PRODUCT CATALOG PROTECTIVE DEVICES Middle South Union Electric Co.Ltd. Wenzhou Bridge Industry Zone,Beibaixiang Town Yueqing City,China. SUB-STATION SWITCH The Sub-station Switches manufactured by Middle South Union Electric Co. Ltd., fully comply the respective International Standards of ANSI and IEC. The switches have been tested by internationally recognized Laboratory and successfully passed all relevant tests. Quality materials and latest production technology have made these switches more reliable and durable. Some salient features of the switches are mentioned below; 1. Silver-plated hard drawn solid Copper Blade ensures greater rigidity & conductivity. 2. Silver-plated Hard Drawn Copper Contacts ensure uniform conductivity with self wiping characteristics. 3. Tin-Plated Bronze Parallel Groove Terminal Pads ensure firm contact of conductors & switch terminals. 4. Hot Dipped Galvanized Structural Steel Channel ensures strong switch support. 5. The switches have very low operating torque and are virtually maintenance free. VOLTAGE REGULATOR BYPASS SWITCH Outdoor Single Pole hook operated Voltage Regulator Bypass Switch, Type/ Model: MSU-15.4 of Middle South Union Electric Co. Ltd., can be used in 11 KV, 50 Hz distribution lines in a tropical climate with an average ambient temperature of 40°C and high annual rainfall . These switches are to be vertically mounted and manually operated. The switch ratings fully comply with ANSI C37.30 and ANSI TECHINICAL DETAILS: Nominal System Voltage Maximum Voltage Basic Insulation Level Continuous Current Rating Momentary Current Rating Short Time Current (3 sec) Connector Range Mounting Position : : : : : : : : 11 KV 15.5 KV 110 KV 400 A 65 KA 25 KA # 4 to 4/0 Vertical SUB-STATION SWITCH FUSED RECLOSER BYPASS & DISCONNECT SWITCH TECHINICAL DETAILS: Nominal System Voltage Maximum Voltage Basic Insulation Level Continuous Current Rating Momentary Current Rating Rated Max. Fused Current Symmetrical Int. Current Connector Range Fuse Tube Fuse Link Fused current (max) Current carring contract : : : : : : : : : : : : 11 KV 15.5 KV 110 KV 600 A 65 KA 200 A. 7100 A 2/0-350 MCM Bone fiber lining 100T 200A Silver plated DISCONNECT SWITCH, SINGLE POLE Outdoor Single Pole Hook operated Disconnect Switch, Type/ Model: MSU-18.6 & MSU-19.6 of Middle South Union Electric Co. Ltd., can be used in 11 KV & 33 KV, 50 Hz distribution lines in a tropical climate with an average ambient temperature of 40°C and high annual rainfall. These switches are to be mounted in horizontally under hung or vertical position and manually operated. The switch ratings fully comply with ANSI C37.30 and ANSI C37.34. TECHINICAL DETAILS: Type/ Model MSU-18.6 Nominal System Voltage 11 KV Maximum Voltage 15.5 KV Basic Insulation Level 110 KV Continuous Current Rating 600 A Momentary Current Rating 65 KA Short Time Current 25 KA Connector Range #6to500mcm,Cu/Al Mounting Hor. under hung Blade open position 160° Operation Manual with Hot stick Load Brick Hook attachment Current Carrying Contrat Silver plated Connector accommodation Tin plated parallel grove. MSU-19.6 33 KV 38 KV 200 KV 600 A 65 KA 25 KA #6to500mcm,Cu/Al Vertical 160 ° Manual with Hot stick Hook attachment Silver plated Tin plated parallel grove. SUB-STATION SWITCH VOLTAGE REGULATOR BYPASS & DISCONNECT SWITCH Outdoor Single Pole Hook operated Regulator Bypass & Disconnect Switch, Type/ Model: MSU5.12 of Middle South Union Electric Co. Ltd.,can be used in 11 KV, 50 Hz distribution lines in a tropical climate with an average ambient temperature of 40°C and high annual rainfall. These switches are to be mounted in vertical position and manually operated. The switch ratingsfully comply with ANSI C37.30 and ANSIC37.34 TECHINICAL DETAILS: Type/ Model MSU-5.12 Nominal System Voltage 11 KV Maximum Voltage 15.5 KV Basic Insulation Level 110 KV Continuous Current Rating 1200 A Momentary Current Rating(peak) 65 KA Short Time Current (rms) 25 KA Connector Range 350 mcm Mounting Vertical Offset 15° Vertical Stop 90° Contact Silver Plate Interrupter are interruption device THREE-POLE GANG-OPERATED AIR-BREAKER SWITCH Outdoor Gang operated Three-Pole Air Break Switches with Load Interrupters, Type/ Model : MSU-13.6 & MSU-14.6 of Middle South Union Electric Co. Ltd., can be used in 11 KV 38 KV, 50 Hz Power distribution lines in a tropical climate with an average ambient temperature of 40°C and high annual rainfall. These switches are to be mounted in horizontal position and manually gang operated. The switch ratings fully comply with ANSI C37.30 and ANSI C37.34. TECHINICAL DETAILS: Type/ Model Nominal System Voltage Maximum Voltage Basic Insulation Level Continuous Current Rating Momentary Current Rating Short Time Current Connector Range Contact Operating System Knife Operation Connol Rod Length Terminal Pad Break/interrupter MSU-13.6 MSU-19.6 34.5 KV 33 KV 38 KV 38 KV 200 KV 200 KV 600 A 600 A 65 KA 65 KA 25 KA 25 KA 4/0 Al or Cu #6to500 mcm Silver plated Three phase gang operated Horizontal/Vertical 30’ with Handle NEMA 2 hole 4/0 Load Break/interrupter SUB-STATION SWITCH SINGLE POLE DROP OUT FUSL HOLDER Outdoor Single Pole hook operated Drop Out Fuse Holder, Type/ Model: MSU-6.002 of Middle South Union Electric Co. Ltd., can be used in 33 KV, 50 Hz distribution lines in a tropical climate with an average ambient temperature of 40°C and high annual rainfall. The Drop out Fuse Holder is to be vertically mounted and manually operated by hook stick. This Drop out Fuse Holder ratings fully comply with ANSI C37.30 and ANSI. TECHINICAL DETAILS: Rated Maximum Voltage 38 KV Nominal System Voltage 34.5 KV Rated Frequency 50 Hz Basic Insulation Level (BIL) 200 KV Rated Continuous Current 200 Amps Connector Range 6-500 mcm Mounting Position Vertical Offset 15 ° Blade Strip at open position. 160° RIV Test voltage(KV) RIV Limit (at 1 MHz) 23.0 KV 500 micro volt Construction : Complete with drop out fuse holder,175E standard speed power fuse similar to S & C type SMD-20 Cat-No.192504-L station styles. MSU Series Power Fuses are especially suited for protecting transformers, capacitor banks, and cables in outdoor distribution substations through 34.5 kV. They incorporate precisionengineered non damageable silver or nickel-chrome fusible elements with time-current characteristics that are precise and permanently accurate — assuring not only dependable performance, but also continued reliability of system coordination plans. With MSU Series Power Fuses, source-side devices may be set for faster operation than practical with other power fuses or circuit breakers, thereby providing better system protection without compromising coordination. These fuse units are offered in a variety of ampere ratings, in four different speeds Standard, Slow and Very Slow. They provide interrupting ratings of up to 25,000 amperes symmetrical at 50 Hz. This broad selection of ampere ratings and speeds permits close fusing to achieve maximum protection and optimum coordination. SZ Series Power Fuses are manufactured in accordance with a quality system certified to ISO9001:2008. SUB-STATION SWITCH Amperes Ratings Fuse Type KV Rating Nominal Fast Standard Slow Very Slow Maximum Interrupting MSU-38-15K MSU-38-15E MSU-38-15SE MSU-38-15SSE 15 6700 MSU-38-20K MSU-38-20E MSU-38-20SE MSU-38-20SSE 20 6700 MSU-38-25K MSU-38-25E MSU-38-25SE MSU-38-25SSE 25 6700 MSU-38-30K MSU-38-30E MSU-38-30SE MSU-38-30SSE 30 6700 MSU-38-40K MSU-38-40E MSU-38-40SE MSU-38-40SSE 40 6700 MSU-38-50K MSU-38-50E MSU-38-50SE MSU-38-50SSE 50 10000 MSU-38-65K MSU-38-65E MSU-38-65SE MSU-38-65SSE 65 10000 MSU-38-80K MSU-38-80E MSU-38-80SE MSU-38-80SSE 80 10000 MSU-38-100K MSU-38-10SE MSU-38-100SE MSU-38-100SSE 100 10000 MSU-38-125K MSU-38-125E MSU-38-125SE MSU-38-125SSE 125 10000 MSU-38-150K MSU-38-150E MSU-38-150SE MSU-38-150SSE 150 10000 MSU-38-175K MSU-38-175E MSU-38-175SE MSU-38-175SSE 175 10000 MSU-38-200K MSU-38-200E MSU-38-200SE MSU-38-200SSE 200 17500 MSU-38-300K MSU-38-300E MSU-38-300SE MSU-38-300SSE 300 25000 34.5 KV Maximum 38 KV BIL 200 KV SUB-STATION SWITCH Blown Fuse Indicator (In-blown fuse Position) Contact Rod Upper end fittings Clamp Screw Locking Pin (Inside Bore) Locking Slot (Inside Bore) Lower end fittings Upper Seal Actuating Pin extends through upper seal when fuse unit is blown and extends the blown-fuse indicator Locking Slot Fuse Unit Fuse Unit with end fittings and muffler attached Lower Ferrule Blue cap (remove and discard before installing muffler) Locking Pin Shoulder Muffler 0.944 DIA Fuse Unit Fittings kV Max. A B C 17 19.08 27.19 28.82 27 22.56 30.69 32.32 38 28.76 36.87 38.50 1.244 DIA B REF. A C LIGHTENING ARRESTER MSU surge arresters protects substation and polemounted equipment from voltage impulses or surges resulting from lightning strokes, system faults, circuit switching, load rejection or other events. MSU design Station Intermediate and Distribution classes arrester to be used on 33 KV and 11 KV systems respectively, and provided with Gapless Valve Elements. REFERANCE STANDARD MUS Lighting Arrester designed and manufactured in accordance with – ANSI/IEEE C62.22, ANSI C62.2, ANSI/IEEE C62.11: IEEE, ANSI/IEEE C62.1, NEMA Pub. No. PH25, ANSI/ASTM A153, ANSI , B18.21.1. TYPE / MODEL: 9KV Distribution Class L/A 9KV Station Class L/A 33/36KV Station Class L/A : : : GBZN - 11KV GBZNS - 11KV GBZN - 33KV TECHNICAL FEATURES: SERVICE CONDITIONS: a. Ambient temperature above 40°C b. Maximum relative humidity 90 % c. Altitude up to 1,000 meters above sea level d. Nominal system frequency 50 Hz The surge arrester have following protective characteristics a. Rated Voltage(RMS) b. Max Continuous Operating Voltage (MOV) c. Standard Nominal discharge current (8/20 micro second) d. Lightning impulse (8/20 micro second) maximum residual voltage e. Impulse withstand level on the arrester housing. i) Lightning impulse voltage ii) Power frequency voltage (dry) iii) Power frequency voltage (wet) 9/9 KV 7.65 KV 33/36 KV 29 KV 5/10 KA 5/10 KA 35 KV 110 KV 95 KV 35 KV 30 KV 200 KV 95 KV 80 KV CONSTRUCTIONS: a. Gap less Arresters with elements of zinc oxide to perform both the surge discharge and power frequency reseal functions. b. 9 KV Distribution type arrester provided with an ISOLATOR to ensure positive isolation and visual i dentification if arrester becomes damaged internally. LIGHTENING ARRESTER INSULATORS Arresters shall be protected in a hermetically sealed wet process porcelain or polymer jacket, with a high Creepage distance and a high dielectric strength. CONNECTORS a. Both line lead and isolator terminals of distribution class arresters shall accommodate # 6 solid through 1/0 AWG stranded copper or aluminum conductors. b. The high voltage terminal of Sub-Station class arrester accommodate 1/0 through 4/0 AWG MHD bare Copper or Aluminum conductors. The ground terminal accommodate 1/0 AWG MHD bare Copper or Aluminum conductor. The high side voltage terminal to be provided on the top of the arrester and both the line and ground terminal shall be a two-hole or four-hole standard pad NEMA connector. MOUNTINGS Supplied with a cross arm mounting bracket. Intermediate & Sub-station class arresters shall be equipped with (3) 14-22 mm dia slots (120 degree apart), 222-254 mm dia Bolt Circle Equipment/ structure mounting arrangement. All exposed steel or iron parts of the arrester including all mounting bolts, Lock washers shall be hotdip galvanized. PROTECTIVE CHARACTERISTICS MSU arresters have the following protective characteristic based on per unit crest arrester rating as summarized from ANSI C 62.22 Station and Intermediate Class Arrester Characteristics Steady state Operation System Voltage & Arrester Protective Leve ls Range if Industry Maximum Per Unit Ratings Crest of MCOV Maximum System Voltage L-L (KV/rms) Minimum System Voltage L-G (KV/rms) Minimum MCOV Rating Duty Cycle Rating (KV/rms) 0.5 micro sec Discharge Voltage (DV) 8/20 micro sec wave DV Switching Surge-DV Maximum High-Amp withstand Crest Amps 13.1 7.56 7.65 9-12 2.33-2.48 1.97-2.23 1.70-1.85 6500 13.9 8.03 7.65 9-15 2.33-2.48 1.97-2.23 1.70-1.85 6500 36.2 20.90 22 27-36 2.43-2.48 1.97-2.23 1.70-1.85 6500 2.28-2.55 1.80-2.10 6.500 Intermediate Class 4.37-169 2.52-97.57 2.8-98 3-144 2.38-2.85 LIGHTENING ARRESTER Distribution Arrester Protective Characteristics Distribution Class Steady state Operation System Voltage & Arrester Ratings Crest of MCOV Protective Levels Range if Industry Maximum Per Unit Crest of MCOV FOW Protective level Discharge Voltage with 8/20 micro Sec Wave Maximum System Voltage L-L (KV/rms) Minimum System Voltage L-G (KV/rms) Minimum MCOV Rating Duty Cycle Rating (KV/rms) 5 KA ND 10 KA HD 5KA ND 10 KA HD 13.1 7.56 7.65 9 33.5-36 26.5-35.3 30.0-33.5 21.7-31.5 13.9 8.03 8.4 10 36.0-37.2 29.4-39.2 31.5-33.8 24.5-35 36.2 20.90 24.4 30 107.0-108 85.0-109.5 94.5-99 71.8-99 36.2 20.90 29 36 125 99.0-136 116.0 83.7-125 MCOV= Maximum Continuous Operating Voltage ND= Normal Duty HD= Heavy Duty PACKAGING Each Surge Arrester shall be clearly marked with the manufacturers name, catalog number and below marking information: a. Arrester classification b. Manufacturers identification or symbol c. Arrester model and identification number d. Arrester voltage rating e. Date of manufacture 33/36 KV Station Type Lightening Arrester 9/9 KV station Type Lightening Arrester Distribution fuse cutouts designed and manufactured in accordance with ANSI C37.42. Distribution Fuse cutouts Model: GBZN - 15KV is open, expulsion, drop-out type & mounted by means of steel brackets on wood poles and cross arms. The cutouts are intended for use with buttontype fuse links meeting the interchangeability requirements of ANSI C37.42. DISTRIBUTION FUSE CUTOUT REFERANCE STANDARD Distribution fuse cutouts Model: GBZN - 15KV designed and manufactured in accordance with – ANSI/IEEE C37.40, ANSI C37.41, ANSI C37.42, ANSI B18.21.1, ANSI A153. TECHNICAL FEATURES SERVICE CONDITIONS a. Temperature - up to 40°C b. Altitude - up to 1,000 meters Rated Voltage a. Nominal System Voltage - 11,000 Grd Y/6,350 volts b. Rated Maximum Voltage - 15,000 volts c. Low Frequency Withstand KV, RMS dry, 60 sec. - 35 wet, 10 sec. - 30 d. Rated Impulse Withstand Voltage - 95 KV. e. Rated Frequency - 50 Hertz. f. Rated Continuous Current - 100 amperes. g. Rated Short Time Current i. Momentary (1 cycle) - 10,000 amperes ii. 15 cycles - 7,100 amperes iii. 3 seconds - 1,600 amperes. h. Rated Symmetrical Interrupting Current - 7,100 amperes. DISTRIBUTION FUSE CUTOUT ACCESSORIES I). Fuse Support Assembly a. Fuse Support Insulator - wet process porcelain. b. Contacts - Silver Plated c. Connectors - tin-plated bronze parallel groove type, for #6 to 4/0 AWG Copper or Aluminum Conductors. d. Load-buster tool attachment hooks. e. Mounting Supports - provided to mount the cut-out so that the centerline of the fuse support insulator is at an angle of 15° to 20° from the vertical. II). Fuse Holder Assembly a. Fuse Tube - bone fiber lining with exterior painted gray, non-expendable cap. b. Contacts - Silver Plated c. Fuse Link Position - the fuse tube is designed sothat the fuse link is centered in the tube, with provision for mechanical ejection of the fuse link leader on low current faults. d. Opening and Lifting Eyes. e. Thumb Screw - for securing the fuse link to fuse holder assembly. III). Mounting Bracket Each distribution fuse cutout shall be provided with hot dip galvanized mounting bolt, lock washer, A Type mounting bracket adjustable to accommodate standard 2.4384 meter (8 foot) and 3.048 (10 foot) wood cross arms. PACKAGING Each distribution fuse cutout & its mounting bracket is packaged in a paper box clearly labeled with below marking: Manufacturer's Identification Product Type Date of Manufacture* Rated Continuous Current Rated Maximum Voltage Rated Interrupting Current Basic Impulse Level For export standard seaworthy wooden packing is available. Middle South Union Electric Co. Ltd. Wenzhou Bridge Industry Zone, Beibaixiang Town Yueqing City, China.