Motor Application Fuse ratings recommended in the following tables have been chosen with the following considerations in mind. 4 evenly spaced starts per hour. Maximum 32 degree C ambient. The motor data and fuse ratings presented are based on 1800 rpm high efficiency motors. For operating conditions or motor types outside the scope of these tables, please request a copy of our fuse selection software (pg. 59), or contact our offices with application details. How to use motor tables ! ! Select voltage range. Select Class 10 or Class 20 overload column. Class 10 Use this column for overload relays that trip within 10s. at locked rotor. eg; IEC control. Class 20 Use this column for overload relays that trip within 20s. at locked rotor. eg; Nema control Read off amp rating of fuse opposite appropriate motor HP size and under appropriate column. ! Motor Selection table for Class C fuses 575/600Vac Motor data HP FLA 3/4 1 460/480Vac Fuse rating Overload type Motor data HP FLA 6 3/4 6 6 2.1 10 2.7 10 3.9 5 230/240Vac Fuse rating Overload type Motor data HP FLA 6 3/4 6 6 2.6 10 3.4 15 3 4.8 15 5 20 20 11 25 15 17 20 IEC NEMA IEC NEMA 1.1 6 1.4 6 1.4 1 1.8 1.5 2 10 1.5 10 2 3 15 15 6.1 15 7.5 9 10 Fuse rating Overload type IEC NEMA 2.8 10 10 1 3.6 15 15 10 1.5 5.2 15 15 15 2 6.8 20 20 15 15 3 9.6 25 25 7.6 20 20 5 15.2 30 30 7.5 11 25 25 7.5 22 40 50 30 10 14 30 30 10 28 50 60 30 40 15 21 40 40 15 42 60 80 22 40 50 20 27 50 60 20 54 80 100 25 27 50 60 25 34 60 60 25 68 100 125 30 32 60 60 30 40 60 80 30 80 125 150 40 41 80 80 40 52 80 100 40 104 150 200 50 52 80 100 50 65 100 125 50 130 200 200 60 62 100 125 60 77 125 125 60 154 200 250 75 77 125 125 75 96 150 150 75 192 250 300 100 99 150 150 100 124 200 200 100 248 350 350 125 125 200 200 125 156 200 250 125 312 400 400 150 144 200 250 150 180 250 300 150 360 450 500 200 192 300 300 200 240 350 350 200 480 600 600 250 237 350 350 250 296 400 400 250 - - - 300 284 350 400 300 354 450 500 300 - - - 350 328 400 500 350 410 500 600 350 - - - 400 374 500 500 400 - 600 600 400 - - - Switch Size 30 60 100 200 400 600 pg 5 Class C Specifications IEC Voltage Rating: Interrupting Rating: Amp Range: Approvals: 600Vac, 250Vdc 200kA @ 600Vac 40kA @ 250Vdc 2-600A C22.2 no. 248 IEC269-1&2 CE Ratings available: 2, 4, 6, 10, 15, 20, 25, 30, 40, 45, 50, 60, 80, 100, 125, 150, 200, 250, 300, 350, 400, 450, 500, 600A 2CO - offset blades, 2CC - long center blades, 2CM - non-standard dimensions. Part number example - 2CC-125 Although initially a British design, the Class C fuse was the original Canadian HRC fuse. Introduced at a time when the only choices were one-time or renewable fuses, the Class C fuse was quickly specified by the Canadian pulp, paper, and mining industry, and is still in widespread use in these industries today. ! ! ! ! Provides Type 2 protection for IEC and NEMA control. Fully plated parts for low contact resistance and cool running. Notched tags for easy fuse replacement. (2-100A) Ceramic bodies throughout the range. Companion Products Deadfront fuseholders (page 9) Class C selection tables for transformers and ballast fuse rating primary full load amps (A) from to 2 0 0.37 4 0.38 6 fuse rating primary full load amps (A) from to 80 49 64 1.1 100 65 80 1.2 1.7 125 81 100 10 1.8 3.5 150 101 120 15 3.6 7.3 200 121 160 20 7.4 10.7 250 161 200 25 10.8 13.3 300 201 240 30 13.4 17.3 350 241 280 40 17.4 26.7 400 281 320 50 26.8 33.3 450 321 360 60 33.4 48 500 361 400 600 401 480 pg 4 These tables assume that the secondary side of the transformer is protected at 125% of its full load current. This is usually the case. Fuses used on the primary side of transformers must be capable of: ! Withstanding the magnetising inrush to the windings of approximately 12x the normal full load current of the primary for 0.1 sec. without operation or element damage. ! Carrying short-term overloads not exceeding 150% of the normal full load primary current. The fuse ratings recommended meet these requirements. Class CA, CB Fusetek 'N' series fuses are a British dimension current limiting HRC fuse with very compact dimensions. They are used for a wide variety of control applications where excellent current limitation and compact dimensions are required. IEC 'N' Series fuses can be used on any 600Vac or less circuit. N1 types are best suited to applications where surge currents are not seen. For surge current applications such as transformers, capacitors and motors, the N2 series are better suited due to their medium blow characteristic. SSD fuses are used only for replacement purposes in imported equipment. 600Vac 250Vdc ! ! All metal parts are tin plated for low contact resistance and cool running. Ceramic bodies. Capacitor Application Apply N1 fuses at 250-300% of the capacitor full load current rating. Apply N2 fuses at 200-250% of capacitor full load rating. Choose nearest fuse rating next size up. Resistive Loads Use N1B or N1C fuses sized at 125% of the full load current. N2 fuses should not be used for resistive loads. Companion products Deadfront fuseholders - page 11. General Specifications - Class CA/CB 51mm 14mm 14mm CA CB 44mm 58mm N1B Voltage rating N2B 600Vac/250Vdc I.R (rms symm) 200kA @ 600Vac N1C N2C 600Vac/250Vdc 80kA @ 250Vdc 3.6mm SSD 250Vac 80kA@250Vac Amp ratings available 1, 3, 6, 10, 15, 20A 2, 4, 6, 10, 15, 20A 1, 3, 6, 10, 15, 20, 25A 2, 4, 6, 10, 15, 20A 2, 4, 6, 10, 15, 20, 25, 32A Operating Speed Fast Medium Fast Medium Medium Approvals CSA Class CSA C22.2 no.106 HRCI-CA HRCII-CA HRCI-CB IEC269-2 HRCII-CB - pg 7 Accessories/Accessoires adapter microswitch for/pour Adaptor for 660/700V fuses 2800102 Adapter for 1000V fuses 2800103 Microswitch only 2800104 Bases for DIN 43653 fuses fuse type Amps Terminal Centres Fig. 21 189 01 700V - 00, 00c 400A 125mm 1 21 313 01 700V - 1, 2, 3 short 630A 150mm 2 21 313 02 700V - 1, 2, 3 long 1250A 150mm 2 21 323 01 1300V - 1, 2, 3 630A 180mm 2 21 323 02 1300V - 1, 2, 3 1250A 180mm 2 Fig. 1 FIG.2 pg 56 Melting Time Current Characteristics General Specifications 1000 Total Part Amps I2t Number x 1000 100 Time in seconds 10 6 10 15 25 40 60 100 200 20 30 50 80 150 400 350 600 10 L CC 100 1000 RMS Amperes 10000 D L CC D CC 2CC 125-200A & 2CM 80-100A pg 6 25 25 10 .654 15 .9 2.8 30 5.3 40 11.2 45 12.0 50 14.9 60 26 80 34.7 100 96.6 125 155 150 243 200 622 250 819 2CC 300 1180 center tag 350 1862 400 3805 450 3229 500 4088 600 7268 2CM 80 34.7 center tag 100 96.6 2CM 125 155 offset tag 150 243 200 622 250 819 300 1180 350 1862 400 3805 2CM 2CC 250-400A 2CC 450-600A .207 25 H 'H' 6 offset tag 100000 2C0 2-100A & 2CM 125-200A .048 1.6 0.01 1 4 20 0.1 4 .006 2CO 1 2 2 short center tag Dimensions (mm) CC L D 73 83 21 73 88 26 94 110 36 111 135 41 133 206 58 133 208 74 111 135 36 94 106 41 111 135 58 Motors & Transformers: ! ! The tables below are based on the following parameters: Motors. 4 evenly spaced starts per hour. Max. 32 degree C ambient. Transformers. Secondary protection installed. Max. 12x FLC inrush at 0.1s. N1C & N1B Motor Circuits 5 sec. run-up 10 sec. run up from A to A from A to A 0 .27 0 .24 .28 .72 .25 .67 .73 1.3 .68 1.9 1.3 2.3 1.2 2.0 2.3 4.3 2.1 3.7 4.3 6.3 3.8 4.3 6.3 8.8 4.4 7.9 Fuse rating 1 3 6 10 15 20 25 Transformer circuits Primary FLA from A to A 0 .25 .26 .67 .68 1.5 1.6 2.5 2.6 6.0 6.1 8.7 8.8 12.0 N2C & N2B 2 4 6 10 15 20 0 .49 .81 1.7 2.7 6.2 .48 .8 1.6 2.6 6.1 9.0 0 .46 .81 1.5 2.6 5.7 .45 .8 1.4 2.5 5.6 8.0 100 10 10 T im e in seco nds 100 T im e in seco nds 1000 1 3 6 10 15 20 25 1 2 0.1 4 6 10 15 20 0.1 0.01 0.01 1 10 100 R M S A m peres pg 8 .54 .93 1.6 3.2 8.3 12.0 N2C/N2B Melting Characteristics N1C/N1B Melting Charcteristics 1000 1 0 .55 .94 1.7 3.3 8.4 1000 1 10 100 RM S Amperes 1000 British semiconductor fuses (BS88) These fuses are British dimension, ultra fast acting types for the protection of semiconductor devices such as diodes, rectifiers, SCR's, thyristors, ect.. 240 & 690Vac 100kA I.R aR Characteristic They are often used in electronic speed control devices such as soft-starts or inverters, or anywhere where sensitive electronic components need protection. SIBA UR fuses have excellent energy let-thru characteristics under short circuit conditions. Companion products LSCR001 and LSCR002 stud mount fuseholders. Refer to Littelfuse PowrGard catalogue. 240Vac Part Number 5007606 5005306 5005406 5007106 pg 50 Amps 5 6 10 12 16 20 25 32 35 40 50 63 75 80 100 125 160 180 160 200 250 315 355 400 450 400 450 500 630 710 800 900 Watts Loss (W) 1.5 1.7 3.3 2.0 2.4 3.3 3.6 4.5 5.0 5.3 6.7 7.7 9.4 9.7 12.7 16 22 24 23 27 34 36 38 40 46 55 56 59 62 72 74 90 I2t (A2s) melting total 1.7 2.9 4.2 8.0 18 25 39 40 63 100 130 250 330 420 620 1000 1500 2300 1300 2500 4600 7800 11800 18500 26600 10000 19000 27000 50000 70000 106000 150000 9.5 16 24 41 92 130 260 270 430 700 900 1700 2300 2900 4300 6800 10200 15700 8000 15300 28000 48000 72000 113000 163000 61000 116000 165000 305000 427000 647000 915000 I.R (rms symm) 100kA 100kA 100kA 100kA 660Vac Part Number 5007706 5007306 5007406 5007506 2055920 Amps 6 10 12 16 20 25 32 35 40 50 63 80 100 100 125 160 200 250 315 355 315 355 400 450 500 630 710 32 35 40 50 63 80 100 125 160 180 200 250 315 Watts Loss (W) 3.2 3.7 3.9 5.5 7.5 7 9 10 11 12 15 18 23 22 29 30 31 40 44 56 48 55 58 63 68 87 104 8 9 10 12 14 18 22 26 32 35 39 47 58 I2t (A2s) melting total 3 8 11 18 32 25 50 60 80 190 290 420 740 1000 1700 4000 9000 18000 27000 36000 18500 22300 26100 52300 70100 106000 145000 52 66 90 1540 250 470 730 1300 2800 3700 4500 8000 14000 20 53 77 120 215 110 210 260 330 780 1200 1700 3100 6500 11000 26000 58000 116000 173000 231000 119000 143000 167000 335000 449000 679000 928000 290 360 500 770 1400 2600 4000 7200 15400 20400 25000 44000 77000 I.R (rms symm) 100kA 100kA 100kA 100kA 660V 300kA 700V 200kA 250Vac (Kyosan equals) P a rt N umber N AK 75 W a tts Loss (W ) 9 100 10 4300 125 14 6800 140 18 7200 160 20 10200 Am ps I 2 t (A 2 s ) To ta l I.R (rm s sym m ) 2300 100kA pg 51 Introducing the Global Pro System Offering World Class Performance and Global Acceptance The International Challenge The benefits of the Global Pro System include: Engineers and equipment designers are faced with a dilemma when choosing the right circuit protection for their globally distributed equipment. They need to determine what markets the product will be used in, what local electrical standards apply in each of those markets, and what fuses should be used so users can find replacements easily. The Global Pro System resolves these design issues by incorporating North American standards to fit internationally accepted IEC fuse dimensions. This allows touch-safe fuseholders that can be used in virtually any market and permits equipment to be easily adapted by simply replacing the fuse with one that meets local standards. It’s that simple. Global Acceptance – Total Pro-Tection Universal voltages The Littlefuse Global Pro circuit protection system combines fuses and fuseholders in a simple package designed to comply with UL and IEC requirements. The result is the single best solution for your worldwide circuit protection needs. Touch-safe components Flexible Components Integrated lockout/ tagout devices for OSHA compliance The components of the Global Pro system are vital to its performance. The key component within the integrated system is the fuse. The Littelfuse Global Fuse is designed to offer UL Class J performance, but with the compact size and international compatibility associated with fuses manufactured to IEC dimensions. Global Acceptance UL and IEC approval Class J performance in an IEC package Blown fuse indication Design versatility for OEM’s Built-in microswitch to integrate into PLC networks, turn on stack lighting, and remote blown fuse indication More Protection In Less Space Global Pro fuses are significantly smaller in size than 30, 60, and 100 amp Class J fuses. All Global Pro fuses offer: Good Extremely Compact Size Pop-up Pin Blown Fuse Indication Class J Performance Compatibility with IEC style fuse holders Blown Littelfuse, Inc. - POWR-GARD Products 800 E. Northwest Highway - Des Plaines, IL 60016 Technical Hot-Line: 1-800-TEC-FUSE (832-3873) Visit us on the web! www.littelfuse.com LgD Series Global Pro-tection Fuses 600 Volts AC – Time Delay - 1-100 Amperes SPECIFICATIONS Voltage Rating: AC: 600 Volts (UL) 690 Volts (IEC) DC: 500 Volts (1-30A) 300 Volts (35-60A) Interrupting Rating: AC: 200,000 amps DC: 100,000A (1-30A) 20,000A (35-60A) Ampere Range: 1-100* amperes Approvals: The Global Pro system is designed to save valuable space in a crowded panel while providing designers with the flexibility of a universally accepted design for easy replacement. Global Pro fuses are far more compact and have greater power handling capability than conventional products. Global Pro fuses are up to 75% smaller than Class R fuses and up to 50% smaller than Class J fuses while providing the time delay that is necessary for motor circuit protection. Global Pro fuses also provide quick and positive visual identification of blown fuses by using a pop-up indicator design that protrudes from the top of the fuse. The popup indicator is designed to immediately alert maintenance personnel that it needs to be replaced. Touch-safe fuse holders are available with a built-in microswitch that is activated by the pop-up indicator. The microswitch can be used to integrate into PLC networks, turn on stack lighting , and provide equipment operators with a remote method of determining when the fuse needs to be replaced. UL Listed Special Purpose (1-30 amps) UL Recognized (35-60 amps) CSA Certified (1-60 amps) *Contact factory for ratings above 60A AMPERE RATINGS 1 3 6 8 10 12 15 20 25 30 35 40 45 50 60 70* 80* 90* 100* *Contact factory for ratings above 60A Example part number (series & amperage): LgD 60 RECOMMENDED FUSEHOLDERS LPSG Series Global PRO Fuseholders FEATURES AND BENEFITS Extremely compact size Pop-up Pin Indication Class J performance Global acceptance UL and IEC approval Touch-safe components APPLICATIONS Design versatility for the OEM Motor control centers DIMENSIONS Motor branch circuits Primary & secondary protection Part Number Amperage English Metric LgD 0-30A 0-30A 9/16” x 2” 14mm x 51mm of transformers LgD 35-60A 35-60A 13/13” x 2-1/4” 22mm x 58mm Equipment designed for export LgD 70-100A 70-100A 1-1/16” x 2-3/8” 27mm x 60mm Littelfuse, Inc. - POWR-GARD Products 800 E. Northwest Highway - Des Plaines, IL 60016 Technical Hot-Line: 1-800-TEC-FUSE (832-3873) Visit us on the web! www.littelfuse.com LPSG Series Global Pro Fuseholders SPECIFICATIONS Voltage Rating: 750 AC/DC Withstand Rating: 200,000 amps Ampere Range: 30, 60, and 100* amperes *Contact Factory for ratings above 60 amps. Terminal Type: Pressure Plate Recommended Torque: 30A: 35 In. lbs. 60A: 45 In. lbs. Wire Range: #2-14 CU Material: Thermo-plastic Approvals: UL Recognized Littelfuse’s Global Protection System simplifies circuit protection by incorporating North American electrical requirements into fuse styles found in the rest of the world. The Global Pro fuseholder features a microswitch that is actuated by a blown fuse. This allows the Global Pro system to integrate into PLC networks and provide remote blown fuse indication. An indicator light also allows maintenance personnel to locate blown fuses quickly. CSA Certified IEC 269/947-3 Indicator: Neon Lamp • Minimum 90 VAC, 115VDC to operate indicator • Less than 0.7mA leakage current at 600V FEATURES and BENEFITS • IP20 Touch-Safe Design to IEC 529 • DIN Rail Mounting (35mm rail) • Integrated Lock-out/tagout device for OSHA compliance • Compact Size – up to 60% smaller than Class R blocks and up to 25% smaller than Class J blocks. • Blown Fuse Indicator to quickly identify blown fuses • Integrated microswitch for remote fuse status and PLC integration RECOMMENDED FUSES LgD series Global Pro Fuses ORDERING INFORMATION Catalog No. LPSG30-1MI LPSG30-2MI LPSG30-3MI LPSG60-1MI LPSG60-2MI LPSG60-3MI LPSG100-1MI LPSG100-2MI LPSG100-3MI Amp Rating 30A 30A 30A 60A 60A 60A 100A 100A 100A Poles 1 2 3 1 2 3 1 2 3 Pack Qty. 6 3 2 6 3 2 6 3 2 Note: LPSG series fuseholders are not approved to be a load-break disconnect. Littelfuse, Inc. - POWR-GARD Products 800 E. Northwest Highway - Des Plaines, IL 60016 Technical Hot-Line: 1-800-TEC-FUSE (832-3873) Visit us on the web! www.littelfuse.com 660/700 Vac Square body rectifier fuses 599 Norris Court, Kingston, Ontario, Canada, K7P 2R9 tel. (800) 479-3875 fax (800) 1 Halbleiterschutzsicherungen 690/700 V IEC 60269-4 Fuses for Semiconductor Protection UL 248-13 Europäische Bauform Stichmaß 80 European Standard Fixing center 80 Art.-Nr.: 20 610 32 20 620 32 20 630 32 Dimension [mm] Größe 1 Größe 2 Größe 3 size 1 size 2 size 3 a1 a2 b e e1 e2 i 109 47,5 26 76 51 6 11 109 47,5 26 76 60 6 11 109 49 35 76 73 6 11 20 611 32 20 621 32 20 631 32 Dimension [mm] Größe 1 Größe 2 Größe 3 size 1 size 2 size 3 a1 a2 b e e1 e2 i 109 47,5 26 76 51 6 11 109 47,5 26 76 60 6 11 109 49 35 76 73 6 11 20 612 32 20 622 32 20 632 32 Dimension [mm] Größe 1 Größe 2 Größe 3 size 1 size 2 size 3 a1 a2 b e e1 e2 i 109 47,5 26 76 51 6 11 109 47,5 26 76 60 6 11 109 49 35 76 73 6 11 Part.-No.: Kontakt contact Stichmaß 80 fixing center 80 Klappmelder flap indicator Art.-Nr.: Part.-No.: Kontakt contact Stichmaß 80 fixing center 80 Einz. Grifflasche single bracket Art.-Nr.: Part.-No.: Kontakt contact Stichmaß 80 fixing center 80 Mittenmelder button indicator Europäische Bauform Gewinde: Metrisch European Standard Thread: metric Art.-Nr.: 20 660 32 20 670 32 20 680 32 Dimension [mm] Größe 1 Größe 2 Größe 3 size 1 size 2 size 3 C D L a2 e1 24 M8 50,5 47,5 51 24 M 10 50,5 47,5 60 28 M 12 50,5 49 73 20 661 32 20 671 32 20 681 32 Dimension [mm] Größe 1 Größe 2 Größe 3 size 1 size 2 size 3 C D L a2 e1 24 M8 50,5 47,5 51 24 M 10 50,5 47,5 60 28 M 12 50,5 49 73 Part.-No.: Kontakt contact Gewinde threaded hole Klappmelder flap indicator Art.-Nr.: Part.-No.: Kontakt contact Gewinde threaded hole Mittenmelder button indicator URS 2 Halbleiterschutzsicherungen 690/700 V IEC 60269-4 Fuses for Semiconductor Protection UL 248-13 Europäische Bauform Stichmaß 110 European Standard Fixing center 110 Art.-Nr.: 20 613 32 20 623 32 20 633 32 Dimension [mm] Größe 1 Größe 2 Größe 3 size 1 size 2 size 3 a1 a2 b e e1 e2 i 134 47,5 26 106 51 6 11 134 47,5 26 106 60 6 11 134 49 35 106 73 6 11 20 614 32 20 624 32 20 634 32 Dimension [mm] Größe 1 Größe 2 Größe 3 size 1 size 2 size 3 a1 a2 b e e1 e2 i 134 47,5 26 106 51 6 11 134 47,5 26 106 60 6 11 134 49 35 106 73 6 11 20 615 32 20 625 32 20 635 32 Dimension [mm] Größe 1 Größe 2 Größe 3 size 1 size 2 size 3 a1 a2 b e e1 e2 i 134 47,5 26 106 51 6 11 134 47,5 26 106 60 6 11 134 49 35 106 73 6 11 Part.-No.: Kontakt contact Stichmaß 110 fixing center 110 Klappmelder flap indicator Art.-Nr.: Part.-No.: Kontakt contact Stichmaß 80 fixing center 80 Einz. Grifflasche single bracket Art.-Nr.: Part.-No.: Kontakt contact Stichmaß 80 fixing center 80 Mittenmelder button indicator Amerikanische Bauform Gewinde: UNC US Standard Thread: UNC Art.-Nr.: 20 663 32 20 673 32 20 683 32 Dimension [mm] Größe 1 Größe 2 Größe 3 size 1 size 2 size 3 C D L a2 e1 24 5/16” 50,5 47,5 51 24 3/8” 50,5 47,5 60 28 1/2” 50,5 49 73 20 664 32 20 674 32 20 684 32 Dimension [mm] Größe 1 Größe 2 Größe 3 size 1 size 2 size 3 C D L a2 e1 24 5/16” 50,5 47,5 51 24 3/8” 50,5 47,5 60 28 1/2” 50,5 49 73 Part.-No.: Kontakt contact Gewinde threaded hole Klappmelder flap indicator Art.-Nr.: Part.-No.: Kontakt contact Gewinde threaded hole Mittenmelder button indicator URS 3 Halbleiterschutzsicherungen 690/700 V IEC 60269-4 Fuses for Semiconductor Protection UL 248-13 Amerikanische Bauform Kurze Version US Standard Short Version Art.-Nr.: 20 616 32 20 626 32 20 636 32 Dimension [mm] Größe 1 Größe 2 Größe 3 size 1 size 2 size 3 A a2 B1 B2 e1 e2 134 47,5 109 73 51 6 134 47,5 109 73 60 6 134 49 109 75 73 6 20 617 32 20 627 32 20 637 32 Dimension [mm] Größe 1 Größe 2 Größe 3 size 1 size 2 size 3 A a2 B1 B2 e1 e2 134 47,5 109 73 51 6 134 47,5 109 73 60 6 134 49 109 75 73 6 Part.-No.: Kontakt contact US kurze Version US short version Mittenmelder button indicator Art.-Nr.: Part.-No.: Kontakt contact US kurze Version US short version Amerikanische Bauform Lange Version US Standard Long Version Art.-Nr.: 20 618 32 20 628 32 20 638 32 Dimension [mm] Größe 1 Größe 2 Größe 3 size 1 size 2 size 3 A a2 B1 B2 e1 e2 154 47,5 128 92 51 6 154 47,5 128 92 60 6 154 49 128 94 73 6 20 619 32 20 629 32 20 639 32 Dimension [mm] Größe 1 Größe 2 Größe 3 size 1 size 2 size 3 A a2 B1 B2 e1 e2 154 47,5 128 92 51 6 154 47,5 128 92 60 6 154 49 128 94 73 6 Part.-No.: Kontakt contact US lange Version US long version Mittenmelder button indicator Art.-Nr.: Part.-No.: Kontakt contact US lange Version US long version URS 4 Halbleiterschutzsicherungen 690/700 V IEC 60269-4 Fuses for Semiconductor Protection UL 248-13 Parallelsicherung SQB 2 parallel fuse SQB 2 Bemessungsstrom / rated current : 1000 - 1600 A Bemessungsspannung / rated voltage : 690 V Art.-Nr. / part-no. : 20 678 32 GL-Mikroschalter M-Mikroschalter GL-micro switch M-micro switch Bemessungsstrom / rated current : 5 A Bemessungsspannung / rated voltage : AC 250 V Kontakt / contact: 1 Wechsler / 1 alternating contact Bemessungsstrom / rated current : 6 A Bemessungsspannung / rated voltage : AC 250 V Kontakt / contact : 1 Wechsler / 1 alternating contact Art.-Nr. / part-no. : 28 002 05 Art.-Nr. / part-no.: 28 001 04 25,5 22,5 31 19,5 19,5 25,5 URS 5 Halbleiterschutzsicherungen 690/700 V IEC 60269-4 Fuses for Semiconductor Protection UL 248-13 SQB 1 Betriebsklasse operating class aR Bemessungs- Bemessungs- Bemessungsspannung strom spannung rated current IN A 63 -200 A 200 250 315 350 400 450 500 550 630 700 800 900 IEC 60269-4 UL 248-13 rated voltage rated voltage UN V 690 690 690 690 690 690 690 690 690 690 690* 690* 600* UN V Leistungsabgabe Schmelzl2t-Wert Ausschaltl2t-Wert power loss pre-arcing l2t-value total l2t-value A2s x 103 bei / at 660 V PV W auf Anfrage/ on request 700 700 700 700 700 700 700 700 700 700 700 700 600 44 51 59 61 65 70 72 75 80 85 99 105 * Prüfspannung / testvoltage: 1,05 x UN Koeffizienten für erschwerte Verwendung coefficients for heavy duty application a A2 B1 130 0,55 1,25 B2 0,6 Cf3 0,8 N 1,5 Strombegrenzungsdiagramm cut-off characteristic URS 6 A2s x 103 2,4 3,7 6,6 9,9 17 22 31 41 61 86 120 170 13 21 39 55 96 130 180 250 370 490 750 990 Halbleiterschutzsicherungen 690/700 V IEC 60269-4 Fuses for Semiconductor Protection UL 248-13 Zeit/Strom-Kennlinien Time/current characteristics Schaltspannungsdiagramm arc-voltage-diagramm Umrechnungskoeffizient für Ausschalt-l2t-Wert exchange factor for total-l2t-value Umrechnungskoeffizient für Leistungsabgabe exchange factor for power loss URS 7 Halbleiterschutzsicherungen 690/700 V IEC 60269-4 Fuses for Semiconductor Protection UL 248-13 SQB 2 Betriebsklasse operating class aR Bemessungs- Bemessungs- Bemessungsspannung strom spannung rated current IN A 400 450 500 550 630 700 800 900 1000 1100 1250 IEC 60269-4 UL 248-13 rated voltage rated voltage UN V 690 690 690 690 690 690 690 690* 690* 600* 600* UN V Leistungsabgabe Schmelzl2t-Wert Ausschaltl2t-Wert power loss total l2t-value PV W pre-arcing l2t-value A2s x 103 bei / at 660 V 65 75 80 85 94 99 108 111 115 130 140 13 18 26 36 55 74 100 170 230 290 370 700 700 700 700 700 700 700 700 700 600 600 * Prüfspannung / testvoltage: 1,05 x UN Koeffizienten für erschwerte Verwendung coefficients for heavy duty application a A2 B1 130 0,55 1,25 B2 0,6 Cf3 0,8 N 1,5 Strombegrenzungsdiagramm cut-off characteristic URS 8 A2s x 103 75 110 150 195 300 410 580 950 1260 1600 2140 Halbleiterschutzsicherungen 690/700 V IEC 60269-4 Fuses for Semiconductor Protection UL 248-13 Zeit/Strom-Kennlinien Time/current characteristics Schaltspannungsdiagramm arc-voltage-diagramm Umrechnungskoeffizient für Ausschalt-l2t-Wert exchange factor for total-l2t-value Umrechnungskoeffizient für Leistungsabgabe exchange factor for power loss URS 9 Halbleiterschutzsicherungen 690/700 V IEC 60269-4 Fuses for Semiconductor Protection UL 248-13 SQB 3 Betriebsklasse operating class aR Bemessungs- Bemessungs- Bemessungsspannung strom spannung rated current IN A 500 550 630 700 800 900 1000 1100 1250 1400 1500 1600 IEC 60269-4 UL 248-13 rated voltage rated voltage UN V 690 690 690 690 690 690 690 690* 690* 690* 600* 600* UN V Leistungsabgabe Schmelzl2t-Wert Ausschaltl2t-Wert power loss total l2t-value PV W pre-arcing l2t-value A2s x 103 bei / at 660 V 90 100 108 113 118 120 131 136 147 161 170 190 18 22 32 50 85 115 140 210 290 380 490 590 700 700 700 700 700 700 700 700 700 700 600 600 * Prüfspannung / testvoltage: 1,05 x UN Koeffizienten für erschwerte Verwendung coefficients for heavy duty application a A2 B1 130 0,55 1,25 B2 0,6 Cf3 0,8 N 1,5 Strombegrenzungsdiagramm cut-off characteristic URS 10 A2s x 103 100 130 190 300 480 660 860 1200 1750 2200 3000 3700 Halbleiterschutzsicherungen 690/700 V IEC 60269-4 Fuses for Semiconductor Protection UL 248-13 Zeit/Strom-Kennlinien Time/current characteristics Schaltspannungsdiagramm arc-voltage-diagramm Umrechnungskoeffizient für Ausschalt-l2t-Wert exchange factor for total-l2t-value Umrechnungskoeffizient für Leistungsabgabe exchange factor for power loss URS 11 1300Vac Square body rectifier fuses 599 Norris Court, Kingston, Ontario, Canada, K7P 2R9 tel. (800) 479-3875 fax (800) 866-7690 1 Halbleiterschutzsicherungen 1250/1300 V IEC 60269-4 Fuses for Semiconductor Protection UL 248-13 Europäische Bauform Stichmaß 110 European Standard Fixing center 110 Art.-Nr.: 20 713 32 20 723 32 20 733 32 Dimension [mm] Größe 1 Größe 2 Größe 3 size 1 size 2 size 3 a1 a2 b e e1 e2 i 138 70,5 26 106 51 6 11 138 70,5 26 106 60 6 11 138 72 35 106 73 6 11 20 714 32 20 724 32 20 734 32 Dimension [mm] Größe 1 Größe 2 Größe 3 size 1 size 2 size 3 a1 a2 b e e1 e2 i 138 70,5 26 106 51 6 11 138 70,5 26 106 60 6 11 138 72 35 106 73 6 11 20 715 32 20 725 32 20 735 32 Dimension [mm] Größe 1 Größe 2 Größe 3 size 1 size 2 size 3 a1 a2 b e e1 e2 i 138 70,5 26 106 51 6 11 138 70,5 26 106 60 6 11 138 72 35 106 73 6 11 Part.-No.: Kontakt contact Stichmaß 110 fixing center 110 Klappmelder flap indicator Art.-Nr.: Part.-No.: Kontakt contact Stichmaß 110 fixing center 110 Einz. Grifflasche single bracket Art.-Nr.: Part.-No.: Kontakt contact Stichmaß 110 fixing center 110 Mittenmelder button indicator Europäische Bauform Gewinde: Metrisch European Standard Thread: metric Art.-Nr.: 20 760 32 20 770 32 20 780 32 Dimension [mm] Größe 1 Größe 2 Größe 3 size 1 size 2 size 3 D a2 C e1 L M8 70,5 24 51 73,5 M 10 70,5 24 60 73,5 M 12 72 28 73 73,5 20 761 32 20 771 32 20 781 32 Dimension [mm] Größe 1 Größe 2 Größe 3 size 1 size 2 size 3 D a2 C e1 L M8 70,5 24 51 73,5 M 10 70,5 24 60 73,5 M 12 72 28 73 73,5 Part.-No.: Kontakt contact Gewinde threaded hole Mittenmelder button indicator Art.-Nr.: Part.-No.: Kontakt contact Gewinde threaded hole Klappmelder flap indicator URS 12 Halbleiterschutzsicherungen 1250/1300 V IEC 60269-4 Fuses for Semiconductor Protection UL 248-13 Amerikanische Bauform US Standard Art.-Nr.: 20 718 32 20 728 32 20 738 32 Dimension [mm] Größe 1 Größe 2 Größe 3 size 1 size 2 size 3 A a2 b B1 B2 e1 e2 i 157 70,5 26 132 96 51 6 14 157 70,5 26 132 96 60 6 14 158 72 35 132 98 73 6 16 20 719 32 20 729 32 20 739 32 Dimension [mm] Größe 1 Größe 2 Größe 3 size 1 size 2 size 3 A a2 b B1 B2 e1 e2 i 157 70,5 26 132 96 51 6 14 157 70,5 26 132 96 60 6 14 158 72 35 132 98 73 6 16 Part.-No.: Kontakt contact US lange Version US long version Mittenmelder button indicator Art.-Nr.: Part.-No.: Kontakt contact US lange Version US long version Amerikanische Bauform Gewinde: UNC US Standard Thread: UNC Art.-Nr.: 20 763 32 20 773 32 20 783 32 Dimension [mm] Größe 1 Größe 2 Größe 3 size 1 size 2 size 3 C D L a2 e1 24 5/16” 73,5 70,5 51 24 3/8” 73,5 70,5 60 28 1/2” 73,5 72 73 20 764 32 20 774 32 20 784 32 Dimension [mm] Größe 1 Größe 2 Größe 3 size 1 size 2 size 3 C D L a2 e1 24 5/16” 73,5 70,5 51 24 3/8” 73,5 70,5 60 28 1/2” 73,5 72 73 Part.-No.: Kontakt contact Gewinde threaded hole Klappmelder flap indicator Art.-Nr.: Part.-No.: Kontakt contact Gewinde threaded hole Mittenmelder button indicator URS 13 Halbleiterschutzsicherungen 1250/1300 V IEC 60269-4 Fuses for Semiconductor Protection UL 248-13 SQB 1 Betriebsklasse operating class aR Bemessungs- Bemessungs- Bemessungsspannung strom spannung Leistungsabgabe Schmelzl2t-Wert Ausschaltl2t-Wert IEC 60269-4 UL 248-13 rated current rated voltage rated voltage power loss pre-arcing l2t-value total l2t-value bei 1000 V A V V W A2s x 103 A2s x 103 50-125 160 200 250 280 315 350 400 450 500 550 630 1250 1250 1250 1250 1250 1250 1250 1250 1250 1100 1100 1100 1300 1300 1300 1300 1300 1300 1300 1300 1300 1200 1200 1200 auf Anfrage/ on request 45 49 58 60 67 70 75 80 87 94 99 Koeffizienten für erschwerte Verwendung coefficients for heavy duty application a A2 B1 130 0,55 1,25 URS 14 B2 0,6 Cf3 0,8 N 1,5 2,5 4,6 8,4 12,5 15 22 36 44 66 83 126 at 1000 V 14 25 46 64 81 120 200 250 340 430 670 Halbleiterschutzsicherungen 1250/1300 V IEC 60269-4 Fuses for Semiconductor Protection UL 248-13 Zeit/Strom-Kennlinien Time/current characteristics Schaltspannungsdiagramm arc-voltage-diagramm Umrechnungskoeffizient für Ausschalt-l2t-Wert exchange factor for total-l2t-value Umrechnungskoeffizient für Leistungsabgabe exchange factor for power loss URS 15 Halbleiterschutzsicherungen 1250/1300 V IEC 60269-4 Fuses for Semiconductor Protection UL 248-13 SQB 2 Betriebsklasse operating class aR Bemessungs- Bemessungs- Bemessungsspannung strom spannung Leistungsabgabe Schmelzl2t-Wert Ausschaltl2t-Wert IEC 60269-4 UL 248-13 rated current rated voltage rated voltage power loss pre-arcing l2t-value total l2t-value bei 1000 V A V V W A2s x 103 A2s x 103 250 280 315 350 400 450 500 550 630 700 800 1250 1250 1250 1250 1250 1250 1250 1250 1250 1100 1100 1300 1300 1300 1300 1300 1300 1300 1300 1300 1200 1100 55 59 66 71 75 80 90 105 110 115 123 Koeffizienten für erschwerte Verwendung coefficients for heavy duty application a A2 B1 130 0,55 1,25 URS 16 B2 0,6 Cf3 0,8 N 1,5 8,2 9,9 14 20 31 42 56 71 105 148 225 at 1000 V 45 56 78 110 170 240 310 350 540 710 1180 Halbleiterschutzsicherungen 1250/1300 V IEC 60269-4 Fuses for Semiconductor Protection UL 248-13 Zeit/Strom-Kennlinien Time/current characteristics Schaltspannungsdiagramm arc-voltage-diagramm Umrechnungskoeffizient für Ausschalt-l2t-Wert exchange factor for total-l2t-value Umrechnungskoeffizient für Leistungsabgabe exchange factor for power loss URS 17 Halbleiterschutzsicherungen 1250/1300 V IEC 60269-4 Fuses for Semiconductor Protection UL 248-13 SQB 3 Betriebsklasse operating class aR Bemessungs- Bemessungs- Bemessungsspannung spannung strom rated current IN A 315 350 400 450 500 550 630 700 800 900 1000 1100 1250 1400 IEC 60269-4 UL 248-13 rated voltage rated voltage UN V 1250 1250 1250 1250 1250 1250 1250 1250 1250 1200 1000 1000 900 900 Leistungsabgabe Schmelzl2t-Wert Ausschaltl2t-Wert power loss PV W pre-arcing l2t-value total l2t-value A2s x 103 A2s x 103 83 85 92 99 110 115 120 131 135 140 150 174 198 210 11 15 22 33 42 56 83 113 201 236 350 443 652 852 60 90 130 190 230 320 480 640 1070 1300 1900 2400 3300 3900 bei 1000 V UN V 1300 1300 1300 1300 1300 1300 1300 1300 1300 1300 1000 1000 – – Koeffizienten für erschwerte Verwendung coefficients for heavy duty application a A2 B1 130 0,55 1,25 URS 18 B2 0,6 Cf3 0,8 N 1,5 at 1000 V Halbleiterschutzsicherungen 1250/1300 V IEC 60269-4 Fuses for Semiconductor Protection UL 248-13 Zeit/Strom-Kennlinien Time/current characteristics Schaltspannungsdiagramm arc-voltage-diagramm Umrechnungskoeffizient für Ausschalt-l2t-Wert exchange factor for total-l2t-value Umrechnungskoeffizient für Leistungsabgabe exchange factor for power loss URS 19 Halbleiterschutzsicherungen IEC 60269-4 Fuses for Semiconductor Protection UL 248-13 Sicherungsunterteil 1250 A für Sicherungseinsätze mit Schraubkontakten Gr. 1 bis 3 nach DIN 43653 fuse-base 1250 A for fuse-links with bolted contacts size 1 up to 3 according to DIN 43653 Art.-Nr. part-no. Bemessungsstrom rated current Bemessungsspannung rated voltage Stichmaß “e” fixing center “e” Maß X dimension X 21 313 02 ≤ 1250 A 900 V 80 mm 150 mm 21 323 02 ≤ 1250 A 1400 V 110 mm 180 mm URS 20 Next Semiconductor Fuses 150/250/500/600/700 VAC ■ Very Fast-Acting ■ 1 – 1000 Amperes SPECIFICATIONS Voltage Ratings: L15S: 150 V AC/DC (1 – 60A) 150 VAC (70 – 1000A) 100 VDC (70 – 1000A) L25S: 250 V AC/DC (1 – 200A) 250 VAC (225 – 800A) 200 VDC (225 – 800A) L50S: 500 VAC/450VDC L60S: 600 VAC KLC: 600 VAC L70S: 700VAC/650VDC Interrupting Rating: AC: 200,000 rms amperes (L15S series 100,000 amperes) DC: 20,000 amperes Ampere Range: 1 – 1000 amperes See Rating Table for ratings available in each series. Approvals: UL Recognized under the Components Program and CSA Recognized under the Component Acceptance Program. UL File No: E71611 CSA File No: LR29862 L15S and L25S series fuses are Littelfuse Certified for DC ratings shown in Rating Table. AMPERE RATINGS See Rating Table. RECOMMENDED FUSE BLOCKS LSCR series:Refer to Fuse Block section of this catalog for additional information. Designed to protect today’s equipment and systems, Littelfuse semiconductor fuses are manufactured with Littelfuse-developed technology that sets tomorrow’s standards for accuracy, consistent quality, reliability, and predictable performance. By using advanced metallurgical, polymer, and materials research; mathematical modeling, and computerized statistical analysis; Littelfuse engineers have redefined “State-of-the-Art.” SAFETY ■ 200,000 A.I.R. — Reliable interruption of all overcurrents up to 200,000 amperes . . . meets present and future system requirements. (Note: L15S series has 100,000 A.I.R.) ■ Extremely Current Limiting — Low I2t and peak let-through currents meet most semiconductor requirements. ■ UL Recognized — Littelfuse semiconductor fuses are recognized under the components program of Underwriters Laboratories, Inc., and carry the mark. UL Recognized semiconductor fuses may be used to provide supplementary protection in UL listed equipment. APPLICATIONS Designed specifically for supplementary protection of semiconducting devices such as silicon controlled rectifiers (SCR’s), diodes, thyristors, triacs, transistors, and similar solid-state devices. These devices are used in power equipment including variable speed drives, power rectifiers, UPS systems, DC power supplies, and in a wide range of electronic equipment. May be used wherever extremely fast-acting, current-limiting fuses with no time delay are required. 80 LONGER EQUIPMENT LIFE ■ Low Watt Losses — Means less heating and power consumption in circuit. ■ Controlled Transient Overvoltages — All circuits are subject to transient overvoltages during fault current interruption. These transient overvoltages (arc voltages) start when fuse links melt or circuit breaker contacts part, and subside when circuit is interrupted. Semiconductors are very sensitive to overvoltages. Littelfuse semiconductor fuse designs keep transient overvoltages to low levels and help reduce semiconductor failure. Previous Next Semiconductor Fuses 150/250/500/600/700 VAC ■ Very Fast-Acting ■ 1 – 1000 Amperes RATING TABLE Series & Voltage Ampere Ratings 1 2 3 4 5 6 7 8 9 10 12 15 171⁄2 20 25 30 35 40 45 50 60 70 80 90 100 110 125 150 175 200 225 250 275 300 350 400 450 500 550 600 700 800 900 1000 L15S L25S 150V AC 250V AC 150V DC (1 – 60A) 250V DC (1 – 200A) 100V DC (70 – 1000A) 200V DC (225 – 800A) L50S L60S KLC‡ L70S 500V AC 450V DC 600V AC 600V AC 700V AC 650V DC L15S 1 L15S 2 L15S 3 L15S 4 L15S 5 L15S 6 L15S 7 L15S 8 L15S 9 L15S 10 L15S 12 L15S 15 L25S 1 L25S 2 L25S 3 L25S 4 L25S 5 L25S 6 L60S 1 L60S 2 L60S 3 L60S 4 L60S 5 L60S 6 L25S 8 L60S 8 L25S 10 L25S 12 L25S 15 L50S 10 L50S 12 L50S 15 L15S 20 L15S 25 L15S 30 L15S 35 L15S 40 L15S 45 L15S 50 L15S 60 L15S 70 L15S 80 L15S 90 L15S 100 L25S 20 L25S 25 L25S 30 L25S 35 L25S 40 L25S 45 L25S 50 L25S 60 L25S 70 L25S 80 L25S 90 L25S 100 L50S 20 L50S 25 L50S 30 L50S 35 L50S 40 L15S 125 L15S 150 L25S 125 L25S 150 L25S 175 L25S 200 L25S 225 L25S 250 L25S 275 L25S 300 L25S 350 L25S 400 L25S 450 L25S 500 L15S 200 L15S 250 L15S 300 L15S 350 L15S 400 L15S 450 L15S 500 L15S 600 L15S 800 L25S 600 L25S 700 L25S 800 L50S 50 L50S 60 L50S 70 L50S 80 L50S 90 L50S 100 L50S 125 L50S 150 L50S 175 L50S 200 L50S 225 L50S 250 L50S 275 L50S 300 L50S 350 L50S 400 L50S 450 L50S 500 L50S 550 L50S 600 L50S 700 L50S 800 L60S 10 L60S 12 L60S 15 L60S 171⁄2 L60S 20 L60S 25 L60S 30 L60S 35 L60S 40 L60S 45 L60S 50 L60S 60 L60S 70 L60S 80 L60S 90 L60S 100 KLC 1 KLC 2 KLC 3 KLC 4 KLC 5 KLC 6 KLC 7 KLC 8 L60S 125 L60S 150 L60S 175 L60S 200 L60S 225 L60S 250 KLC 10 KLC 12 KLC 15 KLC 171⁄2 KLC 20 KLC 25 KLC 30 KLC 35 KLC 40 KLC 45 KLC 50 KLC 60 KLC 70 KLC 80 KLC 90 KLC 100 KLC 110 KLC 125 KLC 150 KLC 175 KLC 200 KLC 225 KLC 250 L70S 10 L60S 300 L60S 350 L60S 400 L60S 450 L60S 500 KLC 300 KLC 350 KLC 400 KLC 450 KLC 500 L70S 300 L70S 350 L70S 400 L70S 450 L70S 500 L60S 600 L60S 700 L60S 800 KLC 600 KLC 700 KLC 800 L70S 600 L70S 700 L70S 800 L70S 15 L70S 20 L70S 25 L70S 30 L70S 35 L70S 40 L70S 50 L70S 60 L70S 70 L70S 80 L70S 90 L70S 100 L70S 125 L70S 150 L70S 175 L70S 200 L70S 225 L70S 250 L15S 1000 ‡ KLC series fuses are recommended for replacement use only. 81 Previous Next Semiconductor Fuses 150/250/500/600/700 VAC ■ Very Fast-Acting ■ 1 – 1000 Amperes L15S SERIES, 150* VOLTS AC (Replaces KLA, KLW, L13S) AMPERE RATING DIMENSIONS IN INCHES (mm in parentheses) FIG. NO. A B C D E F G H — 3/8 (9.5) 13/32 (10.3) — — — — 1 – 30 1 1-1/2 (38.1) 31 – 60 1 2 (50.8) — 5/8 (15.9) 13/16 (20.6) — — — — 61 – 450 3 1-5/32 (29.4) 1-7/8 (47.6) 2-3/16 (55.6) 2-21/32 (67.5) 1 (25.4) 43/64 (17.1) 5/16 (7.9) 3/16 (4.8) 451 – 1000 3 1-1/4 (31.8) 1-15/16 (49.2) 2-9/16 (65.1) 3-1/2 (88.9) 1-1/2 (38.1) 1 (25.4) 13/32 (10.3) 1/4 (6.4) L25S SERIES, 250 VOLTS AC (Replaces KLB) AMPERE RATING FIG. NO. DIMENSIONS IN INCHES (mm in parentheses) A B C D E F G H — 1/2 (12.7) 9/16 (14.3) — — — — 1 – 30 1 2 (50.8) 31 – 60 2 1-5/8 (41.3) 2-1/4 (57.2) 2-1/2 (63.5) 3-3/16 (81.0) 13/16 (20.6) 23/32 (18.3) 11/32 (8.7) 1/8 (3.2) 61 – 200 3 1-5/8 (41.3) 2-5/16 (58.7) 2-7/16 (61.9) 3-1/8 (79.4) 1-7/32 (31.0) 1 (25.4) 5/16 (7.9) 3/16 (4.8) 201 – 700 3 1-19/32 (40.5) 2-9/32 (57.9) 2-29/32 3-27/32 (73.8) (97.6) 1-1/2 (38.1) 1 (25.4) 13/32 (10.3) 1/4 (6.4) 701 – 800 3 1-19/32 (40.5) 2-9/32 (57.9) 2-29/32 3-27/32 (73.8) (97.6) 2 (50.8) 1-1/2 (38.1) 13/32 (10.3) 1/4 (6.4) L50S SERIES, 500 VOLTS AC / 450 VOLTS DC (Replaces KLH) DIMENSIONS IN INCHES (mm in parentheses) AMPERE RATING FIG. NO. A B C D E F G H 10 – 30 1 2 (50.8) — 1/2 (12.7) 9/16 (14.3) — — — — 31 – 60 2 1-5/8 (41.3) 2-1/4 (57.2) 2-1/2 (63.5) 3-3/16 (81.0) 13/16 (20.6) 23/32 (18.3) 11/32 (8.7) 1/8 (3.2) 61 – 100 3 2-1/8 (54.0) 2-11/16 (68.3) 3-1/32 (77.0) 3-5/8 (92.1) 1 (25.4) 3/4 (19.1) 11/32 (8.7) 1/8 (3.2) 101 – 200 3 2-1/8 (54.0) 2-13/16 2-15/16 (71.4) (74.6) 3-5/8 (92.1) 1-7/32 (31.0) 1 (25.4) 5/16 (7.9) 3/16 (4.8) 201 – 400 3 2-3/32 (53.2) 2-25/32 3-13/32 4-11/32 (70.6) (86.5) (110.3) 1-1/2 (38.1) 1 (25.4) 13/32 (10.3) 1/4 (6.4) 401 – 600 3 2-7/32 (56.4) 2-29/32 3-17/32 4-15/32 (73.8) (89.7) (113.5) 2 (50.8) 1-1/2 (38.1) 13/32 (10.3) 1/4 (6.4) 601 – 800 3 2-7/32 (56.4) 4-9/32 (108.7) 2-1/2 (63.5) 2 (50.8) 17/32 (13.5) 3/8 (9.5) D F G C A Fig. 1 82 4-5/8 6-15/32 (117.5) (164.3) A B C D Fig, 2 H E Previous Next Semiconductor Fuses 150/250/500/600/700 VAC ■ Very Fast-Acting ■ 1 – 1000 Amperes L60S SERIES, 600 VOLTS AC DIMENSIONS IN INCHES (mm in parentheses) AMPERE RATING FIG. NO. A B C D E F G H 1 – 30 1 5 (127.0) — 5/8 (15.9) 13/16 (20.6) — — — — 31 – 60 2 2-25/32 (70.6) 3-7/16 (87.3) 3-11/16 4-3/8 (93.7) (111.1) 13/16 (20.6) 23/32 (18.3) 11/32 (8.7) 1/8 (3.2) 61 – 100 2 2-29/32 3-17/32 3-25/32 4-15/32 (73.8) (89.7) (96.0) (113.5) 1-1/16 (27.0) 23/32 (18.3) 11/32 (8.7) 1/8 (3.2) 101 – 200 2 2-29/32 (73.8) 3-9/16 (90.5) 3-3/4 (95.3) 4-13/32 (111.9) 1-5/16 (33.3) 1 (25.4) 5/16 (7.9) 3/16 (4.8) 201 – 400 2 2-29/32 3-31/32 (73.8) (100.8) 4-5/32 (105.6) 5-1/8 (130.2) 1-37/64 (40.1) 1 (25.4) 13/32 (10.3) 1/4 (6.4) 401 – 600 2 2-7/8 (73.0) 3-31/32 (100.8) 4-9/64 (105.2) 5-1/8 (130.2) 2-1/16 (52.8) 1-1/2 (38.1) 13/32 (10.3) 1/4 (6.4) 601 – 800 2 3-1/32 (77.0) 5-5/32 (133.4) 5-11/32 (135.7) 7-1/4 (184.2) 2-1/2 (63.5) 2 (50.8) 17/32 (13.5) 3/8 (9.5) L70S SERIES, 700 VOLTS AC / 650 VOLTS DC AMPERE RATING DIMENSIONS IN INCHES (mm in parentheses) FIG. NO. A B C D E F G H J — 1/2 (12.7) 9/16 (14.3) — — — — — 10 – 30 1 2 (50.8) 31 – 60 3 2-7/8 (73.0) 3-7/16 3-25/32 4-3/8 1 (87.3) (96.0) (111.1) (25.4) 43/64 (17.1) 11/32 (8.7) 1/8 (3.2) — 61 – 100 3 2-7/8 (73.0) 3-9/16 3-11/16 4-3/8 1-7/32 (90.5) (93.7) (111.1) (31.0) 29/32 (22.9) 5/16 (7.9) 3/16 (4.8) — 101 – 200 3 2-27/32 3-17/32 4-5/32 5-3/32 1-1/2 (72.2) (89.7) (105.6) (129.4) (38.1) 1 (25.4) 13/32 (10.3) 1/4 (6.4) — 201 – 400 3 2-27/32 3-17/32 4-5/32 5-3/32 (72.2) (89.7) (105.6) (129.4) 2 (50.8) 1-1/2 (38.1) 13/32 (10.3) 1/4 (6.4) — 401 – 600 3 2-27/32 4-29/32 5-1/4 7-3/32 2-1/2 (72.2) (124.6) (133.4) (180.2) (63.5) 2 (50.8) 17/32 (13.5) 3/8 (9.5) — 601 – 800 4 3-5/16 5-5/16 6-13/16 (84.1) (134.9) (173.0) 2 (50.8) 5/8 (15.9) 3/8 (9.5) 5/16 (7.9) — 2-7/8 (73.0) KLC SERIES, 600 VOLTS AC FIG. NO. AMPERE RATING DIMENSIONS IN INCHES (mm in parentheses) A B C D E F G H 2-1/2 (63.5) — 2-7/8 (73.0) 9/16 (14.3) 13/32 (10.3) 1/4 (6.4) 3/64 (1.2) 1 – 30 2 1-7/8 (47.6) 31 – 60 2 2-3/4 (69.9) 3-3/8 (85.7) 3-5/8 (92.1) 4-5/16 (109.5) 13/16 (20.6) 23/32 (18.3) 11/32 (8.7) 1/8 (3.2) 61 – 100 3 2-7/8 (73.0) 3-21/32 (92.9) 4-1/16 (103.2) 5 (127.0) 1 (25.4) 3/4 (19.1) 13/32 (10.3) 1/8 (3.2) 101 – 200 3 2-27/32 3-17/32 (72.2) (89.7) 4-3/8 (111.1) 5-3/32 (129.4) 1-1/2 (38.1) 1 (25.4) 13/32 (10.3) 1/4 (6.4) 201 – 400 3 2-27/32 4-21/32 4-27/32 6-1/4 (72.2) (118.3) (123.0) (158.8) 2 (50.8) 1-5/8 (41.3) 9/16 (14.3) 1/4 (6.4) 401 – 800 3 2-27/32 4-21/32 5-11/32 6-1/4 (72.2) (118.3) (135.7) (158.8) 2-1/2 (63.5) 2 (50.8) 9/16 (14.3) 3/8 (9.5) F F G A B C D Fig. 3 H E G A B C J H E Fig. 4 83 Previous Next Fork-Lift and Stud-Mounted Fuses 32 – 130 Volts DC ■ Fast-Acting and Time-Delay SPECIFICATIONS Voltage Ratings: CNL: 32 Volts DC CNN: 48 Volts DC, 75 Volts AC Interrupting Rating: 2,500 amperes Ampere Range: 10 – 800 amperes Recommended Fuse Block: LFFB001 AMPERE RATINGS CNL 35 40 50 60 80 100 125 130 150 175 200 225 250 275 300 325 350 400 500 CNN 10 80 175 300 500 35 90 200 325 600 40 100 225 350 700 50 125 250 400 800 60 150 275 Example part number (series & amperage): CNN 700 2.43" CNL/CNN Limiter Fuses CNL fast-acting and CNN very fast-acting fuses are recommended for use on battery-operated lift-trucks and other low voltage battery-operated equipment. .343" 3.18" SPECIFICATIONS Voltage Ratings: CBO: 32 Volts DC CCK: 130 Volts DC (1-100A) 72 Volts DC (120-200A) 48 Volts DC (225-300A) CCL: 125 Volts DC Interrupting Rating: CBO, CCK & CCL: 10,000A Ampere Range: 1 – 300 amperes For operating characteristics contact factory AMPERE RATINGS CBO Fast-Acting CCK Time-Delay CBO/CCK/CCL Lift-Truck Fuses CBO fast-acting, CCK and CCL dual-element time-delay fuses are recommended for fork-lift trucks and other similar battery-operated equipment. PART NO. CCK 1-15A CCK 20-30A CCK 35-60A CCK 70-120A CCK 140-200A CCK 225-300A CCL 30-60A CCL 80-120A A 2.810 3.060 3.629 4.129 4.362 4.612 3.060 3.38 B 2.204 2.454 3.454 3.579 3.829 2.454 2.70 C .510 .510 .750 1.00 1.00 1.00 .510 .75 10 12 15 20 25 30 35 40 50 60 70 75 80 100 125 150 1 2 5 10 15 20 25 30 35 40 50 60 70 75 80 90 100 120 140 150 160 175 200 225 250 300 CCL 30 40 60 100 35 50 80 120 Example part number (series & amperage): CCK 150 Time-Delay 1.625" A B .312" C 1.00" CCK/CCL 84 CBO Previous Next Cable Limiters 600 Volts AC SPECIFICATIONS Voltage Rating: 600 volts AC Interrupting Rating: 200,000 Amperes Cable Size Range: 4/0 – 750MCM Copper or Aluminum Minimum Operating Temperature: 80°C ORDERING INFORMATION Type of Termination Terminal Material (Aluminum or Copper) Littelfuse Cable Limiter Conductor Size LFCL - 500 - C - 1 DESCRIPTION Cable limiters are fusible devices that provide very fast short-circuit protection, primarily to faulted cables, but also to other conductors such as busway. Cable limiters do not have an ampere rating, and cannot be used to provide overload protection. Cable limiters are selected by cable size; for example, a 500 kcmil cable requires a 500 kcmil cable limiter. Their main use is to isolate faulted cables in circuits containing three or more parallel conductors per phase. They may be installed on the line side of the main service to provide short-circuit protection to the service conductors. This is especially important when service conductors are tapped from large low-voltage networks or from large low impedance transformers. Cable limiters have terminals which permit them to be installed in a variety of equipment. The most common configuration is the offset blade on one end and the crimp terminal on the other end. This permits the limiter to replace a cable terminal (lug). CATALOG NUMBER Cable Type Type Termination Cable Size COPPER ALUMINUM 4/0 LFCL4/0C1 LFCL4/0A1 250MCM LFCL250C1 LFCL250A1 1 350MCM LFCL350C1 LFCL350A1 Cable to 500MCM LFCL500C1 LFCL500A1 Cable 750MCM LFCL750C1 LFCL750A1 4/0 250MCM 350MCM 500MCM 750MCM LFCL4/0C3 LFCL250C3 LFCL350C3 LFCL500C3 LFCL750C3 5 4/0 250MCM Straight Bus 350MCM to 500MCM Offset Bus 750MCM LFCL4/0C5 LFCL250C5 LFCL350C5 LFCL500C5 LFCL750C5 6 Mole to Cable 4/0 250MCM 350MCM 500MCM 750MCM LFCL4/0C6 LFCL250C6 LFCL350C6 LFCL500C6 LFCL750C6 Mole to Offset Bus 4/0 250MCM 350MCM 500MCM 750MCM LFCL4/0C8 LFCL250C8 LFCL350C8 LFCL500C8 LFCL750C8 3 Cable to Offset Bus APPLICATIONS Service entrance conductors Between transformer or network bus and busway terminal boxes Large feeders with three or more conductors per phase FEATURES ■ ■ ■ Current-limiting characteristics provide protection to conductor insulation and reduce damage when faults occur. Properly applied cable limiters may permit the use of equipment with reduced withstand ratings Wide variety of terminations and cable ratings permit use in almost every situation. 8 LFCL4/0A3 LFCL250A3 LFCL350A3 LFCL500A3 LFCL750A3 LFCL4/0A6 LFCL250A6 LFCL350A6 LFCL500A6 LFCL750A6 Contact factory for shrink tubing availability. 85 Previous Next British Dimension HRCII-C Fuses 600 Volts AC ■ 2 – 600 Amperes SPECIFICATIONS Voltage Rating: 600 Volts AC, 250 Volts DC Interrupting Rating: 200,000 amperes rms symmetrical AC 80,000 amperes rms symmetrical DC Ampere Range: 2 – 600 amperes Approvals: CSA Certified to Standard C22.2 No. 106-M90 (File No. LR90341) AMPERE RATINGS 2CO 2 4 6 10 15 20 25 30 40 50 60 80 100 2CC 125 150 200 250 300 350 400 450 500 600 2CM 80 125 200 300 400 100 150 250 350 Example part number (series & amperage): 2CM 150 RECOMMENDED FUSE BLOCKS DF30 (F, B, FB) — Fits 2 – 30 amps DF60 (F, B, FB) — Fits 40 – 60 amps DF100 (F, B, FB) — Fits 80 – 100 amps HRCII-C fuses are stud-mounted fuses designed to British standard dimensions. They are generally used for motor short circuit protection in dead-front holders, and are normally required to be used in conjunction with a motor running overload device. For additional information on HRCII-C fuse holders, contact factory. D G A D G A B B H F E J J F FIG. 1 FIG. 2 G K E H FIG. 3 OLD LF PART NO. REFER TO FIG. NO. 2CO 2-30 FII 1 2CO 40-60 FII 2CO 80-100 CAT. NO. DIMENSIONS IN MM (Inches in parentheses) A 56 (2.2) B 21 (0.83) C — D 85 (3.3) E 9 (0.35) F 1 (0.04) G 73 (2.87) H 5.5 (0.21) J 7.5 (0.29) K — 1 57 (2.24) 26 (1.02) — 88 (3.45) 13 (0.51) 1.6 (0.06) 73 (2.87) 5.5 (0.21) 7.5 (0.29) — FII 1 68 (2.88) 36 (1.42) — 110 (4.33) 19 (0.75) 2.4 (0.09) 94 (3.7) 8.7 (0.34) — — 2CC 125-200 FIIC 2 76 (3) 41 (1.61) — 137 (5.39) 19 (0.75) 3.6 (0.14) 111 (4.37) 8.7 (0.34) 16 (0.63) — 2CC 250-400 FIIC 3 81 (3.19) 58 (2.28) — 210 (8.27) 26 (1.02) 6.5 (0.26) 133 (5.24) 10.3 (0.4) 16 (0.63) 25.4 (1) 2CC 450-600 FIIC 3 83 (3.27) 74 (2.91) — 210 (8.27) 26 (1.02) 6.5 (0.25) 133 (5.24) 10.3 (0.4) 16 (0.63) 25.4 (1) 2CM 80-100 FIIM 2 66 (2.6) 31 (1.22) — 135 (5.31) 19 (0.75) 3.6 (0.14) 111 (4.37) 8.7 (0.34) 16 (0.63 — 2CM 125-200 FIIM 1 77 (3.03) 41 (1.81) — 110 (4.33) 19 (0.75) 2.4 (0.09) 94 (3.7) 8.7 (0.34) 10.3 (0.4) — 2CM 250-400 FIIM 2 81 (3.19) 58 (2.25) — 136 (5.35) 26 (1.02) 5.2 (0.2) 111 (4.37) 8.7 (0.34) 16 (0.63) — *Hole diameter to accept insulated stud (types C and D) mm min 86 Next L17T Series Telecommunications Power Fuse 170 VDC Current Limiting ■ ■ 70 – 1200 Amperes SPECIFICATIONS Voltage Rating: 170 VDC Interrupting Rating: 100,000 amperes Ampere Range: 70 – 1200 amperes NEW Approvals: UL Recognized under the Components Program (File No: E71611) CSA Recognized under the Component Acceptance Program (File No: LR29862) AMPERE RATINGS 70 80 100 Photo #9 125 150 200 225 250 300 350 400 450 500 600 800 1000 1200 Example part number (series & amperage): L17T 200 RECOMMENDED FUSE BLOCKS LTFD 6001 series Refer to the LTFD series in this catalog section for additional information. Specifically designed for short circuit protection of Telecommunications circuits, the Littelfuse L17T series fuses provide reliable protection of sensitive DC power distribution systems. Constructed with silver plated elements for low I2t and peak let-through, these advanced fuses virtually eliminate equipment damage due to surges and spikes. The L17T series fuse’s unique element geometry also provides cooler running temperatures, helping to minimize heat within enclosures. FEATURES ■ ■ ■ ■ F H A B C D G E Fig. 3 AMPERE RATING DIMENSIONS IN INCHES (mm in parentheses) A B 70 – 250 1-5/32 (29.4) 1-7/8 (47.6) 300 – 800 1-1/4 1-15/16 2-9/16 (31.8) (49.2) (65.1) 1000 – 1200 1-11/32 (34.0) — C D E 2-3/16 2-21/32 1 (55.6) (67.5) (25.4) — G H 5/16 (7.9) 3/16 (4.8) 3-1/2 (88.9) 1-1/2 (38.1) 1 (25.4) 13/32 (10.3) 1/4 (6.35) 4-1/16 (103.12) — 1-1/2 (38.1) — 1/4 (6.35) Contact Littelfuse for characteristic curves. 74 F 7/8 (22.2) Low I2t Extremely current limiting Low operating temperature 170 VDC rating Previous Next TLN Series Telecommunications Power Fuse 170 VDC ■ Current Limiting ■ 1 – 600 Amperes SPECIFICATIONS Voltage Rating: 170 VDC Interrupting Rating: 100,000 amperes NEW Ampere Range: 1 – 600 amperes Approvals: UL Recognized under the components program (File No: E71611) AMPERE RATINGS 1 3 5 6 10 15 20 25 30 35 40 45 50 60 70 80 90 100 110 125 150 175 200 225 250 300 350 400 450 500 600 Example part number (series & amperage): TLN450 RECOMMENDED FUSE BLOCKS LR250 Series Refer to Fuse Block section of this catalog for additional information. FEATURES ■ 170 VDC ■ Fast acting and current limiting ■ 1 to 600 amperes ■ Dimensionally similar to 250V Class R fuses The TLN Series fuses are specifically designed for the protection of telecommunications DC power distribution circuits. A F A K G C D B B F D H E J C FIG. 2 FIG. 1 AMPERE RATING DIMENSIONS IN INCHES (mm in parentheses) A B C D E F G H J K 1 – 30 2 (50.8) 1/2 (12.7) 1/2 (12.7) 9/16 (14.3) 5/64 (2.0) 5/32 (4.0) 3/8 (9.5) — — — 35 – 60 3 (76.2) 3/4 (19.1) 5/8 (15.9) 13/16 (20.6) 3/32 (2.4) 3/16 (4.8) 5/8 (15.9) — — — 70 – 100 5-7/8 (149.2) 1 (25.4) 1-1/16 (27.0) 1-1/16 (27.0) 1/8 (3.2) 3/4 (19.1) 1-1/4 (31.6) 1/4 (6.4) 9/32 (7.1) 1/2 (12.7) 110 – 200 7-1/8 (181.0) 1-1/2 1-15/32 1-19/32 (38.1) (37.3) (40.5) 3/16 (4.8) 1-1/8 (28.6) 1-27/32 (46.8) 7/16 (11.1) 9/32 (7.1) 11/16 (17.5) 225 – 400 8-5/8 (219.1) 2 1-15/16 2-3/32 (50.8) (49.2) (53.2) 1/4 (6.4) 1-5/8 (41.3) 2-11/32 (59.5) 5/8 (15.9) 13/32 (10.3) 15/16 (23.8) 450 – 600 10-3/8 (263.5) 2-1/2 (63.5) 1/4 (6.4) 2 (50.8) 2-27/32 (72.2) 3/4 (19.1) 17/32 (13.5) 1-1/8 (28.6) Figure 1 Figure 2 2-3/8 (60.3) 2-19/32 (65.9) Contact Littelfuse for characteristic curves. 75 Previous Next TLS Series Telecommunications Power Fuse 170 VDC ■ Current Limiting ■ 1 – 70 Amperes SPECIFICATIONS Voltage Rating: 170 VDC Interrupting Rating: 100,000 amperes NEW Ampere Range: 1 – 70 amperes Approvals: UL Recognized under the components program (File No: E71611) Construction: Caps: Silver-plated brass Body: Glass melamine AMPERE RATINGS 1 3 5 6 10 15 20 25 30 40 50 60 70 Example part number (series & amperage): TLS050 ORDERING INFORMATION Littelfuse’s TLS Series fuses are designed specifically for the protection of telecommunications equipment. TLS fuses have been engineered to operate up to 170 VDC to provide current limiting short circuit protection for cables and components found in the DC power distribution circuits of telecommunications systems. The TLS’ compact design provides superior protection and high power density in an extremely compact package. FEATURES ■ ■ ■ ■ 170 VDC Current limiting 1 to 70 amperes Circuit board mounting available (TLS_L series) TLS TLS-L Catalog Catalog No. No. Leaded Version* TLS001 TLS001L TLS003 TLS003L TLS005 TLS005L TLS006 TLS006L TLS010 TLS010L TLS015 TLS015L TLS020 TLS020L TLS025 TLS025L TLS030 TLS030L TLS040 TLS040L TLS050 TLS050L TLS060 TLS060L TLS070 TLS070L * Used for circuit board applications. RECOMMENDED FUSE BLOCKS LTFD series disconnect switches Contact factory for more information. .562 .195 .562 TLS 60A TLS 60A .880 Contact Littelfuse for characteristic curves. 76 .880 1.760 Ampere Rating 1 3 5 6 10 15 20 25 30 40 50 60 70 Previous LTFD 6001 Series Telecommunications Disconnect Switch 145 VDC, 60 VDC ■ 70 – 1200 Amperes SPECIFICATIONS Voltage Rating: 145 VDC 70 – 600 amperes 60 VDC 800 – 1200 amperes Ampere Range: 70 – 1200 amperes NEW Approvals: UL Recognized (E122674) RECOMMENDED FUSES L17T Series fuses ORDERING INFORMATION Catalog No. LTFD6001-00 LTFD6001-01 LTFD1200-01 Photo #9 Stud Size (A) 3/4 – 16 x 3.5 in. 7/8 – 14 x 3.5 in. Contact Factory Amperes 70 – 600 70 – 800 800 – 1200 Contact Nut Max. Torque 100 feet-pound 120 feet-pound Contact Factory FEATURES ■ ■ 145 VDC, 70 to 600 amperes 60 VDC, 800 amperes Littelfuse’s compact LTFD 6001 Series holders are designed for use as a combination fuseholder and disconnect switch for telecommunications equipment. The rugged unit utilizes a pull-out fuse carrier to safely disconnect power and provide easy fuse replacement. Contact factory for 1200A switch dimensions. 77 Introducing the Global Pro System Offering World Class Performance and Global Acceptance The International Challenge The benefits of the Global Pro System include: Engineers and equipment designers are faced with a dilemma when choosing the right circuit protection for their globally distributed equipment. They need to determine what markets the product will be used in, what local electrical standards apply in each of those markets, and what fuses should be used so users can find replacements easily. The Global Pro System resolves these design issues by incorporating North American standards to fit internationally accepted IEC fuse dimensions. This allows touch-safe fuseholders that can be used in virtually any market and permits equipment to be easily adapted by simply replacing the fuse with one that meets local standards. It’s that simple. Global Acceptance – Total Pro-Tection Universal voltages The Littlefuse Global Pro circuit protection system combines fuses and fuseholders in a simple package designed to comply with UL and IEC requirements. The result is the single best solution for your worldwide circuit protection needs. Touch-safe components Flexible Components Integrated lockout/ tagout devices for OSHA compliance The components of the Global Pro system are vital to its performance. The key component within the integrated system is the fuse. The Littelfuse Global Fuse is designed to offer UL Class J performance, but with the compact size and international compatibility associated with fuses manufactured to IEC dimensions. Global Acceptance UL and IEC approval Class J performance in an IEC package Blown fuse indication Design versatility for OEM’s Built-in microswitch to integrate into PLC networks, turn on stack lighting, and remote blown fuse indication More Protection In Less Space Global Pro fuses are significantly smaller in size than 30, 60, and 100 amp Class J fuses. All Global Pro fuses offer: Good Extremely Compact Size Pop-up Pin Blown Fuse Indication Class J Performance Compatibility with IEC style fuse holders Blown Littelfuse, Inc. - POWR-GARD Products 800 E. Northwest Highway - Des Plaines, IL 60016 Technical Hot-Line: 1-800-TEC-FUSE (832-3873) Visit us on the web! www.littelfuse.com LgD Series Global Pro-tection Fuses 600 Volts AC – Time Delay - 1-100 Amperes SPECIFICATIONS Voltage Rating: AC: 600 Volts (UL) 690 Volts (IEC) DC: 500 Volts (1-30A) 300 Volts (35-60A) Interrupting Rating: AC: 200,000 amps DC: 100,000A (1-30A) 20,000A (35-60A) Ampere Range: 1-100* amperes Approvals: The Global Pro system is designed to save valuable space in a crowded panel while providing designers with the flexibility of a universally accepted design for easy replacement. Global Pro fuses are far more compact and have greater power handling capability than conventional products. Global Pro fuses are up to 75% smaller than Class R fuses and up to 50% smaller than Class J fuses while providing the time delay that is necessary for motor circuit protection. Global Pro fuses also provide quick and positive visual identification of blown fuses by using a pop-up indicator design that protrudes from the top of the fuse. The popup indicator is designed to immediately alert maintenance personnel that it needs to be replaced. Touch-safe fuse holders are available with a built-in microswitch that is activated by the pop-up indicator. The microswitch can be used to integrate into PLC networks, turn on stack lighting , and provide equipment operators with a remote method of determining when the fuse needs to be replaced. UL Listed Special Purpose (1-30 amps) UL Recognized (35-60 amps) CSA Certified (1-60 amps) *Contact factory for ratings above 60A AMPERE RATINGS 1 3 6 8 10 12 15 20 25 30 35 40 45 50 60 70* 80* 90* 100* *Contact factory for ratings above 60A Example part number (series & amperage): LgD 60 RECOMMENDED FUSEHOLDERS LPSG Series Global PRO Fuseholders FEATURES AND BENEFITS Extremely compact size Pop-up Pin Indication Class J performance Global acceptance UL and IEC approval Touch-safe components APPLICATIONS Design versatility for the OEM Motor control centers DIMENSIONS Motor branch circuits Primary & secondary protection Part Number Amperage English Metric LgD 0-30A 0-30A 9/16” x 2” 14mm x 51mm of transformers LgD 35-60A 35-60A 13/13” x 2-1/4” 22mm x 58mm Equipment designed for export LgD 70-100A 70-100A 1-1/16” x 2-3/8” 27mm x 60mm Littelfuse, Inc. - POWR-GARD Products 800 E. Northwest Highway - Des Plaines, IL 60016 Technical Hot-Line: 1-800-TEC-FUSE (832-3873) Visit us on the web! www.littelfuse.com LPSG Series Global Pro Fuseholders SPECIFICATIONS Voltage Rating: 750 AC/DC Withstand Rating: 200,000 amps Ampere Range: 30, 60, and 100* amperes *Contact Factory for ratings above 60 amps. Terminal Type: Pressure Plate Recommended Torque: 30A: 35 In. lbs. 60A: 45 In. lbs. Wire Range: #2-14 CU Material: Thermo-plastic Approvals: UL Recognized Littelfuse’s Global Protection System simplifies circuit protection by incorporating North American electrical requirements into fuse styles found in the rest of the world. The Global Pro fuseholder features a microswitch that is actuated by a blown fuse. This allows the Global Pro system to integrate into PLC networks and provide remote blown fuse indication. An indicator light also allows maintenance personnel to locate blown fuses quickly. CSA Certified IEC 269/947-3 Indicator: Neon Lamp • Minimum 90 VAC, 115VDC to operate indicator • Less than 0.7mA leakage current at 600V FEATURES and BENEFITS • IP20 Touch-Safe Design to IEC 529 • DIN Rail Mounting (35mm rail) • Integrated Lock-out/tagout device for OSHA compliance • Compact Size – up to 60% smaller than Class R blocks and up to 25% smaller than Class J blocks. • Blown Fuse Indicator to quickly identify blown fuses • Integrated microswitch for remote fuse status and PLC integration RECOMMENDED FUSES LgD series Global Pro Fuses ORDERING INFORMATION Catalog No. LPSG30-1MI LPSG30-2MI LPSG30-3MI LPSG60-1MI LPSG60-2MI LPSG60-3MI LPSG100-1MI LPSG100-2MI LPSG100-3MI Amp Rating 30A 30A 30A 60A 60A 60A 100A 100A 100A Poles 1 2 3 1 2 3 1 2 3 Pack Qty. 6 3 2 6 3 2 6 3 2 Note: LPSG series fuseholders are not approved to be a load-break disconnect. Littelfuse, Inc. - POWR-GARD Products 800 E. Northwest Highway - Des Plaines, IL 60016 Technical Hot-Line: 1-800-TEC-FUSE (832-3873) Visit us on the web! www.littelfuse.com FUSES URE FUSES FOR SEMICONDUCTOR PROTECTION EUROPEAN-BRITISH STANDARD Standards: IEC 60 269-4 BS 88-4 Class: aR Voltage ratings: AC 240 V – AC 700 V Current ratings: 5 A – 900 A Features / Benefits High interrupting rating 100 kA Voltage rating AC 240 V – AC 700 V Protection of Power Semiconductors according to IEC 60269-4 Complies with BS 88 Standard with or without striker for microswitch operation Class aR 5 A – 900 A according to IEC 60269-4 URE 1 URE FUSES FUSES FOR SEMICONDUCTOR PROTECTION EUROPEAN-BRITISH STANDARD Selection Guide Fuses Rated Voltage AC Size Part No. Selector Guide Page Techn. Data Page 240 V 240 V 240 V 240 V 690 V 690 V 690 V 690 V 690/700 V 8.4 x 38 17.5 x 41.8 35 x 59 2 x 35 x 59 8.4 x 64.3 17.5 x 63.5 35 x 85 2 x 35 x 85 000 50 076 06 50 053 06 50 054 06 50 071 06 50 077 06 50 073 06 50 074 06 50 075 06 20 559 21 URE 3 URE 4 URE 5 URE 6 URE 7 URE 8 URE 9 URE 10 URE 11 URE 12 URE 13 URE 14 URE 15 URE 16 URE 17 URE 18 URE 19 URE 20 Selection Guide Set of mounting clips for Indicator Fuse Size Part No. Techn. Data Page 17.5 mm 35 mm 58 053 04 58 054 04 URZ 21 URZ 21 Selection Guide Indicator Fuse Rated Voltage Part No. Techn. Data Page 240 V 690 V 58 053 07 58 073 07 URZ 21 URZ 21 Selection Guide Microswitch Rated Voltage Part No. Techn. Data Page 250 V 58 053 05.1 URZ 21 URE 2 URE FUSES FUSES FOR SEMICONDUCTOR PROTECTION EUROPEAN-BRITISH STANDARD Rated voltage AC 240 V Rated current Part No. 5A 6A 10 A 12 A 16 A 20 A 50 076 06 50 076 06 50 076 06 50 076 06 50 076 06 50 076 06 UL Rec. Size 8.4 x 38 mm Standard BS 88-4 Weight Pack (kg/100) 0.55 0.55 0.55 0.55 0.55 0.55 50 50 50 50 50 50 A B C D E F G K L 1.06 ” (27 mm) 0.33 ” (8.4 mm) 0.16 ” (4 mm) 0.24 ” (6 mm) 1.50 ” (38 mm) 0.25 ” (6.4 mm) 0.35 ” (9 mm) 0.03 ” (0.8 mm) 1.80 ” (46 mm) URE 3 URE FUSES FUSES FOR SEMICONDUCTOR PROTECTION EUROPEAN-BRITISH STANDARD A B C D E F G K L Rated voltage AC 240 V Rated current Part No. 25 A 32 A 35 A 40 A 50 A 63 A 80 A 100 A 125 A 160 A 180 A 50 053 06 50 053 06 50 053 06 50 053 06 50 053 06 50 053 06 50 053 06 50 053 06 50 053 06 50 053 06 50 053 06 1.02 ” (26 mm) 0.70 ” (17.5 mm) 0.25 ” (6.35 mm) 0.30 ” (8 mm) 1.57 ” (40 mm) 0.50 ” (13 mm) 0.73 ” (18.5 mm) 0.10 ” (2.5 mm) 2.17 ” (55 mm) URE 4 UL Rec. Size 17.5 x 41.8 mm Standard BS 88-4 Weight Pack (kg/100) 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 10 10 10 10 10 10 10 10 10 10 10 URE FUSES FUSES FOR SEMICONDUCTOR PROTECTION EUROPEAN-BRITISH STANDARD Rated voltage AC 240 V Rated current Part No. 160 A 200 A 250 A 315 A 355 A 400 A 450 A 50 054 06 50 054 06 50 054 06 50 054 06 50 054 06 50 054 06 50 054 06 UL Rec. Size 35 x 59 mm Standard BS 88-4 Weight Pack (kg/100) 15 15 15 15 15 15 15 2 2 2 2 2 2 2 A B C D E F G K L 1.22 ” (31 mm) 1.38 ” (35 mm) 0.40 ” (10.3 mm) 0.53 ” (13.5 mm) 2.32 ” (59 mm) 0.98 ” (25 mm) 1.54 ” (39 mm) 0.12 ” (3 mm) 3.30 ” (84 mm) URE 5 URE FUSES FUSES FOR SEMICONDUCTOR PROTECTION EUROPEAN-BRITISH STANDARD A B C D E F G H K L Rated voltage AC 240 V Rated current Part No. 300 A 350 A 400 A 450 A 500 A 630 A 710 A 800 A 900 A 50 071 06 50 071 06 50 071 06 50 071 06 50 071 06 50 071 06 50 071 06 50 071 06 50 071 06 1.22 ” (31 mm) 1.38 ” (35 mm) 0.40 ” (10.3 mm) 0.53 ” (13.5 mm) 2.32 ” (59 mm) 1.0 ” (25 mm) 1.65 ” (42 mm) 1.65 ” (78 mm) 0.24 ” (6 mm) 3.30 ” (84 mm) URE 6 UL Rec. Size 2 x 35 x 59 mm Standard BS 88-4 Weight Pack (kg/100) 29 29 29 29 29 29 29 29 29 1 1 1 1 1 1 1 1 1 URE FUSES FUSES FOR SEMICONDUCTOR PROTECTION EUROPEAN-BRITISH STANDARD Rated voltage AC 690 V Rated current Part No. 5A 6A 10 A 12 A 16 A 20 A 50 077 06 50 077 06 50 077 06 50 077 06 50 077 06 50 077 06 UL Rec. Size 8.4 x 64.3 mm Standard BS 88-4 Weight Pack (kg/100) 0.88 0.88 0.88 0.88 0.88 0.88 50 50 50 50 50 50 A B C D E F G K L 2.13 ” (54 mm) 0.33 ” (8.4 mm) 0.16 ” (4 mm) 0.24 ” (6 mm) 2.52 ” (64 mm) 0.25 ” (6.4 mm) 0.35 ” (9 mm) 0.03 ” (0.8 mm) 2.87 ” (73 mm) URE 7 URE FUSES FUSES FOR SEMICONDUCTOR PROTECTION EUROPEAN-BRITISH STANDARD A B C D E F G K L Rated voltage AC 690 V Rated current Part No. 25 A 32 A 40 A 50 A 63 A 80 A 100 A 50 073 06 50 073 06 50 073 06 50 073 06 50 073 06 50 073 06 50 073 06 1.90 ” (48 mm) 0.70 ” (17.5 mm) 0.25 ” (6.35 mm) 0.30 ” (8 mm) 2.48 ” (63 mm) 0.50 ” (13 mm) 0.73 ” (18.5 mm) 0.10 ” (2.5 mm) 3.03 ” (77 mm) URE 8 UL Rec. Size 17.5 x 63.5 mm Standard BS 88-4 Weight Pack (kg/100) 4.2 4.2 4.2 4.2 4.2 4.2 4.2 10 10 10 10 10 10 10 URE FUSES FUSES FOR SEMICONDUCTOR PROTECTION EUROPEAN-BRITISH STANDARD Rated voltage AC 690 V Rated current Part No. 100 A 125 A 160 A 200 A 250 A 315 A 355 A 50 074 06 50 074 06 50 074 06 50 074 06 50 074 06 50 074 06 50 074 06 UL Rec. Size 35 x 85 mm Standard BS 88-4 Weight Pack (kg/100) 19 19 19 19 19 19 19 3 3 3 3 3 3 3 A B C D E F G K L 2.05 ” (52 mm) 1.38 ” (35 mm) 0.40 ” (10.3 mm) 0.53 ” (13.5 mm) 3.15 ” (80 mm) 0.98 ” (25 mm) 1.54 ” (39 mm) 0.12 ” (3 mm) 4.13 ” (105 mm) URE 9 URE FUSES FUSES FOR SEMICONDUCTOR PROTECTION EUROPEAN-BRITISH STANDARD A B C D E F G H K L Rated voltage AC 690 V Rated current Part No. 315 A 355 A 400 A 450 A 500 A 630 A 710 A 50 075 06 50 075 06 50 075 06 50 075 06 50 075 06 50 075 06 50 075 06 2.05 ” (52 mm) 1.38 ” (35 mm) 0.40 ” (10.3 mm) 0.53 ” (13.5 mm) 3.15 ” (80 mm) 0.98 ” (25 mm) 1.65 ” (42 mm) 3.07 ” (78 mm) 0.24 ” (6 mm) 4.12 ” (105 mm) URE 10 UL Rec. Size 2 x 35 x 85 mm Standard BS 88-4 Weight Pack (kg/100) 37 37 37 37 37 37 37 1 1 1 1 1 1 1 URE FUSES FUSES FOR SEMICONDUCTOR PROTECTION EUROPEAN-BRITISH STANDARD Rated voltage AC 660/700 V Rated current Part No. 32 A 35 A 40 A 50 A 63 A 80 A 100 A 160 A 200 A 250 A 315 A 20 559 21 20 559 21 20 559 21 20 559 21 20 559 21 20 559 21 20 559 21 20 559 21 20 559 21 20 559 21 20 559 21 UL Rec. Size 000 Standard BS 88-4 Weight Pack (kg/100) 17 17 17 17 17 17 17 17 17 17 17 6 6 6 6 6 6 6 6 6 6 6 A max. B C D E F G K L 2.13 ” (54 mm) 1.42 ” (36 mm) 0.35 ” (9 mm) 0.47 ” (12 mm) 2.76 ” (70 mm) 1.26 ” (32 mm) 0.93 ” (23.5 mm) 0.08 ” (2 mm) 3.70 ” (94 mm) URE 11 URE Electrical Characteristics FUSES Size 8.4 x 38 mm Rated voltage AC 240 V Operating class aR Rated current Part No. Power loss W Pre-arcing l2t-value A2s 5A 6A 10 A 12 A 16 A 20 A 50 076 06 50 076 06 50 076 06 50 076 06 50 076 06 50 076 06 1.5 1.7 3.3 2.0 2.4 3.3 1.7 2.9 4.2 8.0 18.0 25.0 Rated breaking capacity 100 kA Total l2t-value @ 240 V A2s 9.5 16 24 41 92 130 Cut-off-characteristics Time / Current Characteristics Prospective Short Circuit Current Arc voltage-Diagram Reduction factor for total I2t-value I(kA) Virtual Pre-arcing Time t(s) Cut-off Current Peak Ic (kA) Reduction factor for power loss UL ____ KB VAC KW UB ____ UB ____ IB ___ VAC VAC IN URE 12 RMS Prospective Current I(A) Electrical Characteristics Size 17.5 x 41.8 mm FUSES Rated voltage AC 240 V Operating class aR Rated breaking capacity 100 kA Rated current Part No. Power loss W Pre-arcing l2t-value A2s Total l2t-value @ 240 V A2s 25 A 32 A 35 A 40 A 50 A 63 A 75 A 80 A 100 A 125 A 160 A 180 A 50 053 06 50 053 06 50 053 06 50 053 06 50 053 06 50 053 06 50 053 06 50 053 06 50 053 06 50 053 06 50 053 06 50 053 06 3.6 4.5 5.0 5.3 6.7 7.7 9.4 9.7 12.7 16.0 22.0 24.0 39 40 63 100 130 250 330 420 620 1,000 1,500 2,300 260 270 430 700 900 1,700 2,300 2,900 4,300 6,800 10,200 15,700 Cut-off-characteristics URE Time / Current Characteristics t(s) Virtual Pre-arcing Time Cut-off Current Peak Ic (kA) Prospective Short Circuit Current Arc voltage-Diagram Reduction factor for total I2t-value I(kA) Reduction factor for power loss UL ____ KB VAC KW UB ____ UB ____ IB VAC VAC IN ___ RMS Prospective Current I(A) URE 13 URE Electrical Characteristics FUSES Size 35 x 59 mm Rated voltage AC 240 V Operating class aR Rated breaking capacity 100 kA Rated current Part No. Power loss W Pre-arcing l2t-value A2s Total l2t-value @ 240 V A2s 160 A 200 A 250 A 315 A 355 A 400 A 450 A 50 054 06 50 054 06 50 054 06 50 054 06 50 054 06 50 054 06 50 054 06 23 27 34 36 38 40 46 1,300 2,500 4,600 7,800 11,800 18,500 26,600 8,000 15,300 28,000 48,000 72,000 113,000 163,000 Cut-off-characteristics Time / Current Characteristics t(s) Virtual Pre-arcing Time Cut-off Current Peak Ic (kA) Prospective Short Circuit Current Arc voltage-Diagram Reduction factor for total I2t-value I(kA) Reduction factor for power loss UL ____ KB VAC KW UB ____ UB ____ IB ___ VAC VAC IN URE 14 RMS Prospective Current I(A) Electrical Characteristics Size 2 x 35 x 59 mm FUSES Rated voltage AC 240 V Operating class aR Rated breaking capacity 100 kA Rated current Part No. Power loss W Pre-arcing l2t-value A2s Total l2t-value @ 240 V A2s 400 A 450 A 500 A 630 A 710 A 800 A 900 A 50 071 06 50 071 06 50 071 06 50 071 06 50 071 06 50 071 06 50 071 06 55 56 59 62 72 74 90 10,000 19,000 27,000 50,000 70,000 106,000 150,000 61,000 116,000 165,000 305,000 427,000 647,000 915,000 Cut-off-characteristics URE Time / Current Characteristics t(s) Virtual Pre-arcing Time Cut-off Current Peak Ic (kA) Prospective Short Circuit Current Arc voltage-Diagram Reduction factor for total I2t-value I(kA) Reduction factor for power loss UL ____ KB VAC KW UB ____ UB ____ IB VAC VAC IN ___ RMS Prospective Current I(A) URE 15 URE Electrical Characteristics FUSES Size 8.4 x 64.3 mm Rated voltage AC 690 V Operating class aR Rated breaking capacity 100 kA Rated current Part No. Power loss W Pre-arcing l2t-value A2s Total l2t-value @ 690 V A2s 6A 10 A 12 A 16 A 20 A 50 077 06 50 077 06 50 077 06 50 077 06 50 077 06 3.2 3.7 3.9 5.5 7.5 3 8 11 18 32 20 53 77 120 215 Cut-off-characteristics Time / Current Characteristics Prospective Short Circuit Current Arc voltage-Diagram Reduction factor for total I2t-value I(kA) Virtual Pre-arcing Time t(s) Cut-off Current Peak Ic (kA) Reduction factor for power loss UL ____ KB VAC KW UB ____ UB ____ IB ___ VAC VAC IN URE 16 RMS Prospective Current I(A) Electrical Characteristics Size 17.5 x 63.5 mm FUSES Rated voltage AC 690 V Operating class aR Rated breaking capacity 100 kA Rated current Part No. Power loss W Pre-arcing l2t-value A2s Total l2t-value @ 690 V A2s 25 A 32 A 35 A 40 A 50 A 63 A 80 A 100 A 50 073 06 50 073 06 50 073 06 50 073 06 50 073 06 50 073 06 50 073 06 50 073 06 7 9 10 11 12 15 18 23 25 50 60 80 190 290 420 740 110 210 260 330 780 1,200 1,700 3,100 Cut-off-characteristics URE Time / Current Characteristics t(s) Virtual Pre-arcing Time Cut-off Current Peak Ic (kA) Prospective Short Circuit Current Arc voltage-Diagram Reduction factor for total I2t-value I(kA) Reduction factor for power loss UL ____ KB VAC KW UB ____ UB ____ IB VAC VAC IN ___ RMS Prospective Current I(A) URE 17 URE Electrical Characteristics FUSES Size 35 x 85 mm Rated voltage AC 690 V Operating class aR Rated breaking capacity 100 kA Rated current Part No. Power loss W Pre-arcing l2t-value A2s Total l2t-value @ 690 V A2s 100 A 125 A 160 A 200 A 250 A 315 A 355 A 50 074 06 50 074 06 50 074 06 50 074 06 50 074 06 50 074 06 50 074 06 22 29 30 31 40 44 56 1,000 1,700 4,000 9,000 18,000 27,000 36,000 6,500 11,000 26,000 58,000 116,000 173,000 231,000 Cut-off-characteristics Time / Current Characteristics t(s) Virtual Pre-arcing Time Cut-off Current Peak Ic (kA) Prospective Short Circuit Current Arc voltage-Diagram Reduction factor for total I2t-value I(kA) Reduction factor for power loss UL ____ KB VAC KW UB ____ UB ____ IB ___ VAC VAC IN URE 18 RMS Prospective Current I(A) Electrical Characteristics Size 2 x 35 x 85 mm FUSES Rated voltage AC 690 V Operating class aR Rated breaking capacity 100 kA Rated current Part No. Power loss W Pre-arcing l2t-value A2s Total l2t-value @ 690 V A2s 315 A 355 A 400 A 450 A 500 A 630 A 710 A 50 075 06 50 075 06 50 075 06 50 075 06 50 075 06 50 075 06 50 075 06 48 55 58 63 68 87 104 18,500 22,300 26,100 52,300 70,100 106,000 145,000 119,000 143,000 167,000 335,000 449,000 679,000 928,000 Cut-off-characteristics URE Time / Current Characteristics t(s) Virtual Pre-arcing Time Cut-off Current Peak Ic (kA) Prospective Short Circuit Current Arc voltage-Diagram Reduction factor for total I2t-value I(kA) Reduction factor for power loss UL ____ KB VAC KW UB ____ UB ____ IB VAC VAC IN ___ RMS Prospective Current I(A) URE 19 URE Electrical Characteristics FUSES Size 000 Rated voltage AC 690/700 V Operating class aR Rated breaking capacity 600 V/300 kA · 700 V/200 kA Rated current Part No. Part No. without indicator Power loss W Pre-arcing l2t-value A2s Total l2t-value A2s 32 A 35 A 40 A 50 A 63 A 80 A 100 A 125 A 160 A 180 A 200 A 250 A 315 A 20 559 20 20 559 20 20 559 20 20 559 20 20 559 20 20 559 20 20 559 20 20 559 20 20 559 20 20 559 20 20 559 20 20 559 20 20 559 20 20 559 21 20 559 21 20 559 21 20 559 21 20 559 21 20 559 21 20 559 21 20 559 21 20 559 21 20 559 21 20 559 21 20 559 21 20 559 21 8 9 10 12 14 18 22 26 21 35 39 47 58 52 66 90 140 250 470 730 1,300 2,800 3,700 4,500 8,000 14,000 290 360 500 770 1,400 2,600 4,000 7,200 15,400 20,400 25,000 44,000 77,000 Cut-off-characteristics Time / Current Characteristics t(s) Virtual Pre-arcing Time Cut-off Current Peak Ic (kA) Prospective Short Circuit Current Arc voltage-Diagram Reduction factor for total I2t-value I(kA) Reduction factor for power loss UL ____ KB VAC KW UB ____ UB ____ IB ___ VAC VAC IN URE 20 RMS Prospective Current I(A) FUSES URE Sets for Indicator fuses with microswitch Part No. fuse links 50 053 06 50 054 06 50 073 06 50 074 06 50 071 06 50 075 06 I Set of clips for indicator fuse II III indicator fuse Microswitch 58 053 04 58 054 04 58 053 04 58 054 04 58 053 07 58 073 07 58 053 07 58 053 07 58 073 07 58 073 07 58 053 07 58 073 07 58 053 05.1 58 053 05.1 58 053 05.1 58 053 05.1 58 053 05.1 58 053 05.1 H I J 0.98 “ (25 mm) 1.60 “ (41 mm) 0.98 “ (25 mm) 1.60 “ (41 mm) 0.98 “ (25 mm) 1.60 “ (41 mm) 0.87 “ (22 mm) 1.46 “ (37 mm) 0.87 “ (22 mm) 1.46 “ (37 mm) 0.87 “ (22 mm) 1.46 “ (37 mm) 0.94 “ (24 mm) 1.54 “ (39 mm) 0.94 “ (24 mm) 1.54 “ (39 mm) 0.94 “ (24 mm) 1.54 “ (39 mm) URE 21 FUSES URDC DC-APPLICATION / TRACTION FUSE Class: gR/aR Voltage rating: DC 660 V – DC 5000 V Current rating: 6 A to 800 A Standards: UIC 550 IEC 60269-4 DIN VDE 0636-40 SIBA-DC-Fuses are offered in clip-mounted and bolt-design. The fuses are used for applications in traction-, battery, and railwaymain-circuits. They are largely used for the protection of frequency-inverters. Because the application is possible in a big variety one should contact SIBA to have information regarding the use at different voltage ratings, classes or L/R’s. Features / Benefits Designed for heavy duty applications Shock and vibration proved Some types with additional microswitches Developed according customers specification Individual tested time constants Designed for long lasting live under severe service conditions URDC 1 URDC FUSES Selection Guide Size Rated Voltage DC 14 x 51 14 x 51 27 x 60 27 x 60 20 x 127 20 x 127 20 x 127 20 x 190 20 x 190 SQB-5000 SQB-5000 NH 4 NH 1 700 V 700 V 660 V 660 V 1000 V 1000 V 1500 V 1500 V 1500 V 5000 V 5000 V 1000 V 750 V URDC 2 Indicator Type without indicator without indicator without indicator with striker pin with indicator with striker pin with striker pin without indicator with striker pin without indicator withour indicator without indicator with topindicator Part No. Selector Guide Page Techn. Data Page 50 118 06 50 201 06 50 190 06 50 191 06 90 080 10 90 082 10 90 081 10 90 090 10 90 092 10 90 200 20 90 210 20 90 083 10 20 556 04 URDC 3 URDC 3 URDC 4 URDC 5 URDC 6 URDC 7 URDC 8 URDC 9 URDC 10 URDC 11 URDC 12 URDC 13 URDC 14 URDC 15 URDC 16 URDC 17 URDC 17 URDC 18 URDC 18 URDC 19 URDC 20 URDC 20 URDC 21 URDC 21 URDC 22 URDC 23 URDC FUSES DC-APPLICATION / TRACTION FUSE Rated current Part No. 6A 8A 10 A 12 A 16 A 20 A 25 A 30 A 35 A 40 A 50 A 50 118 06 50 118 06 50 118 06 50 118 06 50 118 06 50 118 06 50 118 06 50 118 06 50 118 06 50 118 06 50 118 06 Size 14 x 51 mm UL Rec. Rated voltage DC 700 V Weight ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 10 10 10 10 10 10 10 10 10 10 10 UL Rec. Size 14 x 51 mm Pack Weight Pack ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 (kg/100) Rated voltage DC 700 V Rated current Part No. 10 A 12 A 16 A 20 A 25 A 32 A 40 A 50 A 50 201 06 50 201 06 50 201 06 50 201 06 50 201 06 50 201 06 50 201 06 50 201 06 (kg/100) 10 10 10 10 10 10 10 10 A B 2.01 ” (51 mm) 0.55 ” (14 mm) URDC 3 URDC FUSES DC-APPLICATION / TRACTION FUSE Rated voltage DC 660 V Rated current Part No. 8A 10 A 12 A 16 A 20 A 25 A 32 A 40 A 50 A 50 A 63 A 80 A 100 A 110 A 50 190 06 50 190 06 50 190 06 50 190 06 50 190 06 50 190 06 50 190 06 50 190 06 50 190 06 50 190 06 50 190 06 50 190 06 50 190 06 50 190 06 without striker pin A 2.36 ” (60 mm) B 1.06 ” (27 mm) URDC 4 UL Rec. Size 27 x 60 mm Weight Pack (kg/100) 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 10 10 10 10 10 10 10 10 10 10 10 10 10 10 FUSES URDC DC-APPLICATION / TRACTION FUSE Rated voltage DC 660 V Rated current Part No. 8A 10 A 12 A 16 A 20 A 25 A 32 A 40 A 50 A 50 A 63 A 80 A 100 A 110 A 50 191 06 50 191 06 50 191 06 50 191 06 50 191 06 50 191 06 50 191 06 50 191 06 50 191 06 50 191 06 50 191 06 50 191 06 50 191 06 50 191 06 UL Rec. Size 27 x 60 mm with striker pin Weight Pack (kg/100) 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 10 10 10 10 10 10 10 10 10 10 10 10 10 10 with striker pin A 2.36 ” (60 mm) B 1.06 ” (27 mm) Cmin 0.28 ” (7 mm) D 0.19 ” (4.9 mm) URDC 5 URDC FUSES DC-APPLICATION / TRACTION FUSE A B Rated voltage DC 1000 V Rated current Part No. 6A 8A 10 A 12 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A 90 080 10 90 080 10 90 080 10 90 080 10 90 080 10 90 080 10 90 080 10 90 080 10 90 080 10 90 080 10 90 080 10 5.00 ” (127 mm) 0.80 ” (20 mm) URDC 6 UL Rec. Size 20 x 127 mm with indicator Weight Pack (kg/100) 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 12 12 12 12 12 12 12 12 12 12 12 URDC FUSES DC-APPLICATION / TRACTION FUSE Rated voltage DC 1000 V Rated current Part No. 6A 8A 10 A 12 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A 90 082 10 90 082 10 90 082 10 90 082 10 90 082 10 90 082 10 90 082 10 90 082 10 90 082 10 90 082 10 90 082 10 UL Rec. Size 20 x 127 mm with striker pin Weight Pack (kg/100) 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 12 12 12 12 12 12 12 12 12 12 12 A B C(min) D 5.00 ” (127 mm) 0.80 ” (20 mm) 0.28 ” (7 mm) 0.20 ” (4.9 mm) URDC 7 URDC FUSES DC-APPLICATION / TRACTION FUSE A B C(min) D Rated voltage DC 1500 V Rated current Part No. 5A 6A 8A 10 A 12 A 16 A 20 A 25 A 32 A 40 A 90 081 10 90 081 10 90 081 10 90 081 10 90 081 10 90 081 10 90 081 10 90 081 10 90 081 10 90 081 10 5.00 ” (127 mm) 0.80 ” (20 mm) 0.28 ” (7 mm) 0.20 ” (4.9 mm) URDC 8 UL Rec. Size 20 x 127 mm with striker pin Weight Pack (kg/100) 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 12 12 12 12 12 12 12 12 12 12 URDC FUSES DC-APPLICATION / TRACTION FUSE Rated voltage DC 1500 V Rated current Part No. 6A 8A 10 A 12 A 16 A 20 A 25 A 32 A 90 090 10 90 090 10 90 090 10 90 090 10 90 090 10 90 090 10 90 090 10 90 090 10 UL Rec. Size 20 x 190 mm Weight Pack (kg/100) 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0 12 12 12 12 12 12 12 12 A B 7.48 ” (190 mm) 0.80 ” (20 mm) URDC 9 URDC FUSES DC-APPLICATION / TRACTION FUSE A B C(min) D Rated voltage DC 1500 V Rated current Part No. 6A 8A 10 A 12 A 16 A 20 A 25 A 32 A 90 092 10 90 092 10 90 092 10 90 092 10 90 092 10 90 092 10 90 092 10 90 092 10 7.48 ” (190 mm) 0.80 ” (20 mm) 0.28 ” (7 mm) 0.20 ” (4.9 mm) URDC 10 with striker pin UL Rec. Size 20 x 190 mm Weight ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ 26.0 26.0 26.0 26.0 26.0 26.0 26.0 26.0 Pack (kg/100) 12 12 12 12 12 12 12 12 URDC FUSES DC-APPLICATION / TRACTION FUSE Rated voltage DC 5000 V Rated current Part No. 200 A 250 A 315 A 350 A 90 200 20 90 200 20 90 200 20 90 200 20 UL Rec. Size SQB-5000 Bolted Contact Weight Pack (kg/1) 3.54 3.54 3.54 3.54 1 1 1 1 A B C D E F H I J L 14.50 ” (368 mm) 2.36 ” (60 mm) 0.35 ” (9 mm) 2.56 ” (65 mm) 15.50 ” (394 mm) 0.12 ” (3 mm) 2.80 ” (71 mm) 0.50 ” (13 mm) 0.35 ” (9 mm) 16.38 ” (416 mm) URDC 11 URDC FUSES DC-APPLICATION / TRACTION FUSE A B C D E F G H I J L Rated voltage DC 5000 V Rated current Part No. 400 A 500 A 630 A 700 A 90 210 20 90 210 20 90 210 20 90 210 20 14.50 ” (368 mm) 2.36 ” (60 mm) 1.10 ” (28 mm) 2.56 ” (65 mm) 15.50 ” (394 mm) 0.24 ” (6 mm) 2.90 ” (74 mm) 5.60 ” (142 mm) 0.50 ” (13 mm) 0.35 ” (9 mm) 16.38 ” (416 mm) URDC 12 UL Rec. Size SQB-5000 Bolted Contact Weight Pack (kg/1) 7.08 7.08 7.08 7.08 1 1 1 1 URDC FUSES DC-APPLICATION / TRACTION FUSE Rated voltage DC 1000 V Rated current Part No. 800 A 90 083 10 UL Rec. Size NH 4 Weight Pack (kg/1) 4.0 1 A B C D E F K L 6.30 ” (160 mm) 1.97 ” (50 mm) 0.70 ” (18 mm) 3.98 ” (101 mm) 4.25 ” (108 mm) 0.30 ” (8 mm) 8.27 ” (210 mm) 10.30 ” (262 mm) URDC 13 URDC FUSES DC-APPLICATION / TRACTION FUSE A(max) B C D E F G H I L Rated voltage DC 750 V Rated current Part No. 32 A 40 A 50 A 63 A 80 A 100 A 125 A 160 A 20 556 04 20 556 04 20 556 04 20 556 04 20 556 04 20 556 04 20 556 04 20 556 04 2.95 ” (75 mm) 0.80 ” (20 mm) 2.56 ” (65 mm) 1.65 ” (42 mm) 2.03 ” (51.5 mm) 0.24 ” (6 mm) 1.57 ” (40 mm) 2.52 ” (64 mm) 0.55 ” (14 mm) 5.30 ” (135 mm) URDC 14 UL Rec. Size NH 1 topindicator Weight Pack (kg/100) 27.0 27.0 27.0 27.0 27.0 27.0 27.0 27.0 3 3 3 3 3 3 3 3 Electrical Characteristics Size 14 x 51 mm FUSES Rated voltage DC 700 V Rated current Part No. Power Loss 6A 8A 10 A 12 A 16 A 20 A 25 A 30 A 35 A 40 A 50 A 50 118 06 50 118 06 50 118 06 50 118 06 50 118 06 50 118 06 50 118 06 50 118 06 50 118 06 50 118 06 50 118 06 1.3 1.7 2.6 3.1 4.7 6.0 7.6 9.8 10.3 11.2 12.6 Operating class aR Pre-arcing l2t-value A2s URDC Rated braking capacity 50 kA Total l2t-value @ 700 V DC A2s 2 2.9 3.9 6.5 8 12 20 32 72 103 128 12 17 25 41 52 70 130 190 430 620 770 Time / Current Characteristics Virtual Pre-arcing Time t(s) Arc Voltage Diagram DC-Application UL L VDC R Reduction factor for power loss KW UB UB IB VDC VDC IN RMS Prospective Current I(A) URDC 15 URDC Electrical Characteristics FUSES Size 14 x 51 mm Rated voltage DC 700 V Operating class aR Rated current Part No. Power Loss Pre-arcing l2t-value A2s Total l2t-value @ 700 V DC A2s 10 A 12 A 16 A 20 A 25 A 32 A 40 A 50 A 50 201 06 50 201 06 50 201 06 50 201 06 50 201 06 50 201 06 50 201 06 50 201 06 1.1 1.2 2.0 2.3 3.1 4.1 4.6 7.0 12 12 32 63 82 130 250 330 67 120 190 360 480 740 1,460 1,900 Rated braking capacity 30 kA Time / Current Characteristics Virtual Pre-arcing Time t(s) Arc Voltage Diagram DC-Application UL L VDC R Reduction factor for power loss KW UB UB IB VDC VDC IN URDC 16 RMS Prospective Current I(A) Electrical Characteristics Size 27 x 60 mm FUSES Rated voltage DC 660 V Operating class gR URDC Rated braking capacity 50 kA Rated current Part No. without striker Part No. with striker pin Power Loss A2s Pre-arcing l2t-value A2s Total l2t-value @ 660 V DC A2s 8A 10 A 12 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A 80 A 100 A 110 A 50 190 06 50 190 06 50 190 06 50 190 06 50 190 06 50 190 06 50 190 06 50 190 06 50 190 06 50 190 06 50 190 06 50 190 06 50 190 06 50 191 06 50 191 06 50 191 06 50 191 06 50 191 06 50 191 06 50 191 06 50 191 06 50 191 06 50 191 06 50 191 06 50 191 06 50 191 06 2.0 2.2 2.7 3.1 3.5 3.9 4.6 6.6 7.5 8.9 10.9 13.5 14.2 4 8 12 32 62 130 250 420 620 1,200 2,100 3,500 4,600 20 40 60 160 310 650 1,250 2,100 3,100 6,000 10,500 17,500 23,000 Time / Current Characteristics Virtual Pre-arcing Time t(s) Arc Voltage Diagram DC-Application UL L VDC R Reduction factor for power loss KW UB UB IB VDC VDC IN RMS Prospective Current I(A) URDC 17 URDC Electrical Characteristics FUSES Size 20 x 127 mm Rated voltage DC 1000 V Operating class gR Rated breaking capacity 100 kA Rated current Part No. with indicator Part No. with striker pin Power loss W Pre-arcing l2t-value A2s Total l2t-value @ 1000 V DC A2s 6A 8A 10 A 12 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A 90 080 10 90 080 10 90 080 10 90 080 10 90 080 10 90 080 10 90 080 10 90 080 10 90 080 10 90 080 10 90 080 10 90 082 10 90 082 10 90 082 10 90 082 10 90 082 10 90 082 10 90 082 10 90 082 10 90 082 10 90 082 10 90 082 10 3.0 3.2 3.4 4.6 5.7 6.8 8.1 10.0 12.0 13.2 17.7 3 7 13 20 52 82 118 184 472 737 1,311 17 42 75 120 300 470 670 1,050 2,700 4,200 7,500 Time / Current Characteristics Virtual Pre-arcing Time t(s) Arc Voltage Diagram DC-Application UL L VDC R Reduction factor for power loss KW UB UB IB VDC VDC IN URDC 18 RMS Prospective Current I(A) Electrical Characteristics Size 20 x 127 mm FUSES Rated voltage DC 1500 V Rated current Part No. with striker pin Power Loss 6A 8A 10 A 12 A 16 A 20 A 25 A 32 A 40 A 90 081 10 90 081 10 90 081 10 90 081 10 90 081 10 90 081 10 90 081 10 90 081 10 90 081 10 3 3.2 3.4 3.6 4.6 5.5 6.9 8 9.4 Operating class gR Pre-arcing l2t-value A2s URDC Rated braking capacity 30 kA Total l2t-value @ 1500 V DC A2s 3 7.4 13 30 52 90 149 237 597 18 44 80 180 320 550 900 1,420 3,600 Time / Current Characteristics Virtual Pre-arcing Time t(s) Arc Voltage Diagram DC-Application UL L VDC R Reduction factor for power loss KW UB UB IB VDC VDC IN RMS Prospective Current I(A) URDC 19 URDC Electrical Characteristics FUSES Size 20 x 190 mm Rated voltage DC 1500 V Operating class gR Rated current Part No. without indicator Part No. with striker pin Power loss W 6A 8A 10 A 12 A 16 A 20 A 25 A 32 A 90 090 10 90 090 10 90 090 10 90 090 10 90 090 10 90 090 10 90 090 10 90 090 10 90 092 10 90 092 10 90 092 10 90 092 10 90 092 10 90 092 10 90 092 10 90 092 10 3.1 4.1 4.4 4.7 6.2 7.6 8.1 9.7 Pre-arcing l2t-value A2s 7.4 13 30 53 90 150 240 600 Rated breaking capacity 60 kA Total l2t-value @ 1500 V DC A2s 44 80 180 320 550 900 1,400 3,600 Time / Current Characteristics Virtual Pre-arcing Time t(s) Arc Voltage Diagram DC-Application UL L VDC R Reduction factor for power loss KW UB UB IB VDC VDC IN URDC 20 RMS Prospective Current I(A) Electrical Characteristics Size SQB-5000 Rated voltage DC 5000 V FUSES Operating class UR Rated current Part No. Power Loss Pre-arcing l2t-value A2s Total l2t-value @ 5000 V DC A2s 200 A 250 A 315 A 350 A 400 A* 500 A* 630 A* 700 A* 90 200 20 90 200 20 90 200 20 90 200 20 90 210 20 90 210 20 90 210 20 90 210 20 218 229 238 278 460 481 505 584 17,000 30,000 55,000 77,000 68,000 120,000 220,000 308,000 83,000 144,000 260,000 354,000 332,000 576,000 1,040,000 1,416,000 URDC Rated braking capacity 30 kA * Double Body Time / Current Characteristics Virtual Pre-arcing Time t(s) RMS Prospective Current I(A) URDC 21 URDC Electrical Characteristics FUSES Size NH 4 Rated voltage DC 1000 V Operating class gF Rated breaking capacity 40 kA Rated current Part No. Power Loss Pre-arcing l2t-value A2s Total l2t-value @ 1000 V DC = 15 ms A2s 800 A 90 083 10 124 1,030,000 2,900,000 Time / Current Characteristics Virtual Pre-arcing Time t(s) RMS Prospective Current URDC 22 I(A) Electrical Characteristics Size NH 1 FUSES Rated voltage DC 750 V Operating class UR · gR Rated current Part No. with topindicator Power Loss Pre-arcing l2t-value A2s Total l2t-value @ 750 V DC A2s 32 A 40 A 50 A 63 A 80 A 100 A 125 A 160 A 20 556 04 20 556 04 20 556 04 20 556 04 20 556 04 20 556 04 20 556 04 20 556 04 5.9 7.1 8.6 10 12 15 19 23 100 180 290 410 740 1,300 2,500 3,700 800 1,400 2,200 3,200 5,700 10,000 19,000 29,000 URDC Rated braking capacity 50 kA Time / Current Characteristics Virtual Pre-arcing Time t(s) Arc Voltage Diagram UL Reduction factor for power loss KW VDC UB IB VDC IN RMS Prospective Current I(A) URDC 23