Safe electrical distribution for petrol forecourts

advertisement
Safe electrical distribution for petrol forecourts
The Petrol Forecourt Incomer has been specifically designed to
provide safe electrical distribution in this hazardous environment.
Our unit is a simple enclosure with all devices fitted and is easy to
install.
The unit is assembled to the highest standards and meets requirements of
the APEA & IP publication “Code of Practice for the Design, Construction,
Modification, Maintenance and Decommissioning of Filling Stations (The
Blue Book).” This specifies that the electrical supply to a petrol filling station
should not have combined neutral and productive conductors (i.e. TN-C-S
system) or protective multiple earthings. This prevents uncontrollable current
to earthed metalwork from the supply system external to the petrol filling
station which could lead to incendiary sparking.
This unit has been installed at many leading petroleum retail outlets across
the United Kingdom.
The unit consists of a Form 1 IP43 Polyester
enclosure fitted with:
NSX compact moulded case circuit breaker (MCCB) for over current and short circuit protection and disconnection
Adjustable residual current module (RCD) added to the MCCB for earth fault protection and test buttons for checking the operation of the RCD module. The adjustment settings and test buttons are protected by a sealed transparent cover to protect against unauthorised access.
A 13 amp socket used for connecting an earth fault impedance tester. This socket is protected by a miniature circuit breaker and interlocked as
required by paragraph 14.4.5 of the “Blue Book”. The earth terminal from this socket is connected to a separate earth stud. This socket is
protected by a transparent lockable cover.
As an option three ‘Phase Healthy’ lamps can be provided.
A further option is for push buttons to initiate the time delay on the test socket stopping unauthorised use.
Top or bottom cable entry versions are available.
In addition to the Petrol Forecourt Incomer we are able to supply complete switchboards for petrol
stations incorporating all of the requirements of “The Blue Book”
We are able to provide solutions for metering and monitoring of your energy use and if required this data
can be transmitted to corporate headquarters.
Petrol incoming units
Catalogue number
Cable entry
Options Price
standard
standard
with lamps
with lamps
with push button with push button
combination (L&PB)*
combination (L&PB)*
£708.00
£708.00
£767.00
£767.00
£720.00
£720.00
£780.00
£780.00
standard
standard
with lamps
with lamps
with push button
with push button
combination (L&PB)*
combination (L&PB)*
£838.00
£838.00
£896.00
£896.00
£851.00
£851.00
£909.00
£909.00
standard
standard
with lamps
with lamps
with push button
with push button
combination (L&PB)*
combination (L&PB)*
£867.00
£867.00
£923.00
£923.00
£878.00
£878.00
£937.00
£937.00
standard
standard
with lamps
with lamps
with push button
with push button
combination (L&PB)*
combination (L&PB)*
£1094.00
£1094.00
£1213.00
£1213.00
£1106.00
£1106.00
£1225.00
£1225.00
Retrofit (for existing installation)
£144.00
100Amp, 2 pole rating, H540xW270xD210
LVE-PFD100BS
LVE-PFD100TS
LVE-PFD100BL
LVE-PFD100TL
LVE-PFD100BP
LVE-PFD100TP
LVE-PFD100BC
LVE-PFD100TC
Bottom
Top
Bottom
Top
Bottom
Top
Bottom
Top
125Amp, 4 pole rating, H540xW270xD210
LVE-PFI125BS
LVE-PFI125TS
LVE-PFI125BL
LVE-PFI125TL
LVE-PFI125BP
LVE-PFI125TP
LVE-PFI125BC
LVE-PFI125TC
Bottom
Top
Bottom
Top
Bottom
Top
Bottom
Top
160Amp, 4 pole rating, H540xW270xD210
LVE-PFI160BS
LVE-PFI160TS
LVE-PFI160BL
LVE-PFI160TL
LVE-PFI160BP
LVE-PFI160TP
LVE-PFI160BC
LVE-PFI160TC
Bottom
Top
Bottom
Top
Bottom
Top
Bottom
Top
250Amp, 4 pole rating, H900xW270xD210
LVE-PFI250BS
LVE-PFI250TS
LVE-PFI250BL
LVE-PFI250TL
LVE-PFI250BP
LVE-PFI250TP
LVE-PFI250BC
LVE-PFI250TC
Bottom
Top
Bottom
Top
Bottom
Top
Bottom
Top
Retrofit kit, H200xW245xD112
LVE-PFITESTSKT
* L&PB = Lamps and push buttons.
If you require higher ratings of forecourts incomers or distribution boards please contact us.
Make the most of your energySM
For more information
please contact us on 0870 608 8 608
or visit www.schneider-electric.co.uk
SE7152
JAN 11
Download