Bulletin: 3050IM9101 December 31, 1991 Instruction Bulletin ProductInterfacefor MICROLOGIC CircuitBreakers Type PIF-3 Class 3050 Bulletin No. 3050IM9101 December 31, 1991 TableofContents Chapter 1 – Introduction About this Manual ------------------------------------------------------------1-1 Notational Conventions ----------------------------------------------------1-1 Receiving, and Storage -------------------------------------------------------1-1 What is the Product Interface? ----------------------------------------------1-2 Chapter 2 – Specifications and Applications Product Interface Hardware--------------------------------------------------2-1 Product Interface Specifications --------------------------------------------2-3 Product Interface Applications ----------------------------------------------2-4 Local Display of Circuit Breaker Data -----------------------------------2-4 Remote Display of Circuit Breaker Data --------------------------------2-4 Local and Remote Display of Circuit Breaker Data--------------------2-4 Chapter 3 – Installation Mounting the Product Interface ---------------------------------------------3-1 Connecting to Communications Adapters ---------------------------------3-2 Connecting to the PowerLogic Communications Link ------------------3-4 Biasing the Communications Link ---------------------------------------3-6 Terminating the Communications Link ----------------------------------3-8 Connecting Control Power -------------------------------------------------3-10 AC Installation -------------------------------------------------------------3-10 DC Installation -------------------------------------------------------------3-10 Grounding the Product Interface Chasis ----------------------------------3-10 Chapter 4 – Setup and Operation Resetting the Product Interface ----------------------------------------------4-1 Setting the Baud Rate ---------------------------------------------------------4-2 Understanding Addressing ---------------------------------------------------4-2 Choosing a Base Communications Address -----------------------------4-3 Other Important Addressing Considerations ----------------------------4-4 Setting the Base Communications Address --------------------------------4-5 Setting the Number of Connected Circuit Breakers ----------------------4-6 Installing the Battery----------------------------------------------------------4-7 Initial Startup ------------------------------------------------------------------4-7 Setting the Clock and Assigning Labels and Nameplates ---------------4-7 Chapter 5 – Maintenance and Troubleshooting Replacing the Lithium Battery ----------------------------------------------5-1 Battery Specifications ------------------------------------------------------5-1 Replacing the Control Power Fuse------------------------------------------5-2 Troubleshooting ---------------------------------------------------------------5-3 Customer Service -----------------------------------------------------------5-3 Appendix A – Register Listing -------------------------------------------A-1 Appendix B – Maximum Distances for Communications ------------B-1 Appendix C – Cable Pinouts ----------------------------------------------C-1 1991 Square D. All Rights Reserved Page i Table of Contents Figures and Tables Page ii Table Figure Figure Figure Figure Figure Figure Figure Figure Table Figure Figure Figure Figure Figure 1-1 2-1 2-2 2-3 2-4 2-5 2-6 3-1 3-2 3-1 3-3 3-4 3-5 3-6 3-7 Figure Figure Figure Figure Table Figure Figure Table Table Table 3-8 3-9 3-10 4-1 4-1 4-2 5-2 5-1 A-1 A-2 Available Data -------------------------------------------------1-2 Product Interface Side View ---------------------------------2-1 Product Interface Switches -----------------------------------2-2 Product Interface Dimensions -------------------------------2-3 Local Display --------------------------------------------------2-4 Remote Display ------------------------------------------------2-5 Local & Remote Display -------------------------------------2-5 Panel Preparation ----------------------------------------------3-1 Communications Adapter Placement -----------------------3-2 Product Interface to CIM3F Connection Information ----3-3 Connecting a Comms Adapter to the Product Interface --3-3 Multiple PowerLogic Device Types on a Comm Link ---3-4 RS-485 Communication Terminal --------------------------3-5 RS-485 Communication Wiring -----------------------------3-5 Connecting the Product Interface as the First Device on a PowerLogic Communications Link ------------------3-6 RS-485 Terminator Placement -------------------------------3-8 Terminating the Product Interface---------------------------3-9 Control Power and Ground Terminal Location ----------3-10 Product Interface Switches -----------------------------------4-1 Baud Rate Settings --------------------------------------------4-2 Addressing Example ------------------------------------------4-5 Control Power Fuse Location --------------------------------5-2 Troubleshooting Table ----------------------------------------5-3 Product Interface Command Operations ------------------A-2 Product Interface Register Listing --------------------------A-3 1991 Square D All Rights Reserved Listed 4L57 Ind. Cont. Eq. COPYRIGHT NOTICE TRADEMARK NOTICE PLEASE NOTE: FCC NOTICE 1991 by Square D Company All rights reserved. This Bulletin may not be copied in whole or in part, or transferred to any other media, without the written permission of Square D Company. SY/MAX, SY/NET, SY/LINK, MICROLOGIC, and PowerLogic are registered trademarks of Square D Company. Electrical equipment should be serviced only by qualified electrical maintenance personnel, and this Instruction Bulletin should not be viewed as sufficient instruction for those who are not otherwise qualified to operate, service, or maintain the equipment discussed. Although reasonable care has been taken to provide accurate and authoritative information in this bulletin, no responsibility is assumed by Square D for any consequences arising out of the use of this material. This equipment complies with the requirements in Part 15 of FCC rules for a Class A computing device. Operation of this equipment in a residential area may cause unacceptable interference to radio and TV reception requiring the operator to take whatever steps are necessary to correct the interference. Chapter 1 Introduction Bulletin No. 3050IM9101 December 31, 1991 Chapter1–Introduction ABOUT THIS MANUAL Notational Conventions RECEIVING AND STORAGE This manual provides the information necessary to install, setup, and operate the Product Interface for MICROLOGIC Circuit Breakers (PIF-3). The document is organized into five chapters, and three appendices. The person(s) responsible for installing, applying, or operating the Product Interface should read all of this document. To find information on a specific topic, refer to the table of contents or use the table below. To See Read a general description of the Product Interface Read about specifications and typical applications Learn how to install the Product Interface Learn how to setup the Product Interface Learn how to change the battery or fuse Learn how to troubleshoot problems See a detailed listing of registers Read about maximum distances for communications See communication cable pinouts Chapter 1 Chapter 2 Chapter 3 Chapter 4 Chapter 5 Chapter 5 Appendix A Appendix B Appendix C This document uses the following notational conventions: • Bulleted Lists. Bulleted lists, such as this one, provide information but not procedural steps. • Numbered lists. Numbered lists show a sequence of steps describing a specific task. • Cross References. Cross references to other sections in the document appear in boldface and a different type face like this—See Chapter 3 Installation for more information. If the Product Interface is shipped via UPS or air freight, inspect the shipping carton for damage. If the Product Interface is to be installed soon, unpack and inspect it for damage. If damage is evident, notify the carrier to initiate a claim. You can obtain replacement equipment through your Square D distributor. For additional assistance, contact PowerLogic Customer Service at (615) 459-8591. The Product Interface uses a long-life Lithium battery to maintain the clock and non-volatile RAM during periods of control power loss. When the Product Interface is shipped via UPS or air freight, the battery is not installed. Do not install the battery until you have installed the Product Interface and are ready to apply control power. This will prevent battery drain while the Product Interface is in storage. When the Product Interface is supplied as a factory installed option in power equipment, the battery is already installed. For maximum battery life, remove the battery and re-install it when you are ready to apply control power to the Product Interface. See Chapter 5 Maintenance and Troubleshooting for instructions on battery installation. 1991 Square D. All Rights Reserved Page 1-1 Bulletin No. 3050IM9101 December 31, 1991 WHAT IS THE PRODUCT INTERFACE? Chapter 1 Introduction The PowerLogic Product Interface for MICROLOGIC circuit breakers, together with MICROLOGIC Series III A/B circuit breakers, provides an economical means to perform remote current monitoring, without the need for additional current transformers or metering equipment. In addition, the Product Interface reports a wealth of valuable historical trip data and circuit breaker data from MICROLOGIC Series III A/B circuit breakers. Table 1-1 lists the available data. The Product Interface can be mounted in QED switchboards to enable local and remote monitoring of circuit breaker data. The data from up to 32 circuit breakers can be displayed using a PowerLogic System Display for MICROLOGIC Circuit Breakers (SD-100/SD-120), or an IBM PC compatible computer equipped with PowerLogic software. Using the Square D SY/NET network, personal computers running PowerLogic software can monitor virtually any number of MICROLOGIC circuit breakers, PowerLogic Circuit Monitors, Lifegard Model 85 Transformer Temperature Controllers, and other compatible devices. Table 1-1 Available Data Real-Time Current • A, B, C Phase True RMS Currents • Ground Fault Current (Optional) Real-Time Current Values The Product Interface reports per-phase true RMS currents, allowing you to evaluate circuit loading and avoid overload conditions. And for circuit breakers equipped with a ground fault sensor, ground fault current can also be monitored. Historical Data • Date and Time of Last Trip Circuit Breaker History • Cause of Trip • Phase Currents at Trip • Ground Fault Current at Trip • # of Overload Trips • # of Short Circuit Trips • # of Ground Fault Trips Circuit Breaker Data • Breaker Type • Sensor Rating • Plug Rating • Long Time Settings: Pickup and Delay • Short Time Settings: Pickup and Delay • Instantaneous Settings • Ground Fault Settings: Pickup and Delay Page 1-2 During troubleshooting stages, the trip unit’s historical data, reported by the Product Interface, can aid in reducing further system down-time and help in preventing future electrical outages. Last trip data provided includes Cause of Last Trip, Date and Time of Last Trip, and Phase and Ground Fault Current Magnitudes at time of trip. And, to aid in preventative maintenance planning, the Product Interface reports a summary of the total number of trips for overload, short circuit and ground fault. Circuit Breaker Data and Trip Settings Circuit breaker data available through the Product Interface includes the type of circuit breaker, the sensor rating and the plug rating. In addition, the trip unit delay and pickup settings for Long Time, Short Time, Instantaneous, and Ground Fault are provided. This data allows you to compare the settings to existing records, to determine tampering or inadvertent changes to the protection functions. And using the System Display for MICROLOGIC circuit breakers with optional printer port (SD-120), you can send the data to a serial printer creating a permanent record of the circuit breaker’s settings. 1991 Square D. All Rights Reserved Chapter 2 Specifications and Applications Chapter2–Specificationsand The PowerLogic Product Interface for MICROLOGIC Circuit Breakers (PIF-3) is housed in an aluminum case designed to be mounted in power equipment. The compact Product Interface mounts in low-voltage switchboards and other small spaces. Figure 2-3 shows the overall dimensions. The terminal strip connections for communications cables and control power are housed behind a protective cover held in place by three captive screws. This cover can be removed for connection to additional circuit breakers, for changing the control power fuse, or for inspection of installed wiring. The protective cover must be securely attached at all other times. This safeguard is designed to prevent inadvertent damage to the connections. The Product Interface provides eight removable 4-position terminal plugs for connection of up to eight MICROLOGIC Series IIIA/B circuit breakers. Each circuit breaker must be connected to a communications adapter (CIM3F) for isolation and power. Each communications adapter is then connected to the appropriate terminal strip position on the side of the Product Interface. (See Figure 2-1). RS485 Communications to other devices 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 D+ GND +12V D- ADD + 1 D+ GND +12V DGND +12V DD+ GND +12V DD+ GND +12V D- MICROLOGIC CIRCUIT BREAKERS ADD + 3 ADD + 4 ADD + 5 D+ ADD + 2 SE D- ADD + 0 +12V 8 D+ GND +12V D- ADD + 6 DC AC GND 7 - N 38 IN+ 6 G 39 5 U IN- RS485 COMMS OUT+ 4 + L 40 D+ GND +12V D- ADD + 7 Cable Tie 8-32 Nut DC AC Control Power Terminal Strip FUS FUSE 250V, 2 AMP Control Power Fuse S FU E OUT- 3 Ground Terminal SHLD 2 Communications Terminal Strip 1 Cable Tie 8-32 Nut E F PRODUCT INTERFACE HARDWARE Bulletin No. 3050IM9101 December 31, 1991 Applications D+ Communications Adapters (CIM3F) 1 required for each Circuit Breaker Figure 2-1 Product Interface Side View 1991 Square D. All Rights Reserved To Micrologic Circuit Breakers (Up to eight per PIF-3) Page 2-1 Bulletin No. 3050IM9101 December 31, 1991 Chapter 2 Specifications and Applications Also located on the side of the Product Interface are a ground terminal, a control power terminal strip connector, and a control power fuse. (See Figure 2-1). The Control power is fused with a 2A 250V Slow Blow fuse. A flush mounted door on the front of the Product Interface provides access to a number of switches. (See Figure 2-2). Two ten position rotary switches are used to set the Product Interface base communications address. Another ten position rotary switch is used to set the Product Interface baud rate. A 16 position rotary switch is used to specify the number of circuit breakers connected to the Product Interface. A push button switch is used to reset the Product Interface. Chapter 4 Setup and Operation provides instructions for using these switches. Also housed behind the door is a lithium battery. This battery is used to maintain the Product Interface clock and non-volatile RAM in the event of a power loss. The front of the Product Interface contains three LEDs. Two green LEDs, labeled 12V OK and 5V OK, are lit when the Product Interface is receiving adequate control power. The red LED, labeled Battery Low, is a warning light for the lithium battery. When the red LED is lit, the battery voltage is low, and the battery must be replaced. See Chapter 5 Maintenance and Troubleshooting for instructions on replacing the battery. # of Connected Circuit Breakers Switch (+) Lithium Battery 789A 01 EF 2 BCD 3 4 56 4 56 4 56 BAUD 78 9 01 9 01 9 01 78 4 56 ADDRESS 78 23 RESET 23 Hardware Reset Switch 23 7 89 A 01 EF 2 BCD 3 4 56 4 56 23 4 56 BAUD 78 9 01 9 01 9 01 78 4 56 ADDRESS 78 23 RESET Product Interface for Micrologic Circuit Breakers 23 66 Address Switches Baud Rate Switch 12V OK Figure 2-2 Product Interface Switches Page 2-2 1991 Square D. All Rights Reserved BATTERY 5V LOW OK MADE IN USA Chapter 2 Specifications and Applications Bulletin No. 3050IM9101 December 31, 1991 PRODUCT INTERFACE SPECIFICATIONS Communications ..............................One RS-485, eight MICROLOGIC connectors Clock/Calendar ......................................Accuracy +/- 1.5 sec in 24 hours at 25° C Electrical Control Power Input: AC Nominal Voltage ....................................................................120VAC AC Operating Range ..............................................................85-132 VAC Burden ...............................................................1A @ 120VAC (132 VA) Frequency Range ................................................................47.0 to 65.0 Hz Isolation...............................................................................2000 V, 1 min. DC Operating Range ............................................................110-170 VDC Ride Through of Power loss .......................................................20 ms at 120 VAC Fusing .....................................................................................2A 250V Slow Blow +12V LED ............................................................indicates +12V power supply ok +5V LED ..................................................................indicates 5V power supply ok Battery Low LED .......................................when on, indicates low battery voltage Environmental Operating Temperature .....................................................................0 to 70° C Storage Temperature ...................................................................-40 to +85° C Humidity Rating ................................................95% RH max non-condensing Weight .......................................................................Approximately 4 lbs (1.8 kg) Dimensions .......................................................................................See Figure 2-3 R 0.250 6.4 .250 6.4 2.999 76.2 12V OK BATTERY 5V LOW OK 8.375 212.7 Product Interface for Micrologic Circuit Breakers 66 7.869 199.9 8.875 225.4 MADE IN USA .378 8.000 203.2 4.375 111.1 Dimensions in Inches Millimeters Figure 2-3 Product Interface Dimensions 1991 Square D. All Rights Reserved Page 2-3 Bulletin No. 3050IM9101 December 31, 1991 PRODUCT INTERFACE APPLICATIONS Chapter 2 Specifications and Applications The Product Interface mounts easily in Square D QED switchboards. In new equipment, any MICROLOGIC series A or B circuit breaker can communicate to the Product Interface. These include the ME, NE, PE, and SE circuit breakers. Up to 8 circuit breakers can be connected to a single Product Interface, and up to 32 circuit breakers can be monitored on a single PowerLogic communications link. Local Display of Circuit Breaker Data For local display of circuit breaker data, PowerLogic provides the System Display for MICROLOGIC Circuit Breakers (Class 3050 Types SD-100 and SD-120). The System Display can display data from up to 32 circuit breakers, and can be installed up to 10,000 feet from the farthest Product Interface. (See Appendix B for Maximum Distances). Figure 2-4 shows Product Interfaces daisy-chained to a System Display for MICROLOGIC Circuit Breakers. A PowerLogic Circuit Monitor with display typically provides metering for the Main. Remote Display of Circuit Breaker Data For remote monitoring of circuit breaker data, Product Interfaces can be connected to a personal computer equipped with PowerLogic application software. Product Interfaces, Circuit Monitors, and other PowerLogic devices can share a single RS-485 communications link. The personal computer can be located up to 10,000 feet from the farthest PowerLogic device. (See Appendix B for Maximum Distances and Baud Rates). Figure 2-5 shows a personal computer connected to Product Interfaces and other PowerLogic devices. Local and Remote Display of Circuit Breaker Data For local and remote monitoring, Product Interfaces can be connected to a PowerLogic Network Interface Module (PNIM) for connection to the SY/NET network. A PowerLogic System Display for MICROLOGIC Circuit Breakers provides local readout of circuit breaker data. A personal computer running PowerLogic software can monitor virtually any number of MICROLOGIC circuit breakers, PowerLogic Circuit Monitors, and other compatible devices. Figure 2-6 shows a system using both local and remote monitoring of circuit breaker data. System Display for MICROLOGIC CBs CM CIM3F's PIF3 PIF3 PIF3 CB CB CB CB CB CB CB CB CB Up to 32 CBs Max. Figure 2-4 Local Display Page 2-4 1991 Square D. All Rights Reserved Circuit Monitor Typically Provides Main Metering Up to 8 CBs Per Interface Chapter 2 Specifications and Applications Bulletin No. 3050IM9101 December 31, 1991 CIM3F's PIF3 PIF3 CB CB CB CB CB CB PIF85 * CM M85 Up to 8 CBs Per Interface Up to 32 Devices (CBs + CMs +M85s) Max. Figure 2-5 Remote Display System Display for MICROLOGIC CBs Network Interface CIM3F's PIF3 PIF3 CB CB CB CB CB CB PIF85 * CM M85 Up to 8 CBs Per Interface Up to 32 Devices (CBs + CMs +M85s) Max. Figure 2-6 Local & Remote Display * The PIF-85 is a PowerLogic Product Interface for the Lifeguard Model 85 Transformer Temperature Controller. The Model 85 is a temperature fan controller for Square D PowerCast and conventional dry type transformers. 1991 Square D. All Rights Reserved Page 2-5 Chapter 3 Installation Bulletin No. 3050IM9101 December 31, 1991 Chapter3–Installation MOUNTING THE PRODUCT INTERFACE The Product Interface is designed to be mounted in power equipment. When choosing a mounting location, consider the following points: • Mount the Product Interface no more than 50 feet from any circuit breaker connected to it. • Mount the Product Interface in a location that allows access to the door on its front cover. • Allow adequate clearance on the side of the Product Interface for wiring connections. • Mount the Product Interface to allow for adequate heat dissipation. If environmental conditions produce temperatures higher than the operating range, (0° C to +70° C), make provisions to bring the ambient temperature to 70° C or less. • Refer to Figure 2-3 for Product Interface Dimensions. To prepare the panel for installation, drill four 1/4" mounting holes. Figure 3-1 shows the drilling pattern. The Product Interface enclosure is equipped with slotted mounting brackets that accept four mounting screws. Secure the Product Interface to the panel using 1/4" pan head or filister head machine screws and locknuts. 3.000" R 0.25" 4 Holes 8.375" Figure 3-1 Panel Preparation 1991 Square D. All Rights Reserved Page 3-1 Bulletin No. 3050IM9101 December 31, 1991 CONNECTING TO COMMUNICATIONS ADAPTERS Chapter 3 Installation ! CAUTION HAZARD OF EQUIPMENT DAMAGE. Do not connect the Product Interface directly to circuit breakers. The Product Interface must be connected to Communications Adapters (CIM3F) which are in turn connected to circuit breakers. Failure to observe this precaution could result in damage to the circuit breaker. The Product Interface provides eight removable 4-position terminal plugs for connection of up to eight MICROLOGIC Series III A/B circuit breakers using MICROLOGIC Communications Adapters (catalog no. CIM3F). Each MICROLOGIC circuit breaker is first wired to a Communications Adapter which is then connected to the appropriate terminal strip position on the side of the Product Interface. Figure 3-2 illustrates this point. Up to 8 Circuit Breakers Circuit Breaker CIM3F Circuit Breaker CIM3F Circuit Breaker CIM3F Product Interface Figure 3-2 Communications Adapter Placement For instructions on connecting the Communications Adapter to a circuit breaker, refer to the instruction bulletin for the Communications Adapter (#48040-720-01). To wire a Communications Adapter to the Product Interface, complete the following steps: 1. The CIM3F Communications Adapter comes with a 10 foot communication cable. One end of the cable has a modular connector which plugs into the Communications Adapter. Plug this modular connector into the Communications Adapter. 2. If the 10 foot cable is too long, cut the cable to the desired length. If the 10 foot cable is not long enough, use Manhattan M3802 cable or equivalent (50 ft max). 3. The other end of the 10 foot cable has four flying leads. Expose the four cable conductors by stripping the cable sheath back 2 inches. Then strip the insulation for each conductor back 1/4 inch. Page 3-2 1991 Square D. All Rights Reserved Chapter 3 Installation Bulletin No. 3050IM9101 December 31, 1991 4. Inspect the stripped ends for stray wires to minimize the possibility of shorts across terminals. 5. The Product Interface has eight removable 4-position terminal plugs for connecting Communications Adapters. The terminal jacks are labeled “ADD+0, ADD+1, ADD+2....ADD+8”. Connect the flying leads on the 10 foot cable to the lowest available terminal plug. For example, wire the first Communications Adapter to plug “ADD+0”, the second to plug “ADD+1”, the third to plug “ADD+2”, and so on. Follow the color code shown in Table 3-1. This color code illustration also appears on the label inside the terminal strip protective cover. Figure 3-3 illustrates the connections. IMPORTANT: Follow the color codes carefully. Failure to do so will result in improper operation or damage to the Communications Adapter. Table 3-1 Product Interface to CIM3F Connection Information PIF-3 Terminal Label GND CIM3F Wire Color Black Used For +12Vdc Common +12V Red +12Vdc Supply D- Orange Serial Data D+ Blue Serial Data Product Interface Side View OUT+ 4 IN- 5 IN+ 6 GND 7 +12V 8 D- 9 10 11 12 13 14 15 16 17 18 19 20 2 D+ 10' Cable Supplied with CIM3F Removable Plug Black ADD + 0 Red Orange Blue CIM3F To Circuit Breaker GND +12V D- ADD + 1 D+ GND +12V DGND +12V DD+ MICROLOGIC C ADD + 3 D+ ADD + 2 SE 3 U 2 OUT- RS485 COMMS 1 FUS E F FUSE 250V, 2 AMP S FU E SHLD Figure 3-3 Connecting a Communications Adapter to the Product Interface 1991 Square D. All Rights Reserved Page 3-3 Bulletin No. 3050IM9101 December 31, 1991 CONNECTING TO THE POWERLOGIC COMMUNICATIONS LINK Chapter 3 Installation As in all other PowerLogic devices, the Product Interface uses an industry standard RS-485 (RS-422 compatible) electrical interface for data communications. Multiple Product Interfaces, Circuit Monitors, and other PowerLogic devices can be daisy-chained together on a single PowerLogic communications link. Figure 3-4 shows multiple device types on a communications link. The Product Interface can be connected to a communications port on: • A PowerLogic System Display for MICROLOGIC Circuit Breakers • A PowerLogic Network Interface Module (PNIM) • A personal computer equipped with a SY/LINK PC interface board All PowerLogic devices have an RS-485 communications port for connection to a PowerLogic communications link. The Product Interface uses a removable, fiveposition terminal plug labeled “RS485 COMMS” for this purpose. (See Figure 3-5). As in all other PowerLogic devices, the Product Interface requires a communication cable containing two shielded twisted pairs (Belden 8723 or equivalent). Communication cables are daisy-chained from the Product Interface’s RS-485 communications terminals to the matching RS-485 communications terminals of the next device. That is, SHLD is wired to SHLD, OUT- to OUT-, OUT+ to OUT+, IN- to IN-, and IN+ to IN+. If the Product Interface is the last device on the communications link, it must be terminated using a Multipoint Communications Terminator (MCT-485). See Terminating the Communications Link below for termination instructions. If the Product Interface is the first device on the link, it must be connected to a System Display for Micrologic CBs PNIM 0 1 CIM3F PIF3 PIF3 PIF85 CB CB M85 CB CB CB CB CM Figure 3-4 Multiple PowerLogic Device Types on a Communications Link Page 3-4 1991 Square D. All Rights Reserved Chapter 3 Installation Bulletin No. 3050IM9101 December 31, 1991 communications port using a Multipoint Communications Adapter (MCA-485). See Biasing the Communications Link below for biasing instructions. If the Product Interface is “buried” in the communications link, complete the following steps: 1. Strip back the cable sheath 2 inches on both ends of the communications cable. Then strip back the insulation for each conductor 1/4 inch. 2. Inspect the stripped ends for stray wires to minimize the possibility of shorts across terminals. 3. Connect one wire to the IN+ terminal on the Product Interface’s RS-485 5-position terminal block. Connect the other end of the same wire to the IN+ terminal of the next device. 4. Repeat step 3, connecting the IN- terminal on the Product Interface to the IN- terminal on the next device, the OUT+ terminal on the Product Interface to the OUT+ terminal on the next device, and so on. For example, to wire a Product Interface to a Circuit Monitor, connect the SHLD terminal on the Product Interface to the SHLD terminal on the Circuit Monitor, connect the OUT- terminal on the Product Interface to the OUT- terminal on the Circuit Monitor, connect the OUT+ terminal on the Product Interface to the OUT+ terminal on the Circuit Monitor, and so on. Figure 3-6 illustrates this example. RS-485 Communications Terminals Product Interface Side View 2 OUT- 3 OUT+ 4 IN- 6 7 +12V 8 D- 9 10 D+ ADD + 0 5 IN+ GND RS485 COMMS 1 SHLD GND Figure 3-5 RS-485 Communication Terminal Belden 8723 or Equivalent To Comms Terminals of Next Device SHLD SHLD OUT- OUT- OUT+ OUT+ IN- IN- IN+ IN+ PIF-3 RS-485 Terminals To Comms Terminals of Next Device CM RS-485 Terminals Figure 3-6 RS-485 Communication Wiring 1991 Square D. All Rights Reserved Page 3-5 Bulletin No. 3050IM9101 December 31, 1991 Chapter 3 Installation Biasing the Communications To ensure reliable communications, the PowerLogic communications link must be Link biased. This is done using a biasing device called a Multipoint Communications Adapter (MCA-485). The adapter is placed between the first device on the link and the communications port of the System Display, PNIM, or SY/LINK card. Figure 3-7 illustrates the installation of the adapter when the first device on the link is a Product Interface. If the first device on the link is not a Product Interface, refer to the first device’s instruction bulletin for biasing instructions. To connect the Product Interface as the first device on the PowerLogic communications link, you will need the following items: • One PowerLogic Multipoint Communications Adapter (3090 MCA-485). (This is not included with the Product Interface and must be purchased separately). • One PowerLogic cable 3090 CAB-107. (This is not included with the Product Interface and must be purchased separately). • A five position terminal block—1 provided with each Product Interface. • Belden 8723 or equivalent cable. (This is not included with the Product Interface and must be purchased separately). Figure 3-7 illustrates the wiring connections. Refer to this figure when completing the steps listed below. PRODUCT INTERFACE Belden 8723 SHLD OUTOUT+ ININ+ Terminal Block 24 SHLD 23 OUT- 22 OUT+ 21 IN- 20 IN+ CAB-107 MCA-485 To Comm port of System Display for MICROLOGIC, or PNIM, or SY/LINK Card PIF-3 RS-485 Terminals Figure 3-7 Connecting the Product Interface as the First Device on a PowerLogic Communications Link To connect the Product Interface as the first device on the PowerLogic communications link, complete the following steps: 1. Install the terminal block in a convenient location. The CAB-107 is a ten foot cable. If the terminal block must be located farther than ten feet from the PNIM, PC, or System Display, a custom cable must be built. To build a custom cable, use Belden 8723 cable and a male DB9 connector. Appendix C shows the required pinout for the CAB-107 cable. Page 3-6 1991 Square D. All Rights Reserved Chapter 3 Installation Bulletin No. 3050IM9101 December 31, 1991 2. Plug the Male end of the Multipoint Communications Adapter (MCA-485) into the communications port of the System Display (SD-100 or SD-120), PNIM, or SY/LINK board. NOTE: When connecting to a PNIM, connect the Product Interface to the top RS-422 port, labeled port 0. This port must be configured for PowerLogic mode. 3. Mark the flying leads on the CAB-107 as indicated in the table below. For example, mark the white wire, labeled 20, as “IN+”; mark the green wire, labeled 21, as “IN-”; and so on. Existing Label Wire Color Mark As 20 Green IN+ 21 White IN- 22 Red OUT+ 23 Black OUT- 24 Silver SHLD 4. Attach the Male DB-9 connector on the CAB-107 to the Multipoint Communications Adapter. 5. Connect the CAB-107 spade connectors to the terminal block. 6. Cut a length of Belden 8723 (or equivalent) cable that is long enough to reach from the terminal block to the Product Interface. Strip the cable sheath from both ends and expose 1/4" of each conductor. 7. Connect one end of the Belden 8723 (or equivalent) cable to the terminal block. 8. Connect the other end of the Belden 8723 (or equivalent) cable to the removable 5-position terminal plug (labeled RS-485 Comms) on the Product Interface. Be sure to connect the terminal accepting the IN- wire on the CAB-107 to the IN- terminal on the Product Interface, the terminal accepting the IN+ wire on the CAB-107 to the IN+ terminal on the Product Interface, and so on. NOTE An alternative to using a terminal block and a CAB-107 is to build a custom cable using Belden 8723 cable (or equivalent) and a male DB-9 connector. When building the cable, follow the CAB-107 pinout shown in Appendix C. 1991 Square D. All Rights Reserved Page 3-7 Bulletin No. 3050IM9101 December 31, 1991 Terminating the Communications Link Chapter 3 Installation To ensure reliable communications, the last device on a PowerLogic communications link must be terminated. Figure 3-8 illustrates terminator placement when the last device on the link is a Product Interface for MICROLOGIC Circuit Breakers. If the last device is not a Product Interface, refer to the last device’s instruction bulletin for termination instructions. NOTE If a communications link contains only a single device, it must be terminated. If a link contains multiple devices, as in Figure 3-8, only the last device must be terminated. To connect the Product Interface as the last device on the PowerLogic communications link, you’ll need the following items: • One PowerLogic RS-485 Multipoint Communications Terminator (3090 MCT-485). (This is not included with the Product Interface and must be purchased separately). • A five position terminal block—1 provided with each Product Interface. • Belden 8723 or equivalent cable. (Not included). Figure 3-9 illustrates proper termination. Refer to this figure when completing the steps listed below. System Display for Micrologic CBs PNIM The Communications Link Must Be Terminated at the Last Device 0 1 CIM3F PIF3 PIF3 PIF85 CB CB M85 CB CB CB CB CM Figure 3-8 RS-485 Terminator Placement Page 3-8 1991 Square D. All Rights Reserved Chapter 3 Installation Bulletin No. 3050IM9101 December 31, 1991 To connect the Product Interface as the last device on the PowerLogic communications link, complete the following steps: 1. Install the terminal block in a convenient location. 2. Cut a length of cable long enough to reach from the Product Interface to the terminal block. 3. Strip the cable sheath from both cable ends and expose 1/4" of each conductor. 4. Connect one end of the cable to the IN+, IN-, OUT+, OUT-, and SHLD terminals on the Product Interface. 5. Trace the conductor color codes and mark the cable conductors at the other end of the cable as IN+, IN-, OUT+, OUT-, and SHLD, corresponding to the RS485 COMMS terminals on the Product Interface. 6. Connect the marked conductors to the terminal block. 7. Connect the four spade connectors on the Multipoint Communications Terminator to the OUT-, OUT+, IN-, and IN+ positions on the terminal block. Product Interface (Last Device on Link) Terminal Block Terminator Belden 8723 Cable SHLD OUTOUT+ ININ+ RS-485 Terminals SHLD OUTOUT+ ININ+ Figure 3-9 Connecting the RS-485 Terminator to a Product Interface 1991 Square D. All Rights Reserved Page 3-9 Bulletin No. 3050IM9101 December 31, 1991 CONNECTING CONTROL POWER Chapter 3 Installation The Product Interface accepts either AC or DC control power. Control power connections are made to a terminal strip on the side of the Product Interface. (See Figure 3-10). The control power is fused with a 2.0 AMP slow blow fuse. See Chapter 5 for instructions on changing the fuse. IMPORTANT: In all wiring installations, wire the Product Interface according to all applicable electrical codes. AC Installation The Product Interface requires 90-132 VAC control power at 50/60 Hz. Connect the power cable to the Line (L), Neutral (N), and Ground (G) terminals as marked on the Product Interface. Use a properly sized disconnect switch as a means to remove control power from the Product Interface. DC Installation The Product Interface requires 110 - 170VDC power. Connect the power cable to the positive (+) and negative (-) terminals as marked on the Product Interface. Important: Observe proper polarity when connecting DC power. Use a properly sized disconnect switch as a means to remove control power from the Product Interface. GROUNDING THE PRODUCT INTERFACE CHASSIS The chassis ground terminal is located on the side of the Product Interface. (See Figure 3-10). Connect the chassis ground terminal to a building column or grounding electrode determined to be a “true earth” ground. Ground wire should be #14 gauge minimum. Product Interface Side View OUT+ 4 IN- D+ ADD + 0 D- 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 GND +12V D- ADD + 1 D+ GND +12V DGND +12V DD+ GND +12V DD+ GND +12V D- MICROLOGIC CIRCUIT BREAKERS ADD + 3 ADD + 4 ADD + 5 D+ ADD + 2 D+ GND +12V D- ADD + 6 DC E F AC +12V 8 - N 38 GND 7 G 39 IN+ 6 + L 40 5 SE 3 U OUT- RS485 COMMS 2 DC AC Control Power Terminal Strip FUS FUSE 250V, 2 AMP Control Power Fuse S FU E 1 Ground Terminal SHLD D+ GND D- ADD + 7 +12V D+ Figure 3-10 Control Power and Ground Terminal Location Page 3-10 1991 Square D. All Rights Reserved Chapter 4 Setup and Operation Bulletin No. 3050IM9101 December 31, 1991 Chapter4–SetupandOperation The Product Interface has five switches located behind its front access door. These switches are used to set its baud rate, set its base address, set the number of circuit breakers connected to it, and reset the Product Interface. Figure 4-1 shows the switch locations. A label on the back of the access door also shows the switch locations and their functions. This chapter describes the purpose and use of each switch. The Product Interface must be reset each time a change is made to the address, baud rate, or number of connected circuit breakers switch settings. There are two ways to reset the Product Interface: Hardware Reset, and Software (remote) Reset. To perform a hardware reset, press the Reset button located behind the access door on the front of the Product Interface. (See Figure 4-1). For instructions on performing a software reset using PowerLogic software, refer to the instruction bulletin accompanying the software. NOTE Reset the Product Interface after changing a switch setting. If you change a switch setting but fail to perform a reset, the Product Interface will not act on the new switch setting. # of Connected Circuit Breakers Switch (+) Lithium Battery 789A 01 EF 2 BCD 3 4 56 4 56 BAUD 78 9 01 9 01 9 01 78 4 56 ADDRESS 78 4 56 RESET 23 Hardware Reset Switch 23 23 7 89 A 01 EF 2 BCD 3 4 56 4 56 4 56 BAUD 78 9 01 9 01 9 01 78 4 56 ADDRESS 78 23 RESET 23 23 RESETTING THE PRODUCT INTERFACE Product Interface for Micrologic Circuit Breakers 66 Address Switches MADE IN USA Baud Rate Switch 12V OK BATTERY 5V LOW OK Figure 4-1 Product Interface Switches 1991 Square D. All Rights Reserved Page 4-1 Bulletin No. 3050IM9101 December 31, 1991 SETTING THE BAUD RATE Table 4-1 Baud Rate Settings Position Baud Rate 1 1200 2 2400 3 4800 4 9600 5 19200 6-0 Reserved Chapter 4 Setup and Operation The Product Interface baud rate must be set to match the baud rate of the device(s) it is connected to. In other words, all devices on the PowerLogic communications link must be set to the same baud rate. For example, if two Circuit Monitors and one Product Interface are daisy-chained to a PNIM, both Circuit Monitors, the Product Interface, and the PNIM port must be set to the same baud rate. The baud rate switch is located behind the access door on the front of the Product Interface. (See Figure 4-1). The baud rate switch settings are clearly identified on a label inside the access door. Table 4-1 repeats the baud rate switch settings. To set the baud rate, complete the following steps: 1. Insert a miniature, flat-bladed screwdriver into the arrow in the center of the baud rate switch. 2. Rotate the switch until the arrow points to the number that corresponds to the desired baud rate. For example, to select 19200 baud, rotate the arrow to switch position 5. 3. Press the Reset button. This forces the Product Interface to recognize the new baud rate setting. NOTE: The Product Interface can also be reset by issuing a reset command using PowerLogic application software. See Resetting the Product Interface, in this chapter, for more information. UNDERSTANDING ADDRESSING Any single PowerLogic communications link can support up to 32 individual device addresses. Therefore, a maximum of 32 circuit breakers can be monitored on a single PowerLogic communications link. Each Product Interface can support from 1 to 8 circuit breakers. The maximum number of Product Interfaces that can be connected to a PowerLogic communications link is tied to this 32 circuit breaker limit. For example, a PowerLogic communications link could contain four Product Interfaces each connected to eight circuit breakers. Or a communications link could contain eight Product Interfaces each connected to only four circuit breakers. Or a communications link could contain 16 Product Interfaces each connected to only two circuit breakers. Each Product Interface on a communications link must be assigned a base communications address. The Product Interface’s base address is assigned using the two ten-position rotary switches housed behind the door on its front. (See Setting the Base Communications Address below for instructions on setting the address switches). Page 4-2 1991 Square D. All Rights Reserved Chapter 4 Setup and Operation Bulletin No. 3050IM9101 December 31, 1991 Each Product Interface must also be told how many circuit breakers are connected to it. The # of connected circuit breakers is set using the sixteen position rotary switch also housed behind the door on the front of the Product Interface. (See Setting the # of Connected Circuit Breakers below for instructions on setting the switch). The base address tells the Product Interface which communication address to use for the first circuit breaker connected to it. The # of connected circuit breakers switch tells the Product Interface how many communication addresses to assign to its circuit breakers. For example, if a Product Interface’s base address is 01, and the # of connected circuit breakers switch is set to 05, then the Product Interface assigns addresses 01, 02, 03, 04, and 05 to its circuit breakers. Or, if a Product Interface’s base address is 07, and the # of connected circuit breakers switch is set to 03, then the Product Interface assigns addresses 07, 08, and 09 to its circuit breakers. Circuit breakers are connected to the Product Interface via eight removable 4position terminal plugs. (See Chapter 3 for connection instructions). The terminal plugs are labeled “ADD+0”, “ADD+1”, “ADD+2”, . . . , “ADD+8”. The circuit breaker connected to position ADD+0 is assigned the Product Interface base address. The circuit breaker connected to position ADD+1 is assigned the base address+1. The circuit breaker connected to position ADD+2 is assigned the base address+2, and so on. For example, assume that a Product Interface’s base address is 09, and the # of connected circuit breakers switch is set to 03. Then the circuit breaker connected to the plug labeled ADD+0 is assigned the address 09. The circuit breaker connected to the plug labeled ADD+1 is assigned the address 10. And the circuit breaker connected to the plug labeled ADD+2 is assigned the address 11. Choosing a Base Communications Address When choosing the base address for a Product Interface, remember that each circuit breaker on the communications link must have a unique address. Duplicate addresses on a PowerLogic communications link will cause communication errors. For example, assume that the base address of a Product Interface is set to 01, and the # of connected circuit breakers switch is set to 04. The Product Interface assigns addresses 01, 02, 03, and 04 to its circuit breakers. These addresses can’t be used again on the same PowerLogic communications link. The next available address is 05. You could set the base address of the second Product Interface to 05. But assume that you want to connect a fifth circuit breaker to Product Interface 01. To do this you must change the # of connected circuit breakers switch from 04 to 05. The Product Interface then assigns the address 05 to the fifth circuit breaker. But if the base address of the second Product Interface is 05, you’ve created a duplicate 1991 Square D. All Rights Reserved Page 4-3 Bulletin No. 3050IM9101 December 31, 1991 Chapter 4 Setup and Operation address. This will cause communication errors. To correct the error, you must change the base address of the second Product Interface to 06 or higher. The addresses of the circuit breakers connected to the second Product Interface will be renumbered according to its new base address. To prevent this from happening, you can assign base addresses with expansion in mind. For example, assume that you have a system with two Product Interfaces, each connected to four circuit breakers. To provide for expansion, you could assign the first Product Interface the base address 01 and set the # of connected circuit breakers switch to 04. Its circuit breakers would be assigned the addresses 01, 02, 03, and 04. You could then assign the second Product Interface the base address 09 and set the # of connected circuit breakers switch to 04. Its circuit breakers would be assigned the address 09, 10, 11, and 12. By doing this, you have left addresses 05, 06, 07, and 08 unused. Then, when you add another circuit breaker to Product Interface 01, you can change the # of connected circuit breakers switch to 05. The Product Interface will assign the circuit breaker the available address 05. Figure 4-2 illustrates this example. Other Important Addressing Considerations The bullet items below list several other items to consider when choosing Product Interface base addresses: • • Page 4-4 Each PowerLogic communications link must have one device whose address is “01.” - If a communications link contains several daisy-chained Product Interfaces (and no other PowerLogic devices), one Product Interface must be assigned the base address “01.” - If a communications link contains only one PowerLogic device, a Product Interface, its base address must be “01.” - If a communications link contains Product Interfaces and other PowerLogic devices, and a System Display for Micrologic Circuit Breakers (SD-100/SD-120) is used to display circuit breaker data, then device “01” must be a Product Interface. Figure 3-4 shows a systems where this rule applies. When Product Interfaces are connected to a PowerLogic Network Interface Module (PNIM), the PNIM should be assigned either the address 0, or an address above the highest address assigned to any circuit breaker. For example, if a communications link has four Product Interfaces and 32 circuit breakers addressed as 1-32, the PNIM address should be either 0 or 33 or higher. 1991 Square D. All Rights Reserved Chapter 4 Setup and Operation Bulletin No. 3050IM9101 December 31, 1991 SETTING THE BASE COMMUNICATIONS ADDRESS Each Product Interface must be assigned a base communications address. The Product Interface uses the base address to assign addresses to the circuit breakers connected to it. Before attempting to set the base address, be sure and read the section Understanding Addressing above. The base address is set using two ten position rotary switches located behind the door on the front of the Product Interface. (See Figure 4-1). The address switch closest to the Baud Rate switch sets the ones digit. The address switch closest to the Reset switch sets the tens digit. To set the base address, complete the following steps: 1. Insert a miniature, flat-bladed screwdriver into the arrow in the center of the ones switch. 2. Rotate the switch until the arrow points to the desired number. 3. Insert a miniature, flat-bladed screwdriver into the arrow in the center of the tens switch. 4. Rotate the tens switch until the arrow points to the desired number, from 1 to 8. Position 9 is not a valid setting. 5. Press the Reset button. This forces the Product Interface to recognize the new switch setting. NOTE: The Product Interface can also be reset by issuing a reset command using PowerLogic application software. See Resetting the Product Interface, in this chapter, for more information. Terminator PIF3 Base Address = 09 # Breakers switch = 04 PIF3 Base Address = 01 # Breakers switch = 04 CB Address 09 CB Address 01 CB CB Address 10 CB CB Address 02 CB Address 12 CB Address 04 CIM3F Address 11 Address 03 Addresses 05 through 08 are reserved for expansion Figure 4-2 Addressing Example 1991 Square D. All Rights Reserved Page 4-5 Bulletin No. 3050IM9101 December 31, 1991 SETTING THE NUMBER OF CONNECTED CIRCUIT BREAKERS Chapter 4 Setup and Operation The number of circuit breakers connected to the Product Interface is set using the sixteen position rotary switch located above the Address switches. (See Figure 4-1). This switch tells the Product Interface how many addresses it must assign to its connected circuit breakers. For example, if the Product Interface has a base address of 10, and this switch is set to 4, then the Product Interface reserves addresses 10, 11, 12, and 13 for the circuit breakers connected to it. The circuit breaker connected to the terminal labeled ADD+0 is assigned the address 10. The circuit breaker connected to the terminal labeled ADD+1 is assigned the address 11. The circuit breaker connected to the terminal labeled ADD+2 is assigned the address 12. And the circuit breaker connected to the terminal labeled ADD+3 is assigned the address 13. See Understanding Addressing above for more on addressing. This switch should always match the exact number of connected circuit breakers. If a Product Interface is connected to four circuit breakers, but the # of connected circuit breakers switch is set to 3, then the Product Interface will not recognize the fourth circuit breaker. To set the number of connected circuit breakers, complete the following steps: 1. Insert a miniature, flat-bladed screwdriver into the arrow in the center of the 16 position switch. 2. Rotate the switch until the arrow points to the number of connected circuit breakers, from 1 to 8. Note: Switch positions 9, A, B, C, D, and E are reserved. If the switch is inadvertently set to one of these settings, the Product Interface defaults to 8 connected circuit breakers and operates accordingly. Switch positions F and 0 are reserved for specific functions. If the switch is set to either of these positions, the Product Interface will not operate. 3. Press the Reset button. This forces the Product Interface to recognize the new switch setting. Note: The Product Interface can also be reset by issuing a reset command using PowerLogic application software. See Resetting the Product Interface, in this chapter, for more information. Page 4-6 1991 Square D. All Rights Reserved Chapter 4 Setup and Operation INSTALLING THE BATTERY Bulletin No. 3050IM9101 December 31, 1991 The Product Interface uses a long-life lithium battery to maintain the clock and nonvolatile RAM in the event of a control power loss. The user must install the battery before initial start-up of the Product Interface. For maximum battery life, do not install the battery until you are ready to apply control power to the Product Interface. The battery is located behind the door on the front of the Product Interface. To install the battery, open the door and press the battery into the battery clip. Make sure that the “+” end of the battery matches the “+” symbol on the battery clip. INITIAL START-UP Before starting the Product Interface, review Chapter 3 and Chapter 4. Verify that all external wiring is connected according to color codes. Inspect for stray wires and short conditions. Check the baud rate and address settings. Be sure that the Product Interface baud rate matches the baud rate of all other devices on the PowerLogic communications link. Verify that the addresses of the circuit breakers connected to the Product Interface are unique. Check the # of connected circuit breakers switch to make sure that it is set to the actual number of connected circuit breakers. Replace the terminal strip protective cover. The cover should remain in place to prevent inadvertent damage to wiring connections. Close and secure the front access door. After verifying proper installation and setup, apply control power to the Product Interface. The two green LEDs on the front of the enclosure should light indicating that the Product Interface is functioning properly. The red LED on the front of the enclosure is the low battery warning indicator and should not light. If the red light comes on, check the battery to see that it is seated properly. If one or both of the green LEDs does not light, or the red LED does light and you’ve verified that the battery is properly seated, refer to Chapter 5 - Maintenance and Troubleshooting for troubleshooting tips. SETTING THE CLOCK AND ASSIGNING LABELS AND NAMEPLATES The final steps required to set up the Product Interface for operation are (1) setting the Product Interface Clock, and (2) assigning a Label and Nameplate for each circuit breaker. The Product Interface clock is used to record the time and date of important events such as the Time and Date of Last Trip. The Product Interface’s lithium battery maintains the clock in the event of a control power loss. 1991 Square D. All Rights Reserved Page 4-7 Bulletin No. 3050IM9101 December 31, 1991 Chapter 4 Setup and Operation The label is a four character alpha-numeric string. The PowerLogic Product Communications Software and other PowerLogic products display the label to help identify the circuit breaker being viewed. A typical label might be “CB-1,” where “CB” indicates that the device being viewed is a circuit breaker, and “1” is the circuit breaker’s address. The nameplate is 16 character alpha-numeric string. The PowerLogic Product Communications Software and other PowerLogic products display the nameplate to help identify the circuit breaker being viewed. For example, if a circuit breaker feeds the welder on production line 3, the nameplate might be “Welder Line 3.” The clock, label, and nameplate can all be set using a System Display for MICROLOGIC circuit breakers, or PowerLogic application software. Refer to the instruction bulletin for the System Display or software for instructions on setting theses values. Page 4-8 1991 Square D. All Rights Reserved Chapter 5 Maintenance and Troubleshooting Chapter5–MaintenanceandT roubleshooting ! Bulletin No. 3050IM9101 December 31, 1991 WARNING HAZARD OF ELECTRICAL SHOCK. All maintenance must be performed by qualified service personnel. Disconnect control power before attempting to service the device. Failure to observe this precaution could result in severe personal injury or death! REPLACING THE LITHIUM BATTERY The Product Interface is equipped with a long-life lithium battery. The battery maintains the Product Interface clock and non-volatile RAM in the event of a control power loss. The battery is located behind the flush mounted door on the front of the Product Interface. The front of the Product Interface enclosure has three LEDs. The red LED, labeled Battery Low, is a warning light for lithium battery. When the red LED is lit, the battery voltage is low, indicating the battery must be replaced. The battery can be changed while the Product Interface is operating. To change the battery, open the door on the front of the Product Interface. Remove the old battery and replace it with a new battery. Make sure that the “+” end of the battery matches the “+” symbol on the battery holder. NOTE When replacing the battery, use extreme care not to touch the circuit board. — For maximum battery life, remove the battery when storing the Product Interface for extended periods of time. Battery Specifications Square D Part Number ...................................................................... 29904-08961 Manufacturer ..................................................... Tadiran Electronic Industries Inc. Mfg. Type Number .................................................................................... TL-5104 Mfg. Catalog Number ................................................................ 15-51-04-210-000 Rated Voltage .......................................................................... Lithium AA, 3.6 V Capacity (200 uA @ 3V) ................................................................ 1.9 Amp Hours (Typical Cells stored at 25° C for one year) 1991 Square D. All Rights Reserved Page 5-1 Bulletin No. 3050IM9101 December 31, 1991 REPLACING THE CONTROL POWER FUSE Chapter 5 Maintenance and Troubleshooting The Product Interface is equipped with a control power fuse to protect its internal power supplies. The fuse is located on the side of the Product Interface, behind the terminal strip protective cover. (See Figure 5-2). To change the fuse, complete the following steps: 1. Disconnect control power from the Product Interface 2. Remove the terminal strip protective cover from the Product Interface. 3. Remove the fuse cover by pressing down on it and rotating it counterclockwise. 4. Remove the blown fuse and replace it with an equivalent 250V, 2 AMP slow blow fuse. 5. Replace the fuse cover and the terminal strip protective cover. 6. Reapply control power to the Product Interface. Product Interface Side View D- 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 D+ GND +12V D- ADD + 1 D+ GND +12V DGND +12V DD+ GND +12V DD+ GND +12V D- MICROLOGIC CIRCUIT BREAKERS ADD + 3 ADD + 4 ADD + 5 D+ ADD + 2 SE 8 U +12V ADD + 0 7 D+ GND +12V D- ADD + 6 DC E F AC 6 - N 38 IN+ GND RS485 COMMS IN- 5 G 39 D+ GND +12V DD+ ADD + 7 1991 Square D. All Rights Reserved OUT+ 4 + L 40 Page 5-2 OUT- 3 DC AC Figure 5-2 Control Power Fuse Location 2 FUS FUSE 250V, 2 AMP S FU E 1 Control Power Fuse SHLD Chapter 5 Maintenance and Troubleshooting TROUBLESHOOTING Customer Service Bulletin No. 3050IM9101 December 31, 1991 Most problems occur due to improper installation or setup. It may be helpful to review Chapters 3 and 4 before referring to the troubleshooting table below. Table 5-1 offers a list of potential problems and their likely causes, along with checks and/or solutions for each. If after completing the Troubleshooting checks in Table 5-1, the problem has not been solved, contact your local Square D distributor, or contact PowerLogic customer service at (615) 459-8591. Table 5-1 Troubleshooting Table Problem Possible Cause(s) Check or Cure Red “Battery Low” Light Comes On. Battery is not connected. Check the battery to see that it is seated properly. Battery voltage is low. Replace the battery. See “Replacing the Lithium Battery” in this chapter for instructions. Control power connection faulty. Check control power circuit and connections. Control Power fuse not present or blown. Replace fuse with 2 Amp, 250 V Slow Blow Fuse. See “Replacing the Control Power Fuse” in this chapter for instructions. Product Interface is addressed incorrectly. Verify that the address switches are set to a unique address. Check for address duplication on the communications link. See “Setting the Base Address” in Chapter 4 for instructions on addressing. Product Interface Baud Rate is set wrong. Reset the Product Interface to the correct baud rate. See “Setting the Baud Rate” in Chapter 4 for instructions. Last device on the communications link is not terminated using the Multipoint Communications Terminator. Check the last device on the link for proper termination. See “Terminating the RS485 Link” in Chapter 3 for instructions. Communications link is not biased using the Multipoint Communications Adapter. Check to see that the Multipoint Communications Adapter is used and properly placed. See “Connecting the Product Interface to a communications port” in Chapter 3. Break in RS-485 communications link. Check all wiring connections on RS-485 link. Custom cable built incorrectly. If a custom cable was built, verify that the proper pinouts were used. Control power is applied, but green LEDs on front of Product Interface do not light. Can't communicate to the Product Interface at all. 1991 Square D. All Rights Reserved Page 5-3 Bulletin No. 3050IM9101 December 31, 1991 Chapter 5 Maintenance and Troubleshooting Table 5-1 Troubleshooting Table (Continued) Problem Possible Cause(s) Check or Cure Can communicate to the first circuit breaker (that is, the circuit breaker connected to terminal position “ADD+0”) but not some or all of the others. The sixteen position rotary switch that is used to set the # of connected circuit breakers is set too low. Verify that the switch position matches the number of connected circuit breakers. See “Setting the Number of Connected Circuit Breakers” in Chapter 4 for instructions. A breaker is tripped, but the Product Interface is still reporting current for the breaker. Ammeter Threshold Level needs to be adjusted. See the register 6012 in Appendix A for a definition of the Ammeter Threshold Level. Can communicate to some circuit breakers on a Product Interface, but not others. Improper wiring between Product Interface and Communications Adapter (CIM3F). Check wiring connections. See “Connecting to Communications Adapters” in Chapter 3. Improper wiring between Communications Adapter (CIM3F) and circuit breaker. Check wiring connections. See the CIM3F instruction manual for wiring instructions. Communications Adapter (CIM3F) failed due to improper wiring. Replace CIM3F. Page 5-4 1991 Square D. All Rights Reserved Appendix A Register Listing Bulletin No. 3050IM9101 December 31, 1991 Appendix A –RegisterListing PIF Reg PIF Reg CM Reg CM Reg COLUMN HEADINGS R/W Save Description Each Product Interface for MICROLOGIC Circuit Breakers has an identical set of R/W Save Description storage registers. Table A-2 provides a listing of the registers. The table has five column headings: PIF Reg, CM Reg, R/W, Save, and Description. The column headings are described below. PIF Reg - This column shows the Product Interface register number. CM Reg - Some of the registers in the Product Interface store data that is also available in the PowerLogic Circuit Monitor. These registers have an associated Circuit Monitor “shadow” register, listed in the CM Reg column. Each “shadow” register duplicates the data stored in the associated PIF register. For example, Product Interface register 6201 stores Phase A Current. The Circuit Monitor stores Phase A Current in register 3. So if you look at register 6201 in this appendix, you will see that it lists register 3 in the CM Reg column. This means that you can read Phase A Current from either register 6201 or register 3. Both registers return the same data. R/W - An R is shown in this column if the register can only be read, but not written. If the register can be read and written, R/W is shown in this column. Save - This column describes the action taken by the Product Interface upon loss of power. When power is restored, one of three conditions exist for each register: S (SAVE) = The value that existed before power loss is saved. U (UPDATE) =The value that existed before power loss is replaced by the present value. Z (ZERO) = The value that existed before power loss is replaced by zero. Description - This column provides a description of the register contents. IMPORTANT NOTES • Registers 0001 - 5999 and 6400 - 8171 are undefined, except for the registers presented as Circuit Monitor shadow registers. (The shadow registers are listed in the “CM Reg” column of Table A-2). Undefined registers return a value of zero when read. A write to an undefined register does nothing. The Circuit Monitor shadow registers will return valid data when read. • Product Interface register numbers 6000 - 6099 and 8172 - 8192 are Global for all active trip units on the Interface. Reading a global register, using all active trip unit addresses, returns identical results. Writing to a global register, using any one of the trip unit addresses, updates the register value of all of the trip units. 1991 Square D. All Rights Reserved Page A-1 Bulletin No. 3050IM9101 December 31, 1991 PIF Reg PIF Reg CM Reg CM Reg Appendix A Register Listing R/W Save • If communication to the trip unitsDescription is lost for more than 3 seconds, the following R/W Save Description registers are forced to the values shown below: REGISTER EFFECT 6129 ........................................................Bits 1 through 5 forced to 0 6200 ........................................................Bit 8 forced to 1 6201 through 6205 .................................Values forced to -32767 6206 ........................................................Bits 1 and 2 forced to 0 6207 ........................................................All bits forced to 0 6208 ........................................................All bits forced to 0 6209 ........................................................All bits forced to 0 6235 ........................................................Values forced to 0 6236 through 6238 .................................Values forced to 0 • Product Interface register 6111 is a command register that allows the user to perform specific functions by setting specific bits. For example, a write to register 6111 with bit 5 set to 1 restarts the Product Interface. Table A-1 lists the available command operations, the bits that must be set to perform each operation, and the decimal equivalents that can be written to set the bits. Refer to the description of register 6111 in table A-2 for a more detailed description. Table A-1 Product Interface Command Operations Command Operation Page A-2 Bit Decimal Equivalent Restart Product Interface 5 16 Reset PIF Communication Statistics 6 32 Reset Trip History & Time Date of Last Trip 9 256 Reset Trip Unit Communication Statistics 10 512 Restart and Clear Product Interface 11 1024 Reset Trip Event Flag 12 2048 1991 Square D. All Rights Reserved Appendix A Register Listing Bulletin No. 3050IM9101 December 31, 1991 Table Interface Register PIFA-2 RegProduct CM Reg R/W Save Listing PIF Reg CM Reg R/W Save Description PIF Reg CM Reg R/W Save PIF Reg CM Reg R/W Save Description 6000 6001 87 6002 Description Description R U Number of connected circuit breakers. Stores the number of connected circuit breakers (1 - 8) set by the user with the # of connected circuit breakers switch. The switch has sixteen positions labeled 0-9 and A-F. Positions 1-8 are set by the user to indicate the number of breakers connected to the Product Interface. Positions 9, A, B, C, D, and E are reserved. The Product Interface defaults to 8 connected circuit breakers when set to any of these postions. Positions 0 and F are also reserved, but the Product Interface will not function properly when set to these positions. R U Product Interface base address. Stores the Product Interface Base Address switch setting. The Base Address is determined by the position of the address switches upon system power-up or reset. R U Product Interface baud rate. Stores the Product Interface baud rate switch setting. The baud rate is determined by the position of the baud rate switch upon power-up or reset. Baud rate switch positions are: 1 = 1200, 2 = 2400, 3 = 4800, 4 = 9600, and 5 = 19200. Positions 6-0 are reserved for future use and would indicate 9600 baud if inadvertantly chosen. Product Interface Communications Statistics (Registers 6003-6011): 6003 133 R S Number of messages received by the addressed Product Interface. 6004 134 R S Number of messages sent by the addressed Product Interface to other devices. 6005 135 R S Number of messages received by the addressed Product Interface with invalid addresses. 6006 136 R S Number of messages received by the addressed Product Interface with bad checksums. 6007 137 R S Number of messages received by the addressed Product Interface with unclassified errors. 6008 138 R S Number of messages received by the addressed Product Interface with illegal opcodes. 6009 139 R S Number of messages received by the addressed Product Interface with illegal registers. 6010 140 R S Number of messages received by the addressed Product Interface with illegal counts. 6011 141 R S Number of messages received by the addressed Product Interface with frame errors. 1991 Square D. All Rights Reserved Page A-3 Bulletin No. 3050IM9101 December 31, 1991 PIF Reg PIF Reg CM Reg CM Reg 6012 Appendix A Register Listing R/W Save R/W Save R/W S 6013 Description Description Ammeter Threshold Level. The value in this register represents a percentage of the Phase sensor rating. (Registers 6131). This is a user defined value in the range 0 to 500 (0.00 to 5.00% of sensor rating). The default value is 250, (2.5% of sensor rating). Current readings that fall below the Threshold Level are returned as “0 AMPS”. For example, if this register contained the value 120, the Product Interface would report “0 AMPS” for current readings less than 1.2% of the sensor rating. Reserved System Time and Date - Unpacked, SY/MAX Format (Registers 6014-6020): 6014 6015 6016 6017 6018 6019 6020 784 785 786 787 788 789 R R R R R R R U U U U U U U Milliseconds Range = 0 - 999 Seconds Range = 0 - 59 Minutes Range = 0 - 59 Hours Range = 0- 23 Days Range = 1 - 31 Month Range = 1 - 12 Year Range = 0 - 199 (Year is zeroed on 1900. e.g. 1989 is represented as 89, and 2009 is represented as 09). System Time and Date - Packed, Circuit Monitor Format (Registers 6021-6023): 6021 228 R U 6022 229 R U 6023 230 R U 6024 Month (byte 1) Range = 1 - 12 Day (byte 2) Range = 1 - 31 Year (byte 1) Range = 1 - 199 Hour (byte 2) Range = 0 - 23 Minutes (byte 1) Range = 0 - 59 Seconds (byte 2) Range = 0 - 59 (Year is zeroed on 1900. e.g. 1989 is represented as 89. 2009 is represented as 109). Reserved Last Restart Time and Date - Unpacked, SY/MAX Format (Registers 6025-6031): 6025 6026 6027 6028 6029 6030 6031 Page A-4 700 701 702 703 704 705 R R R R R R R S S S S S S S Milliseconds Range = 0 - 999 Seconds Range = 0 - 59 Minutes Range = 0 - 59 Hours Range = 0 - 23 Day Range = 1 - 31 Month Range = 1 - 12 Year Range = 0 - 199 (Year is zeroed on 1900. e.g. 1989 is represented as 89. 2009 is represented as 109). 1991 Square D. All Rights Reserved Appendix A Register Listing PIF Reg PIF Reg Bulletin No. 3050IM9101 December 31, 1991 CM Reg CM Reg R/W Save R/W Save Description Description Last Restart Time and Date - Packed, Circuit Monitor Format (Registers 6032-6034): 6032 88 R S 6033 89 R S 6034 90 R S R U Product Interface Self Test results. A “0” bit setting indicates no system error. A “1” bit setting indicates a system error. Bit map follows: Bit 1 = 1 - Self Test Error/Failure Bit 2= 1 - Battery Low Bit 3 = 1 - Real Time Clock Failure Bit 4 = 1 - Interrupt Controller Failure Bit 5 = 1 - RAM Memory Failure Bit 6 = 1 - EPROM Memory Failure Bit 7 = 1 - EEPROM Memory Failure Bit 8 is reserved for future use Bit 9 is reserved for future use Bit 10 = 1 - Duart #1 Failure Bit 11 = 1 - Duart #2 Failure Bit 12 = 1 - Duart #3 Failure Bit 13 = 1 - Duart #4 Failure Bit 14 = 1 - Duart #5 Failure Bit 15 is reserved for future use Bit 16 is reserved for future use R S Revision Level of Product Interface Software. This register represents the firmware release and revision numbers: 6035 6036 231 Month (byte 1) Range = 1 - 12 Day (byte 2) Range = 1 - 31 Year (byte 1) Range = 0 - 199 Hour (byte 2) Range = 0 - 24 Minutes (byte 1) Range = 0 - 59 Seconds (byte 2) Range = 0 - 59 (Year is zeroed on 1900. e.g. 1989 is represented as 89. 2009 is represented as 109). Lower 2 Digits - represent the operating system revision number. Upper 2 Digits - represent the boot system release number. Note: A release is a major upgrade or change in firmware features whereas a revision is a change to existing features designed to enhance performance. For example, release level 2.0 may provide some new calculated values that were not available in release 1.0. Revision 2.1 may change the format of those new calculated values. 6037 6038 - 6099 242 R S Square D Company product identification number for Product Interface for Micrologic Circuit Breakers. A read from this register will return the product ID number 475. Reserved 1991 Square D. All Rights Reserved Page A-5 Bulletin No. 3050IM9101 December 31, 1991 PIF Reg PIF Reg CM Reg CM Reg Appendix A Register Listing R/W Save R/W Save Description Description NOTE: Registers 6100 to 6199 are used to provide Product Interface register assignments for data values that are computed, rather than generated directly by the MICROLOGIC Series IIIA/B Trip Units. Many registers in this range have a shadow register number to reflect the Circuit Monitor equivalent. 6100 R S Trip Event Flag. When a trip event occurs, bit 1 of this register is set to 1 indicating that a trip has occurred, and either bit 2, 3, 4, or 5 is set indicating the cause of trip. The bits remain set to 1 until one of the following things happens: 1) Current is restored to the circuit, or 2) This register is reset using the Product Interface command register. (To reset this register, set bit 12 of register 6111). When one of the above conditions is met, all bits are reset to 0 and remain set to 0 until the next trip event. The bit map follows: Bit 1 = 1 - A Trip Event Has Occurred Bit 2 = 1 - Long Time or Full Load Trip Bit 3 = 1 - Short Time or LRC Trip Bit 4 = 1 - Instantaneous Trip Bit 5 = 1 - Ground Fault Trip Bit 6 = Reserved Bit 7 = Reserved Bit 8 = 1 - Cause Unknown Bits 9-16 Reserved 6101-6102 218-219 R/W S Circuit Breaker Label. This is a user-defined, four-character alphanumeric string. The PowerLogic Product Communications Software and other PowerLogic products display the label to help identify the circuit being viewed. A typical label might be “CB-1” where “CB” indicates that the device being viewed is a circuit breaker, and “1” is the circuit breaker’s address. 6103-6110 220-227 R/W S Circuit Breaker Nameplate. This is a user-defined, sixteen-character alphanumeric string. The PowerLogic Product Communications Software and other PowerLogic products display the nameplate to help identify the circuit being viewed. For example, if a circuit breaker feeds the welder on production line 3, the nameplate might be “WELDER LINE3”. The default nameplate is “CKT BRKR”. 6111 237 R/W Z Command Register. This is a command register that is used to perform specific functions by setting specific bits. For example, a write to register 6111 with bit 5 set to 1 restarts the Product Interface. When this register is read, all bits are returned as 0. Bit map follows: Bits 1-4 Reserved Bit 5 = 1 - Restart Product Interface. This performs the same function as pressing the Restart button on the Product Interface. The date and time of the restart is stored in registers 6025-6034. Bit 6 = 1 - Reset Product Interface Communication Statistics. This zeroes registers 6003-6011. Bits 7-8 Reserved Bit 9 = 1 - Reset Trip History and Time/Date of Last Trip Event. This resets registers 6112 -6122. Page A-6 1991 Square D. All Rights Reserved Appendix A Register Listing PIF Reg PIF Reg Bulletin No. 3050IM9101 December 31, 1991 CM Reg CM Reg R/W Save R/W Save Description Description Bit 10 = 1 - Reset Trip Unit Communication Statistics. This zeroes registers 6123-6127. Bit 11 = 1 - Restart and Clear Product Interface. This restarts the Product Interface and clears all historical data and userdefined configuration entries. Bit 12 = 1 - Reset Trip Event Flag. This sets all bits in register 6100 to 0. Bit 13-16 Reserved. 6112 R S Trip History recorded from register 6100 at the time of the last trip event. This register retains the cause of the last trip until the next trip event occurs. A “0” bit setting indicates no trip event. A “1” setting in Bit 1 indicates that a trip occured, and the cause of the trip is indicated in the other bits as shown below: Bit 1 = 1 - Any Trip Condition Bit 2 = 1 - Long Time Trip Bit 3 = 1 - Short Time Trip Bit 4 = 1 - Instantaneous Trip Bit 5 = 1 - Ground Fault Trip Bit 6 = Reserved Bit 7 = Reserved Bit 8 = 1 - Cause Unknown Bits 9 through 16 are reserved for future use. 6113-6119 R S Time and Date of last trip event, formatted as follows. 6113 Milliseconds Range = 0 - 999 6114 Seconds Range = 0 - 59 6115 Minutes Range = 0 - 59 6116 Hour Range = 0 - 23 6117 Days Range = 1 - 31 6118 Month Range = 1 - 12 6119 Year Range = 0 - 199 (Year is zeroed on 1900. e.g. 1989 is represented as 89, and 2009 is represented as 109). 6120-6122 R S Time and date of last trip event, formatted as in circuit monitors: 6120 Byte 1 = Month Range = 1 - 12 Byte 2 = Day Range = 1 - 31 6121 Byte 1 = Year Range = 0 - 199 Byte 2 = Hour Range = 0 - 23 6122 Byte 1 = Minutes Range = 0 - 59 Byte 2 = Seconds Range = 0 - 59 (Year is zeroed on 1900. e.g., 1989 is represented as 89, and 2009 as 109, etc.). 1991 Square D. All Rights Reserved Page A-7 Bulletin No. 3050IM9101 December 31, 1991 PIF Reg PIF Reg CM Reg CM Reg Appendix A Register Listing R/W Save R/W Save Description Description Trip Unit Communications Statistics (Registers 6123-6127): 6123-6124 R S Number of valid data packets received from the addressed trip unit. 6125 R S Number of data packets received from the addressed trip unit with checksum error. 6126 R S Number of data packets received from the addressed trip unit with frame errors. 6127 R U Trip Unit Communications Status: This register stores the time (in seconds) since the Product Interface received good data from the addressed trip unit. In other words, a nonzero value indicates that communications to the addressed trip unit are currently bad. A value of 0 indicates that communications are good. 6128 Reserved 6129 R U Current Overrange Register indicates the current is greater than 16383 AMPS. Bit map follows: Bit 1 = 1 - Present Phase A current is overrange Bit 2 = 1 - Present Phase B current is overrange Bit 3 = 1 - Present Phase C current is overrange Bit 4 = 1 - Present Ground Fault current is overrange Bit 5 = 1 - Present Max Phase current is overrange Bits 6 through 16 are reserved for future use. (A “0” bit setting indicates no overrange condition exists). 6130 R U Last Trip Current Overrange This register indicates the current may have been greater than 16383 AMPS at the time of the last trip. A “1” bit setting indicates overrange condition as follows: Bit 1 = 1 - Last Trip Phase A overrange Bit 2 = 1 - Last Trip Phase B overrange Bit 3 = 1 - Last Trip Phase C overrange Bit 4 = 1 - Last Trip Ground Fault overrange Bit 5 = 1 - Last Trip Maximum Phase Bits 6 through 16, are reserved for future use. (A “0” bit setting indicates no overrange condition). NOTE: Registers 6131 through 6141 are read only registers that allow the user to read the switch settings on the Micrologic IIIA/B Circuit Breakers. 6131 Page A-8 R U Phase Sensor Rating: (Factory Setting). The Phase Sensor rating is the maximum amount of current the sensor system will permit the breaker to carry continuosly without tripping. The rating of the breaker is determined by combining the sensor rating and the rating plug value resident in the breaker. 1991 Square D. All Rights Reserved Appendix A Register Listing PIF Reg PIF Reg Bulletin No. 3050IM9101 December 31, 1991 CM Reg CM Reg R/W Save R/W Save 6132 Description Description Reserved 6133 R U Rating Plug Multiplier*10000. This register stores the circuit breaker’s rating plug multiplier*10000. Divide this value by 10000 to get the actual rating plug multiplier. The rating plug multiplier times the sensor rating determines the maximum continuous ampere rating of the circuit breaker. 6134 R U Plug Rating in amperes. Value = {(Phase Sensor Rating) * (RP Multiplier)}, or; {(register 6131) * (register 6133)} 6135 R U Long time Pickup*100. This register stores the circuit breaker’s long time pickup setting * 100. Divide this value by 100 to get the actual long time pickup setting. The long time pickup setting is the current level at which the long time tripping function picks up and begins timing. 6136 R U 6137 R U Long Time Delay*100. This register stores the circuit breaker’s long time delay setting*100. Divide this value by 100 to get the actual long time delay setting. The long time delay setting represents the time the circuit breaker will carry a sustained overcurrent (within the long time trip range) before tripping. This provides the ability to withstand temporary overloads without tripping. Short Time Pickup*100. This register stores the circuit breaker’s short time pickup setting*100. Divide this value by 100 to get the actual short time pickup setting. The short time pickup represents the current level at which the breaker will trip after the preset short time delay has expired. 6138 R U Short Time Delay*100. This register stores the circuit breaker’s short time delay setting*100. Divide this value by 100 to get the actual short time delay setting. The short time delay represents the amount of time the circuit breaker will carry an overcurrent that exceeds the short time pickup value. 6139 R U Instantaneous Pickup*100. This register stores the circuit breaker’s instantaneous pickup setting*100. Divide this value by 100 to get the actual instantaneous pickup setting. The instantaneous pickup represents the level of current at which the circuit breaker will trip with no intentional time delay. 6140 R U Ground Fault Pickup*100. This register stores the circuit breaker’s ground fault pickup setting*100. Divide this value by 100 to get the actual ground fault pickup setting. The ground fault pickup represents the level of current at which the breaker will trip after the preset ground fault delay expires. 1991 Square D. All Rights Reserved Page A-9 Bulletin No. 3050IM9101 December 31, 1991 PIF Reg PIF Reg CM Reg CM Reg 6141 6142 7 Appendix A Register Listing R/W Save R/W Save Description R U Ground Fault Delay*100. This register stores the circuit breaker’s ground fault delay setting*100. Divide this value by 100 to get the actual ground fault delay setting. The ground fault delay represents the amount of time the breaker will carry ground fault current before tripping. R U Apparent Current, RMS. Max-Phase Current divided by the square root of 2. (Max-Phase Current is the peak value associated with the highest RMS value. This value is reported in Register 6205). NOTE: Apparent RMS is not equivalent to RMS values. 6143-6186 6187-6199 Description Reserved. 243-255 R/W S Utility registers for user assignment. These registers are provided for the benefit of the user. They can be used to develop customized operations within the software. NOTE: Registers 6200-6299 provide the Product Interface register assignments for raw data values received from each Micrologic IIIA/B Trip Unit. Because much of this data is unique to the trip unit, few registers in this range have Circuit Monitor shadow register numbers. 6200 Reserved. 6201 3 R U Phase A RMS Current present in the addressed trip unit. Range: 0 16383 AMPS. Overrange current indicators are recorded in register 6129. 6202 4 R U Phase B RMS Current present in the addressed trip unit. Range: 0 16383 AMPS. Overrange current indicators are recorded in register 6129. 6203 5 R U Phase C RMS Current present in the addressed trip unit. Range: 0 16383 AMPS. Overrange current indicators are recorded in register 6129. 6204 R U Ground Fault RMS Current present in the addressed trip unit. Range: 016383 AMPS. Overrange current indicators are recorded in register 6129. 6205 R U Max-Phase Peak Current present in the addressed trip unit. Range: 0 16383 AMPS. This is an instantaneous peak current value for the maximum phase. Note that this value does not represent RMS current. 6206 R U Short Circuit and Ground Fault Restraint Inputs. A “high” restraint input indicates that a fault has occured but the addressed circuit breaker is in “restraint”; i.e., it is delayed to allow the downstream breaker closest to the fault to react, thereby limiting the zone of power interruption. Since the restraint input resets automatically when the fault is cleared, the user will not typically see this condition. Bit map follows: Bit 1 = 1 - Short Circuit Restraint Input high Bit 2 = 1 - Ground Fault Restraint Input high Bits 3 through 16 are reserved for future use. (Bit setting = 0 indicates no fault condition). Page A-10 1991 Square D. All Rights Reserved Appendix A Register Listing PIF Reg PIF Reg Bulletin No. 3050IM9101 December 31, 1991 CM Reg CM Reg R/W Save R/W Save Description Description 6207 R U Overload Pickups A “1” bit setting indicates that the current value in the addressed trip unit is approaching or has exceeded the maximum continuous ampere rating of the circuit breaker. Bits 1 - 4 indicate current value in excess of 90% of the rating. Bits 5 - 8 indicate current value in excess of 100% of the rating. Note that bits 5 - 8 supplement bits 1 - 4; that is, a bit in the range 1 - 4, and a bit in the range 5 - 8 can display a “1” setting simultaneously. Bit map follows: Bit 1 = 1 - Phase A, B, or C greater than 90% of breaker rating. Bit 2 = 1 - Phase A current greater than 90% of breaker rating. Bit 3 = 1 - Phase B current greater than 90% of breaker rating. Bit 4 = 1 - Phase C current greater than 90% of breaker rating. Bit 5 = 1 - Phase A, B, or C greater than 100% of breaker rating. Bit 6 = 1 - Phase A current greater than 100% of breaker rating. Bit 7 = 1 - Phase B current greater than 100% of breaker rating. Bit 8 = 1 - Phase C current greater than 100% of breaker rating. Bits 9 through 16 are reserved for future use. (Bit setting = 0 indicates no overload condition). 6208 R U Short Circuit and Ground Fault Pickups. A “1” bit setting indicates that current has exceeded the pickup setting due to a short circuit fault condition. After a trip event, bit 1 and one or more bits in the range 2 - 5 will display a “1” setting. Bit map follows: Bit 1 = 1 - Phase A, B, or C, or Ground Fault greater than Short Circuit Pickup Bit 2 = 1 - Phase A current greater than Short Circuit Pickup Bit 3 = 1 - Phase B current greater than Short Circuit Pickup Bit 4 = 1 - Phase C current greater than Short Circuit Pickup Bit 5 = 1 - Ground Fault current greater than Ground Fault Pickup Bits 6 through 16 are reserved for future use. (A “0” bit setting indicates no fault was detected). 6209 R U Maximum Phase ID. Identifies the phase within the addressed trip unit that is experiencing or has experienced the greatest peak current magnitude. Refer to register 6205. Note that this current value is not equivalent to RMS current. Bit map follows: Bit 1 = 1 - Phase A is max phase Bit 2 = 1 - Phase B is max phase Bit 3 = 1 - Phase C is max phase Bit 4 = 1 - Ground Fault is max phase Bits 5 through 16 are reserved for future use. 6210 R U ID Code for Breaker Type. Factory setting. 6211 - 6214 6215 Reserved R U ID code for Trip Unit. Embedded in trip unit firmware. 1991 Square D. All Rights Reserved Page A-11 Bulletin No. 3050IM9101 December 31, 1991 PIF Reg PIF Reg 6216 CM Reg CM Reg Appendix A Register Listing R/W Save R/W Save R U 6217 - 6224 Description Description Purchase Options installed with Circuit Breaker. A “1” bit setting indicates the option is installed. A “0” bit setting indicates the option is not installed. Bit map follows: Bit 1 = 1 - External Ground Fault system Bit 2 = 1 - Short Time option Bit 3 = 1 - Ground Fault option Bit 4 = 1 - Instant Pickup option Bits 5 through 16 are reserved for future use. Reserved 6225 R U Accumulated number of Overload Trips. Range: 0 - 63 trip events. 6226 R U Accumulated number of Short Circuit Trips. Range: 0 - 63 trip events. 6227 R U Accumulated number of Ground Fault Trips Range: 0 - 63 trip events. 6228 Reserved 6229 R U Last Trip, Phase A Current. Range: 0 - 16383 AMPS. (Refer to register 6129 for current overrange indication). 6230 R U Last Trip, Phase B Current. Range: 0 - 16383 AMPS. (Refer to register 6129 for current overrange indication). 6231 R U Last Trip, Phase C Current. Range: 0 - 16383 AMPS. (Refer to register 6129 for current overrange indication). 6232 R U Last Trip, Ground Fault Current. Range: 0 - 16383 AMPS. (Refer to register 6129 for current overrange indication). 6233 R U Last Trip, Max Phase Current . Range: 0 - 16383 AMPS. (Refer to register 6129 for current overrange indication). 6234 R U Last Trip, Relative Current Records values of phase currents relative to Short Circuit and Overload pickup settings at the time of the last trip. Bit map follows: Bit 1 = 1 - Phase A current greater than Short Circuit pickup Bit 2 = 1 - Phase B current greater than Short Circuit pickup Bit 3 = 1 - Phase C current greater than Short Circuit pickup Bit 4 = 1 - Phase A current greater than Overload Pickup Bit 5 = 1 - Phase B current greater than Overload Pickup Bit 6 = 1 - Phase C current greater than Overload Pickup Bit 7 = 1 - Either Ground Fault or Short circuit restraint was high at last trip. (Refer to register 6206). Bits 8 through 16 are reserved for future use. (A “0” bit setting indicates the phase current was less than pickup value). Page A-12 1991 Square D. All Rights Reserved Appendix A Register Listing PIF Reg PIF Reg 6235 Bulletin No. 3050IM9101 December 31, 1991 CM Reg CM Reg R/W Save R/W Save R U 6236-6238 6239 Description Long Time Memory Ratio. Range: 0 - 100 percent of Long Time Delay. Reserved R U 6240-8171 8172-8192 Description Trip Unit Software Version ID. Reserved R S SY/MAX compatibility registers. Used to support the Product Interface functions necessary to maintain Sy/Max compatibility. These Registers are read only, but some may be altered as a result of system operation. NOTE: Register 8188 reports “475” to identify the Product Interface for MICROLOGIC Circuit Breakers. 1991 Square D. All Rights Reserved Page A-13 Appendix B Maximum Distances AppendixB–MaximumDistancesforComms Bulletin No. 3050IM9101 December 31, 1991 All PowerLogic devices are equipped with RS-485 communications. This RS-485 standard allows up to 32 devices to be daisy-chained to a single communications port. For example, up to 32 Circuit Monitors can be connected to the top RS-422 communications port of a PowerLogic Network Interface Module (PNIM). When 1 to 16 PowerLogic devices are connected to a single communications port, the maximum length of the communications link, that is the distance from the communications port to the last PowerLogic device on the chain, is 10,000 feet. When more than 16 PowerLogic devices are connected to a single communications port, the maximum length of the communications link changes in relation to the baud rate. This is necessary to insure accurate communications at high rates of speed (up to 19,200 baud). The table below shows the maximum distances recommended at varying baud rates. Table B-1 Maximum Distance for PowerLogic Communications Maximum Distances in Feet Number of Devices Baud Rate 16 17-32 1200 10,000' 10,000' 2400 10,000' 5,000' 4800 10,000' 5,000' 9600 10,000' 4,000' 19200 10,000' 2,500' 1991 Square D. All Rights Reserved Page B-1 Appendix C Communication Cable Pinouts AppendixC–CommunicationCablePinouts Bulletin No. 3050IM9101 December 31, 1991 CAB-107 Product Interface Terminal IN(#4) White IN+ (#5) Green OUT- (#2) Black OUT+ (#3) Red (#1) Shield 1991 Square D. All Rights Reserved 1 2 3 4 5 6 7 8 9 Page C-1