H569445 BATTERY DISTRIBUTION
FUSE/CIRCUIT BREAKER BAY (BDFB/BDCBB)
A
GENERAL
The Battery Distribution Fuse Bay (BDFB) or Battery Distribution Circuit Breaker Bay (BDCBB)
serves as a secondary power distribution center for -48VDC power delivered from
B
a central
office battery plant to the load equipment. It provides power redundancy from
the battery plant
B
through the use of multiple load busses.
The BDFB/BDCBB may be configured for use in 7 FT, 8FT, 9 FT, or 11-1/2 FT
office environments.
It can be set up for top feed or bottom feed and equipped with multiple
fuse/circuit breaker
panels, load busses and optional return busses.
HOW TO ORDER A BDFB/BDCBB
C
C
The following table lists the standard configurations for the BDFB. These BDFB's offer the
shortest manufacturing lead time. Alternative configurations may be requested
by following
a six step configuration process to list the needed H569445 Group options.
Lineage Power
Product Management can then assign an ordering code for this request. Refer to
sheets A4 and A5.
STANDARD BDFB/BDCBB CONFIGURATIONS
ORDERING
CODE
D
E
F
DESCRIPTION
7 FOOT HIGH, 26 INCH WIDE CABINETS
D
CC109147377
2 LOAD, 6 20-POSITION FUSE PANELS, METER, TOP FEED
(H569445G1,10A,20,(3) 30B,60.72)
CC109147393
2 LOAD, 6 20-POSITION FUSE PANELS, METER, TOP FEED, INTERNAL RETURNS
(H569445G1,10A,20,(3) 30B,61,(3) 61A, 72)
CC109148276
2 LOAD, 6 20-POSITION BULLET PANELS, METER, TOP FEED
(H569445G1,10A,20,(3) 31B,60.72)
CC109148268
2 LOAD, 6 20-POSITION BULLET PANELS, METER, TOP FEED, INTERNAL RETURNS
(H569445G1,10A,20,(3) 31B,61,(3) 61A, 72)
150020730
2 LOAD, 6 28-POSITION BULLET PANELS, METER, TOP FEED
H569445 G7 G10A G23 G33-3 G60 G272
150020729
2 LOAD, 6 28-POSITION BULLET PANELS, METER, TOP FEED, INTERNAL RETURNS
H569445 G7 G10A G23 G33-3 G63 G63A-3 G272
150025419
2 LOAD, 4 28-POSITION BULLET PANELS, METER, TOP FEED, INTERNAL RETURNS
H569445 G7 G10A G23 G33-2 G63 G63A-2 G272
150025421
2 LOAD, 4 28-POSITION BULLET PANELS, METER, BOTTOM FEED, INTERNAL RETURNS
H569445 G7 G10C G23 G33-2 G63 G63A-2 G272
150025420
4 LOAD, 4 28-POSITION BULLET PANELS, METER, TOP FEED, INTERNAL RETURNS
H569445 G7 G10A G23-2 G33-2 G63 G63A-2 G272
150025422
4 LOAD, 4 28-POSITION BULLET PANELS, METER, BOTTOM FEED, INTERNAL RETURNS
H569445 G7 G10C G23-2 G33-2 G63 G63A-2 G272
CC109168547
6 LOAD, 6 28-POSITION BULLET PANELS, METER, TOP FEED
H569445 G7 G10A G23-3 G33-3 G60 G272
CC109168530
6 LOAD, 6 28-POSITION BULLET PANELS, METER, TOP FEED, INTERNAL RETURNS
H569445 G7 G10A G23-3 G33-3 G63 G63A-3 G272
E
F
9 FOOT HIGH, 26 INCH WIDE CABINETS
G
H
C2FORMAT.FRM DEC 2002
GROUP 7 BDFB
CC109152071
2 LOAD, 8 20-POSITION FUSE PANELS, METER, TOP FEED
(H569445G2,10A,20,(4) 30B,60.72)
CC109152088
2 LOAD, 8 20-POSITION FUSE PANELS, METER, TOP FEED, INTERNAL RETURNS
(H569445G2,10A,20,(4) 30B,61,(4) 61A, 72)
CC109152063
2 LOAD, 8 20-POSITION BULLET PANELS, METER, TOP FEED
(H569445G2,10A,20,(4) 31B,60.72)
CC109152055
2 LOAD, 8 20-POSITION BULLET PANELS, METER, TOP FEED, INTERNAL RETURNS
(H569445G2,10A,20,(4) 31B,61,(4) 61A, 72)
GROUP 8 BDFB
SHEET INDEX
7 FOOT HIGH, 34 INCH WIDE CABINETS
150024806
2 LOAD, 6 28-POSITION BULLET PANELS, METER, TOP FEED
H569445 G8 G10A G23 G33-3 G60 G272
150024805
2 LOAD, 6 28-POSITION BULLET PANELS, METER, TOP FEED, INTERNAL RETURNS
H569445 G8 G10A G23 G33-3 G63 G63A-3 G272
150026177
2 LOAD, 4 28-POSITION BULLET PANELS, METER, TOP FEED, INTERNAL RETURNS
H569445 G8 G10A G23 G33-2 G63 G63A-3 G272
150026179
2 LOAD, 4 28-POSITION BULLET PANELS, METER, BOTTOM FEED, INTERNAL RETURNS
H569445 G8 G10C G23 G33-2 G63 G63A-3 G272
Group 1, 2 or 3 cabinets ship with a documentation kit that includes the
150026178
4 LOAD, 4 28-POSITION BULLET PANELS, METER, TOP FEED, INTERNAL RETURNS
H569445 G8 G10A G23-2 G33-2 G63 G63A-2 G272
Product Manual: 108405283
150026180
4 LOAD, 4 28-POSITION BULLET PANELS, METER, BOTTOM FEED, INTERNAL RETURNS
H569445 G8 G10C G23-2 G33-2 G63 G63A-2 G272
Schematic Drawing: SD-83150-01
150024804
6 LOAD, 6 28-POSITION BULLET PANELS, METER, TOP FEED
H569445 G8 G10A G23-3 G33-3 G60 G272
Documentation may also be downloaded from our web site at
150024803
6 LOAD, 6 28-POSITION BULLET PANELS, METER, TOP FEED, INTERNAL RETURNS
H569445 G8 G10A G23-3 G33-3 G63 G63A-3 G272
0
1
2
DOCUMENTATION FOR BDFB/BDCBB
Group 7 or 8 cabinets ships with product manual 850018552.
following:
ISSUE
30
27
24
28
26
30
22
28
22
28
SHEET#
A1
A2
A3
A4
A5
A6
B1
B1A
B1B
B1C
ISSUE
22
22
22
25
28
23
23
22
22
22
SHEET#
B2
B3
B4
B5
B6
B7
B8
B8A
B9
B9A
ISSUE
23
23
22
26
22
22
26
22
22
22
SHEET#
B10
B11
B12
B12A
B12B
B12C
B12D
B13
F1
F2
TITLE
SECONDARY POWER DISTRIBUTION BAY (BDFB/DBCBB)
Wiring Drawing: T-83150-30
H
DRAWING DESCRIPTION
DWG
4
5
SHEET
DOC TYPE
www.lineagepower.com. Click on Energy Systems Products/Bays and Frames/BDFB.
3
G
6
7
H569445-AD
8
A1
ISSUE
DWG
SIZE
30
9
C2/A1R
0
A
1
2
4
5
Various cabinet options are available:
Description
6
7
The frame alarm lights when power is lost to a
Each G30B, G31B and G31C DC panels are equipped
fuse/circuit breaker panel or there is a fuse/
with a BEP1A alarm module. The alarm module shown
circuit breaker alarm. Power for lighting the frame
on sheet B6 provides two Form-C contacts for power loss
DC panels (Fuse or Circuit Breaker) or blank panels are
alarm lamp comes from the battery plant on a
and three Form-C contacts for fuse/circuit breaker operation.
ordered in sets of 2. For example, (1)G30B provides
Auxiliary Battery Supply (ABS) lead. A 48V lamp
These alarm contacts are located on the output connector P101.
2 side by side -48V DC panels. (1)G90 provides 2
is factory installed in a G1, G2 or G3 cabinet as
When power loss to a panel occurs, a closure exists between
side by side blank panels.
shown on sheet B9. The frame alarm light on a
pins 1 and 2, and pins 3 and 4, while an open exists between
1
7ft blue cabinet (26"W x 15"D) with BEP1 alarm cards
2
9ft blue cabinet (26"W x 18"D) with BEP1 alarm cards
3
7ft gray cabinet (24"W x 24"D) with BEP1 alarm cards and doors
Group 30B Fuse panels come equipped with 20 single position
G7 or G8 cabinet is LEDs on the Bay Alarm Board.
pins 1 and 9, and pins 3 and 10. When a fuse or circuit breaker
7
7ft blue cabinet (26"W x 15"D) with Customer Interface Card.
3-70 amp TPS type fuse blocks. If optional alternate fuse blocks
See sheet B10.
operates, a closure exists between pins 8 and 15, pins 11 and 12,
8
7ft blue cabinet (34"W x 15"D) with Customer Interface Card.
are desired, these are ordered from Table 4C and are mounted
9
A
and pins 13 and 14, while an open condition exists between pins
7 and 8, pins 6 and 12 and pins 5 and 13. Sheet 9 and 9A shows
in the field. The alternate fuse blocks available are the GMT fuse
B
8
BEP1A ALARM CIRCUIT MODULE
FRAME ALARM LAMP
CHOOSE FUSE PANELS OR
BULLET PANELS (STEP 4)
CHOOSE A CABINET (STEP 1)
Group
3
The List 7 and 8 cabinets update the alarm scheme used on the List 1
module providing space for 3 GMT fuses (0-5 amp) and the double
to eliminate BEP1 alarm cards and includes a customer interface
position 70-150 amp TPL type fuse block. Fuses are ordered
card for alarm connection terminal blocks and ABS connection.
seperately from Tables 4B (TPS), 4D (GMT), and 4E (TPL).
the internal wiring and sheet F1 shows the customer wiring.
B
With the VIM1 meter, the alarms on the individual BEP1A boards
are not required unless the customer wishes to monitor unique
An alarm fuse must be ordered for each TPS or TPL load
Extension cabinets are available for taller office environments.
fuse. Sheet B6 shows the fuse panel. Note: There are no restrictions
1ft, 2ft and 4-1/2ft extensions are available for the 7ft cabinets with
requiring skipping of fuse positions with either 0-70A TPS or 70-150A
a 15 inch depth and a 2-1/2ft extension is available for the 9ft cabinet.
TPL-B Fuses.
alarms from every panel. Most customers just want a single set
of alarms from the BDFB. The VIM1 provides Form-C contacts for
power loss, overload condition and fuse/circuit breaker alarm.
Cabinet extension kits are ordered separately from Table 1D and
are field installed.
Group 31B Bullet panels have 20 positions for
C
The 7 FT cabinet has 6 fuse/circuit breaker panel positions and the
pluggable circuit breakers or pluggable fuse blocks.
9 FT cabinet has 8 fuse/circuit breaker panels positions.
Bullet-style circuit breakers and fuseholders are ordered
separately from Sheet A6, Table 4A. Sheet B6 shows the
CHOOSE TOP OR BOTTOM CABLE
ROUTING FOR LOAD FEEDS AND
DISTRIBUTION OUTPUT (STEP 2)
D
BAY ALARM BOARD ON G7 OR G8
CABINETS
bullet panel. Fuseholders accept TPS or TLS style
At the top of the cabinet is a Customer Interface Board
fuses (Table 4B). Note: 80A, 90A and 100A single pole
for connecting Output Alarms and an Alarm Battery Supply
breakers must have an adjoining position left unoccuppied
(ABS) to redundantly power the alarms and the meter.
for thermal considerations. There are no restrictions for
The VIM1 receives redundant power from the A and B panels
0-70A fuses or circuit breakers or two-pole breakers to 150A.
as well as an external ABS connection. So the ABS connection
TPS fuses larger than 70A require an adjoining position be
is not mandatory for proper operation but some customers
left unoccupied.
require its use. A Return connection is required for operation of
the meter and alarms. The Return connection on the Bay Alarm
Sheet B3 shows four options for different cable
Group 31C Bullet panels are similar but have 18 positions
routing into and out of the BDFB. These options also
Board is factory wired when internal return buses are ordered.
and capacitors mounted on the panel.
Otherwise it must be field wired to the external return bus.
determine whether the panels are mounted from the
top down or the bottom up. Order one of these groups.
Group 33 Bullet panels have 28 positions with no spacing
form-C for current overload and one form-C for fuse/breaker
restrictions on single pole breakers through 100A, two pole
alarms (Note: there are two connection points for FAJ/CB but thet
breakers through 175A or TPS fuses through 125A.
are connected to the same form-C contact). Contacts are rated for
G10B: Top Load Feed Input , Bottom Distribution Output
60V, 1/2A. Maximum wire size to the terminal blocks is 12 gage.
G10C: Bottom Load Feed Input , Bottom Distribution Output
G10D: Bottom Load Feed Input , Top Distribution Output
VIM1 METER
DIGITAL METER OPTION (STEP 5)
CHOOSE NUMBER OF LOAD BUSSES
(STEP 3)
VIM1 smart meter is used on all BDFB's. They do have
G72, G172, G272 provide a VIM1 digital meter. This smart meter
different mechanical mountings depending on the cabinet.
has an alarm sensitive back-lit display that changes color from green
Group 72 for List 1 and 2 cabinets.
to red on alarm. Current, voltage and alarm information for the A and B
Group 172 for List 3 cabinets.
buses is accessed thru the display. There are three primary alarms:
E
Group 272 for List 7 cabinets.
The 7 FT cabinet type may be configured with 2, 4, or 6
Replacement Kits for older versions of the meter are
Power Loss/Under Voltage: Generates an alarm when
available per Table AA.
power is lost to either the A or B bus or when a user
configurable low voltage threshold is reached.
fuse/circuit breaker panels and the 9 FT cabinet may be
configured with 2, 4, 6, or 8 fuse/circuit breaker panels.
Fuse/Circuit Breaker panels come in sets of 2 (left
F
D
Alarm Outputs consists of one form-C contact for power loss, one
G10A: Top Load Feed Input , Top Distribution Output
E
C
Overload: Generates an alarm when a user configurable
CHOOSE INTERNAL OR EXTERNAL
RETURN BUS OPTION (STEP 6, 6A)
& right).
A load bus is defined as one or more fuse/circuit breaker
panels protected by a single fuse or circuit breaker at the
current threshold is reached. A configurable time delay
may also be set to avoid nuisance alarms due to bus
F
transients.
There are two options for terminating fuse/circuit breaker return leads
battery plant. Up to two 750 MCM cables from the battery plant
Breaker/Fuse: Generates an alarm when either a
on the BDFB/BDCBB. (1) Internal Returns or (2) External Returns.
may be terminated to each load shunt bus detail in the BDFB.
circuit breaker trips or a fuse blows.
G20 provides bus details for two side-by-side G30B, G31B
Step 6. INTERNAL RETURNS (G61
or G31C panels. Each has a 800A shunt and a 600A bus rating.
& G61A or G62
& G62A or G63
& G63A)
This display has visual alarms with the display turning
G23 provides bus details for two G33 panels. Each has a 1500A
shunt and a 800A bus rating.
If multiple distribution panels are connected to the same load, a
bus bar link is used to connect the two panels (see sheet B5).
G
G61A provides a internal returns bus mounted on G30B and 31B panels.
red on an alarm condition. It has an audible alarm with
G62A provides a internal returns bus mounted on G31C panels.
a user configurable on/off feature. It also has remote
G63A provides a internal returns bus mounted on G33 panels.
monitoring with a form-C relay for each of the three alarms.
Note: These Groups provide a pair of bus bars, one for the right side and
CC848846287alarm cable is shipped with each G72 and
one for the left side. These bus bars are linked to the bus bar mounted
G172 meter to access these alarms. G272 includes a cable
above/below it to create one long bus bar assembly (per side). This long
to connect the alarms up to the Bay Alarm Board at the top
bus bar assembly connects to a pair of bus bars (G61 or G63) located at the
of the G7 cabinet where the customer connects to alarm
top (for top feed) or bottom (for bottom feed). Discharge return cabling from
terminal blocks.
G
the battery plant is terminated on this bus bar. Note: The maximum current
for G61 and G63 is 1200A per side. A second G61 or G63 may be added
This meter can monitor up to eight load buses. The meter display
at the other end for a 2400A rating. G62 includes bus bars for both sides and
indicates which load it is monitoring. The meter is redundantly
has a 1800A rating. G61 provides 5 lug landing positions per bus and G62 and
powered by the A and B load bus and ABS power from the battery
G63 provides 6.
plant. Sheet B9 and B10 show the wiring for the meter.
TITLE
SECONDARY POWER DISTRIBUTION BAY (BDFB/DBCBB)
Step 6A: EXTERNAL RETURNS (G60)
H
H
DRAWING DESCRIPTION
To reduce internal cable congestion, external returns may be ordered.
There are two options for external return bus bar assemblies and these are
shown on sheets B7 and B8. These bus bar assemblies require a 15 inch
DWG
Table 6A. Terminal lugs are ordered seperately from Table 6AA.
C2FORMAT.FRM DEC 2002
0
1
2
3
SHEET
DOC TYPE
or 20 inch ladder type rack to be mounted and are ordered from Sheet A4,
4
5
6
7
H569445-AD
8
A2
ISSUE
DWG
SIZE
27
9
C2/A1R
0
A
1
2
C
4
5
6
INSTALLATION INFORMATION
FIELD INSTALLED EQUIPMENT
FIELD INSTALLED PARTS
B
3
Anchor Bolts
Table 1B :
Cabinet Ground Lugs and Hardware
Table 1C :
Battery-Input Lugs and Hardware
Table 1D :
Cabinet Extension Kits
Table 4A :
Plug-In Breakers, Plug in Fuse Holders
Table 4B :
TPS Fuses, TLS Fuses
Table 4BB :
Circuit Breaker and Fuse Lugs and Hardware
Table 4D :
GMT Fuses
Table 4E:
TPL Fuses
Table 4C :
Alternate Fuse Blocks
Table 4DD :
Lugs and Hardware for Alternate Fuse Blocks
Table 6A :
External Bus Bar Kits
Table 6AA :
Lugs and Hardware for External Bus Bars
8
9
CONVERTING CABINET FROM
TOP FEED TO BOTTOM FEED
(SEE SHEET B13)
Cabinet Anchoring (Sheet A4, Table 1A)
Table 1A :
7
A
Changing a top feed to a bottom feed (or vice versa) is
accomplished by simply rotating the G20 load shunt assembly
180 degrees. Note: Bus bar links may need to be moved in
addition to what is described below.
1. Disconnect the shunt wires from the 2 shunts of the
load shunt assembly.
2. Remove the Nuts/Lock Washers/Flat Washers that connect
the load shunt assembly to the 2 panels. Save this hardware
to reattach the load shunt assembly.
3. Disconnect the shunt wires from the charge bus where you
wish to reconnect the load shunt assembly.
4. Rotate the load shunt assembly 180 degrees from it original
orientation and mount to the charge bus on the desired
DC panel pair.
5. Reconnect the shunt wires from step 1 to the shunts. Refer
to T-83150-30 to for wire orientation.
6. Reconnect the shunt wires from step 3 to the desired charge
bus bars (as they are connected on other charge bus bars)
or connect the respective shunt wires to each other using the
quick connects that are "pig tailed" onto the shunt wires.
7. If internal returns are present, then relocate as shown on sheet B13.
The bay has two floor footprints. G1 and G7 cabinets are 26inches wide
by 15 inches deep. The G2 cabinet is 26 inches wide by 18 inches
deep. G8 cabinet is 34 inches wide by 15 inches deep. The G3 cabinet
is 23.6 inches wide by 23.6 inches deep. Cabinets are equipped with
four .75x1.00 inch slots to accomodate various sizes and types of anchor
bolts (Table 1A). See sheets B12A, B12B, B12C and B12D.
Cabinet Extensions (Sheet A4, Table 1D)
All mounting hardware is included with the cabinet extensions to connect
to cabinets.
(4)804220838 Screw, HH .625-11x1-1/2
(4)840058044 Loch Washer, .625
(4)814251930 Washer, .625
Interframe ground cable and mounting hardware is also furnished to
provide a continuous frame ground to the top of the cabinet.
(1)846524130 Ground Strap
(2)801462987 Screw, HH .250-20x1
(4)801098963 Washer, .250
(2)803690668 Lock Washer, .250
(2)841064751 Hex nut .250-20
B
C
Cabinet Ground
The frame ground connection located on top of the cabinets is sized for
1/4 inch bolts on .625 centers (See Table 1B). Lists 3 and 7 also include
ground connection sized for 3/8 inch bolts on 1 inch centers (See Table 1C
for these lugs). List 1 and 2 include a 846337798 bus bar adapter for the
larger ground connection.
D
INSTALLATION MATERIAL PROVIDED
F
G
Connection
Screw or Nut Size
Torque Tool Settings
(inch/pounds)
GMT Fuse Module
#6
10
TPL Type Fuse Block
Frame Ground
Internal Return Bus
1/4
65
Input battery and returns
External return bus
Anchor bolts
3/8
240
Central Office Ground
* Frame ground mounting hardware (1/4 inch).
* Battery and battery return lead mounting hardware (3/8 inch).
*Load lead mounting hardware (1/4 inch).
*Load lead return mounting hardware (1/4 inch) (internal only)
E
RECOMMENDED TORQUE SETTINGS
It is recommended that C.O. ground be run from the battery plant discharge
return bus to building ground. BDFB/BDCBBs equipped with local discharge
return busses do not require their own C.O. grounds. However, Tyco's
BDFB/BDCBB is equipped with C.O. ground termination points for both
internal and external return buses. These connection points are as follows:
(See Table 1C and 6AA)
External Returns
848258679: Row A, Position 21
108785452: (ED-83019-50 G1) Row B. Position 9
Internal Returns
G-61: 1 of the 5 positions is for C.O. ground
G-62: 1 of the 6 positions may be used for C.O. ground
INSTALLATION MATERIAL REQUIRED
BUT NOT PROVIDED
* Input and output cables and terminal lugs.
* Material handling equipment to unload bay at site, remove from
shipping container and set in final position.
* Lifting eye bolts with 5/8-11 threads.
* Floor mounting hardware.
* Drill to bore holes for floor anchors.
* Cable rack and associated hardware.
* Common electrician's hand tools including jewler's screwdriver,
electrical tape, wire cutters and strippers, etc.
* Proper crimping tools and dies for connectors. The connectors
specified in this ordering guide are WP-91412 and may be
installed with compression tools made by Thomas & Betts using
color dies.
* Common mechanic's hand tools, including flat blade screwdriver,
socket and torque wrenches for 1/4 inch and 3/8 inch bits,
crowbar for uncrating and a soldering iron.
* All load fuses.
* All load circuit breakers.
* All alarm fuses (0.18 amp GMT 402328926).
* Mounting hardware for connecting load return leads to external
discharge return bus.
* Central office frame and ground lugs.
* 22 gage wiring to connect external ground leads to digital
meters and alarm circuit modules.
E
Cable Routing Strategy
Load leads are routed along cable troughs on either side of the bay.
Location of the cable rack is important to reduce cable routing
problems. If possible, locate the cable rack along the front of the
bay as shown on sheet B4. The load leads should be run in three distinct
quadrants down the side of the cabinet. Run load leads to the top panels
toward the front of the cabinet , and run load leads to the bottom panels
toward the back of the cabinets. This is a recommended cabling scheme for
simplifying future cabling of the bay. See sheet B4.
F
Alarm Verification
Perform the following verification procedures with the load buses powered
from the battery plant, but with no load equipment in service.
G
Simulate a fuse failure alarm on each fuse panel by inserting a blown GMT
fuse in the indicating fuse position. Verify that the red LED on the
associated BEP1 circuit pack lights as well as the frame alarm lamp at the
top of the bay. If remote alarms are connected, verify that office alarms
are generated as specified by job records.
Simulate a panel power loss alarm on each fuse/circuit breaker panel by
turning off or disconnecting the circuit breaker or fuse feeding each load
bus. Verify that the green LED on the associated BEP1 circuit pack is
extinguished and that the frame alarm lamp at the top of the bay lights. If
remote alarms are connected, verify that office alarms are generated as
specified by the job record.
TITLE
SECONDARY POWER DISTRIBUTION BAY (BDFB/DBCBB)
If alarms are not generated, re-check alarm wiring per T-83150-30.
If alarms still do not function, it may be necessary to replace the BEP1
circuit pack comcode 106849508.
H
H
DRAWING DESCRIPTION
SHEET
DOC TYPE
DWG
C2FORMAT.FRM DEC 2002
D
0
1
2
3
4
5
6
7
H569445-AD
8
A3
ISSUE
DWG
SIZE
24
9
C2/A1R
0
1
2
3
4
5
6
7
8
9
HOW TO CONFIGURE A LINEAGE POWER BDFB/BDCBB
A
(1)
E/W
H569-445 G1
CHOOSE ONLY ONE
7' x 26" x 15" BLUE CABINET
G2
9' x 26" x 18" BLUE CABINET
G3
7' x 24" x 24" GRAY CABINET
WITH DOORS
G7
G8
C
(1)
(3)
G 20
STEP 3
(1)
G30B
STEP 4
G10B
7' x 26" x 15" BLUE CABINET
WITH ALARM INTERFACE CARD
G10C
7' x 34" x 15" BLUE CABINET
WITH ALARM INTERFACE CARD
G10D
TABLE 3: LOAD INPUT FEEDS
(ORDER MAX 3 FOR G1, G3, G7 OR G8)
(ORDER MAX 4 FOR G2)
TOP LOAD FEED INPUT
TOP DISTRIBUTION OUTPUT
TOP LOAD FEED INPUT
BOTTOM DISTRIBUTION OUTPUT
G20
BOTTOM LOAD FEED INPUT
BOTTOM DISTRIBUTION OUTPUT
G23
BOTTOM LOAD FEED INPUT
TOP DISTRIBUTION OUTPUT
TWO LOAD SHUNT CONNECTIONS.
(FOR SIDE BY SIDE G30B, G31B,
G31C DISTRIBUTION PANELS ONLY)
TWO LOAD SHUNT CONNECTIONS.
(FOR SIDE BY SIDE GROUP 33
DISTRIBUTION PANELS ONLY.)
ORDER FIELD
MOUNTED COMPONENTS LIKE
ANCHOR BOLTS, GROUND
CABLES, CABINET
EXTENSIONS AND LUGS
FROM TABLES 1A-1D
(3)
G61A
STEP 6A
ORDER ONLY WITH
G61, G62 OR G63
CHOOSE ONLY ONE
TABLE 7: INTERNAL OR EXTERNAL
DISCHARGE RETURN BUS
TABLE 5: DIGITAL METER
TABLE 4: DISTRIBUTION PANELS
(ORDER MAX 3 FOR G1, G3, G7 OR G8)
(ORDER MAX 4 FOR G2)
G61
STEP 6
STEP 5
CHOOSE ONLY ONE
TABLE 2: TOP OR BOTTOM CABLE ROUTING
G10A
(1)
G 72
CHOOSE ONLY ONE
TABLE 1: CABINET TYPE
G1
G10A
STEP 2
STEP 1
B
A
ORDER THE REQUIRED GROUPS IN EACH STEP.
PRODUCT MANAGEMENT WILL ASSIGN AN ORDERING CODE FOR THIS CONFIGURATION.
EXAMPLE BELOW SHOWS A 7FT, TOP FEED, 2 LOAD, 6 PANELS, DIGITAL METER WITH INTERNAL RETURN BUSSES.
G72
VIM1A METER FOR G1 OR G2
G30B
TWO 20 POSITION FUSE PANELS E/W
TPS FUSE HOLDERS
G172
VIM1B METER FOR G3
G272
VIM1C METER FOR G7 OR G8
G31B
TWO 20 POSITION BULLET PANELS
G31C
TWO 18 POSITION BULLET PANELS WITH
CAPACITORS FOR G3 ONLY (REQUIRES G62A)
NOTE: GROUP 70, 71, AND 170
ARE ONLY AVAILABLE AS
REPLACEMENT KITS FOR
EXISTING BDFB'S PER TABLE AA
G33
TWO 28 POSITION BULLET PANELS
G40
6 POSITION GMT FUSE PANEL FOR MOUNTING
AT THE TOP OF G3 ONLY
(5A MAX FUSES, 15A TOTAL)
PANEL MOUNTED INTERNAL
RETURN BUSES
G60
EXTERNAL
G61
INTERNAL FOR G1 OR G2
G61A
ORDER 1 PER G30B OR 31B
G62
INTERNAL FOR G3
G62A
ORDER 1 PER G31C
G63
INTERNAL FOR G7
G63A
ORDER 1 PER G33
B
C
NOTE: BLANK PANELS ARE FACTORY INSTALLED
IN ANY UNEQUIPPED PANEL POSITIONS
EQUIPMENT ABOVE THIS LINE IS FACTORY MOUNTED
EQUIPMENT BELOW THIS LINE IS FIELD MOUNTED
D
TABLE 1A: ANCHOR BOLTS (REFER TO H569-407)
ORDERING
CODE
DESCRIPTION
847135654
(4) 1/2 SELF DRILL (ZONE 0-2)
847135662
(4) 1/2 DROP IN (ZONE 0-2)
847135670
(4) 12MM NUT, ROD AND HOLD DOWN
PLATE (ZONE 3-4)
(4) 12MM CAP BOLT AND HOLD DOWN
PLATE (ZONE 3-4)
847135688
E
CC109121588
CC109121596
1/2 INCH SHIM KIT WITH ISOLATION
ISO BUSHING KIT
NOTE: HILTI HSL-1 M12/65 APPROVED
FOR USE WITH G3 CABINET
TABLE 1B: CABINET GROUND LUG
F
G
WIRE GAGE
ORDERING
CODE
STD
FLEX
406021626
8
8
405347519
6
6
405347576
4
4
405348202
2
-
405347683
-
2
407817568
1/0
-
407817550
2/0
1/0
407817576
-
2/0
ORDERING
CODE
DESCRIPTION
848258588
4-1/2 FT EXTENSION KIT
FOR G1 OR G7 CABINET IN
11-1/2 FT ENVIRONMENTS
848258570
2 FT EXTENSION KIT
FOR G1 OR G7 CABINET IN
9 FT ENVIRONMENTS
848258562
2-1/2 FT EXTENSION KIT
FOR G2 CABINET IN
11-1/2 FT ENVIRONMENTS
CC109132040
1 FT EXTENSION KIT
FOR G1 OR G7 CABINET IN
8 FT ENVIRONMENTS
150030560
2-HOLE LUG
#10 ON 5/8"
4-1/2 FT EXTENSION KIT
FOR G8 CABINET IN
11-1/2 FT ENVIRONMENTS
SEE SHEET
A3 NOTE
FOR
CABINET
GROUND
FLEX
406021725
2/0
4/0
4/0
406335141
0
2-HOLE LUG
3/8" ON 1"
WIRE GAGE
ORDERING
CODE
LUG
WIDTH
ORDERING
CODE
LUG
WIDTH
ORDERING
CODE
LUG
WIDTH
STD
FLEX
405356171
0.36
406144428
0.41
407890771
0.56
14-10
14-10
405348178
0.41
406021626
0.41
406338269
0.59
8
8
406338400
0.44
405347519
0.44
406332841
0.59
6
6
--
405347576
0.55
406332940
0.55
4
4
--
405348202
0.59
406338665
0.59
2
-
--
405347683
0.68
407726041
0.68
-
2
--
407817568
0.75
405348228
0.74
1/0
-
--
407817550
0.83
405348236
0.83
2/0
1/0
--
407817576
0.94
406021725
0.93
--
--
405348251
1.00
--
--
405347923
1.09
--
--
407890763
0.96
--
--
405348277
1.29
--
--
407890748
0.97
--
--
406021915
1.55
--
--
407850833
0.96
--
--
405348293
1.55
--
--
407890755
1.63
--
--
406434241
1.79
--
--
406335141
1.63
--
--
--
--
407890730
1.63
--
--
406434290
2.18
847073756
8-32, 10-32 AND 10-24 HARDWARE BOLT KIT
847073699
1/4-20 HARDWARE BOLT KIT
847073731
3/8-16 HARDWARE BOLT KIT
848258679
(1) 2400A EXTERNAL GROUND BAR FOR MOUNTING ON
A 15 OR 20 INCH LADDER TYPE CABLE RACK.
(SEE SHEET B7)
848258687
(1) SUPPLEMENTARY 2400A EXTERNAL GROUND BAR FOR
STACKING ON A 848258679 GROUND BAR.
(SEE SHEET B7)
108785452
ED83019-50 GROUP 1: (1) 1300A EXTERNAL GROUND BAR
FOR MOUNTING ON AUXILIARY FRAMING OR 15 OR 20 INCH
LADDER TYPE CABLE RACK. (SEE SHEET B8)
108874322
ED83019-50 GROUP 3: (1) SUPPLEMENTARY 1300A
EXTERNAL GROUND BAR FOR STACKING ON A GROUP 1
GROUND BAR. (SEE SHEET B8)
150021156
ED83019-50 GROUP 13: (1) 2400A EXTERNAL GROUND BAR
FOR MOUNTING ON A 15 OR 20 INCH LADDER TYPE CABLE
RACK. (SEE SHEET B8A)
150021157
ED83019-50 GROUP 13A: (1) SUPPLEMENTARY 2400A
EXTERNAL GROUND BAR FOR STACKING ON A GROUP 13
GROUND BAR. (SEE SHEET B8A)
2/0
4/0
4/0
350
350
DESCRIPTION
500
E
F
500
750
G
750
TITLE
SECONDARY POWER DISTRIBUTION BAY (BDFB/BDCBB)
350
H
DRAWING DESCRIPTION
500
405348293
407890730
2-HOLE LUG
1/4" ON 5/8"
350
405348277
407890755
ORDERING
CODE
HARDWARE BOLT KITS (INCLUDES 2 NUTS, 2 LOCK WASHERS, 4 FLAT WASHERS AND VARIOUS LENGTH BOLTS)
2/0
405348251
407890748
CLASS B
D
TABLE 6A:
EXTERNAL BUS BAR ASSEMBLIES
(SEE SHEETS B7 AND B8)
TABLE 6AA
TERMINAL LUGS
WIRE GAGE
ORDERING
CODE
405347923
C2FORMAT.FRM DEC 2002
TABLE 1D: CABINET EXTENSION KITS
TABLE 1C:
BATTERY INPUT AND RETURN CABLES
405348236
H
ORDER FIELD MOUNTED
COMPONENTS LIKE
CIRCUIT BREAKERS,
FUSE HOLDERS, FUSES
AND LUGS ON
SHEET A5
OPTIONAL: CHOOSE ONLY ONE
CHOOSE ONE ONLY
500
SHEET
DOC TYPE
750
DWG
750
1
2
3
4
5
6
7
H569445-AD
8
A4
ISSUE
DWG
SIZE
28
9
C2/A1R
0
1
2
3
4
5
6
7
8
9
FIELD INSTALLED EQUIPMENT
FROM SHEET A4
A
TABLE 4A PLUG-IN BREAKERS/FUSE HOLDERS
(G31B AND G33)
B
C
D
TABLE 4B TPS/TLS FUSES
(TPS: G30B TPS or TLS: G31B, G33)
PLUG IN CIRCUIT BREAKERS
COMCODE
AMPERAGE
TPS
COMCODE
BREAKER
POSITIONS
MIN
WIRE
407998137
3
1
10
407998145
5
1
10
407998152
10
1
10
407998160
15
1
10
407998178
16
1
10
407998186
20
1
10
407998194
25
1
10
407998202
30
1
8
407998210
45
1
8
407998228
50
1
8
407998236
60
1
6
407998244
70
1
6
407998251
80
1
4
407998269
90
1
4
407998277
100
1
2
408185353
125*
2
2
408185346
150*
2
1/0
450023081
175*
2
2/0
CC109171674
125**
2
2
CC109141735
150**
2
1/0
408564941
200***
3
2/0
408573975
225***
3
4/0
408535752
250***
3
4/0
PLUG IN FUSE HOLDERS
CC408617410
E
A
One 0.18 amp GMT fuse is required per
TPS, TLS or TPL fuse (see Table 4B
or 4E) USE BUSSMANN FUSE ONLY
408548944
PLUG-IN FUSE HOLDER FOR
TLS or TPS FUSES.
ALARMS ON BLOWN FUSE ONLY
TLS
COMCODE
AMPERAGE
402328926
MIN
WIRE
406700567
CC408617914
3
10
406700583
CC408617922
5
10
406700591
N/A
6
10
406700609
CC408617930
10
10
406700617
CC408617947
15
10
406700625
CC408617955
20
10
406700633
CC408617963
25
10
406700641
CC408617971
30
10
406700658
CC408617988
40
8
406700674
CC408617996
50
8
406700682
CC408618004
60
6
406700690
CC408618012
70
6
N/A
CC408618020
80
4
N/A
CC408618037
90
4
N/A
CC408618045
100
2
N/A
CC408618053
110
2
N/A
CC408618061
125
2
F
1-HOLE LUG
1/4"
2-HOLE LUG
1/4" ON 5/8"
406338152
406144428
405356189
406021626
405347436
G62A RETURNS
2-HOLE LUG
1/4" ON 3/4"
108319427
108785460
TABLE 4G
GMT FUSES FOR
G40 PANEL
DESCRIPTION
ED83127-30 GD
70-150 AMP TPL
FUSE BLOCK
ED83127-30 GB
0-5 AMP GMT
FUSE MODULE
COMCODE
AMPERAGE
406203182
1/2
406530725
1-1/3
406421032
2
406204230
3
406203976
5
TABLE 4F
ORDERABLE DISTRIBUTION PANEL POSITION LABELS
LABELS FOR G30B, G31B, G31C
DISTRIBUTION PANELS
POSITION NUMBERING
848270765*
1-20 (1 LABEL)
TABLE 4D
GMT FUSES
FOR ED83127-30 GB
COMCODE
AMPERAGE
401231501
1/2
401841473
1
400994604
1 -1/3
401231527
3
401231535
5
402099436
DUMMY
1.1 - 1.20 (1 LABEL)
2.1 - 2.20 (1 LABEL)
3.1 - 3.20 (1 LABEL)
4.1 - 4.20 (1 LABEL)
5.1 - 5.20 (1 LABEL)
6.1 - 6.20 (1 LABEL)
7.1 - 7.20 (1 LABEL)
8.1 - 8.20 (1 LABEL)
MIN
WIRE
10
848272399
N/A
*** THESE 3-POLE BREAKERS ARE FOR
G33 PANELS ONLY. ALSO ORDER TWO
850025679 3-POLE ADAPTER BUS KITS.
COMCODE
TPL FUSE
AMP
RATING
406794776
BA
70
408239648
BB
80
406794784
BD
100
406794792
BF
150
402328926
B
LABELS FOR G33
DISTRIBUTION PANELS
COMCODE
POSITION NUMBERING
850018546 ***
1.1 - 1.28 (1 LABEL)
2.1 - 2.28 (1 LABEL)
3.1 - 3.28 (1 LABEL)
4.1 - 4.28 (1 LABEL)
5.1 - 5.28 (1 LABEL)
6.1 - 6.28 (1 LABEL)
C
1-20 (8 LABELS)
20-1 (8 LABELS)
21-40 (8 LABELS)
40-21 (8 LABELS)
41-60 (8 LABELS)
60-41 (8 LABELS)
61-80 (8 LABELS)
80-61 (8 LABELS)
BUS A (2 LABELS)
BUS B (2 LABELS)
BUS C (2 LABELS)
BUS D (2 LABELS)
BUS E (2 LABELS)
BUS F (2 LABELS)
BUS G (2 LABELS)
BUS H (2 LABELS)
TABLE 4E
TPL FUSES
FOR ED83127-30 GD
** THIS 2-POLE BREAKER KIT IS FOR G31B
PANELS ONLY (KIT INCLUDES ADAPTER BUS).
848656823
21-40 (4 LABELS)
41-60 (2 LABELS)
61-80 (2 LABELS)
848469946
81-100 (2 LABELS)
101-120 (2 LABELS)
121-140 (2 LABELS)
141-160 (2 LABELS)
0.18 A ALARM FUSE
D
E
* APPLIED IN FACTORY
** LABEL SHEET SHIPS WITH BDFB
*** LABEL SHEET APPLIED IN FACTORY AND SECOND SHEET SHIPS WITH BDFB
TABLE 4DD LUGS AND HARDWARE
FOR ED83127-30 GB OR G40 PANEL
LOAD AND RETURN ARE THE SAME
850019325 &
850025679
ADAPTER BUS
2-HOLE LUG
3/8" ON 1"
COMCODE
848689709**
* THESE 2-POLE BREAKERS ARE FOR
G33 PANELS ONLY. ALSO ORDER TWO
850019325 2-POLE ADAPTER BUS KITS.
PLUG-IN FUSE HOLDER FOR
TLS or TPS FUSES.
ALARMS ON BLOWN FUSE
OR HEAD REMOVAL
G33 LOADS
G61A, G63A
RETURNS
COMCODE
0.18 ALARM FUSE
TABLE 4BB LUGS AND HARDWARE FOR BREAKERS AND FUSES
G30B, G31B,
G31C LOADS
TABLE 4C OPTIONAL
ALTERNATE FUSE BLOCKS
(G30B)
WIRE GAGE
STD
FLEX
14-10
14-10
406338343
8
8
405347519
406338442
6
6
405347543
405347576
406338574
4
4
405348186
405348202
406338673
406338665
2
-
405347659
405347683
407726041
-
2
406338707
407817568
406338715
405348228
1/0
-
406467183
407817550
406338764
405348236
2/0
1/0
HARDWARE
LUG
COMCODE
TYPE
997758891
WIRE GAGE
STD
FLEX
EITHER
18-22
18-22
403950975
EITHER
14-16
14-16
401437033
EITHER
10-12
10-12
HARDWARE
CIRCUIT BREAKER APPROVED FOR
G30B, G31B, G31C DISTRIBUTION PANELS
(NOT ORDERABLE FROM LINEAGE POWER)
PROVIDED
CURRENT RATING
FOR ED83127-30 GD
PROVIDED
G
406338376
LOAD
405347519
RTN
406338483
LOAD
405347576
RTN
407334697
LOAD
405347683
RTN
406338616
LOAD
405348202
RTN
406434514
LOAD
407817568
RTN
406338822
LOAD
407817550
RTN
406434076
LOAD
407817576
RTN
6
4
2
1/0
2/0
-
6
4
2
-
PROVIDED
1/0
2/0
AIRPAX
PART NUMBER
1 LONG DELAY
LMLK1-1RLS4-32742-18
3 LONG DELAY
LMLK1-1RLS4-32742-1
5 LONG DELAY
LMLK1-1RLS4-32742-2
10 LONG DELAY
LMLK1-1RLS4-32742-3
15 LONG DELAY
LMLK1-1RLS4-32742-4
20 LONG DELAY
LMLK1-1RLS4-32742-6
25 LONG DELAY
LMLK1-1RLS4-32742-7
30 LONG DELAY
LMLK1-1RLS4-32742-8
30 MOTOR - START DELAY
LMLK1-1RLS4-32744-8
40 LONG DELAY
LMLK1-1RLS4-32742-17
50 LONG DELAY
LMLK1-1RLS4-32742-10
60 LONG DELAY
LMLK1-1RLS4-32742-11
70 LONG DELAY
LMLK1-1RLS4-32742-12
80 LONG DELAY
LMLK1-1RLS4-32742-13
90 LONG DELAY
LMLK1-1RLS4-32742-14
100 LONG DELAY
LMLK1-1RLS4-32742-15
F
G
TITLE
SECONDARY POWER DISTRIBUTION BAY (BDFB/DBCBB)
H
H
DRAWING DESCRIPTION
SHEET
DOC TYPE
DWG
C2FORMAT.FRM DEC 2002
0
1
2
3
4
5
6
7
H569445-AD
8
A5
ISSUE
DWG
SIZE
26
9
C2/A1R
0
1
2
3
4
ENG
DES
SUP
DATE
REV
GGL
GGL
SCS
31-JAN-2014
30
TABLE AA: SPARE, GROWTH, AND UPGRADE EQUIPMENT
SPARES, GROWTH AND UPGRADES FOR GROUP 1, 2 OR 3 CABINETS
B
COMCODE
DESCRIPTION
848376323
(2) FUSE PANEL (20 POSITION) KIT
848376315
(2) BULLET PANEL (20 POSITION) KIT
848433918
(1) BLANK PANEL KIT
848376331
(1) LOAD SHUNT ASSY KIT (800 AMP FOR J85568C2/H569445)
848363792
(1) LOAD SHUNT ASSY KIT (600 AMP FOR J85568C-1)
848648135
(1) 300 AMP SHUNT ASSEMBLY (FOR J865568C-2)
848433363
(1) BUS BAR BATTERY STRAP KIT (G30B,G31B,G31C)
848589537
(1) INTERNAL RETURN KIT (INCLUDES ONE G61 AND FOUR G61A)
C
CC109124608
(1) FILTER CAPACITOR ASSEMBLY LEFT (G31C ONLY)
CC109124616
(1) FILTER CAPACITOR ASSEMBLY RIGHT (G31C ONLY)
(1) TOP COVER KIT (G1 OR G7, 7FT CABINETS) (FOR USE ON
BOTTOM FEED/BOTTOM DISTRIBUTION APPLICATION ONLY)
(1) TOP COVER KIT (G2, 9FT CABINET) (FOR USE ON
BOTTOM FEED/BOTTOM DISTRIBUTION APPLICATION ONLY)
150037640
TOP COVER KIT, 34IN WIDE BDFB, J85568C2L67 (PLASTIC TOP COVER)
150037677
DOOR WITH GUARD, H569445G33 PANEL KIT ASSY
METERS AND ALARM BOARDS FOR GROUP 1, 2 OR 3 CABINETS
848376349
D
E
(1) G70 DIGITAL CURRENT METER KIT FOR G1 OR G2 BDFB:
INCLUDES METER AND HARDWARE NEEDED FOR METER INSTALLATION
848498804
(1) G71 DIGITAL VOLTAGE/CURRENT METER KIT FOR G1 OR G2 BDFB:
INCLUDES METER AND HARDWARE NEEDED FOR METER INSTALLATION
DES
SUP
DATE
REV
HKS
GGL
SCS
12-AUG-2008
20
CC109144341
CC109144812
DATE
REV
PDI:02ESDJ0521
KEG
KEG
SCS
25-MAR-2009
21
MCN
ENG
DES
SUP
DATE
REV
KEG
KEG
SCS
01-NOV-2011
22
ENG
DES
SUP
DATE
REV
KEG
KEG
SCS
19-DEC-2011
23
SCS
26-APR-2012
24
(1) G72 DIGITAL VOLTAGE/CURRENT METER KIT FOR G1 OR G2 BDFB:
INCLUDES METER AND HARDWARE NEEDED FOR METER INSTALLATION
ADD CONFIGURATIONS TO STANDARD
CONFIGURATION TABLE ON SHEET A1.
ADD 3-POLE BREAKER OPTIONS ON
TABLE 4A. SHOW EXTENDED BUS ON
GROUP 23 LOAD SHUNT ON SHEET B5.
CN-0009824
CC109145620
(1) CABLE ASSEMBLY FROM G72 OR G172 METER TO BAY LAMP
(2) 28-POSITION BULLET DISTRIBUTION PANELS
150021902
(2) LOAD BUS SHUNT ASSEMBLIES (1500A SHUNT SIZE)
150026362
INTERNAL RETURN BUS KIT (G63)
150027305
INTERNAL RETURN BUS KIT (G63A) (MOUNTS ON G33 DISTRIBUTION PANELS)
CC109172747
ALARM TERMINATION BOARD
CC109172730
PANEL LED ALARM BOARD
CC109172854
VIM1C DIGITAL METER ASSEMBLY
ENG
DES
SUP
DATE
REV
KEG
KEG
SCS
24-JUL-2012
25
KAL
15-OCT-2003
13
CHGD: SHA3: TORQUE CALLOUT IN
TABLE F "65" WAS "75".
SHA1: SHEET INDEX.
SHA6: ISSUE BLOCK ADDED
848745118-LBL
PDI: 04ESDJ0325
DES
CL:ME
DATE
REV /
ISSUE
MCN/SCS 17-NOV-2004
14
ENG
DES
ENG
BAR
SKR
DATE
REV /
ISSUE
31-JAN-2006
15
SHA1: UPDATED SHEET INDEX.
SHA4: TABLE 6AA COMCODE
407890730 WAS 405434290
SHA6: ADDED ISSUE 16.
ENG
KAL
DATE
20-APR-2006
16
KEG
KEG
SCS
23-AUG-2012
26
DES
ENG
KAL
SHEET A4, ADDED 4-1/2 FOOT
EXTENSION (150030560) IN
TABLE 1D. ADDED BREAKER
COVER SHOWN ON VARIOUS
SHEETS
GGL
SCS
20-NOV-2013
28
FUSE HOLDER FOR (10) GMT FUSES (1 ON EACH FUSE PANEL)
IN TABLE AA, ADDED THE
PLASTIC TOP COVER (150037640)
KAL
SHA1: CHG'D FIG A TO READ
TOP/TOP. CHG'D FIG B TO
READ TOP/BOTTOM, CHG'D
FIG C TO READ BOTTOM/
BOTTOM. CHG'D FIG D TO
READ BOTTOM/TOP. STEP 4
ADDED 90 AMP TO NOTE WAS
100 AMP. SHA2: ADDED
STEP 6A TO DISCHARGE
RETURN BUS OPTIONS.
ADDED STEP 4A TO DIGITAL
CURRENT METER AND DIGITAL
VOLTAGE/CURRENT METER.
SHA3: LOC. C1 TABLE FIELD
INSTALLED EQUIP. ADDED LINE
TABLE 4G SPARE FUSE HOLDER
EQPT LOC. D5 CABINET GROUND
CH'D TEXT TO READ GREATER
THAN 2/0 WAS GREATER THAN
1/0. LOC E5 CENTRAL OFF.
GND. ADD REF TO SEE TBL
SEE TBL 1C & 6AA. LOC. A9
RMV NTS. LOC A9 CH COMCODE
TO READ 106849508 WS
106849506. CH'D DSCR ON
848376323, 848376315 TO
QTY 2, WS 1. ADD 848363792,
108405283 TO SPARE GROWTH
& UPDGRADE TBL. ADD TXT
FOR FIG'S A-D TO "CABLE
ROUTING STRATEGY". SHA4:
ADD NT TO TBL 1A (REFER TO
H569-407). ADD (ZN'S 0-2)
TO 1ST 2 ITMS. (847135654 &
847135662). RMVD LAST TWO
ITMS (847135712 AND
847135720). ADD "ROD" TO
847135670 & "BOLT" TO
847135688. TBL 1B & 1C,
RMVD HARDWARE PROVIDED
COLUMN, RMVD HARDWARE
COLUMN FRM TBLS 1B & 1C.
ADD NTS FOR INFO ON
HARDWARE. TBL 1C, ADD
STRND'D WIRE. TBL 4DD
ADD 402099436. TBL 4E ADD
408239648. TBL 4C ADD
1083194270. SHA5: ADD TBL
4G, ADD NEW STANDARD CC
TO TBL BB. SHB10: ADD
DUMMY BOARD. SH B7: ADD
1-24 TO FIG.6. SHD: ADD
ITMS 73,74,82,83. SHA4:
TBL 4BB ADD 406467183 WS
406896373. SHB5: ADD NEW
COMCODE FOR INTERNAL RTN
KIT
PDI: 00ESDJ0173
REV /
ISSUE
REV
GGL
FUSE PULLER FOR TPS AND TLS FUSES
KAL
DATE
DESCRIPTION
407573641
DATE
REV /
ISSUE
SUP
COMCODE
GMT FUSE PULLER
CL:ME
DES
REV
406420273
12
ENG
DATE
FUSE HOLDER FOR (1) TPL-B FUSE.
TYPICALLY ORDERED WHEN TPL-B FUSE BLOCKS
ARE EQUIPPED IN BDFB. HAVE INSTALLER REPLACE
EITHER OF THE TWO HOLDERS LISTED ABOVE.
05-JUN-2003
SHA1: UPDATED SHEET INDEX.
SHA4: ADDED 1 FT EXTENSION
SHA6: ADDED ISSUE 17.
SUP
407559491
MCN
KAL
DES
FUSE HOLDER FOR (6) TPS, TLS FUSES (1 ON EACH FUSE PANEL)
REV /
ISSUE
ENG
DES
ENG
407559467
DATE
SHA3: ADD CC109121563 AND
CC109121571 TO TABLE AA
SHA4: TABLE1A CC109121588 WAS
848692612. CC109121596 WAS
848692620
TABLE 4G: SPARE FUSE HOLDERS AND HARDWARE (REF H569431)
407559459
DES
MCN
ADD HARDWARE KITS TO TABLE 6AA.
UPDATE TABLE AA SPARES AND
UPGRADE. ADD DIMENSIONS TO TOP
VIEWS ON SHEETS B12A AND B12D.
CN-0010275
150021903
CL:ME
ENG
PDI: 03ESDJ0315
KEG
(1) ALARM OUTPUT CABLE ASSEMBLY FOR G72 OR G172 METER.
11
SH A1: CORRECTED SH INDEX
SH B6: CORRECTED ISSUE NO.
KEG
CC109145612
PDI: 03ESDJ0172
MCN
(1) G172 DIGITAL VOLTAGE/CURRENT METER KIT FOR G3 BDFB:
INCLUDES METER AND HARDWARE NEEDED FOR METER INSTALLATION
(1) FIELD UPGRADE G72 METER KIT FOR G1 OR G2 BDFB TO REPLACE A G71 METER:
INCLUDES METER, HARDWARE AND CONVERSION CABLE FOR FIELD UPGRADE KIT.
CONVERSION CABLE INTERFACES BETWEEN EXISTING CABLE AND NEW METER.
CL:ME
MCN
10-15-02
SCS
SHB11: CHGD CALLOUTS (A2), (A4).
RMVD WIRING SCHEMATICS & ADD A
NEW SCHEMATIC TO ZN (A7). SH F1:
RMV VIEW ZN (C8), ADD 2 VIEWS ZN
(C8), (F8). ADD SHB12C
DES
REV
CC109145315
10
CHG B4, B10, B11. ADD B1B, B12B,
F1, F2. RENAMED B1 TO B1A, B12
TO B12A, ADDED INFO TO A SHEETS.
ADDED TABLE TL TO SHT A5
ADD GRPS 3,31C,40,170,62,&62A
SUP
DATE
(1) FIELD UPGRADE G172 METER KIT FOR G3 BDFB TO REPLACE A G171 METER:
INCLUDES METER, HARDWARE AND CONVERSION CABLE FOR FIELD UPGRADE KIT.
CONVERSION CABLE INTERFACES BETWEEN EXISTING CABLE AND NEW METER.
MCN
10-01-02
SCS
DES
SUP
CC109145307
9
CL: ME
MCN
ENG
DES
METERS AND ALARM BOARDS FOR GROUP 7 OR 8 CABINETS
G
ENG
ENG
SPARES, GROWTH AND UPGRADES FOR GROUP 7 OR 8 CABINETS
F
PDI: 02ESDJ0450
ADD GROUP 8. ADD 125 AND 175
AMP BREAKER KITS TO TABLE 4A
CN-0008283
(1) BEP1A- ALARM CIRCUIT MODULE
8
CHANGE TABLE BB TO HAVE ALL
NEW COMCODES.
UPDATE SHEET A5 TABLES.
ADD SHEET B8A EXTERNAL RETURN
BUS OPTIONS. ADD WIRING
DIAGRAMS ON SHEETS B10 AND B11.
CN-0006293
(1) TOP COVER KIT (G1 OR G7, 7FT CABINET) (FOR USE ON
TOP FEED/TOP DISTRIBUTION APPLICATION ONLY)
848430179
CC109129615
CHANGES REQUIRED DUE TO THE
NEW BDFB METER,
ADDED SHEET B11A,
REMOVED SHEET D1
ADD G7, G23, G33, G63, G63A
AND G272 INFORMATION.
(1) BAY INTERCONNECTION KIT FOR LIST 3 CABINET (NORTEL BDFB)
CC109121571
7
SHEETS A1 - A6 UPDATED
TO CLARIFY PRODUCT INFORMATION
CC109121563
848429288
6
IN TABLE AA, ADDED THE
ORDERABLE DOOR KIT (150037677)
SPARE, GROWTH AND UPGRADE EQUIPMENT
A
5
DATE
REV /
ISSUE
27-SEP-2006
17
A
B
C
D
CL:ME
E
SH A1: UPDT FUSE/CB PANEL TO ADD
INFO ON PLUG-IN FUSE HOLDERS.
SH A2: CORRECT DOC ERRORS
SH A3: ADD PLUG-IN FUSE HLDR AND
TLS FUSE INFO TO TBL OF FIELD
INSTALLED PARTS
SH A6: ADD PLUG-IN FUSE HLDRS
AND TLS FUSES
DES
ENG
KAL
KAL
F
DATE
REV /
ISSUE
01-MAY-2007
18
ENG
DES
SUP
DATE
REV
CHANGE NOTE SHA1 ZONE C6
PER JEFF PLATTENBURG
GGL
GGL
SCS
30-JAN-2014
29
ENG
DES
SUP
DATE
REV
SHA4: UPDT TBL F WITH
848656823.
SHD1: ADD ITMS 1, 2 WHICH
WERE ACCIDENTALLY RMVD IN
PAST.
MCN
MCN
SCS
15-OCT-2007
19
PDI: 01ESDJ0524
G
CL:ME
TITLE
SECONDARY POWER DISTRIBUTION BAY (BDFB/DBCBB)
H
H
DRAWING DESCRIPTION
***
SHEET
DOC TYPE
DWG
C2FORMAT.FRM DEC 2002
0
1
2
3
4
5
6
7
H569445-AD
8
A6
ISSUE
DWG
SIZE
30
9
C2/A1R
0
1
2
3
4
5
6
7
8
9
15.00 REF
G61 SET OF 2 RETURN BUS BARS. MOUNTS
TOP OF CABINET FOR G10A AND G10B (SHOWN).
BOTTOM OF CABINET FOR G10C AND G10D.
A
B
A
B
G20 LOAD SHUNT DETAIL
SEE SHEET B5
VIM1 METER (G72)
848204939
7 FT CABINET
C
G30B
2 SIDE BY SIDE
FUSE PANELS
OR
G31B
2 SIDE BY SIDE
BULLET PANELS
(3 PLACES SHOWN)
OR
G90
2 SIDE BY SIDE
BLANK PANELS
D
C
83.94
REF
D
2 SIDE BY SIDE
BUS BAR LINKS
PANEL RETURN BUS LINK
PROVIDED WITH G61A
E
E
G61A
2 SIDE BY SIDE
PANEL RETURN
BUS BARS.
F
F
G
G
SIDE VIEW
FRONT VIEW}
SCALE 3/16
REAR VIEW
(CLEAR COVERS REMOVED)
25.94 REF
TITLE
SECONDARY POWER DISTRIBUTION BAY (BDFB/DBCBB)
H569445 G1 E/W G10A, G20,
(3)G31B, G61, (3) G61A, G72
H
H
DRAWING DESCRIPTION
SHEET
DOC TYPE
DWG
C2FORMAT.FRM DEC 2002
0
1
2
3
4
5
6
7
H569445-AD
8
B1
ISSUE
DWG
SIZE
22
9
C2/A1R
0
1
2
3
4
5
6
7
8
9
G63 SET OF 2 RETURN BUS BARS.
MOUNTS TOP OF CABINET FOR G10A
AND G10B (SHOWN). BOTTOM OF
CABINET FOR G10C AND G10D.
15.00
A
A
APPLY LABEL
850036078
(LABEL IS SUPPLIED WITH
THE G108 BREAKER PANEL ASSY)
6 PLACES
COVER
850035641
(SUPPLIED WITH THE
G108 BREAKER PANEL)
6 PLACES
SCREW
901354878
(SUPPLIED WITH BREAKER
PANEL)
24 PLACES
B
B
850017023
7 FT CABINET
VIM1 METER (G272)
C
C
G33
2 SIDE BY SIDE
BULLET PANELS
(3 PLACES SHOWN)
OR
G90
LOAD SHUNT DETAIL
(G23) SEE SHEET B5A
2 SIDE BY SIDE
BLANK PANELS
D
D
83.94
2 SIDE BY SIDE
BUS BAR LINKS
PANEL RETURN BUS LINK
PROVIDED WITH G63A
E
E
G63A
2 SIDE BY SIDE
PANEL RETURN
BUS BARS.
F
F
G
G
HARDWARE BOX LOCATED
BEHIND THIS COVER
SIDE VIEW
FRONT VIEW
SCALE 3/16
REAR VIEW
(CLEAR COVERS REMOVED)
25.94
TITLE
SECONDARY POWER DISTRIBUTION BAY (BDFB/DBCBB)
H569445 G7 E/W G10A, G23,
(3)G33, G63, (3) G63A, G272
H
H
DRAWING DESCRIPTION
SHEET
DOC TYPE
DWG
C2FORMAT.FRM DEC 2002
0
1
2
3
4
5
6
7
H569445-AD
8
B1A
ISSUE
DWG
SIZE
28
9
C2/A1R
0
1
2
3
4
5
6
7
8
9
(2) 848689998
REAR DOOR
A
A
G62 SET OF 4 RETURN BUS BARS. MOUNTS
TOP AND BOTTOM OF CABINET.
VIM1 METER (G172)
848689972
CABINET
B
B
G20 LOAD
SHUNT DETAIL
SEE SHEET B5
C
C
2 SIDE BY SIDE
BUS BAR LINKS
PANEL RETURN
BUS LINK
PROVIDED
WITH G62A
D
D
83.7
848689972
CABINET
E
E
G62A
2 SIDE BY SIDE
PANEL RETURN
BUS BARS.
G31C
2 SIDE BY SIDE
BULLET PANELS
(3 PLACES SHOWN)
OR
G90
2 SIDE BY SIDE
BLANK PANELS
F
G
F
23.6
REAR VIEW
DOOR REMOVED 848689998
SIDE VIEW
FRONT VIEW
DOOR REMOVED 848689998
TITLE
SECONDARY POWER DISTRIBUTION BAY (BDFB/DBCBB)
H569445 G3 E/W (3)G20,
(3)G31C, G62, (3)G62A, G172
H
G
23.6
H
DRAWING DESCRIPTION
SHEET
DOC TYPE
DWG
C2FORMAT.FRM DEC 2002
0
1
2
3
4
5
6
7
H569445-AD
8
B1B
ISSUE
DWG
SIZE
22
9
C2/A1R
0
1
2
3
4
5
6
7
8
9
G63 SET OF 2 RETURN BUS BARS.
MOUNTS TOP OF CABINET FOR G10A
AND G10B (SHOWN). BOTTOM OF
CABINET FOR G10C AND G10D.
A
A
APPLY LABEL
850036078
(LABEL IS SUPPLIED WITH THE
G108 BREAKER PANEL ASSY)
6 PLACES
B
B
850022780
7 FT CABINET
C
C
G33
2 SIDE BY SIDE
BULLET PANELS
(3 PLACES SHOWN)
OR
G90
2 SIDE BY SIDE
BLANK PANELS
LOAD SHUNT DETAIL
(G23) SEE SHEET B5A
D
D
83.94
2 SIDE BY SIDE
BUS BAR LINKS
PANEL RETURN BUS LINK
PROVIDED WITH G63A
E
E
G63A
2 SIDE BY SIDE
PANEL RETURN
BUS BARS.
F
F
G
G
SIDE VIEW
FRONT VIEW
HARDWARE BOX LOCATED
BEHIND THIS COVER
REAR VIEW
(CLEAR COVERS REMOVED)
15.00
33.94
TITLE
DISTRIBUTION BAY, BDFB/CBB
H569445 G8 E/W G10A, G23,
(3)G33, G63, (3) G63A, G272
H
H
DRAWING DESCRIPTION
SHEET
DOC TYPE
DWG
C2FORMAT.FRM DEC 2002
0
1
2
3
4
5
6
7
H569445-AD
8
B1C
ISSUE
DWG
SIZE
28
9
C2/A1R
0
1
2
3
4
5
6
7
8
18.00 REF
9
G61 SET OF 2 RETURN BUS BARS. MOUNTS
TOP OF CABINET FOR G10A AND G10B (SHOWN).
BOTTOM OF CABINET FOR G10C AND G10D.
A
A
B
B
G20 LOAD SHUNT DETAIL
SEE SHEET B5
C
C
VIM1 METER (G72)
107.94
REF
PANEL RETURN BUS LINK
PROVIDED WITH G61A
G30B
D
2 SIDE BY SIDE
FUSE PANELS
(4 PLACES SHOWN)
D
OR
G31B
2 SIDE BY SIDE
BULLET PANELS
848241238
9 FT CABINET
OR
G90
2 SIDE BY SIDE
BLANK PANELS
E
E
2 SIDE BY SIDE
BUS BAR LINKS
F
F
G61A
2 SIDE BY SIDE
PANEL RETURN
BUS BARS.
G
G
FRONT VIEW
REAR VIEW
(CLEAR COVERS REMOVED)
SIDE VIEW
SCALE 5/32
TITLE
SECONDARY POWER DISTRIBUTION BAY (BDFB/DBCBB)
25.94 REF
H
H
DRAWING DESCRIPTION
H569445 G2 E/W G10A, G20,
(4)G30B, G61, (4) G61A, G72
DWG
C2FORMAT.FRM DEC 2002
0
1
2
3
4
5
SHEET
DOC TYPE
6
7
H569445-AD
8
B2
ISSUE
DWG
SIZE
22
9
C2/A1R
0
1
2
3
4
5
6
7
8
9
A
A
PANEL
POSITION 2
PANEL
POSITION 1
B
PANEL
POSITION 6
PANEL
POSITION 5
B
C
C
PANEL
POSITION 4
PANEL
POSITION 3
PANEL
POSITION 4
PANEL
POSITION 3
D
D
E
E
PANEL
POSITION 5
PANEL
POSITION 1
PANEL
POSITION 2
PANEL
POSITION 6
F
F
G
G
G10A OR G10D
TOP DISTRIBUTION OUTPUT
PANEL NUMBERING
(SIMILAR FOR 9FT CABINET)
G10B OR G10C
BOTTOM DISTRIBUTION OUTPUT
CABINET IS FILLED WITH
DC PANELS FROM THE TOP DOWN
CABINET IS FILLED WITH
DC PANELS FROM THE BOTTOM UP
OUTPUT CABLES ARE ROUTED OUT THE TOP
TITLE
SECONDARY POWER DISTRIBUTION BAY (BDFB/DBCBB)
OUTPUT CABLES ARE ROUTED OUT THE BOTTOM
H
H
DRAWING DESCRIPTION
SHEET
DOC TYPE
DWG
C2FORMAT.FRM DEC 2002
0
1
2
3
4
5
6
7
H569445-AD
8
B3
ISSUE
DWG
SIZE
22
9
C2/A1R
0
1
2
3
202A TERMINAL
A
CC408576152
FLAT WASHER 3/8
CC408575988
LOCK WASHER 3/8
CC408576086
NUT 3/8 - 16
(10 PLCS PER BUS)
(TORQUE: 240 IN-LB)
202A TERMINAL
E3
4
5
6
7
8
9
E4
CC408576268 LAMP
407226786 LENS COVER
406156729 LAMP SOCKET
A
(4) CC408575963 BOLT HH .375-16 X 1.5"
(8) CC408576152 FLAT WASHER 3/8
(4) CC408575988 LOCK WASHER 3/8
(4) CC408576086 NUT 3/8 - 16
(TORQUE: 240 IN-LB)
B
B
G61
BUS BAR RETURN
TOP OF CABINET FOR G10A AND G10B
BOTTOM OF CABINET FOR G10C AND G10D
C
C
SHUNT, 800A, 50mV
G61A RETURN BUS BAR
D
D
848271771
BUS BAR STRAP
INSTALLED ONLY WHEN
NEXT PANEL HAS NO
SHUNT DETAIL
E
E
846874600
BUS BAR STRAP
LIST 20 SHUNT DETAIL
TOP FEED ORIENTATION
F
BOTTOM FEED ORIENTATION
F
IF LOAD SHUNT ASSEMBLY IS
NOT EQUIPPED ON A PANEL
SHUNT WIRES WILL BE
ATTACHED TO BUS HERE
CC848846642
LAMP CABLE
CC848846287
ALARM CABLE
CC848841783
PRIMARY
CABLE
G
G
CC848841791
SECONDARY
CABLE
G1 OR G2 CABINETS WITH G30B PANELS,
G20 LOAD SHUNTS AND
G61 AND G61A INTERNAL RETURN BUSES
TITLE
SECONDARY POWER DISTRIBUTION BAY (BDFB/DBCBB)
H
H
DRAWING DESCRIPTION
SHEET
DOC TYPE
DWG
C2FORMAT.FRM DEC 2002
0
1
2
3
4
5
6
7
H569445-AD
8
B4
ISSUE
DWG
SIZE
22
9
C2/A1R
0
1
2
3
4
5
6
7
8
9
G63
BUS BAR RETURN ASSEMBLY
TOP OF CABINET FOR G10A AND G10B
BOTTOM OF CABINET FOR G10C AND G10D
A
B
A
B
SHUNT 1500A, 50mV
ATTACH STANDOFFS TO
STUDS ON PANEL
(G23)
(2) 802101790 BOLT 5/16 X 1-1/2
(2) CC408576160 LOCK WASHER
(2) CC408576193 FLAT WASHER
C
(G23)
C
850018532 WIRESET
(2 PER ALARM BOARD)
G63
RETURN BUS BAR
D
D
850018530
ALARM CABLE
42) CC408575963 BOLT HH .375-16 X 1.5"
(8) CC408576152 FLAT WASHER 3/8
(4) CC408575988 LOCK WASHER 3/8
(4) CC408576086 NUT 3/8 - 16
(TORQUE: 240 IN-LB)
850018534
METER INPUT CABLE
E
CC848925743 BUS STRAP INSTALLED
AS SHOWN WHEN NEXT PANEL IS
NOT EQUIPPED WITH LOAD SHUNT.
UNUSED STRAPS AND MOUNTING
HARDWARE SHIP LOOSE IN HARDWARE
BOX.
G23 SHUNT DETAIL
E
P/O G63A
CC848925743 BUS BAR STRAP
F
F
G
G
G7 (SHOWN) OR G8 CABINET WITH
G33 PANELS, G23 LOAD SHUNTS AND
G63 AND G63A INTERNAL RETURN BUSES
850018532 WIRESET
(2 PER ALARM BOARD)
850018533 WIRESET
(CONNECTS BETWEEN ALARM BOARDS)
SCALE 7/16
TITLE
SECONDARY POWER DISTRIBUTION BAY (BDFB/DBCBB)
H
H
DRAWING DESCRIPTION
SHEET
DOC TYPE
DWG
C2FORMAT.FRM DEC 2002
0
1
2
3
4
5
6
7
H569445-AD
8
B5
ISSUE
DWG
SIZE
25
9
C2/A1R
0
1
2
3
4
5
6
7
8
9
(4) 407633601 STANDOFFS
CC109129615 BEP1A PWB
(PER DISTRIBUTION PANEL)
A
A
(4) 407633601 STANDOFFS
CC109129615 BEP1A PWB
(PER DISTRIBUTION PANEL)
POS 1
POS 1
B
B
848270765
POSITION
NUMBERING
LABELS 1-20
848270765
POSITION
NUMBERING
LABELS 1-20
C
C
407559467
SPARE FUSE HOLDER
D
D
407559459
SPARE FUSE HOLDER
GROUP 31B BULLET PANELS
IN GROUP 1 OR 2 CABINETS
GROUP 30B FUSE PANELS
IN GROUP 1 OR 2 CABINETS
E
RISER COVER OVER BEP1A
MODULES NOT SHOWN FOR CLARITY
RISER COVER OVER BEP1A
MODULES NOT SHOWN FOR CLARITY
E
CC109172747
BDFB_BAY_BD
BAY ALARM BOARD
F
F
APPLY LABEL
850036078
SUPPLIED WITH THE G108
BREAKER PANEL)
6 PLACES
CC109172730
BDFB_PNL_BD
PANEL ALARM BOARD
(ONE PER PAIR OF PANELS)
BREAKER COVER
850035641 (6 PLACES)
SCREW
901354878 (24 PLACES)
(COVER AND SCREWS ARE
SUPPLIED WITH THE
BREAKER PANEL)
G
G
TITLE
SECONDARY POWER DISTRIBUTION BAY (BDFB/DBCBB)
GROUP 33 BULLET PANELS
IN GROUP 7 OR 8 CABINETS
H
H
DRAWING DESCRIPTION
C2FORMAT.FRM DEC 2002
0
1
2
3
4
SHEET
DOC TYPE
TOP COVER OVER BAY ALARM
BOARD NOT SHOWN FOR CLARITY
DWG
5
6
7
H569445-AD
8
B6
ISSUE
DWG
SIZE
28
9
C2/A1R
0
1
2
3
4
5
6
7
8
9
848258679 2400A EXTERNAL GROUND BAR KIT
AND 848258687 SUPPLEMENTARY BUS BAR KITS
A
A
B
B
848258687 MOUNTS ON TOP
OF A 848258679 BUS KIT
C
C
.38 REF
4.75
848258687
BUS KIT
4.00
D
D
848258679
BUS KIT
E
E
20 SPACES AT 1.05 = 21.00
(.44" DIA ON 1.00 CENTERS)
23 SPACES AT 0.44 = 10.12
(.22" DIA ON 0.625 CENTERS)
F
ROW A
F
21
1
24
1
ROW B
G
G
4
1
ROW C
6.00
3 SPACES AT 2.00 = 6.00
(.44" DIA ON 1.00 CENTERS)
TITLE
SECONDARY POWER DISTRIBUTION BAY (BDFB/DBCBB)
15.62
FOR 15 INCH CABLE RACK
H
H
DRAWING DESCRIPTION
20.62
FOR 20 INCH CABLE RACK
DWG
26.00
C2FORMAT.FRM DEC 2002
0
1
2
SHEET
DOC TYPE
3
4
5
6
7
H569445-AD
8
B7
ISSUE
DWG
SIZE
23
9
C2/A1R
0
1
2
3
4
5
6
7
8
9
ED8301950 GROUP 1 1300A EXTERNAL GROUND BAR KIT
AND GROUP 3 SUPPLEMENTARY BUS BAR KITS
A
A
B
B
C
C
GROUP 3 MOUNTS ON TOP
OF A GROUP 1 BUS KIT
843780602 BUS
.25 REF
D
D
4.50
GROUP 3 BUS KIT
4.00
E
F
9 SPACES AT 1.12 = 10.08
(.2" DIA ON 0.62 CENTERS)
11 SPACES AT 0.50 = 5.50
(.2" DIA ON 0.62 CENTERS)
ROW A
8 SPACES AT 1.12 = 8.96
(.44" DIA ON 1.00 CENTERS)
34
1
4.50
1
9
6
ROW B
ROW C
ROW D
F
11 SPACES AT 0.50 = 5.50
(.2" DIA ON 0.62 CENTERS)
1
G
E
GROUP 1 BUS KIT
G
5
2
26
1
TITLE
SECONDARY POWER DISTRIBUTION BAY (BDFB/DBCBB)
3 SPACES AT 1.88 = 5.63
(.44" DIA ON 1.00 CENTERS)
2.50
H
H
DRAWING DESCRIPTION
15.62
20.62
C2FORMAT.FRM DEC 2002
0
1
2
SHEET
DOC TYPE
23.62
DWG
3
4
5
6
7
H569445-AD
8
B8
ISSUE
DWG
SIZE
23
9
C2/A1R
0
1
2
3
4
5
6
7
8
9
ED8301950 GROUP 13 2400A EXTERNAL GROUND BAR KIT
AND GROUP 13A SUPPLEMENTARY BUS BAR KITS
A
A
B
B
C
850021151 BUS
GROUP 13A MOUNTS ON TOP
OF A GROUP 13 BUS KIT
.38 REF
C
4.75
4.00
GROUP 13A BUS KIT
D
D
GROUP 13 BUS KIT
E
E
27 SPACES AT 1.00 = 27.00
(.44" DIA ON 1.00 CENTERS)
19 SPACES AT 0.625 = 11.88
(.28" DIA ON 0.625 CENTERS)
F
G
F
28
ROW A
1
ROW B
1
28
ROW C
1
12
6.00
G
3 SPACES AT 2.00 = 6.00
(.44" DIA ON 1.00 CENTERS)
3 SPACES AT 0.625 = 1.88
(.28" DIA ON 0.625 CENTERS)
3 SPACES AT 0.625 = 1.88
(.28" DIA ON 0.625 CENTERS)
DRAWING DESCRIPTION
3 SPACES AT 1.00 = 3.00
(.44" DIA ON 1.00 CENTERS)
3 SPACES AT 1.00 = 3.00
(.44" DIA ON 1.00 CENTERS)
H
TITLE
SECONDARY POWER DISTRIBUTION BAY (BDFB/DBCBB)
THIRD ANGLE PJTN
28.60
C2_ASSY_FORMAT.FRM FEB 2003
0
1
2
2
3
3
DOC TYPE
DWG
4
H
LINEAGE POWER - PROPRIETARY
USE PURSUANT TO COMPANY INSTRUCTIONS
5
6
7
DRAWING ID
H569445-AD
8
SHEET
ISSUE
B8A
23
9
DWG
SIZE
C2/A1R
0
1
2
3
4
BEP1A PWB
(TYP PER PANEL)
A
5
6
7
8
FRAME LIGHT
J701
A
CC848846642
(BK)
J701
FRAME
LAMP
(RD)
202A
TERM
CC848846287
202A
TERM
E3
E4
(RD)
(W-Y)
22 GA
FIELD
WIRING
407227172 LAMP (48V)
407226786 LENS COVER
406156729 LAMP SOCKET
OVL NC
(O)
B
J3
ALARM
OUTPUT
OVL NO
(W-S)
OVL C
(W-O)
PL NC
(W-Y)
TO BEP1 MODULE
OF PANEL POSITION #1
P/O CC848784710 WIRESET
OR 846940872 WIRESET
J3
FUSE C
(S)
TO BEP1 MODULE
OF PANEL POSITION #1
P/O CC848784710 WIRESET
OR 846940872 WIRESET
C
FUSE NO
(BL)
(BK) 22 GA
P102
FUSE NC
(W-BL)
(W-S)
22 GA
B
D
9
PL NO
(Y)
PL C
(W)
C
P102.1
(W-S) TO E3 TERM
FAJ (Y)
(W-Y) TO LAMP
PWR (BL)
J1
TO
DISTRIBUTION
PANEL 1
CC848841783
SHUNT 1+
(W-BL)
RTN (BR) RETURN BUS 1
IF PRESENT OR
DAISY CHAIN TO BR WIRE
ON P102.2 CONNECTOR
RTN (BR) COILED AT
TOP OF CABINET FOR
EXTERNAL RETURN BUS
OPTION ONLY
SHUNT 1-
(BL)
SHUNT 2+
(W-SL)
SHUNT 3+
(W-O)
SHUNT 3-
(O)
P102.2
SHUNT 4+
(W-Y)
FAJ (V)
TO
DISTRIBUTION
PANEL 2
E
FAJ B-2
(BR)
CONNECT TO RETURN BUS 1
IF PRESENT OR COILED AT
TOP OF CABINET FOR
EXTERNAL RETURN BUS
FAJ (Y)
TO
DISTRIBUTION
PANEL 3
PWR (BL)
FAJ A
(RD)
FAJ B
(BK)
RTN
CC848841791
(G)
(W-BL)
(BL)
(W-SL)
(SL)
(W-O)
RTN (BR) RETURN BUS 1
IF PRESENT OR
DAISY CHAIN TO BR WIRE
ON P102.2 CONNECTOR
(O)
(W-Y)
(Y)
(BR)
(W)
(W-BK)
G
E
VOLTAGE 4
(W-BR)
FAJ B-3
FAJ B-4
P102.3
F
VOLTAGE 3
(BR)
FAJ A-4
FAJ B-1
VOLTAGE 2
(W-BK)
FAJ A-3
RTN (BR) RETURN BUS 2
IF PRESENT OR
DAISY CHAIN TO BR WIRE
ON P102.3 CONNECTOR
VOLTAGE 1
(W)
FAJ A-2
J1
PRIMARY
INPUT
SHUNT 4-
(Y)
FAJ A-1
D
SHUNT 2-
(SL)
(BR)
PWR (O)
P102.4
(BR)
(W-BR)
SHUNT 5+
SHUNT 5-
F
SHUNT 6+
SHUNT 6SHUNT 7+
SHUNT 7-
J2
SECONDARY
INPUT
SHUNT 8+
SHUNT 8VOLTAGE 5
VOLTAGE 6
G
VOLTAGE 7
VOLTAGE 8
VIM1A METER
(G72)
FAJ (V)
TO
DISTRIBUTION
PANEL 4
PWR (O)
RTN (BR) RETURN BUS 4
IF PRESENT OR
DAISY CHAIN TO BR WIRE
ON P102.3 CONNECTOR
H
TITLE
SECONDARY POWER DISTRIBUTION BAY (BDFB/DBCBB)
EQUIPMENT SCHEMATIC FOR
G72 VIM1A METER AND
BEP1 ALARM MODULES
H
DRAWING DESCRIPTION
C2FORMAT.FRM DEC 2002
1
DWG
2
2
3
3
4
5
SHEET
DOC TYPE
REPEAT FOR P102.5 - P102.6 (CC848784710 WIRESET)
REPEAT FOR P102.5 - P102.8 (846940872 WIRESET)
0
J2
6
7
H569445-AD
8
B9
ISSUE
DWG
SIZE
22
9
C2/A1R
0
1
2
3
4
5
6
7
8
9
BEP1A ALARM WIRING
A
3
3
3
3
3
3
4
4
4
4
4
4
4
4
5
5
5
5
5
5
5
5
6
6
6
6
6
6
6
6
7
7
7
7
7
7
7
7
8
8
8
8
8
8
8
8
9
9
9
9
9
9
9
9
10
10
10
10
10
10
10
10
11
11
11
11
11
11
11
11
12
12
12
12
12
12
12
12
13
13
13
13
13
13
13
13
14
14
14
14
14
14
14
14
15
15
15
15
15
15
15
15
PANEL 1
PANEL 2
PANEL 3
PANEL 4
PANEL 5
PANEL 6
PANEL 7
PANEL 8
B
C
D
PWR (48V) (O)
FAJ (48V) (V)
RTN (BR)
G-70 METER
PWR (48V) (BL)
PWR (48V) (O)
E
FAJ (48V) (Y)
3
RTN (BR)
3
PWR (48V) (O)
2
FAJ (48V) (V)
2
RTN (BR)
2
PWR (48V) (BL)
2
FAJ (48V) (Y)
2
RTN (BR)
2
PWR (48V) (O)
2
FAJ (48V) (V)
2
RTN (BR)
1
PWR (48V) (BL)
1
FAJ (48V) (Y)
1
RTN (BR)
1
FAJ (48V) (V)
1
RTN (BR)
D
1
RTN (BR)
FROM FRAME
ALARM LED
1
PWR (48V) (BL)
TO TERMINAL E3
1
FAJ (48V) (Y)
C
G-71 METER
P102 FACTORY ALARM WIRING
B
A
E
BAY ALARM POWER
FROM BATTERY PLANT
F
F
G
G
TITLE
SECONDARY POWER DISTRIBUTION BAY (BDFB/DBCBB)
H
H
DRAWING DESCRIPTION
SHEET
DOC TYPE
DWG
C2FORMAT.FRM DEC 2002
0
1
2
3
4
5
6
7
H569445-AD
8
B9A
ISSUE
DWG
SIZE
22
9
C2/A1R
0
1
2
3
4
5
6
7
8
9
CC109172747 BDFB_BAY_BD
SURFACE MOUNT LEDs
BAY ALARM LIGHT
A
A
FIELD WIRING
(ABS FROM POWER PLANT)
METER POWER
J701
RETURN FROM INTERNAL RETURN BUS ON
PANEL 1 IF PRESENT (FACTORY WIRING) OR FROM
LOCAL EXTERNAL RETURN BUS (FIELD WIRING)
J701
FRAME
LAMP
FIELD
WIRING
TO
ALARM
OUTPUTS
B
J3
FUSE NC
FUSE NO
FUSE C
OVL NC
OVL NO
OVL C
PL NC
PL NO
PL C
C
B
J3
ALARM
OUTPUT
C
850018530
(W)
(W-BK)
VOLTAGE 1
VOLTAGE 2
850018534
(BR) RTN
(V) FAJA
D
(Y) FAJB
CC109172730
BDFB_PNL_BD
850018532
850018532
E
850018533
F
CC109172730
BDFB_PNL_BD
850018532
850018532
SHUNT 1+
SHUNT 1SHUNT 2+
SHUNT 2SHUNT 3+
SHUNT 3SHUNT 4+
SHUNT 4VOLTAGE 1
VOLTAGE 2
VOLTAGE 3
VOLTAGE 4
(V) FAJ A
(Y) FAJ B
(BR) RTN
(R) ABS
(W-BL)
(BL)
(W-SL)
(SL)
850018533
G
H
(W-BL)
(BL)
(W-SL)
(SL)
(W-O)
(O)
(W-Y)
(Y)
(W)
(W-BK)
(BR)
(W-BR)
(W)
(W-BK)
E
F
SHUNT 5+
SHUNT 5SHUNT 6+
SHUNT 6-
J2
SECONDARY
INPUT
G
VOLTAGE 5
VOLTAGE 6
TITLE
SECONDARY POWER DISTRIBUTION BAY (BDFB/DBCBB)
850018532
850018532
J1
PRIMARY
INPUT
VIM1C METER
(G272)
CC109172730
BDFB_PNL_BD
EQUIPMENT SCHEMATIC FOR
G272 VIM1C METER,
CC109172747 BAY ALARM PWB AND
CC109172730 PANEL ALARM PWBs
D
H
DRAWING DESCRIPTION
SHEET
DOC TYPE
DWG
C2FORMAT.FRM DEC 2002
0
1
2
3
4
5
6
7
H569445-AD
8
B10
ISSUE
DWG
SIZE
23
9
C2/A1R
0
1
2
3
LIST 63 RETURN BUS
(3/8 STUDS ON 1 INCH CENTERS)
5
OUTPUT
BUS
(1/4-20 STUDS
ON 5/8" CENTERS)
ALARM
BUS
INPUT
BUS
INPUT
BUS
1
6
ALARM
BUS
OUTPUT
BUS
(1/4-20 STUDS
ON 5/8" CENTERS)
7
1
C
(Y) FAJ
TO VIM
TO BAY
BOARD
(BL) PWR
VOLT 2
(W-BK)
PANEL
ALARM
BOARD
(BL) PWR
(Y) FAJ
VOLT 1
(W)
TO VIM
TO BAY
BOARD
LIST 63A RETURN BUS
(1/4-20 STUDS ON 5/8" CENTERS)
PANEL
2
LIST 63A RETURN BUS
(1/4-20 STUDS ON 5/8" CENTERS)
(W-SL) SH+
B
TO BAY
BOARD
RTN
(BR)
9
A
NOTES
** ATTACH SHUNT LEADS DIRECTLY
TO BUS IF G23 SHUNT IS NOT
EQUIPPED ON THE PANEL.
1.7"
(S) SH-
8
EQUIPMENT SCHEMATIC FOR
G33 PANELS, G23 LOAD SHUNTS AND
G63 AND G63A INTERNAL RETURN BUSES
LIST 63 RETURN BUS
(3/8 STUDS ON 1 INCH CENTERS)
LIST 23 SHUNT ASSY
(3/8 HOLES ON 1 INCH
CENTERS FOR BACK
TO BACK LUGS)
A
1.7"
4
*** CC848925743 BUS STRAP
SHOULD BE REMOVED BETWEEN
PANELS THAT ARE BOTH EQUIPPED
WITH A G23 SHUNT
PANEL
1
B
C
(BL) SH(W-BL) SH+
28
CC848925743
BUS STRAP
28
CC848925743
BUS STRAP
CC848925743
BUS STRAP ***
CC848925743
BUS STRAP ***
1
1
D
D
(Y) SHLIST 63A RETURN BUS
(1/4-20 STUDS ON 5/8" CENTERS)
E
NOTE **
TYP
VOLTAGE 4
(W-BR)
(BL) PWR
LIST 63A RETURN BUS
(1/4-20 STUDS ON 5/8" CENTERS)
PANEL
4
(W-Y) SH+
(Y) FAJ
PANEL
ALARM
BOARD
(BL) PWR
(BR)
VOLTAGE 3
(Y) FAJ
PANEL
3
E
(O) SH-
28
28
(W-O) SH+
F
F
1
1
(S) SH-
LIST 63A RETURN BUS
(1/4-20 STUDS ON 5/8" CENTERS)
PANEL
6
LIST 63A RETURN BUS
(1/4-20 STUDS ON 5/8" CENTERS)
G
(W-SL) SH+
(Y) FAJ
VOLTAGE 6
(BL) PWR
(W-BK)
PANEL
ALARM
BOARD
(BL) PWR
(W)
VOLTAGE 5
(Y) FAJ
G
PANEL
5
TITLE
SECONDARY POWER DISTRIBUTION BAY (BDFB/DBCBB)
(BL) SH-
H
28
(W-BL) SH+
H
DRAWING DESCRIPTION
28
SHEET
DOC TYPE
REAR VIEW
C2FORMAT.FRM DEC 2002
0
1
2
3
DWG
4
5
6
7
H569445-AD
8
B11
ISSUE
DWG
SIZE
23
9
C2/A1R
0
1
2
3
4
5
6
7
8
9
A
A
INPUT CABLES FOR UPPER PANEL POSITION
(MAX 4 , 2 PER FEED)
GENERAL PATH OF LOAD
OUTPUT CABLES
INPUT RTN CABLES
INPUT BAT CABLES
INPUT CABLES FOR MIDDLE PANEL POSITION
(MAX OF 4, 2 PER FEED)
INPUT CABLES FOR LOWER PANEL POSITION
(MAX OF 4, 2 PER FEED)
IF MORE THAN 600
AMPS (PER SIDE) IS
REQUIRED, EITHER
EXTERNAL RETURNS ARE
REQUIRED,
OR
G62/G62A INTERNAL RETURNS
ARE REQUIRED
(ONLY WITH G31 TYPE
PANELS)
RTN FEED CABLE
(MAX 5 PER SIDE)
B
B
TO CABLE RACK
C
C
D
D
E
E
F
F
G
BATTERY INPUT CABLING
FOR A 6 LOAD BAY
CABLE
DISCHARGE RETURN CABLING
INTERNAL RETURNS
REAR VIEW
SHOWN FOR A 7FT BAY.
9FT IS SIMILAR
SHOWN FOR TOP FEED ONLY.
BOTTOM FEED IS SIMILAR,
BUT CABLES EXIT FROM BOTTOM
OF BAY.
H
G61 & G61A COMBINE TO
ALLOW A MAX OF 600A PER SIDE
OR
G62 & G62A COMBINE TO ALLOW
A MAX OF 1800A PER SIDE
(CAN ONLY BE USED WITH
G31 TYPE PANELS)
TITLE
SECONDARY POWER DISTRIBUTION BAY (BDFB/DBCBB)
SHOWN FOR A 7FT BAY.
9FT IS SIMILAR
DRAWING DESCRIPTION
ROUTINGS
H
SHOWN FOR TOP FEED ONLY.
BOTTOM FEED IS SIMILAR,
BUT CABLES EXIT FROM BOTTOM
OF BAY.
C2FORMAT.FRM DEC 2002
G
REAR VIEW
0
1
2
3
4
SHEET
DOC TYPE
DWG
5
6
7
H569445-AD
8
B12
ISSUE
DWG
SIZE
22
9
C2/A1R
2
3
8
TOP VIEW
TOP VIEW
TOP VIEW
4.82
A
3.22
.62
3.21
4.83
1.03
1.28
INPUT FEEDS
INPUT FEEDS
15.44
INPUT RETURNS
INPUT RETURNS
OUTPUT LEADS
B
INPUT FEEDS
INPUT RETURNS
12.46
INPUT FEEDS
1.27
OUTPUT LEADS
INPUT RETURNS
INPUT FEEDS
INPUT FEEDS
.63
3.23
3.23
5/8-11
WELD NUTS
1.02
OUTPUT LEADS
3.22
2.79
1.00
4.83
9
2.79
18.85
OUTPUT LEADS
.62
2.79
3.22
5/8-11
WELD NUTS
1.03
INPUT RETURNS
7
GROUP 2 CABINET
1.28
OUTPUT LEADS
6
GROUP 7 CABINET
5/8-11
WELD NUTS
12.44
5
GROUP 1 CABINET
A
B
4
OUTPUT LEADS
1
INPUT RETURNS
0
C
C
1.15
1.15
23.64
23.64
1.15
23.64
D
D
BOTTOM VIEW
BOTTOM VIEW
E
1.20
BOTTOM VIEW
1.19
12.59
12.62
15.00
15.44
15.00
F
G
E
1.28
F
18.00
.75
1.00
3.31
1.56
1.75
19.31
G
22.81
25.94
.75
25.94
3.31
1.00
19.31
25.94
TITLE
SECONDARY POWER DISTRIBUTION BAY (BDFB/DBCBB)
H
H
DRAWING DESCRIPTION
SHEET
DOC TYPE
DWG
C2FORMAT.FRM DEC 2002
0
1
2
3
4
5
6
7
H569445-AD
8
B12A
ISSUE
DWG
SIZE
26
9
C2/A1R
0
1
2
3
4
5
6
7
8
9
GROUP 3 CABINET
BOTTOM VIEW
A
A
ANCHOR POINTS
CABLE ACCESS
B
B
BOTTOM VIEW OF CABINET
SHOWING CABINET MOUNTING LOCATIONS
BOTTOM VIEW OF CABINET
SHOWING CABLE ACCESS LOCATIONS
FRONT OF CABINET
FRONT OF CABINET
3.0 DIA FOR
INPUT LOAD FEEDS
(6 PLCS)
14.1
23.6
17.0
3.3
C
4.7
5.2
3.7
C
3.0 DIA FOR
RETURN FEEDS
(3 PLCS LEFT,
3 PLCS RIGHT)
OUTPUT LOAD
CABLE AREA}
ANCHOR BOLT
SLOT .75 X 1.00
(4 PLCS)
OUTPUT LOAD
CABLE AREA
D
D
23.6
17.7
3.6
14.0
15.7
E
E
3.6
1/4-20
7.7
F
2.000 (TYP)
1.75
2.0
4.8
3/8-16
F
.690 (TYP)
3.9
1.000 (TYP)
2.4
REAR OF CABINET
1.0
6.1
.62
6.0
REAR OF CABINET
G
G
FRAME GROUND
CONNECTION
ATTACHED FROM INSIDE
OF CABINET
(NO HOLES IN FLOOR REQUIRED)
TITLE
SECONDARY POWER DISTRIBUTION BAY (BDFB/DBCBB)
H
H
DRAWING DESCRIPTION
SHEET
DOC TYPE
DWG
C2FORMAT.FRM DEC 2002
0
1
2
3
4
5
6
7
H569-445
8
B12B
ISSUE
DWG
SIZE
22
9
C2/A1R
0
1
2
3
4
5
6
7
8
9
GROUP 3 CABINET
A
A
TOP VIEW
23.6
B
1.2
21.3
B
.7 (TYP)
2.0 (TYP)
2X 1.0
1.0 (TYP)
REAR OF CABINET
7.9
REAR OF CABINET
6.0
1.8
NUT 5/8-11
(4 PLCS)
3.9
C
C
2X .6
5.2
5.2
D
D
14.0
15.7
23.6
3.3
3.3
E
E
3.6
SCALE 3/8
F
FRONT OF CABINET
1.8
F
FRONT OF CABINET
6.6
SCALE 3/8
6.0
1.8
7.9
VIEW 2
1.8
VIEW 1
1.8
G
G
TITLE
SECONDARY POWER DISTRIBUTION BAY (BDFB/DBCBB)
H
H
DRAWING DESCRIPTION
SHEET
DOC TYPE
DWG
C2FORMAT.FRM DEC 2002
0
1
2
3
4
5
6
7
H569-445
8
B12C
ISSUE
DWG
SIZE
22
9
C2/A1R
0
1
2
3
4
5
6
7
8
9
GROUP 8 CABINET
A
A
TOP VIEW
5/8-11
WELD NUTS
4.82
2.79
1.00
.63
3.23
3.23
1.02
B
OUTPUT LEADS
INPUT RETURNS
INPUT FEEDS
12.46
C
INPUT FEEDS
OUTPUT LEADS
B
INPUT RETURNS
1.27
C
D
D
1.15
31.64
E
E
BOTTOM VIEW
F
F
15.00
12.62
G
G
1.19
TITLE
DISTRIBUTION BAY, BDFB/CBB
.75
1.00
1.75
H
H
DRAWING DESCRIPTION
1.56
30.81
DWG
33.94
C2FORMAT.FRM DEC 2002
0
1
2
SHEET
DOC TYPE
3
4
5
6
7
H569445-AD
8
B12D
ISSUE
DWG
SIZE
26
9
C2/A1R
0
1
2
3
4
5
6
7
8
9
RELOCATION OF G20 SHUNT
FOR BOTTOM FEED
A
A
B
B
C
C
D
D
E
E
F
F
G
G
STEP 4 MOVE LOAD SHUNT ASSY
(ROTATE 180 DEG) AND
RECONNECT
STEP 5 CONNECT SHUNT WIRES
AS SHOWN IN T8315-30
H
TITLE
SECONDARY POWER DISTRIBUTION BAY (BDFB/DBCBB)
H
DRAWING DESCRIPTION
SHEET
DOC TYPE
DWG
C2FORMAT.FRM DEC 2002
0
1
2
3
4
5
6
7
H569445-AD
8
B13
ISSUE
DWG
SIZE
22
9
C2/A1R
0
1
2
3
4
5
6
7
8
9
BEP1 ALARM MULTIPLE (NOT REQUIRED WITH VIM1 METER)
A
A
BEP1 WIRING
OPEN ON ALARM
B
B
C
C
D
D
E
E
CLOSED ON ALARM
F
F
G
G
TITLE
SECONDARY POWER DISTRIBUTION BAY (BDFB/DBCBB)
H
H
DRAWING DESCRIPTION
SHEET
DOC TYPE
DWG
C2FORMAT.FRM DEC 2002
0
1
2
3
4
5
6
7
H569445-AD
8
F1
ISSUE
DWG
SIZE
22
9
C2/A1R
0
1
2
3
4
5
6
7
8
9
BEP1 ALARM CONNECTORS FOR GROUP 3 CABINET
CO1
A
B
C
D
E
F
G
C02
C03
J101
C04
1
1
1
1
6
2
2
2
2
10
3
3
3
3
4
4
4
4
5
5
5
5
5
9
6
6
6
6
7
7
7
7
8
8
8
8
9
9
9
9
15
10
10
10
10
12
11
11
11
11
3
12
12
13
13
13
13
13
14
14
14
14
1
15
15
15
15
16
16
16
16
17
17
17
17
18
18
18
18
8
19
19
19
19
11
20
20
20
20
4
21
21
21
21
22
22
22
22
23
23
23
23
24
24
24
24
25
25
25
25
26
TO TOP OR BOTTOM BEP1
CIRCUIT PACk
D
12
26
B
C
12
26
A
E
F
14
G
2
TITLE
SECONDARY POWER DISTRIBUTION BAY (BDFB/DBCBB)
26
H
H
DRAWING DESCRIPTION
GROUP 3 ALARM OUTPUT CONNECTION
C2FORMAT.FRM DEC 2002
0
1
2
3
4
SHEET
DOC TYPE
DWG
5
6
7
H569445-AD
8
F2
ISSUE
DWG
SIZE
22
9
C2/A1R