FEATURES
•
•
•
•
•
•
•
•
•
•
•
Approvals: UL 464. FM, CSFM and MEA Pending.
Field selectable settings for Temporal (Code 3) or
Continuous Horn (MIZ-TC models).
Designed to meet or exceed NFPA/ANSI standards.
Convenient mounting to any standard single gang
box.
No additional trimplate required for flush mounting.
Fast installation with In/Out screw terminals using
#12 to #18 AWG wire.
High sound output/low current draw/low temperature
compensation.
Available in red or off-white color.
24 Vdc models with wide listed voltage range, filtered
DC and FWR.
Polarized inputs for compatibility with standard
reverse polarity type supervision of circuit wiring by
an alarm panel.
Low cost installation via standard electrical boxes.
Attractive flush or surface mounting options.
DESCRIPTION
The Fenwal Series MIZ piezoelectric Mini Horns are
compact electronic alarm signals that are listed under UL
464 for Audible Appliances in public mode Fire Protection
Systems. They are ideal for alarm signaling in individual
rooms, apartments, hotels, motels and offices where
attractive appearance dependable performance and economical installation are prime concerns.
The MIZ-TC models offer field selectable setting for Temporal (Code 3) or Continuous Horn along with an attractive appearance and dependable performance. The
Series MIZ offers high sound output along with low current draw and are available with color choices of red or
off-white which will blend with any decor.
The Series MIZ signals are rated for 24 Vdc input and
may be used with filtered or unfiltered (full-wave-rectified)
input voltages. The Series MIZ Signals have IN/OUT wiring terminations that accept two #12 to #18 AWG wires at
each terminal. Inputs are polarized for compatibility with
standard reverse polarity type supervision.
SPECIFICATIONS
Table 1. dBA Levels and Current Ratings
Anechoic
Voltage
(Vdc)
Model
Continuous
Temporal (Code 3)
dBA
@
10 ft.
Current
(Amps)
dBA
@
10 ft.
Current
(Amps)
N/A
MI Z -24-R
24
90
.012
N/A
MI Z -24-W
24
90
.012
N/A
N/A
MI Z -TC24-R
24
87
.017
88
.017
MI Z -TC24-W
24
87
.017
88
.017
Reverberant per UL 464
Voltage
(Vdc)
Model
Continuous
Temporal (Code 3)
dBA
@
10 ft.
Current
(Amps)
dBA
@
10 ft.
Current
(Amps)
MI Z -24-R
24
85
.017
N/A
N/A
MI Z -24-W
24
85
.017
N/A
N/A
MI Z -TC24-R
24
83
.017
79
.017
MI Z -TC24-W
24
83
.017
79
.017
WIRING DIAGRAM
FROM
PRECEDING +
_
APPLIANCE
OR FACP
TO NEXT
+
_ APPLIANCE
OR EOLR
+
_
Figure 1. Wiring Diagram
INSTALLATION NOTES
WARNING
Failure to comply with the installation
instructions could result in improper installation, application, and/or operation of
these products in an emergency situation,
which could result in property damage and
serious injury or death.
1.
Mini Horn models are listed for indoor use with a
temperature range of 32°F to 120°F (0°C to 49°C)
and maximum humidity of 85% RH.
2. Rated input voltage (either filtered DC or unfiltered
full-wave-rectified FWR): 18-31 Vdc (for 24 Vdc MIZ
models) and 16-33 Vdc (for 24 Vdc MIZ-TC models).
3. Contact Fenwal for Installation Instructions on these
products. These materials contain important information that should be read prior to specifying or
installing these products including:
• Total current required by all appliances connected to system secondary power sources.
• Fuse ratings on notification appliance circuits to
handle peak currents from all appliances on
those circuits.
• The voltage applied to these products must be
within their rated voltage range.
• Conductor size (AWG), length and ampacity
should be taken into consideration prior to design
and installation of these products, particularly in
retrofit installations.
4. Fenwal notification products must be used within the
published specifications and must be PROPERLY
specified, applied, installed, operated, maintained
and operationally tested in accordance with their
installation instructions at the time of installation and
at least twice a year or more often and in accordance with local, state and federal codes, regulations and laws. Specification, application ,
installation, operation, maintenance and testing
must be performed by qualified personnel for proper
operation in accordance with all of the latest
National fire Protection Association (NFPA), Underwriters’ Laboratories (UL), National Electrical Code
(NEC), Occupational Safety and Health Administration (OSHA), local, state, count, province, district,
federal and other applicable building and fire standards, guidelines, regulations, laws and codes
including, but not limited to, all appendices and
amendments and the requirements of the local
authority having jurisdiction (AHJ).
ORDERING INFORMATION
Part No.
Model No.
Input
Voltage
Horn Pattern
Color
Mounting
Options*
75-000020-001
MI Z -24-R
24 Vdc
Continuous
Red
A, B
75-000020-002
MI Z -24-W
24 Vdc
Continuous
White
A, B
75-000025-001
MI Z -TC24-R
24 Vdc
Continuous or
Temporal
Red
A, B
75-000025-002
MI Z -TC24-W
24 Vdc
Continuous or
Temporal
White
A, B
*See Figures 2 and 3 for Mounting Options.
FLUSH MOUNTING
OPTION A
SINGLE-GANG X 3 ½”DEEP BACKBOX
MAXIMUM NUMBER OF CONDUCTORS IS
4 FOR awg #18, #16, #14 AND #12.
Figure 2. Flush Mounting
SURFACE MOUNTING
OPTION B
SINGLE-GANG X 1 3/4”
DEEP WIREMOLD
BACKBOX
MAXIMUM NUMBER OF CONDUCTORS
IS 4 FOR awg #18, #16, #14 AND #12.
Figure 3. Surface Mounting
ARCHITECTS AND ENGINEERS
SPECIFICATIONS
The notification appliance shall be a Fenwal Series MIZTC audible appliance or approved equal. The notification
appliance shall be electronic and shall have field selectable settings for Temporal (Code 3) or Continuous horn.
The sound pressure measurement on Temporal (Code 3)
setting shall be 87 dBA minimum at 24 Vdc and 86 dBA
minimum at 12 Vdc. Operating voltages shall be 24 Vdc
using filtered power or unfiltered power supply (full-waverectified).
In application where only continuous horn is required, the
notification appliance shall be a Fenwal Series MIZ audible appliance or approved equivalent. Sound pressure
measurement at 10 feet shall be 90 dBA minimum at 24
Vdc and 88 dBA minimum at 12 Vdc. Operating voltages
shall be either 12 Vdc or 24 Vdc using filtered power or
unfiltered power supply (full wave rectified).
All models shall have provision for standard reverse
polarity type supervision and in/out wiring using terminals
that accept #12 to #18 AWG wiring. The appliances shall
be mounted indoors and mount to standard electrical
backboxes requiring no additional trimplated or adapters.
Fenwal is a registered trademark of Kidde-Fenwal Inc.
TM
This literature is provided for informational purposes only. KIDDE-FENWAL, INC.
assumes no responsibility for the product’s suitability for a particular application. The product must be properly applied to work correctly.
If you need more information on this product, or if you have a particular problem or question, contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.
F-75-002 Rev AB
© 2007 Kidde-Fenwal Inc.
Printed in USA
R
Protection Systems
A UTC Fire & Security Company
400 Main Street
Ashland, MA 01721
Ph: 508.881.2000
Fax: 508.881.8920
www.fenwalfire.com
Download