Panel SCCR 50kA RMS Symmetrical 480V Maximum • • – • 4 • Short-Circuit Current Rating – SCCR: – The perspective or maximum symmetrical fault current at a nominal voltage to which an apparatus or system is able to be connected without sustaining damage exceeding the defined acceptance criteria. 5 SCCR of Components or Combinations In UL 508A, the term short circuit current rating, refers to either: • Overcurrent Protective Devices (Interrupting Ratings) • Power components short circuit current ratings or • Overcurrent Protective Device Combinations of the two Power components 6 • – Available Fault: 40kA @ 480V 7 52.2kA Available 460 Volt X 200 A 100 A 20 feet 3 – 1/phase 4/0 AWG Cu THW wire In conduit X 20 feet 2 – 1/phase 1000kcmil Cu wire THW in conduit 60 feet 3 – 1/phase #2 Cu wire THW in conduit X X 42.6kA Industrial Control Panel A 450 A X Industrial Control Panel B System studies are used to determine the available fault at any specific electrical location 13.4kA Industrial Control Panel C 44.4kA 4.0kA Isolation Transformer 175 kVA 460V primary 460 V secondary Z=5% # of Occurrences Survey of 300 Industrial Installations 5 10 25 50 Available Fault Level @ 480V (kA) Installation Fault Levels 100 UL 508A Supplement SB Determining Panel Short Circuit Current Ratings 10 How to determine SCCR of a panel? Determining SCCR’s 3 Basic Steps SB4.2.1 Individual Power Circuit Components SB4.2.1 Individual Power Circuit Components – – SB4.2.2 Establish SCCR of Components 100-C Contactor Nameplate & Instruction Sheet PowerFlex 70 Drive User Manual SB4.2.2 Establish SCCR of Components 100-C Contactor Nameplate Installation Sheet SB4.2.2 – Establish SCCR of Components 100-C Contactor Nameplate & Instruction Sheet PowerFlex 70 Drive User Manual Table SB4.1 Unmarked Components • 508A SB - Table SB4.1 – “Assumed” SCCR’s – Line up with UL minimum test SC test requirements to attain listing – These minimum ratings limit “high fault” panel ratings – High Fault SCCR’s on all components & combinations are top priority SB4.2.2 Establish SCCR of Components • xxkA SCC Available – “Current Limiting” Device in Feeder – xxkA Ip Letthrough – • Use of high fault rated components virtually eliminates the need to apply the current limiting provisions! Branch Circuit PD Motor Controller xxkA SCCR “Feeder Circuit” Definition • “Feeder Circuit” covers all power conductors and components from incoming feeder disconnect, …. to the line side of the last branch circuit protective device (BCPD). “Feeder Circuit” “Branch” CPD “Branch Circuit” Definition • “Branch Circuit” covers all power conductors and components from the load-side of the branch circuit, …. to the controller load-side connections. “Branch Circuit” “Branch” CPD • Terms used for protection devices: – Over-current Protection Device (OPD) – Branch Circuit Protection Device (BCPD) 100kA 65kA 100kA 65kA 65kA 70kA 100kA 100kA 65kA Use the lowest of the ratings of any branch component or branch protective device to determine branch rating. 70kA 65kA 100kA 200kA 100kA 65kA 70kA 65kA • • – – • 100kA 200kA 100kA • 65kA Panel rating is 65kA. 70kA 65kA NEC Article 409.110 now requires Industrial Control Panels to be marked with Short Circuit Current Ratings Available Fault: 40kA @ 480V 100kA 100kA 65kA Panel SCCR 65kA rms Symmetrical 480V 70kA 65kA Available Fault: 40kA @ 480V Panel SCCR 65kA rms Symmetrical 480V # of Occurrences Survey of 300 Industrial Installations 5 10 25 50 Available Fault Level @ 480V (kA) 100 Use of Power Transformers with Isolated Secondary OPD SCCR SB4.3.1 Current Limiting w/ Power Transformers SB4.3.1 For branch circuits supplied by a power transformer with an isolated secondary winding, the short-circuit current rating on the line side of the transformer shall be one of the following: a) For a power transformer rated not more than 10 kVA, and where the short circuit current rating of all components in the secondary circuit are not less than 5 kA, the short-circuit current rating of the primary over-current protective device (OPD) is assigned to the line side of the power transformer circuit. Power Transformer (10 kVA max meeting above) The SCCR of the OPD must be equal or greater than the Panel SCCR OPD SCCR 10 kVA Max All secondary components must have a SCCR > 5kA to maintain SCCR of OPD SB4.3.1 Current Limiting w/ Power Transformers OPD SCCR Power Transformer (5 kVA max meeting above) The SCCR of the OPD must be equal or greater than the Panel SCCR Other Transformer The SCCR of the circuit is equal to lowest rated secondary component and must be equal or greater than the Panel SCCR. 5 kVA Max, 120V Sec. All secondary components must have a SCCR > 2kA to maintain SCCR of OPD 65kA SCC Available Feeder CB “Current Limiting” 65kA SCCR ??kA Ip Letthrough This is what we are evaluating Branch Circuit PD 65kA SCCR Motor Controller 18kA SCCR 65kA SCC Available Feeder CB “Current Limiting” 65kA SCCR ??kA Ip Letthrough Branch Circuit PD 100kA SCCR Motor Controller 18kA SCCR Current Limitation UL Listed Circuit Breakers 17kA Let Through 65kA Available “Current Limiting Circuit Breakers” 65kA SCC Available 65kA Feeder CB “Current Limiting” 65kA SCCR 17kA Ip Letthrough Branch Circuit PD 100kA SCCR Feeder Circuit Protective Device limits branch SCCR to 65kA. Motor Controller 18kA SCCR 65kA SCC Available 65kA Feeder CB “Current Limiting” 100kA SCCR 17kA Ip Letthrough Branch Circuit PD 65kA SCCR Branch Circuit Protective Device limits Branch SCCR to 65kA Motor Controller 18kA SCCR 65kA SCC Available Feeder CB “Current Limiting” 65kA SCCR 17kA Ip Letthrough 10kA Motor Controller limits branch SCCR to 10kA. Note: Branch does not meet available fault current. Branch Circuit PD 65kA SCCR Motor Controller 10kA SCCR 65kA SCC Available Feeder Fuse Switch 200kA SCCR 60A Class J ??kA Ip Letthrough Branch Circuit PD 200kA SCCR Motor Controller 10kA SCCR 65kA SCC Available Feeder Fuse Switch 200kA SCCR 60A Class J ??kA Ip Letthrough Branch Circuit PD 200kA SCCR Motor Controller 10kA SCCR Current Limitation UL Listed Fuses 65kA available Must use 100kA or 200kA columns “Current Limiting Fuses” Current Limitation UL Listed Fuses 16kA Let Through at 200kA 10kA Let Through at 100kA Using 100kA limits let through to < 10kA needed for branch components “Current Limiting Fuses” 65kA SCC Available 100kA Feeder Fuse Switch 200kA SCCR 60A Class J 10kA Ip Letthrough Branch Circuit PD 200kA SCCR SCCR of the feeder fuse rating per Table SB4.2 is 100kA to limit the feeder let through below the motor controller SCCR. Branch SCCR is 100kA. Motor Controller 10kA SCCR 65kA SCC Available 65kA Feeder Fuse Switch 200kA SCCR 60A Class J 10kA Ip Letthrough As in previous example the feeder fuse has a SCCR rating of 100kA. The branch circuit protective device limits rating. Branch SCCR is 65kA Branch Circuit PD 65kA SCCR Motor Controller 10kA SCCR 65kA SCC Available Feeder Fuse Switch 200kA SCCR 60A Class J 10kA Ip Letthrough Feeder let through current exceeds motor controller SCCR. Current limiting does not apply. Branch SCCR remains at 5kA. Note: Branch does not meet available fault current. Branch Circuit PD 200kA SCCR Motor Controller 5kA SCCR 5kA 25kA Available SCCR: 100kA max • Feeder “low” letthru affect on the Branch – Motor Controller SCCR is 10kA – Let through of feeder fuse is 8kA at 50kA available 25kA Available SCCR: 50kA 25kA Available Notes: • All BCPD’s must cover the available fault level • The SCCR of all BCPDs must be > 25kA • Cannot use Feeder letthrough current limiting to use BCPDs with an SCCR rating less than the available fault •Panel rating is 25kA SCCR: 25kA Sizing/Coordination issues 10kA Standard Fault Motor Controller = 51 hp minimum! Branch Circuit Solutions 60 61 - SCCR: 65kA @ 460V - 3C Starters w/ UL MCP - Type “2” Coordination 62 Global Voltages: 220V, 380..400V, 415V, 440V, 525V, 690V 50Hz 200-208V, 230V, 460V, 575V 60Hz Short Circuit Performance: 70 & 100kA Type 1, Type 2 Coordination Branch Protection Devices: Fuses & Circuit Breakers Soft-Starters: (1..1,200A) SMC-3 SMC-50 SMC Flex Starting Modes: Line & Delta Connected Motors Standard & Heavy Duty SMC-3 & SMC Flex Line Connected Delta Connected 1 1 3 SMC-50 3 5 Line Connected 1 5 3 BCPD Fused Disconnect Delta Connected 1 5 3 BCPD Fused Disconnect BCPD Fused Disconnect Fuse SCPD K1M Input K1M Input K1M Input K1M Input Terminal Block SCR Fuse SCR Fuse SCR Fuse SMC-3 R SMC-3 SCR Fuse By-pass Starter R SMC-50 K2M Output M 3~ 5 K2M Output K2M Output M 3~ SMC 50 M 3~ K2M Output M 3~ By-pass Starter - Short-circuit Coordination Starter Type: Soft-starter - Delta Connected Motors Heavy Duty Rating - AC53a Fuses + Line Contactors + SMC-50 UL/CSA Class J Fuses, Current Limiting S.C. Protective Device: Line Contactor: Soft-starter: Rated Operational Voltage: Test Voltage: Rated Conditional S.C. Current (Iq): Level of S.C. Coordination: SCCR: 100kA @ 460V UL Fuse Protection Normal Duty Starting Type “2” Coordination 1 3 5 BCPD Fused Disconnect K1M Input Distribution Block SCR Fuse 100-C, 100-D (100S-C, 100S-D) SMC-50 Smart Motor Controller 460V 60Hz (480V Line) 600V 60Hz 100kA (rms sym.) Type "1" or "2" per IEC 60947-4 UL 508 High Fault SCCR R By-pass Starter SMC-50 K2M Output M 3~ 3 ph Motor 1500 rpm Cat. No. 1) SMC-50 (Heavy Duty) Thermal Utilization Setting Category Branch Circuit Protection Device - Fuse App. Current Max. Current Disconnect Switch Class Rating Rating Cat. No. IEC 60947-2 3) (A) [A] Class J & L Fuses Cat. No. Contactor Cat. No. Bypass Starter 6) OLR Cat. No. Adj range SCR Fuse (Optional) IEC Coordination Max Current Coordination Class Rating Type 4) 4) 5) [A] 6) [A] 52 150-SB2NBD 52 - 155 AC53a: 3.5-30: 99-1 J 90 400 194R-J100-1753 1492-BG 100-C72... 100-C72... 193-EEGE 18 - 90 A70QS 175 50 62 150-SB2NBD 52 - 155 AC53a: 3.5-30: 99-1 J 100 400 194R-J200-1753 1492-BG 100-C72... 100-C72... 193-EEGE 18 - 90 A70QS 175 60 75 77 96 150-SB2NBD 150-SB2NBD 52 - 155 52 - 155 AC53a: 3.5-30: 99-1 AC53a: 3.5-30: 99-1 J J 125 150 400 400 194R-J200-1753 194R-J200-1753 1492-BG 1492-BG 100-C85… 100-C97… 100-C85… 100-C97… 193-EEGE 193-EEVE 18 - 90 60 - 120 A70QS A70QS 175 175 8) 100 124 150-SB2NBD 52 - 155 AC53a: 3.5-30: 99-1 J 200 400 194R-J200-1753 1492-BG 100-D140… 100-D140… 193-EEHF 30 - 150 A70QS 175 8) 125 156 150-SB3NBD 65 - 190 AC53a: 3.5-30: 99-1 J 250 500 194R-J400-1753 1492-BG 100-D180… 100-D180… 193-EEJF 40 - 200 A70QS 200 8) 150 200 180 240 150-SB3NBD 150-SB4NBD 65 - 190 82 - 242 AC53a: 3.5-30: 99-1 AC53a: 3.5-30: 99-1 J J 300 400 500 600 194R-J400-1753 194R-J400-1753 1492-BG 1492-BG 100-D180… 100-D250… 100-D180… 100-D250… 193-EEJF 193-EEKG 40 - 200 60 - 300 A70QS A70QS 200 250 250 302 150-SC1NBD 104 - 311 AC53a: 3.5-30: 99-1 J 500 800 194R-J600-1753 1353703 9) 100-D300… 100-D300… 193-EEKG 60 - 300 A70QS 350 8) 300 350 361 414 150-SC2NBD 150-SC3NBD 122 - 363 151 - 450 AC53a: 3.5-30: 99-1 AC53a: 3.5-30: 99-1 J L 600 600 1,000 1,200 194R-J600-1753 194R-L800-1753 1353703 9) 1353703 9) 100-D420… 100-D420… 100-D420… 100-D420… 193-EELG 193-EELG 100 - 500 100 - 500 A70QS A70QS 400 450 8) 400 477 150-SD1NBD 186 - 554 AC53a: 3.5-30: 99-1 L 800 1,200 194R-L800-1753 1352702 9) 100-D630… 100-D630… 193-EEMH 120 - 600 A70QS 500 Type 1 42kA 450 515 150-SD1NBD 210 - 625 AC53a: 3.5-30: 99-1 L 900 1,200 194R-L1200-1753 1352702 9) 100-D630… 100-D630… 193-EEMH 120 - 600 A70QS 500 Type 1 42kA 500 600 590 708 150-SD2NBD 150-SD3NBD 210 - 625 243 - 727 AC53a: 3.5-30: 99-1 AC53a: 3.5-30: 99-1 L L 1,000 1,200 1,600 2,000 194R-L1200-1753 194R-L1200-1753 1352702 9) 1352702 9) 100-D630… 100-D860… 100-D630… 100-D860… 193-EEMH 193-EENH 120 - 600 160 - 800 A70QS A70QS 600 700 Type 1 Type 1 42kA 42kA [A] [A] Line Contactor Input/Output Cat. No. 40 [HP] 2) Dist Block Note: Heavy Duty Ratings - AC53a: Typical applications include centrifugal fans, crushers, mixers, long conveyors, etc. Start NOT TO EXCEED: 350% of the motor FLA, 30 sec. start time, 99% on-load factor, 1 start per hour, with 50 °C surrounding air ambient temperature. Refer to Estimation & Thermal Selection Wizards to ensure the SMC selection meets the application requirements. See http://ab.rockwellautomation.com/Motor-Control/Soft-Starters Note: Heavy Duty Starting may require upsizing of the fuse and/or line contactors and bypass starter. 7) Remark 8) 8) Type 2 8) 8) Type 2 8) 8) Global Voltages: 220V, 380..400V, 415V, 440V, 525V, 690V 50Hz 230/240V, 460/480, 575/600V 60Hz Short Circuit Performance: 65 & 100kA IEC Type 1 & 2 Coordination Branch Protection Devices: Fuses & Circuit Breakers (MCCB, MPCB) PF Drives: (1..800A) PowerFlex 520 Series PowerFlex 4/4M PowerFlex 750 Series Circuit Variables: Circuit Protection Components Power/Line Conditioning Components Control Components Short-circuit Coordination Starter Type: S.C. Protective Device: Drive Ratings - Normal Duty 2) Motor Ratings 3 ph [HP] 1500 rpm [A] 1) Input Output 5 kVA [A] [A] w/ EMC Filter Cat. No. Cat. No. K1M Input Line Reactor Disconnect Switch Max. Fuse Size UL Class - M 3~ 3 1 SCPD - Fuse w/o EMC Filter K2M Output PF 525 R Input/Output Contactor: Bypass Starters: Rated Operational Voltage: Test Voltage: Rated Conditional S.C. Current (Iq): Level of S.C. Coordination: Line Reactor Fuse SCPD AC Variable Frequency Drive PowerFlex 525 UL/CSA Class J or T Fuses, Current Limiting Standard Fuse Selection for Component Sizing 100-C, 100S-C 100-C, 100S-C and 193-E1 Plus, E3 & E3 Plus 460V 60Hz (480V Line) 480V 60Hz 100kA (rms sym.) Type "1" or "2" per IEC 60947-4 [A] By-pass Starter Contactor Bypass Starter 7) IEC Coordination Input Output Contactor Cat. No. Cat. No. Cat. No. Cat. No Cat. No Adj range 4) 5) 5) 5) 6) [A] Remark 3) Input/Output OLR Coordination Type 1/2 1.1 1.7 1.9 1.4 25B-D1P4N104 25B-D1P4N114 J, T 6 194R-J30-1753 1321-3RA1-C/B 100-C09… 100-C09… 100-C09… 193-EECB 1.0 - 5.0 --- 3/4 1.6 2.9 3.2 2.3 25B-D2P3N104 25B-D2P3N114 J, T 6 194R-J30-1753 1321-3RA2-A/A 100-C09… 100-C09… 100-C09… 193-EECB 1.0 - 5.0 --- 1 2.1 2.9 3.2 2.3 25B-D2P3N104 25B-D2P3N114 J, T 10 194R-J30-1753 1321-3RA2-A/A 100-C09… 100-C09… 100-C09… 193-EECB 1.0 - 5.0 --- 1 1/2 3.0 5.2 5.7 4.0 25B-D4P0N104 25B-D4P0N114 J, T 10 194R-J30-1753 1321-3RA4-B/B 100-C09… 100-C09… 100-C09… 193-EECB 1.0 - 5.0 --- 2 3.4 5.2 5.7 4.0 25B-D4P0N104 25B-D4P0N114 J, T 15 194R-J30-1753 1321-3RA4-B/B 100-C09… 100-C09… 100-C09… 193-EECB 1.0 - 5.0 --- 3 4.8 6.9 7.4 6.0 25B-D6P0N104 25B-D6P0N114 J, T 15 194R-J30-1753 1321-3RA8-C/C 100-C09… 100-C09… 100-C09… 193-EECB 1.0 - 5.0 5 7.6 12.6 13.8 10.5 25B-D010N104 25B-D010N114 J, T 30 194R-J30-1753 1321-3RA8-B/B 100-C16… 100-C16… 100-C16… 193-EEDB 3.2 - 16 7 1/2 11 14.1 15.4 13.0 25B-D013N104 25B-D013N114 J, T 35 194R-J60-1753 1321-3RA12-B/B 100-C23… 100-C23… 100-C23… 193-EEDB 3.2 - 16 --- 10 14 16.8 18.4 17.0 25B-D017N104 25B-D017N114 J, T 40 194R-J60-1753 1321-3RA18-B/B 100-C23… 100-C23… 100-C23… 193-EEEB 5.4 - 27 --- 15 21 24.1 26.4 24.0 25B-D024N104 25B-D024N114 J, T 60 194R-J60-1753 1321-3RA25-B/B 100-C43… 100-C43… 100-C43… 193-EEFD 9.0 - 45 --- 20 27 30.2 33.0 30.0 25B-D030N104 25B-D030N114 J, T 70 194R-J100-1753 1321-3RA25-B/B 100-C43… 100-C43… 100-C43… 193-EEFD 9.0 - 45 --- 25 34 30.8 33.7 37.0 --- 25B-D037N114 J, T 70 194R-J100-1753 1321-3RA35-B/B 100-C43… 100-C43… 100-C43… 193-EEFD 9.0 - 45 --- 30 40 35.6 38.9 43.0 --- 25B-D043N114 J, T 80 194R-J100-1753 1321-3RA45-B/B 100-C60… 100-C60… 100-C60… 193-EEGE 18 - 90 --- Drive Ratings - Heavy Duty 2) Motor Ratings 3 ph [HP] 1500 rpm [A] 1) Input Output kVA [A] [A] SCPD - Fuse w/o EMC Filter w/ EMC Filter Cat. No. Cat. No. Line Reactor Disconnect Switch Max. Fuse Size UL Class [A] 3) SCCR: 100kA @ 460V UL Fuse Protection “Standard” Fuse Sizing (Max) Normal & Heavy Duty Starting Type “2” Coordination Input/Output Contactor Bypass Starter 7) --Type 2 --- IEC Coordination Input Output Contactor OLR Coordination Cat. No. Cat. No. Cat. No. Cat. No Cat. No Adj range 4) 5) 5) 5) 6) [A] Remark Type 1/2 1.1 1.7 1.9 1.4 25B-D1P4N104 25B-D1P4N114 J, T 6 194R-J30-1753 1321-3RA1-C/B 100-C09… 100-C09… 100-C09… 193-EECB 1.0 - 5.0 --- 3/4 1.6 2.9 3.2 2.3 25B-D2P3N104 25B-D2P3N114 J, T 6 194R-J30-1753 1321-3RA2-A/A 100-C09… 100-C09… 100-C09… 193-EECB 1.0 - 5.0 --- 1 2.1 2.9 3.2 2.3 25B-D2P3N104 25B-D2P3N114 J, T 10 194R-J30-1753 1321-3RA2-A/A 100-C09… 100-C09… 100-C09… 193-EECB 1.0 - 5.0 --- 1 1/2 3.0 5.2 5.7 4.0 25B-D4P0N104 25B-D4P0N114 J, T 10 194R-J30-1753 1321-3RA4-B/B 100-C09… 100-C09… 100-C09… 193-EECB 1.0 - 5.0 --- 2 3.4 5.2 5.7 4.0 25B-D4P0N104 25B-D4P0N114 J, T 15 194R-J30-1753 1321-3RA4-B/B 100-C09… 100-C09… 100-C09… 193-EECB 1.0 - 5.0 --- 3 4.8 6.9 7.4 6.0 25B-D6P0N104 25B-D6P0N114 J, T 15 194R-J30-1753 1321-3RA8-C/C 100-C09… 100-C09… 100-C09… 193-EECB 1.0 - 5.0 5 7.6 12.6 13.8 10.5 25B-D010N104 25B-D010N114 J, T 30 194R-J30-1753 1321-3RA8-B/B 100-C16… 100-C16… 100-C16… 193-EEDB 3.2 - 16 7 1/2 11 14.1 15.4 13.0 25B-D013N104 25B-D013N114 J, T 35 194R-J60-1753 1321-3RA12-B/B 100-C23… 100-C23… 100-C23… 193-EEDB 3.2 - 16 --- 10 14 16.8 18.4 17.0 25B-D017N104 25B-D017N114 J, T 40 194R-J60-1753 1321-3RA18-B/B 100-C23… 100-C23… 100-C23… 193-EEEB 5.4 - 27 --- 15 21 24.1 26.4 24.0 25B-D024N104 25B-D024N114 J, T 60 194R-J60-1753 1321-3RA25-B/B 100-C43… 100-C43… 100-C43… 193-EEFD 9.0 - 45 --- 15 21 30.2 33.0 30.0 25B-D030N104 25B-D030N114 J, T 70 194R-J100-1753 1321-3RA25-B/B 100-C43… 100-C43… 100-C43… 193-EEFD 9.0 - 45 --- 20 27 30.8 33.7 37.0 --- 25B-D037N114 J, T 70 194R-J100-1753 1321-3RA35-B/B 100-C43… 100-C43… 100-C43… 193-EEFD 9.0 - 45 --- 25 34 35.6 38.9 43.0 --- 25B-D043N114 J, T 80 194R-J100-1753 1321-3RA45-B/B 100-C60… 100-C60… 100-C60… 193-EEGE 18 - 90 --- --Type 2 --- Global Voltages: 110V, 220..230V, 380..400V, 415V, 440V, 525V 50Hz 120V, 230/240V, 460/480, 575/600V 60Hz Short Circuit Performance: 65 & 100kA IEC Type 1 & 2 Coordination Branch Protection Devices: Fuses & Circuit Breakers (MCCB & MPCB) Servo Drives: 300/350 5000 5500 6200/6500 Circuit Variables: Circuit Protection Components Power/Line Conditioning Components Control Components - SCCR: 100kA @ 460V - UL Fuse Protection - Type “2” Coordination Short-circuit Coordination Controller Type: Servo Drives Kinetix 300/350 UL/CSA Class CC Fuses, Fast-Acting Current-Limiting Standard Fuse Selection for Component Sizing 100-C, 100S-C 460V 60Hz (480V Line) 480V 60Hz 100kA (rms sym.) Type "1" or "2" per IEC 60947-4 S.C. Protective Device: Input Contactor: Rated Operational Voltage: Test Voltage: Rated Conditional S.C. Current (Iq): Level of S.C. Coordination: Drive Ratings Continuous Output Phases RMS Input Servo Drive M 3~ 3 1 Line Filter Contactor Side Mount Rear Mount Input Isolation Coordination Cat. No. Cat. No. Cat. No. Cat. No. Type 4) 5) Voltage RMS Pk Cat. No. [kW] 1 or 3 [V] [A] [A] 1) UL Class 2) [A] 3) 2.0 1.0 3 480 2.7 4.5 2097-V34PR3 CC 10 194R-C30-1753 --- 2097-F4 100-C12… 4.0 2.0 3 480 5.5 4.5 2097-V34PR5 CC 10 194R-C30-1753 --- 2097-F5 100-C12… 6.0 3.0 3 480 7.9 22.6 2097-V34PR6 CC 20 194R-C30-1753 2097-F2 --- 100-C23… Alternate catalog number for Kinetix 350, add -LM extension 2) Maximum fuse size for UL Class CC, Bussmann KTK-R 3) Disconnect switch provides direct mounting of Class CC fuses 4) Incomplete catalog number, add coil voltage code and auxiliary contacts 5) Short Circuit Coordination between branch circuit protection device and input isolation contactor IEC Coordination Disconnect Switch [A] 1) Max. Fuse Size KTX 300 5 BCPD - Fuses Main AC Input Current Line Filter K1M Input Fuse BCPD Note: This data is subject to change by Rockwell Automation without notice. Go to www.rockwellautomation.com/go/globalsccr for latest information. Remark --- Type 2 ----- Focus on Branch Circuit Solutions: Electromechanical Starters Soft-Starters Low Voltage AC Drives Servo Drives Selection based on: Common Voltage & Frequency Common SCCR Common Level of Coordination Data subject to change: New component introductions Optimized combination ratings “Always Use Current Posted Documentation”