Nexus 1-8 Loop (A1557) Analogue Addressable Control Panel User Instructions Note: You must turn the ACCESS CONTROLS keyswitch from 0 to 1 before you can operate any controls Fire The RED main fire LED and - if a zonal display is fitted - the zonal fire indicator will pulse, the alarms will sound and the internal buzzer will operate. The LCD display will indicate the exact location of the device. Locate the source of the fire (an LED will be visible on the detector which has been activated). To silence the alarms, turn the keyswitch from 0 to 1 and press SILENCE ALARMS. The alarms will silence and the RED LEDs will change to a steady illumination. When the fire has been extinguished, press SYSTEM RESET. Should the system have activated for no apparent reason, please note which detector has been activated before pressing the SYSTEM RESET button and contact your service engineer. If necessary, the alarms can be resounded by pressing EVACUATE. To silence the alarms during an evacuate condition, press SILENCE ALARMS. To clear fire indication, press RESET. A second alarm condition will re-initiate a full alarm condition. The LCD display will then show the location of the second device operated. Any further device operations will cause the MORE MESSAGES LED to flash. Press the SCROLL MESSAGES button to reveal locations. Fault Call your service engineer immediately. The fault buzzer will sound and the appropriate fault LED will pulse. The LCD display will also indicate fault details. Press SILENCE BUZZER to silence the fault buzzer. When the fault condition has cleared, press RESET FAULTS. WARNING: This equipment contains dangerous voltages. To prevent electric shock, do not open the panel door. No user-serviceable parts inside - for servicing, contact suitably qualified personnel. Evacuate When the panel is in standby (normal) mode, the alarms may be sounded by pressing EVACUATE. Press SILENCE ALARMS and RESET SYSTEM to return the panel to standby. Override Delay When a fire alarm occurs and the Delay On LED is flashing, the fire alarm sounders will not operate until the time delay has timed out. To override this time delay, press the button marked Override Delay. Document Ref: Nex8user.doc/Rev0 09.07.00 Page 1 of 4 Originator MC Checked by AC__ Approved by JBJ__ Test Display The TEST DISPLAY button should be operated every week as part of the system test routine for checking correct operation of the LCD display, panel buzzer and LEDs. Press momentarily to operate. Test Routine This should be carried out in accordance with BS5839 Part 1. Refer to Fire Alarm System Logbook. User Facilities Note: You must turn the keyswitch from 0 to 1 before you can operate any controls The following user facilities are available via the Engineer’s Menu screen. (i) Level 1 Access Code 1278 1:SET TIME/DATE 2:ISOLATE DEVICES 3:EDIT DEV/LOGO TEXT (ii) Single device, range, all (de-isolate only), status Via PC or special QWERTY keyboard Accessing Engineer’s Menu 4 Step 1 - Press 0 9 P a n - - - - - - - ENT ER CO : e D ENGINEER to reveal the following: 0 4 : 2 6 l N a m e - - - - - - - - - - E , P RE S S * Step 2 - Press Engineer’s code S E L ECT L EV 1 : S E T T I ME 2: : I S O L A T E * NEXT P AG Step 3 - Press * 1 2 7 8 and then * to reveal the following: E L 1 O P T I ON / DAT E DEV I C E S E # QU I T to scroll through the Engineer’s Menu. NOTE: No facility is accessible unless it is shown on-screen. Step 4 - Select the required engineer’s facility by pressing the corresponding number button. (iii) Setting Time & Date At Step 4 within the Engineer’s Menu (see section ii above), select 1:SET TIME/DATE. S E L ECT L EVE L 1 ENT E R T I ME h h # BACKS P ACE Document Ref: Nex8user.doc/Rev0 O P T I ON mm s s * 09.07.00 ENT ER Page 2 of 4 Originator MC Checked by _AC_ Time is entered as two digits for each of the hours, minutes and seconds; eg 8am is 08:00:00. The clock starts, at the time set, when the * ENTER key is pressed. The date may then be entered as two digits for each of the day, month and year for example, the 3rd of August 1997 is 03:08:97. It is not necessary to press the ENTER key after entering the date, the system automatically returns to normal operation. (iv) Isolate At Step 4 within the Engineer’s Menu (see section ii above), select 2:ISOLATE DEVICES. Within this sub-menu, the following four options are available. Use the * to view these options (if not currently displayed). Select the required option by pressing the corresponding number button and then follow the on-screen instructions for each option. I S 1 . 2 . * N O S P X LAT I O EN S OR ANE L T P AG N F AC I L I TY S I NPUT S E # QU I T Enables the engineer to isolate/de-isolate loop devices Enables engineer to isolate/de-isolate programmable panel inputs To select next page (printer isolate) Selecting Option 1. SENSORS reveals the following screen: S ENS OR I S O / DE 1 . S I NGL E 2 . R 3 . R EAD 4 . D # = QU I - I SO ANGE E I S AL L T Enables the engineer to isolate/de-isolate a range of devices Enables the engineer to de-isolate all the devices Enables the engineer to view the devices isolated Enables the engineer to isolate/de-isolate a single device Within options 1 and 2 above of the Sensor Iso/Deiso screen, follow the on-screen instructions to enter loop and sensor number(s). Press * ENTER at each stage. After entering loop and sensor (or range of sensors), a screen similar to the following will appear: I DENT I F Y DE 0 1 : 0 0 1 DE - I 1 . I S O 2 . # = Q Loop & device number V S D U I O E I CE LAT ED - I SO T Current Status Press 2 to de-isolate Press 1 to isolate Selecting Option 2 . PANEL INPUTS on the ISOLATION FACILITY screen accesses a screen for single, range or read options. After selecting single or range as appropriate and entering the input * number (s), followed by I DENT I F Y I N I N P UT 0 0 1 D 1 . I S O 2 . # = Q Input number P E D U U I E I ENTER, the following screen is revealed: T S OLAT ED - I SO T Current Status Press 2 to de-isolate Press 1 to isolate When any device is isolated, the DISABLED LED indicator on the panel will illuminate. Document Ref: Nex8user.doc/Rev0 09.07.00 Page 3 of 4 Originator MC Checked by _AC_ (v) Edit This option is used to enter device location messages and to enter the company name of the installation. Text editing must be done using either the PC download facility or special keyboard. Please contact your system provider for details. User Controls and Indications System disabled illuminated when detectors or inputs are isolated LCD display 4 x 20 character line to display 2 events Press to reveal more messages on the LCD display Silence alarms control. Press Press to test the to silence the alarm sounders. alarms. Release to clear. General fault illuminates when a general system fault has occurred Illuminates when the the mains supply is healthy. LED flashes when a fire is triggered. It then goes steady when the SILENCE ALARMS is pressed. Flashing LED in FIRE. Prompts the user to operate the SILENCE ALARMS control in accordance with the fire proceedures in operation. The LED then goes steady. SUPPLY HEALTHY GENERAL FAULT FIRE DISABLED ACCEPT 1 SILENCE ALARMS RESET SYSTEM 7 2 SCROLL MESSAGES CLEAR DISPLAY 8 3 TEST ALARMS TEST DISPLAY 9 4 ACCESS MENU SILENCE BUZZER 0 5 OVERRIDE DELAY ESCAPE # 6 EVACUATE ENTER * TEST DELAY ON SYSTEM FAULT ALERT MORE MESSAGES Illuminates when the alarms and panel outputs would be delayed in the event of a fire condition. Illuminates when the panel is in engineers test mode. Illuminates when there is a system fault. Flashes when there are more events to be viewed on the LCD display. Pressing the SCROLL MESSAGES will reveal the data until the LED goes steady. Press to clear the LCD display after a fault has been cleared. Test display to test all LEDs and panel buzzer. Silence buzzer control. Press to silence the fault or alert buzzer. Press to escape from the engineer programme function. Press to enter engineer's data Press to access engineers menu via access code. ACCESS CONTROLS Illuminates when a device is in an alert condition. System Reset control. Press to reset the system after the Silence Alarms has been pressed. Press to override the output delay. Evacuate control operates the alarm circuits and the fire relays. Press to operate and press SILENCE ALARMS to silence. Access Controls Keyswitch. Position "0" inhibits all the controls. Position "1" enables all the controls LCD Display Example Document Ref: Nex8user.doc/Rev0 09.07.00 Page 4 of 4 Originator MC Checked by _AC_