white wire from relay- N.O. to AH
heater –W1.
Connect supplied brown wire from CXM/DXM-C to AH
heater- C.
Connect supplied yellow wire from CXM/DXM-R to AH
heater- R
c l i m a t e m a s t e r. c o m
3
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Aux Electric Heater Interface Kit
Rev: 14 July , 2016
Typical Wiring Diagram
4
C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Aux Electric Heater Interface Kit
R e v : 1 4 J u l y, 2 0 1 6
Typical Wiring Diagram
c l i m a t e m a s t e r. c o m
5
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Aux Electric Heater Interface Kit
Rev: 14 July , 2016
Notes:
6
C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Aux Electric Heater Interface Kit
R e v : 1 4 J u l y, 2 0 1 6
Notes:
c l i m a t e m a s t e r. c o m
7
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Aux Electric Heater Interface Kit
Rev: 14 July , 2016
Revision History
Date:
Item:
07/14/16
Logo
04/15/16
Revised
08/22/12
First Published
Action:
Updated
7300 S.W. 44th Street
Oklahoma City, OK 73179
Phone: 405-745-6000
Fax: 405-745-6058
climatemaster.com
*97B0012N07*
97B0012N07
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time for order may be changed
without notice and may not be as described herein. Please contact ClimateMaster’s Customer Service Department at 1-405-745-6000 for specific
information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form
the basis of any bargain between the parties, but are merely ClimateMaster’s opinion or commendation of its products.
8
© ClimateMaster, Inc. 2012