01_140M_Circuit_Breakers_A.qxd 4/22/2008 4:14 PM Page 2-2 Bulletin 140M Motor Protection Circuit Breakers Product Overview ! 1 Bulletin 140M Motor Protection Circuit Breakers Table of Contents y Current Range 0.1…630 A y UL Listed for Motor Loads − Short Circuit Protection − Overload Protection y Visible Trip Indication y High Current Limiting y High Switching Capacity Product Selection — Motor Protection Circuit Breakers.......... 2-8 Approximate Dimensions................... 2-49 2 The Bulletin 140M Motor Protection Circuit Breakers provide short circuit and overload protection for individual motor loads. Factoryinstalled internal accessories make installation and wiring easy. 3 Your order must include: cat. no. of the Motor Protection Circuit Breaker selected and, if required, cat. no. of any accessories. Standards Compliance IEC/EN 60947-1, -2, -4-1, -5-1 IEC/EN 60204-1 CSA, C22.2 No.14 UL 508 UL 489 Certifications 4 CE Marked cULus Listed (File No. E197878, E205542, Guide DIVQ/DIVQ7, NKJH/NKJH7) CCC CSA Certified General Information Motor Protection Circuit Breakers may provide the following protective and control functions. 5 y Disconnect for Motor Branch Circuit y Branch-Circuit, Short-Circuit Protection (Magnetic Protection) y Overload Protection (Thermal Protection) y Switching (Manual) 6 In North America, electrical codes require that an individual Motor Branch Circuit be protected by a UL/CSA Listed Fuse, Circuit Breaker or Self-Protected Combination Motor Controller. 140M-C, D and F Frames: 7 8 The 140M-C, D and F frame Motor Protection Circuit Breakers may have 2 cULus Listings – as Manual, Self-Protected Combination Motor Controllers and as Manual Motor Controllers (with optional approvals for Motor Disconnect and Group Installation). When UL/CSA listed as Manual, Self-Protected Combination Motor Controllers, the 140M Motor Protection Circuit Breakers provide all of the necessary NEC/CEC requirements for the protection and control of individual Motor Branch Circuits without additional protective devices. At some higher voltages and currents (particularly at 600V), a few of the 140M-C, D and F frame devices are only UL/CSA Listed as Manual Motor Controllers (with optional approvals for Motor Disconnect and Group Installation). In NEC/CEC Group Installations, these devices must be applied per the appropriate rules which require the use of an upstream Branch-Circuit, Short-Circuit Protective Device (BCPD). See the table on page 2-17 for the specific ratings of each Motor Protection Circuit Breaker. 140-CMN Frame: 9 The 140-CMN frame Motor Protection Circuit Breakers are UL Listed/CSA Certified as Manual Motor Controllers (with optional approvals for Motor Disconnect and Group Installation). In NEC/CEC Group Installations, these devices must be applied per the appropriate rules which require the use of an upstream Branch-Circuit, Short-Circuit Protective Device (BCPD). See the table on page 2-17 for the specific ratings of each Motor Protection Circuit Breaker. 140M-I, J and L Frames: 10 The 140M-I, J and L frame Motor Protection Circuit Breakers are cULus Listed as Circuit Breakers as shown in the table on page 2-9. In these cases, the 140M Motor Protection Circuit Breakers provide all of the necessary NEC/CEC requirements for the protection and control of individual Motor Branch Circuits without additional protective devices. For further details on the proper application of Motor Protection Circuit Breakers, please see the diagrams on the following pages. 11 12 13 Visit our website: www.ab.com/catalogs 2-2 Preferred availability cat. nos. are printed in bold 01_140M_Circuit_Breakers_A.qxd 4/22/2008 4:15 PM Page 2-3 Bulletin 140M Motor Protection Circuit Breakers Product Overview, Continued ! 1 C-Frame D-Frame F-Frame CMN-Frame I-Frame J-Frame Max. Current Ie 25 A 25 A 45 A 90 A 205 A 250 A L-Frame 630 A Current Rating 0.1…25 A 1.6…25 A 6.3…45 A 16…90 A 40…205 A 20…250 A 100…630 A Short Circuit Protection 9 9 9 9 9 9 9 Standard Magnetic Trip 9 9 9 9 9 9 9 High Magnetic Trip 9 9 9 9 — — — Overload Protection 9 9 9 9 9 9 9 Trip Class 10 10 10 10 5…20 10…30 10…30 2 3 Standards Compliance: CSA 22.2, No. 14 9 9 9 9 9 9 9 CSA 22.2, No. 5 — — — — 9 9 9 UL 508 (Group Install.) 9 9 9 9 — — — UL 508 Manual, Self Protected (Type E) 9 9 9 — — — — UL 508 (Overload Protection) 9 9 9 9 9 9 9 UL 489 — — — — 9 9 9 IEC 60947-1, -2 9 9 9 9 9 9 9 IEC 60947-4-1 9 9 9 9 9 9 9 CE 9 9 9 9 9 9 9 ATEX 9 9 — — — — — CCC 9 9 9 — — — — 4 5 6 Accessories Ext. Rotary Operator 9 9 9 9 9 9 9 Flex Cable Operator — — — — 9 9 9 Auxiliary Contacts 9 9 9 9 9 9 9 Trip Indication Contacts 9 9 9 9 9 9 9 7 8 9 10 11 12 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-3 01_140M_Circuit_Breakers_A.qxd 4/22/2008 4:15 PM Page 2-4 Bulletin 140M Motor Protection Circuit Breakers Catalog Number Explanation Cat. No. Explanation Examples given in this section are for reference purposes. This basic explanation should not be used for product selection; not all combinations will produce a valid catalog number. ! 140M – C – 2 – E – A63 – KN – CC – GJ 1 2 a b c d g h a c f, g, h Interrupting Rating / Breaking Capacity Factory-Installed Options Description Code Description 140M Motor Protection Circuit Breakers (MPCBs) 2 Normal Break 8 High Break f Miscellaneous See page 2-33 b d g Protection Type Aux/Trip Contacts See page 2-33 Frame Size and Rating 5 f Bulletin Number Code 3 4 e Code Description C 25 A Code Description D 25 A E Adj Thermal/ Fixed Mag (13 x In) h F 45 A T UV and Shunt Trips See page 2-33 I 205 A Adj Thermal / Fixed Mag (Fixed at 16...20 x In) J 250 A L 400 A and 600 A e Current Range 6 Code Description Example A A = .10 A16 = 0.16 B16 = 1.6 B B = 1.0 C C = 10 C16 = 16 D D = 100 D16 = 160 E E = 1000 E16 = 1600 7 8 9 10 11 12 13 Visit our website: www.ab.com/catalogs 2-4 Preferred availability cat. nos. are printed in bold 01_140M_Circuit_Breakers_A.qxd 4/22/2008 4:15 PM Page 2-5 Bulletin 140M Motor Protection Circuit Breakers Product Selection ! 1 2 3 4 5 6 7 8 9 10 Group Motor Installation 11 12 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-5 01_140M_Circuit_Breakers_A.qxd 4/22/2008 4:15 PM Page 2-6 Bulletin 140M Motor Protection Circuit Breakers Product Selection, Continued 3-Phase Power Supply ! Multiple Motor Installation with MPCBs Each Motor has an Individual Branch Circuit Protective Device 1 2 Bulletin 140M Motor Protection Circuit Breakers (MPCBs) UL/CSA Listed as Type E Manual Self-Protected Combination Motor Controllers or UL/CSA Listed as Circuit Breakers These UL/CSA Listings allow the Bulletin 140M MPCBs to provide the branch-circuit, short-circuit protection (as well as overload protection) for each individual motor circuit. Additional short-circuit protection is not required for the protection of the individual motor cuircuits, leaving only the requirement for protection of the feeder circuit conductors by an upstream protective device. Below is an example that illustrates installations involving multiple motors, each with its own branch-circuit protection (BCPD). 3 4 Bulletin 140M-J…L (Inverse Time Circuit Breakers) may provide the branch-circuit protection for each individual motor circuit Feeder Circuit conductors Bulletin 140M-C…F (Type E Self-Protected Combination Motor Controllers) may provide the branch-circuit protection for each individual motor circuit 5 6 7 8 9 Conductors to each motor sized normally at 125% FLA 10 11 Multi-Motor Installation 12 13 Visit our website: www.ab.com/catalogs 2-6 Preferred availability cat. nos. are printed in bold 01_140M_Circuit_Breakers_A.qxd 4/22/2008 4:15 PM Page 2-7 Bulletin 140M Motor Protection Circuit Breakers Product Selection, Continued Type E and Type F Combination Motor Controllers Most of the 140M-C…F motor protection circuit breakers are UL listed as a manual Type E self-protected combination motor controller. Although there are many tests involved, one of the critical tests a self-protected combination motor controller must pass, is to perform 6000 electrical ops. and an additional 4000 mechanical ops. after a short circuit. ! By definition, a Type F combination motor controller consists of a Type E manual self protected combination motor controller and a magnetic or solid-state motor controller (such as a Bulletin 100-C contactor or an SMC). As with a manual Type E self-protected combination motor controller, additional short-circuit protection is not required for the individual motor circuits. 1 A combination of a Bulletin 140M manual self protected combination motor controller and 100-C contactor can be listed as a Type E selfprotected combination motor controller. In this case, both the 140M and 100-C must pass the additional 6000 electrical and 4000 mechanical operational test. In some cases, this may require over sizing of the Bulletin 140M MPCB or the 100-C contactor to achieve weld free performance and meet the additional life requirements. 2 3 4 5 6 7 8 9 10 11 12 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-7 01_140M_Circuit_Breakers_A.qxd 4/22/2008 4:16 PM Page 2-8 Bulletin 140M Motor Protection Circuit Breakers Product Selection, Continued Product Selection — Motor Protection Circuit Breakers ! y Short Circuit Protection — Standard Magnetic Trip (Fixed at 13 x Ie) y Overload Protection — Trip Class 10 1 2 Cat. No. 140M-C 3 4 5 6 7 Cat. No. 140M-D Ultimate Interrupting Motor Magnetic Rated Current [kA] Current Trip Operational (Icu) Current (Ie) Adjustment Current 400V 480V [A] Range [A] [A] Cat. No. 140M-F Max. 3-phase Hp Ratings9 200V 230V 460V Cat. No. 140-CMN Max. kW, 3-Phase9 575V 230V 400/415V 500V 690V Cat. No. C-Frame 0.16 0.10…0.16 2.1 100 65 — — — — — 0.02 — — 140M-C2E-A16 0.25 0.16…0.25 3.3 100 65 — — — — — 0.06 — — 140M-C2E-A25 0.4 0.25…0.40 5.2 100 65 — — — — — 0.09 — — 140M-C2E-A40 0.63 0.40…0.63 8.2 100 65 — — — — 0.09 0.18 0.18 0.25 140M-C2E-A63 1 0.63…1.0 13 100 65 — — 0.5 0.75 0.12 0.25 0.37 0.55 140M-C2E-B10 1.6 1.0…1.6 21 100 65 — — 1 1 0.25 0.55 0.75 1.1 140M-C2E-B16 2.5 1.6…2.5 33 100 65 0.5 0.75 1.5 2 0.37 0.75 1.1 1.8 140M-C2E-B25 4 2.5…4.0 52 100 65 1 1 3 3 0.75 1.5 2.2 3 140M-C2E-B40 6.3 4.0…6.3 82 100 65 1.5 2 5 5 1.5 2.2 3 4 140M-C2E-B63 10 6.3…10 130 100 65 3 3 7.5 10 2.2 4 6.3 7.5 140M-C2E-C10 16 10…16 208 50 30 5 5 10 15 4 7.5 10 13 140M-C2E-C16 20 14.5…20 260 15 30 5 7.5 15 20 5.5 10 11 17 140M-C2E-C20 25 18…25 325 15 25 7.5 7.5 15 20 — 11 15 22 140M-C2E-C25 D-Frame 8 9 10 11 12 2.5 1.6…2.5 33 100 65 0.5 0.75 1.5 2 0.37 0.75 1.1 1.8 140M-D8E-B25 4 2.5…4.0 52 100 65 1 1 3 3 0.75 1.5 2.2 3 140M-D8E-B40 6.3 4.0…6.3 82 100 65 1.5 2 5 5 1.5 2.2 3 4 140M-D8E-B63 10 6.3…10 130 100 65 3 3 7.5 10 2.2 4 6.3 7.5 140M-D8E-C10 16 10…16 208 100 65 5 5 10 15 4 7.5 10 13 140M-D8E-C16 20 14.5…20 260 50 65 5 7.5 15 20 5.5 10 11 17 140M-D8E-C20 25 18…25 325 50 30 7.5 7.5 15 20 — 11 15 22 140M-D8E-C25 F-Frame 10 6.3…10 130 65 65 3 3 7.5 10 2.2 4 6.3 7.5 140M-F8E-C10 16 10…16 208 65 65 5 5 10 15 4 7.5 10 13 140M-F8E-C16 20 14.5…20 260 65 65 5 7.5 15 20 5.5 10 11 17 140M-F8E-C20 25 18…25 325 65 65 7.5 10 20 25 6.3 11 15 22 140M-F8E-C25 32 23…32 416 65 65 7.5 10 25 30 7.5 15 20 25 140M-F8E-C32 45 32…45 585 65 65 10 15 30 40 13 22 30 40 140M-F8E-C45 CMN-Frame 25 16…25 350 65 65 5 7.5 15 20 7.5 13 15 22 140-CMN-2500 40 25…40 560 65 65 10 10 30 30 11 22 25 30 140-CMN-4000 63 40…63 882 65 42 20 20 40 60 20 32 40 55 140-CMN-6300 90 63…90 1260 50 35 25 30 60 75 25 45 55 75 140-CMN-9000 9 Horsepower/kW ratings shown in the table above are for reference. The final selection of the MPCB depends on the actual motor full load current and, in North America, service factor. 13 Visit our website: www.ab.com/catalogs 2-8 Preferred availability cat. nos. are printed in bold 01_140M_Circuit_Breakers_A.qxd 4/22/2008 4:17 PM Page 2-9 Bulletin 140M Motor Protection Circuit Breakers Product Selection, Continued Motor Protection Circuit Breakers ! y Short Circuit Protection — Standard Magnetic Trip (Fixed at 12...15 x Ie) y Overload Protection — Trip Class 10...30 (Adjustable) 1 Cat. No. 140M-I Cat. No. 140M-J Rated Motor Magnetic Operational Current Trip Current [A] Adjustment Current (Ie) Range [A] [A] Ultimate Interrupting Current [kA] (Icm) 400V 480V 3-phase Hp Ratings9 200V 230V 2 Cat. No. 140M-L 460V 3 Max. kW, 3-Phase9 575V 230V 400/415 V 500V 690V Cat. No. I-Frame 80 40…80 1200 707 65 25 30 60 75 22 37 55 75 140M-I8E-C807‡ 100 80…100 1500 707 65 30 40 75 100 30 55 55 90 140M-I8E-D107‡ 160 100…160 2400 707 65 50 60 125 150 45 75 110 132 140M-I8E-D167‡ 205 160…205 2665 707 65 60 75 150 200 55 110 132 200 140M-I8E-D207§ 50 20…50 700 25 25 25 30 60 75 15 22 30 45 140M-J2E-C50 100 40…100 1400 25 25 30 40 75 100 30 55 55 90 140M-J2E-D10 160 64…160 2240 25 25 50 60 125 150 45 90 110 160 140M-J2E-D16 250 100…250 3500 25 25 75 100 200 250 55 132 160 250 140M-J2E-D25 50 20…50 700 70 65 25 30 60 75 15 22 30 45 140M-J8E-C50 J-Frame 100 40…100 1400 70 65 30 40 75 100 30 55 55 90 140M-J8E-D10 160 64…160 2240 70 65 50 60 125 150 45 90 110 160 140M-J8E-D16 250 100…250 3500 70 65 75 100 200 250 55 132 160 250 140M-J8E-D25 140M-L2E-D25 4 5 6 7 L-Frame 250 100…250 3000 40 35 75 100 200 250 55 132 160 250 400 160…400 4800 40 35 125 150 300 400 132 200 250 400 140M-L2E-D40 630 250…630 7580 40 35 200 250 500 600 200 355 450 630 140M-L2E-D63 250 100…250 3000 70 65 75 100 200 250 55 132 160 250 140M-L8E-D25 400 160…400 4800 70 65 150 150 350 450 132 200 250 400 140M-L8E-D40 630 250…630 7560 70 65 200 250 500 600 200 355 450 630 140M-L8E-D63 9 Horsepower/kW ratings shown in the table above are for reference. The final selection of the MPCB depends on the actual motor full load current and, in North America, service factor. 7 For IEC approvals and CE marking, add an "E" to the end of the Cat. No. Example: 140M-18E-C80E. ‡ Overload Protection ⎯ adjustable Trip Class 5, 10, 15, or 20. § Overload Protection ⎯ fixed Trip Class 10. 8 9 10 11 12 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-9 01_140M_Circuit_Breakers_A.qxd 4/22/2008 4:17 PM Page 2-10 Bulletin 140M Motor Protection Circuit Breakers Product Selection, Continued Motor Protection Circuit Breakers ! y Short Circuit Protection — High Magnetic Trip (Fixed at 16…20 x Ie) y Overload Protection — Trip Class 10 1 2 Cat. No. 140M-C 3 4 5 6 Cat. No. 140M-D Rated Motor Magnetic Operational Current Trip Current [A] Adjustment Current (Ie) Range [A] [A] Ultimate Interrupting Current [kA] (Icm) 400V 480V Cat. No. 140M-F Max. 3-phase Hp Ratings9 200V 230V 460V Max kW, 3-Phase9 575V 230V 400/415V 500V 690V Cat. No. C-Frame 0.16 0.10…0.16 3.3 100 65 — — — — — 0.02 — — 140M-C2T-A16 0.25 0.16…0.25 5.2 100 65 — — — — — 0.06 — — 140M-C2T-A25 0.4 0.25…0.40 8.2 100 65 — — — — — 0.09 — — 140M-C2T-A40 0.63 0.40…0.63 13 100 65 — — — — 0.09 0.18 0.18 0.25 140M-C2T-A63 1 0.63…1.0 21 100 65 — — 0.5 0.75 0.12 0.25 0.37 0.55 140M-C2T-B10 1.6 1.0…1.6 33 100 65 — — 1 1 0.25 0.55 0.75 1.1 140M-C2T-B16 2.5 1.6…2.5 52 100 65 0.5 0.75 1.5 2 0.37 0.75 1.1 1.8 140M-C2T-B25 4 2.5…4 82 100 65 1 1 3 3 0.75 1.5 2.2 3 140M-C2T-B40 6.3 4…6.3 130 100 65 1.5 2 5 5 1.5 2.2 3 4 140M-C2T-B63 10 6.3…10 208 50 30 3 3 7.5 10 2.2 4 6.3 7.5 140M-C2T-C10 16 10…16 260 15 30 5 5 10 15 4 7.5 10 13 140M-C2T-C16 D-Frame 7 16 10…16 260 50 65 5 5 10 15 4 7.5 10 13 140M-D8T-C16 20 14.5…20 325 50 30 5 7.5 15 20 5.5 10 11 17 140M-D8T-C20 F-Frame 8 25 18…25 416 65 65 7.5 10 20 25 6.3 11 15 22 140M-F8T-C25 32 23…32 585 65 65 7.5 10 25 30 7.5 15 20 25 140M-F8T-C32 9 Horsepower/kW ratings shown in the table above are for reference. The final selection of the MPCB depends on the actual motor full load current and, in North America, service factor. 9 10 11 12 13 Visit our website: www.ab.com/catalogs 2-10 Preferred availability cat. nos. are printed in bold 01_140M_Circuit_Breakers_A.qxd 4/22/2008 4:18 PM Page 2-11 Bulletin 140M Motor Circuit Protectors Product Overview Bulletin 140M Motor Circuit Protectors y Current range 0.16…1200 A y UL Listed/Recognized for motor loads − Short-circuit protection − Overload protection must be provided separately y Visible trip indication y High current limiting y High switching capacity The Bulletin 140M Motor Circuit Protectors provide short circuit protection for individual motor loads. Factory-installed internal accessories make installation and wiring easy. Certifications (0.16…45 A) Certifications (3…1200 A) cULus Listed (File No. E54612, Guide No. NLRV, NLRV7) CCC CE Marked UR Recognized component (File No. E224135, Guide DKPU2) CSA Certified (Cleass No. 3211-07) Table of Contents Product Selection — Motor Circuit Protectors ..................... 2-15 Approximate Dimensions................... 2-49 ! Standards Compliance 1 IEC/EN 60947-1, 2, -4-1, -5-1 IEC/EN 60204-1 CSA, C22.2 No.14 UL 508 UL 489 2 Your order must include: cat. no. of the Motor Circuit Protector selected and, if required, cat. no. of any accessories. General Information 3 4 Motor Circuit Protectors may provide the following protective and control functions. y Disconnect for Motor Branch Circuit y Branch-Circuit, Short-Circuit Protection (Magnetic Protection) 5 y Switching (Manual) In North America, electrical codes require that an individual Motor Branch Circuit be protected by a UL/CSA Listed Fuse, Circuit Breaker or Self-Protected Combination Motor Controller. 140M-C, D and F Frames: The 140M-C, D and F frame Motor Circuit Protectors have one UL/CSA Listing – as Manual Motor Controllers (with optional approvals for Motor Disconnect and Group Installation). In NEC/CEC Group Installations, these devices must be applied per the appropriate rules which require the use of an upstream Branch-Circuit, Short-Circuit Protective Device (BCPD). See the table on page 2-19 for the specific ratings of each Motor Circuit Protector. The 140M-C, D and F Frame Motor Circuit Protectors are also UL/CSA Listed, together with a Bulletin 100C contactor and Bulletin 193 overload relay, as part of our Bulletin 103T and 107T Self-Protected IEC Combination Starters. These starters are then able to provide all of the necessary NEC/CEC requirements for the protection and control of individual Motor Branch Circuits without additional protective devices. 6 7 140M-H, J and L Frames: The 140M-H, J and L frame Motor Circuit Protectors are UL/CSA Recognized as Circuit Breakers as shown in the table on page 2-19. They are UL/CSA Recognized, rather than UL/CSA Listed, since they only provide short circuit protection and not thermal overload protection for the motor. 140M-H, J and L frame Motor Circuit Protectors (MCPs) are also UL/CSA Listed, together with a Bulletin 100C contactor and Bulletin 193 overload relay, as part of our Bulletin 113 IEC Combination Starters. These starters are then able to provide all of the necessary NEC/CEC requirements for the protection and control of individual Motor Branch Circuits without additional protective devices. 8 9 10 11 12 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-11 01_140M_Circuit_Breakers_A.qxd 4/22/2008 4:19 PM Page 2-12 Bulletin 140M Motor Circuit Protectors Product Overview, Continued/Catalog Number Explanation Product Line Overview ! 1 2 C-Frame D-Frame F-Frame H-Frame J-Frame L-Frame Max. Current Ie 25 A 25 A 45 A 100 A 250 A 600 A 1200 A Current Rating 0.16…2.5 A 2.5…25 A 25…45 A 3…100 70…250 125…600 640…1200 9 9 9 9 9 9 9 9 9 9 9 Short Circuit Protection N-Frame Standards Compliance: 3 4 CSA 22.2, No. 14 9 9 9 CSA 22.2, No. 5 — — — UL 508 (Group Install.) 9 9 9 UL489 (Recognized) — — — 9 9 9 9 IEC 60947-2 9 9 9 9 9 9 9 CE 9 9 9 9 9 9 9 CCC 9 9 9 — — — — Accessories 5 6 Ext. Rotary Operator 9 9 9 9 9 9 9 Flex Cable Operator — — — 9 9 9 9 Auxiliary Contacts 9 9 9 9 9 9 9 Trip Indication Contacts 9 9 9 9 9 9 9 Cat. No. Explanation Examples given in this section are for reference purposes. This basic explanation should not be used for product selection; not all combinations will produce a valid catalog number. 7 140M – C – 2 – N – A63 – KN – CC – GJ a 8 b c d e f g h a d f, g, h Bulletin Number Protection Type Factory-Installed Options Code Description Code Description 140M Motor Circuit Protectors (MCPs) N Fixed Mag Only (13 x In) P Adj Mag Only (less than 13 x In)- MCPs f R Adj Mag Only (greater than 13 x In) MCP's Miscellaneous See page 2-33 9 b Frame Size and Rating 10 11 Code Description C 25 A D 25 A F 45 A H 125 A J 250 A L 400 A and 600 A N 800 A and 1200 A g e Aux/Trip Contacts See page 2-33 Current Range Code Description Example A A = .10 A16 = 0.16 h B B = 1.0 B16 = 1.6 UV and Shunt Trips See page 2-33 C C = 10 C16 = 16 D D = 100 D16 = 160 E E = 1000 E16 = 1600 c 12 13 Interrupting Rating / Breaking Capacity (Ic at 480V) Code Description 2 Normal Break 8 High Break Visit our website: www.ab.com/catalogs 2-12 Preferred availability cat. nos. are printed in bold 01_140M_Circuit_Breakers_A.qxd 4/22/2008 4:19 PM Page 2-13 Bulletin 140M Motor Circuit Protectors Product Selection ! 1 2 3 4 5 6 7 8 9 10 11 12 Group Motor Installation 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-13 01_140M_Circuit_Breakers_A.qxd 4/22/2008 4:19 PM Page 2-14 Bulletin 140M Motor Circuit Protectors Product Selection, Continued 3-Phase Power Supply ! 1 2 3 4 5 6 7 8 9 10 11 12 Multi-Motor Installation 13 Visit our website: www.ab.com/catalogs 2-14 Preferred availability cat. nos. are printed in bold 01_140M_Circuit_Breakers_A.qxd 4/22/2008 4:19 PM Page 2-15 Bulletin 140M Motor Circuit Protectors Product Selection, Continued Motor Circuit Protectors ! y Short-circuit protection — standard magnetic trip (fixed at 13 x Ie) y Overload protection — none (magnetic trip only) y For Trip Class 10 motor applications‡ 1 2 Cat. No. 140M-D Cat. No. 140M-C Ultimate Rated Magnetic Interrupting Current Operational Trip [kA], (Icm) Current [A] Current (Ie) 400V 480V [A] Max. 3-phase Hp Ratings¹ 200V 230V 460V 3 Cat. No. 140M-F 3-phase kW Ratings9 575V 230V 400/415V 500V 690V Cat. No. 4 C-Frame 0.16 2.1 100 65 — — — — — 0.02 — — 140M-C2N-A16 0.25 3.3 100 65 — — — — — 0.06 — — 140M-C2N-A25 0.4 5.2 100 65 — — — — — 0.09 — — 140M-C2N-A40 0.63 8.2 100 65 — — — — 0.09 0.18 0.18 0.25 140M-C2N-A63 1 13 100 65 — — 0.5 0.75 0.12 0.25 0.37 0.55 140M-C2N-B10 1.6 21 100 65 — — 1 1 0.25 0.55 0.75 1.1 140M-C2N-B16 2.5 33 100 65 0.5 0.75 1.5 2 0.37 0.75 1.1 1.8 140M-C2N-B25 2 0.37 0.75 1.1 1.8 140M-D8N-B25 140M-D8N-B40 D-Frame 2.5 33 100 65 0.5 0.75 1.5 4 52 100 65 1 1 3 3 0.75 1.5 2.2 3 6.3 82 100 65 1.5 2 5 5 1.5 2.2 3 4 140M-D8N-B63 10 130 100 65 3 3 7.5 10 2.2 4 6.3 7.5 140M-D8N-C10 16 208 100 65 5 5 10 15 4 7.5 10 13 140M-D8N-C16 25 325 50 65 7.5 7.5 15 20 — 11 15 22 140M-D8N-C25 5 6 7 F-Frame 25 325 65 65 7.5 10 20 25 6.3 11 15 22 140M-F8N-C25 32 416 65 65 7.5 10 25 30 7.5 15 20 25 140M-F8N-C32 45 585 65 65 10 15 30 40 13 22 30 40 140M-F8N-C45 8 9 Horsepower/kW ratings shown in the table above are for reference. The final selection of the manual starter depends on the actual motor full load current and, in North America, service factor. ‡ For heavy-duty starting applications (exceeding Trip Class 10), please consult your local Rockwell Automation sales office or Allen-Bradley distributor. 9 10 11 12 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-15 01_140M_Circuit_Breakers_A.qxd 4/22/2008 4:20 PM Page 2-16 Bulletin 140M Motor Circuit Protectors Product Selection, Continued Motor Circuit Protectors ! y Short-Circuit Protection — Magnetic Trip (Adjustable at 3...10 x Ie) y Overload Protection — None (Magnetic Trip Only) 1 2 Cat. No. 140M-H Cat. No. 140M-J 3 4 5 6 Rated Operational Current [A] (Ie) Cat. No. 140M-L Magnetic Trip Current [A] 3-phase Hp Ratings9 Cam Setting A B C D E F G H I 200V 230V 460V 575V 3-phase kW Ratings9 230V 400/ 415V 500V 690V Cat. No.7 140M-H8P-B30 H-Frame 3 9 15 21 27 30 33 — — — 0.5 0.5 1.5 2 0.6 0.75 1.1 1.5 7 21 35 49 63 70 77 — — — 1.5 2 3 5 1.1 2.2 3 4 140M-H8P-B70 15 45 75 100 135 150 165 — — — 3 3 10 10 3 5.5 7.5 11 140M-H8P-C15 30 90 150 210 270 300 330 — — — 7.5 10 20 25 5.5 11 15 22 140M-H8P-C30 50 150 250 350 450 500 550 — — — 15 15 30 40 11 22 22 37 140M-H8P-C50 70 210 350 490 630 700 770 — — — 20 25 50 60 15 30 37 55 140M-H8P-C70 100 300 500 700 900 1000 1100 — — — 25 30 60 75 22 45 55 75 140M-H8P-D10 100 500 700 900 1100 1300 1500 — — — 30 30 75 100 30 55 75 110 140M-H8R-D10 100 500 600 700 800 900 1000 — — — 30 30 75 100 22 37 45 55 140M-J8P-D10 125 625 750 875 1000 1125 1250 — — — 40 40 100 125 22 45 55 90 140M-J8P-D12 150 750 900 1050 1200 1350 1500 — — — 50 50 100 150 30 55 75 110 140M-J8P-D15 175 875 1050 1225 1400 1575 1750 — — — 50 60 125 150 37 55 90 132 140M-J8P-D17 200 1000 1200 1400 1600 1800 2000 — — — 60 75 150 200 45 75 90 132 140M-J8P-D20 225 1125 1350 1575 1800 2025 2250 — — — 75 75 150 200 55 90 110 160 140M-J8P-D22 250 1250 1500 1750 2000 2250 2500 — — — 75 100 200 250 55 90 132 160 140M-J8P-D25 J-Frame 7 8 9 10 11 L-Frame 225 1125 1265 1410 1545 1690 1830 1970 2110 2250 50 60 125 150 55 90 110 160 140M-L8P-D22 250 1250 1405 1560 1720 1875 2030 2185 2340 2500 60 75 150 200 55 90 132 160 140M-L8P-D25 300 1500 1690 1875 2060 2250 2440 2625 2810 3000 75 75 150 200 55 110 160 200 140M-L8P-D30 350 1750 1970 2190 2410 2625 2840 3065 3285 3500 75 100 200 250 75 132 160 250 140M-L8P-D35 400 2000 2250 2500 2750 3000 3250 3500 3750 4000 100 100 250 300 90 160 200 250 140M-L8P-D40 450 2250 2530 2810 3098 3375 3660 3940 4220 4500 100 125 250 350 110 160 200 315 140M-L8P-D45 500 2500 2810 3125 3440 3750 4660 4375 4690 5000 125 150 300 400 110 200 250 355 140M-L8P-D50 600 3000 3375 3760 4110 4500 4880 5250 5630 6000 150 150 350 450 132 250 315 450 140M-L8P-D60 N-Frame 800 1600 2400 3200 4000 4800 5600 6400 — — 150 200 400 500 160 250 355 500 140M-N8P-D80 1200 2400 3600 4800 6000 7200 8400 9600 — — 250 300 600 700 200 250 500 710 140M-N8P-E12 9 The Hp and kW ratings shown are for reference only. They allow for a magnetic trip setting of at least up to 13X the motor FLA. However, the final selection of the MCP should be made based on motor full load current and the requirements of local electrical codes. 7 The interrupting rating for MCPs is dependent upon the controller used. Please contact your local Rockwell Automation sales office or Allen-Bradley distributor 12 13 Visit our website: www.ab.com/catalogs 2-16 Preferred availability cat. nos. are printed in bold 01_140M_Circuit_Breakers_A.qxd 4/22/2008 4:21 PM Page 2-17 Bulletin 140M Motor Circuit Protectors Application Ratings UL/CSA Listed Application Ratings — Motor Protection Circuit Breaker (MPCB) Only UL 508 — Manual Motor Controller Group Motor Installation Cat. No. Max. Fuse or C.B. per NEC Motor Disconnect Tap Conductor Protection UL 508 Self-Protected (Type E) Combination Motor Controller UL 489 Inverse Time C.B. w/UL 508 Motor Overload Protection ! Max. Short Circuit Current Max. Short Circuit Current Max. Short Circuit Current Max. Short Circuit Current Max. Short Circuit Current [kA] [kA] [kA] [kA] [kA] 480V 600V 480V 600V 480V 600V 480Y/277V‡ 600Y/347V‡ 480V 600V C-Frame 140M-C2E-A16 450 65 47 65 47 65 47 65 47 — — 140M-C2E-A25 450 65 47 65 47 65 47 65 47 — — 140M-C2E-A40 450 65 47 65 47 65 47 65 47 — — 140M-C2E-A63 450 65 47 65 47 65 47 65 47 — — 140M-C2E-B10 450 65 47 65 47 65 47 65 47 — — 140M-C2E-B16 450 65 47 65 47 65 47 65 47 — — 140M-C2E-B25 450 65 30 65 30 65 30 65 30 — — 140M-C2E-B40 450 65 25 65 25 65 25 65 25 — — 140M-C2E-B63 450 65 30 65 30 65 — 65 — — — 140M-C2E-C10 450 65 30 65 30 65 — 65 — — — 140M-C2E-C16 450 30 30 30 30 30 — 30 — — — 140M-C2E-C20 450 30 30 10 10 10 — 10 — — — 140M-C2E-C25 450 25 10 10 5 — — — — — — D-Frame 140M-D8E-B25 450 65 30 65 30 65 30 65 30 — — 140M-D8E-B40 450 65 30 65 30 65 30 65 30 — — 140M-D8E-B63 450 65 30 65 30 65 30 65 30 — — 140M-D8E-C10 450 65 30 65 30 65 30 65 30 — — 140M-D8E-C16 450 65 30 65 30 65 30 65 30 — — 140M-D8E-C20 450 65 30 65 30 65 — 65 — — — 140M-D8E-C25 450 30 30 30 30 30 — 30 — — — F-Frame 140M-F8E-C10 600 65 30 65 30 65 30 65 30 — — 140M-F8E-C16 600 65 30 65 30 65 30 65 30 — — 140M-F8E-C20 600 65 30 65 30 65 30 65 30 — — 140M-F8E-C25 600 65 30 65 30 65 30 65 30 — — 140M-F8E-C32 600 65 30 65 30 65 30 65 30 — — 140M-F8E-C45 600 65 18 65 18 65 — 65 — — — 1 2 3 4 5 6 7 CMN-Frame 140-CMN-2500 1000 65 42 — — — — — — — — 140-CMN-4000 1000 65 42 — — — — — — — — 140-CMN-6300 1000 42 18 — — — — — — — — 140-CMN-9000 1000 35 10 — — — — — — — — 140M-I8E-C80 — — — — — — — — — 65 30 140M-I8E-D10 — — — — — — — — — 65 30 140M-I8E-D16 — — — — — — — — — 65 30 140M-I8E-D20 — — — — — — — — — 65 30 140M-J2E-C50 — — — — — — — — — 25 18 140M-J2E-D10 — — — — — — — — — 25 18 140M-J2E-D16 — — — — — — — — — 25 18 140M-J2E-D25 — — — — — — — — — 25 18 8 I-Frame 9 J-Frame 140M-J8E-C50 — — — — — — — — — 65 25 140M-J8E-D10 — — — — — — — — — 65 25 140M-J8E-D16 — — — — — — — — — 65 25 140M-J8E-D25 — — — — — — — — — 65 25 10 11 L-Frame 140M-L2E-D25 — — — — — — — — — 25 18 140M-L2E-D40 — — — — — — — — — 25 18 140M-L2E-D60 — — — — — — — — — 25 18 140M-L2E-D63 — — — — — — — — — 25 18 140M-L8E-D25 — — — — — — — — — 65 25 140M-L8E-D40 — — — — — — — — — 65 25 140M-L8E-D60 — — — — — — — — — 65 25 140M-L8E-D63 — — — — — — — — — 65 25 ‡ For full voltage (delta) ratings above 277V or 347V, follow the NEC or CEC rules for group motor applications. Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-17 12 13 01_140M_Circuit_Breakers_A.qxd 4/22/2008 4:21 PM Page 2-18 Bulletin 140M Motor Circuit Protectors Application Ratings, Continued UL/CSA Listed Application Ratings — Motor Protection Circuit Breaker (MPCB) Only, Continued ! UL 508 Manual Motor Controller Group Motor Installation 1 2 3 4 Cat. No. Max. Fuse or C.B. per NEC Max. Short Circuit Current [kA] 480V 600V Motor Disconnect Tap Conductor Protection UL 508 Self-Protected (Type E) Combination Motor Controller Max. Short Circuit Current [kA] Max. Short Circuit Current [kA] Max. Short Circuit Current [kA] 480V 600V 480V 600V 480Y/277V‡ 600Y/347V‡ C-Frame 140M-C2T-A16 450 65 47 65 47 65 47 65 47 140M-C2T-A25 450 65 47 65 47 65 47 65 47 140M-C2T-A40 450 65 47 65 47 65 47 65 47 140M-C2T-A63 450 65 47 65 47 65 47 65 47 140M-C2T-B10 450 65 47 65 47 65 47 65 47 140M-C2T-B16 450 65 47 65 47 65 30 65 30 140M-C2T-B25 450 65 25 65 25 65 25 65 25 140M-C2T-B40 450 65 30 65 30 65 — 65 — 140M-C2T-B63 450 65 30 65 30 65 — 65 — 140M-C2T-C10 450 30 30 30 30 30 — 30 — 140M-C2T-C16 450 30 30 10 10 10 — 10 — D-Frame 140M-D8T-C16 450 65 30 65 30 65 30 65 30 140M-D8T-C20 450 30 30 30 30 30 — 30 — F-Frame 5 140M-F8T-C25 600 65 30 65 30 65 30 65 30 140M-F8T-C32 600 65 18 65 18 65 18 65 18 ‡ For full voltage (delta) ratings above 277V or 347V, follow the NEC or CEC rules for group motor applications. 6 7 8 9 10 11 12 13 Visit our website: www.ab.com/catalogs 2-18 Preferred availability cat. nos. are printed in bold 01_140M_Circuit_Breakers_A.qxd 4/22/2008 4:22 PM Page 2-19 Bulletin 140M Motor Circuit Protectors Application Ratings, Continued UL Listed Application Ratings — Motor Circuit Protectors Only§ UL 489 Instantaneous Trip Circuit Breaker (Magnetic Only) Manual Motor Controller Group Motor Installation Cat. No. Max. Fuse or C.B. per NEC Max. Short Circuit Current [kA] 480V Motor Disconnect Motor Circuit Protector Max. Short Circuit Current [kA] Max. Short Circuit Current [kA]‡ 600V 480V 600V 480V 600V C-Frame 140M-C2N-A16 450 65 47 65 47 — — 140M-C2N-A25 450 65 47 65 47 — — 140M-C2N-A40 450 65 47 65 47 — — 140M-C2N-A63 450 65 47 65 47 — — 140M-C2N-B10 450 65 47 65 47 — — 140M-C2N-B16 450 65 47 65 47 — — 140M-C2N-B25 450 65 30 65 30 — — 450 65 30 65 30 — — 140M-D8N-B40 450 65 30 65 30 — — 140M-D8N-B63 450 65 30 65 30 — — 140M-D8N-C10 450 65 30 65 30 — — 140M-D8N-C16 450 65 30 65 30 — — 140M-D8N-C25 450 30 30 30 30 — — 140M-F8N-C25 600 65 30 65 30 — — 140M-F8N-C32 600 65 30 65 30 — — 140M-F8N-C45 600 65 18 65 18 — — 140M-H8P-B30 — — — — — 65 25 140M-H8P-B70 — — — — — 65 25 140M-H8P-C15 — — — — — 65 25 140M-H8P-C30 — — — — — 65 25 140M-H8P-C50 — — — — — 65 25 140M-H8P-C70 — — — — — 65 25 140M-H8P-D10 — — — — — 65 25 140M-H8R-D10 — — — — — 65 25 140M-J8P-C70 — — — — — 65 25 140M-J8P-C90 — — — — — 65 25 140M-J8P-D10 — — — — — 65 25 140M-J8P-D12 — — — — — 65 25 140M-J8P-D15 — — — — — 65 25 140M-J8P-D17 — — — — — 65 25 140M-J8P-D20 — — — — — 65 25 140M-J8P-D22 — — — — — 65 25 140M-J8P-D25 — — — — — 65 25 1 2 3 D-Frame 140M-D8N-B25 ! 4 F-Frame 5 H-Frame 6 7 J-Frame 8 9 L-Frame 140M-L8P-D22 — — — — — 65 25 140M-L8P-D25 — — — — — 65 25 140M-L8P-D30 — — — — — 65 25 140M-L8P-D35 — — — — — 65 25 140M-L8P-D40 — — — — — 65 25 140M-L8P-D45 — — — — — 65 25 140M-L8P-D50 — — — — — 65 25 140M-L8P-D60 — — — — — 65 25 10 11 N-Frame 140M-N8P-D80 — — — — — 65 35 140M-N8P-E12 — — — — — 65 35 12 § Separate overload protection is required. ‡ The interrupting rating for MCPs is dependent upon the controller used. Contact your local Rockwell Automation sales office or Allen-Bradley distributor for further information. Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-19 13 01_140M_Circuit_Breakers_A.qxd 4/22/2008 4:22 PM Page 2-20 Bulletin 140M Motor Circuit Protectors Application Ratings, Continued UL Listed Application Ratings - Motor Protection Circuit Breakers with Bulletin 100-C Contactors ! UL 508 Manual Motor Controller Group Motor Installation 1 Cat. No. Max. Fuse or C.B. Minimum per Contactor NEC Size UL 508 Type F Combination Motor Controller Motor Disconnect Max. Short Circuit Current [kA] Max. Short Circuit Current [kA] 480V 480V 600V 600V Minimum Contactor Size UL 508 Type E Self-Protected Combination Motor Controller Max. Short Circuit Current [kA] 480Y/277V§ 600Y/347V§ Minimum Contactor Size Max. Short Circuit Current [kA] 480Y/277V§ 600Y/347V§ C-Frame 140M-C2E-A16 140M-C2E-A25 140M-C2E-A40 140M-C2E-A63 140M-C2E-B10 140M-C2E-B16 140M-C2E-B25 140M-C2E-B40 140M-C2E-B63 140M-C2E-C10 140M-C2E-C16 140M-C2E-C20 140M-C2E-C25 140M-C2E-C25 450 450 450 450 450 450 450 450 450 450 450 450 450 450 100-C09 100-C09 100-C09 100-C09 100-C09 100-C09 100-C09 100-C09 100-C09 100-C09 100-C12 100-C16 100-C23 100-C30 65 65 65 65 65 65 65 65 65 65 30 30 25 25 47 47 47 47 47 47 30 25 30 30 30 30 10 10 65 65 65 65 65 65 65 65 65 65 30 10 10 10 47 47 47 47 47 47 30 25 30 30 30 10 10 5 140M-D8E-B25 140M-D8E-B25 140M-D8E-B40 140M-D8E-B63 140M-D8E-C10 140M-D8E-C16 140M-D8E-C20 140M-D8E-C25 450 — 450 450 450 450 450 450 100-C09 — 100-C09 100-C09 100-C09 100-C12 100-C23 100-C23 65 — 65 65 65 65 65 30 30 — 30 30 30 30 30 30 65 — 65 65 65 65 65 30 30 — 30 30 30 30 30 30 8 140M-F8E-C10 140M-F8E-C16 140M-F8E-C20 140M-F8E-C25 140M-F8E-C32 140M-F8E-C45 600 600 600 600 600 600 100-C30 100-C30 100-C30 100-C30 100-C30 100-C37 65 65 65 65 65 65 30 30 30 30 30 18 65 65 65 65 65 65 30 30 30 30 30 18 9 140-CMN-2500 140-CMN-4000 140-CMN-6300 140-CMN-9000 1000 1000 1000 1000 100-C16 100-C30 100-C43 100-C72 65 65 42 35 42 42 18 10 — — — — — — — — 2 3 4 5 6 100-C09 100-C09 100-C09 100-C09 100-C09 100-C09 100-C09 100-C09 100-C09 100-C09 100-C12 100-C23 — — 65 65 65 65 65 65 65 65 65 65 30 10 — — 47 47 47 47 47 47 30 30 — — — — — — 100-C09 100-C09 100-C09 100-C09 100-C09 100-C09 100-C09 — — — — — — — 65 65 65 65 65 65 65 — — — — — — — 47 47 47 47 47 47 — — — — — — — — 65 — 65 65 65 65 65 65 30 — 30 30 30 30 — — 100-C09 100-C23 100-C23 100-C30 100-C30 100-C30 100-C30 100-C30 65 65 65 65 65 65 65 30 — 30 30 30 30 30 — — 65 65 65 65 65 65 30 30 30 30 30 — 100-C30 100-C30 100-C30 100-C30 100-C30 100-C37 65 65 65 65 65 65 30 30 30 30 30 — — — — — — — — — — — — — — — — — — — — — D-Frame 100-C09 — 100-C09 100-C09 100-C09 100-C12 100-C23 100-C23 F-Frame 7 100-C30 100-C30 100-C30 100-C30 100-C30 100-C37 CMN-Frame — — — — § For full voltage (delta) ratings above 277V or 347V, follow the NEC or CEC rules for group motor applications. 10 11 12 13 Visit our website: www.ab.com/catalogs 2-20 Preferred availability cat. nos. are printed in bold 01_140M_Circuit_Breakers_A.qxd 4/22/2008 4:22 PM Page 2-21 Bulletin 140M Motor Circuit Protectors Application Ratings, Continued UL Listed Application Ratings - Motor Circuit Protectors with Bulletin 100-C Contactors§ UL 508 Manual Motor Controller Group Motor Installation Cat. No. Max. Fuse or C.B. per NEC Minimum Contactor Size Motor Disconnect Max. Short Circuit Current [kA] 480V Max. Short Circuit Current [kA] 600V UL 508 Type E (Self-Protected) Combination Motor Controller Max. Short Circuit Current [kA] Max. Short Circuit Current [kA] 480Y/277V7 600Y/347V7 1 2 480V 600V Minimum Contactor Size 65 65 65 65 65 65 65 47 47 47 47 47 47 30 100-C09 100-C09 100-C09 100-C09 100-C09 100-C09 100-C09 65 65 65 65 65 65 65 47 47 47 47 47 47 — 65 — 65 65 65 65 30 30 — 30 30 30 30 30 100-C09 100-C23 100-C23 100-C30 100-C30 100-C30 100-C30 65 65 65 65 65 65 65 — 30 30 30 30 30 — 65 65 65 30 30 18 100-C30 100-C30 100-C37 65 65 65 30 30 — C-Frame 140M-C2N-A16 140M-C2N-A25 140M-C2N-A40 140M-C2N-A63 140M-C2N-B10 140M-C2N-B16 140M-C2N-B25 450 450 450 450 450 450 450 100-C09 100-C09 100-C09 100-C09 100-C09 100-C09 100-C09 65 65 65 65 65 65 65 47 47 47 47 47 47 30 140M-D8N-B25 140M-D8N-B25 140M-D8N-B40 140M-D8N-B63 140M-D8N-C10 140M-D8N-C16 140M-D8N-C25 450 — 450 450 450 450 450 100-C09 — 100-C09 100-C09 100-C09 100-C12 100-C23 65 — 65 65 65 65 30 30 — 30 30 30 30 30 140M-F8N-C25 140M-F8N-C32 140M-F8N-C45 600 600 600 100-C23 100-C30 100-C37 65 65 65 30 30 18 ! D-Frame 3 4 F-Frame 5 § Separate overload protection is required. 7 For full-voltage (delta) ratings above277V or 347V, follow the NEC or CEC rules for group motor applications. 6 7 8 9 10 11 12 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-21 01_140M_Circuit_Breakers_A.qxd 4/22/2008 4:22 PM Page 2-22 Bulletin 140M Motor Circuit Protectors Application Ratings, Continued Definition of Type 2 Short Circuit Coordination: y The contactor or starter must not endanger persons or plant in the event of a short circuit. y No damage to the motor protection device or other parts may occur with the exception of welding of the contactor or starter contacts if these can be easily separated without appreciable deformation (such as with a screwdriver). ! 1 In the event of short circuit, fast-opening, current-limiting Bulletin 140M Motor Protection Circuit Breakers make it possible to build economical, fully short-circuit coordinated starter combinations with Type 2 coordination. Type 2 Coordination 400V Max. Short Circuit Current [kA] Cat. No. 2 400V For Use With Contactors Below (or larger) Standard Trip High Trip Mag Only Trip 140M-C2E-A16 — 140M-C2N-A16 100 100-C09 140M-C2E-A25 140M-C2T-A16 140M-C2N-A25 100 100-C09 140M-C2E-A40 140M-C2T-A25 140M-C2N-A40 100 100-C09 140M-C2E-A63 140M-C2T-A40 140M-C2N-A63 100 100-C09 140M-C2E-B10 140M-C2T-A63 140M-C2N-B10 100 100-C09 140M-C2E-B16 140M-C2T-B10 140M-C2N-B16 100 100-C09 140M-C2E-B25 140M-C2T-B16 140M-C2N-B25 50 100-C09 140M-C2E-B40 140M-C2T-B25 — 50 100-C09 140M-C2E-B63 140M-C2T-B40 — 50 100-C09 140M-C2E-C10 140M-C2T-B63 — 50 100-C09 140M-C2E-C16 140M-C2T-C10 — 50 100-C129 140M-C2E-C20 140M-C2T-C16 — — — 140M-C2E-C25 — — — — C-Frame 3 4 5 D-Frame 6 7 140M-D8E-B25 — 140M-D8N-B25 100 100-C09 140M-D8E-B40 — 140M-D8N-B40 100 100-C09 140M-D8E-B63 — 140M-D8N-B63 100 100-C09 140M-D8E-C10 — 140M-D8N-C10 65 100-C09 140M-D8E-C16 — 140M-D8N-C16 65 100-C12 140M-D8E-C20 140M-D8T-C16 — 65 100-C23 140M-D8E-C25 140M-D8T-C20 140M-D8N-C25 50 100-C23 140M-F8E-C10 — — 100 100-C09 140M-F8E-C16 — — 100 100-C12 140M-F8E-C20 — — 100 100-C23 140M-F8E-C25 — 140M-F8N-C25 100 100-C30 140M-F8E-C32 140M-F8T-C25 140M-F8N-C32 100 100-C30 140M-F8E-C45 140M-F8T-C32 140M-F8N-C45 100 100-C37 F-Frame 8 CMN-Frame 9 10 140-CMN-2500 — — 65 100-C16 140-CMN-4000 — — 65 100-C30 140-CMN-6300 — — 42 100-C43 140-CMN-9000 — — 35 100-C72 9 Cat. No. 100-C16 contactors Type 1 only 11 12 13 Visit our website: www.ab.com/catalogs 2-22 Preferred availability cat. nos. are printed in bold 01_140M_Circuit_Breakers_A.qxd 4/22/2008 4:23 PM Page 2-23 Bulletin 140M Motor Circuit Protectors Application Ratings, Continued Type 2 Coordination 480V Max. Short Circuit Current [kA] Cat. No. Standard Trip High Trip Mag Only Trip 480V ! For Use With Contactors Below (or larger) C-Frame 140M-C2E-A16 — 140M-C2N-A16 65 100-K05, 100-C09 140M-C2E-A25 140M-C2T-A16 140M-C2N-A25 65 100-K05, 100-C09 140M-C2E-A40 140M-C2T-A25 140M-C2N-A40 65 100-K05, 100-C09 140M-C2E-A63 140M-C2T-A40 140M-C2N-A63 65 100-K05, 100-C09 140M-C2E-B10 140M-C2T-A63 140M-C2N-B10 65 100-K05, 100-C09 140M-C2E-B16 140M-C2T-B10 140M-C2N-B16 65 100-K05, 100-C09 140M-C2E-B25 140M-C2T-B16 140M-C2N-B25 50 100-C16 140M-C2E-B40 140M-C2T-B25 — 50 100-C30 140M-C2E-B63 140M-C2T-B40 — 50 100-C30 140M-C2E-C10 140M-C2T-B63 — 50 100-C30 140M-C2E-C16 140M-C2T-C10 — 10 100-C30 140M-C2E-C20 140M-C2T-C16 — 10 100-C30 140M-C2E-C25 — — 10 100-C30 — 140M-D8N-B25 65 100-C09 140M-D8E-B40 — 140M-D8N-B40 65 100-C09 140M-D8E-B63 — 140M-D8N-B63 65 100-C09 140M-D8E-C10 — 140M-D8N-C10 65 100-C09 140M-D8E-C16 — 140M-D8N-C16 65 100-C12 140M-D8E-C20 140M-D8T-C16 — 65 100-C23 140M-D8E-C25 140M-D8T-C20 140M-D8N-C25 65 100-C23 2 3 D-Frame 140M-D8E-B25 1 4 5 F-Frame 140M-F8E-C10 — — 65 100-C09 140M-F8E-C16 — — 65 100-C12 140M-F8E-C20 — — 65 100-C16 140M-F8E-C25 — 140M-F8N-C25 65 100-C23 140M-F8E-C32 140M-F8T-C25 140M-F8N-C32 65 100-C30 140M-F8E-C45 140M-F8T-C32 140M-F8N-C45 65 100-C37 140-CMN-2500 — — 65 100-C16 140-CMN-4000 — — 65 100-C30 140-CMN-6300 — — 42 100-C43 140-CMN-9000 — — 35 100-C72 6 7 CMN-Frame 8 9 10 11 12 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-23 01_140M_Circuit_Breakers_A.qxd 4/22/2008 4:23 PM Page 2-24 Bulletin 140M Motor Circuit Protectors Application Ratings, Continued Type 2 Coordination 600V ! Max. Short Circuit Current [kA] Cat. No. 600V Max Fuse or C.B per NEC For Use With Contactors Below (or larger) Standard Trip High Trip Mag Only Trip 140M-C2E-A16 — 140M-C2N-A16 47 450 100-K05, 100-C09 140M-C2E-A25 140M-C2T-A16 140M-C2N-A25 47 450 100-K05, 100-C09 140M-C2E-A40 140M-C2T-A25 140M-C2N-A40 47 450 100-K05, 100-C09 140M-C2E-A63 140M-C2T-A40 140M-C2N-A63 47 450 100-K05, 100-C09 140M-C2E-B10 140M-C2T-A63 140M-C2N-B10 47 450 100-K05, 100-C09 140M-C2E-B16 140M-C2T-B10 140M-C2N-B16 47 450 100-K05, 100-C09 140M-C2E-B25 140M-C2T-B16 140M-C2N-B25 10 450 100-C16 140M-C2E-B40 140M-C2T-B25 — 10 450 100-C16 C-Frame 1 2 3 4 5 140M-C2E-B63 140M-C2T-B40 — 5 450 100-C23 140M-C2E-C10 140M-C2T-B63 — 5 450 100-C30 140M-C2E-C16 140M-C2T-C10 — 5 450 100-C30 140M-C2E-C20 140M-C2T-C16 — 5 450 100-C30 140M-C2E-C25 — — 5 450 100-C30 D-Frame 140M-D8E-B25 — 140M-D8N-B25 30 450 100-C30 140M-D8E-B40 — 140M-D8N-B40 30 450 100-C30 140M-D8E-B63 — 140M-D8N-B63 30 450 100-C30 140M-D8E-C10 — 140M-D8N-C10 30 450 100-C30 140M-D8E-C16 — 140M-D8N-C16 30 450 100-C30 140M-D8E-C20 140M-D8T-C16 — 5 450 100-C30 140M-D8E-C25 140M-D8T-C20 140M-D8N-C25 5 450 100-C30 140M-F8E-C10 — — 30 600 100-C30 140M-F8E-C16 — — 30 600 100-C30 140M-F8E-C20 — — 30 600 100-C30 140M-F8E-C25 — 140M-F8N-C25 30 600 100-C30 140M-F8E-C32 140M-F8T-C25 140M-F8N-C32 30 600 100-C30 140M-F8E-C45 140M-F8T-C32 140M-F8N-C45 10 600 100-C37 F-Frame 6 7 CMN-Frame 8 140-CMN-2500 — — 42 1000 100-C16 140-CMN-4000 — — 42 1000 100-C30 140-CMN-6300 — — 18 1000 100-C43 140-CMN-9000 — — 10 1000 100-C72 9 10 11 12 13 Visit our website: www.ab.com/catalogs 2-24 Preferred availability cat. nos. are printed in bold 01_140M_Circuit_Breakers_A.qxd 4/22/2008 4:23 PM Page 2-25 Bulletin 140M Motor Protection Circuit Breakers and Motor Circuit Protectors Accessories Description ! Operator Position 9 OFF ON Tripped Term. No. Front-Mounted Auxiliary Contact 1-pole or 2-pole No additional space required -Only 1 per MPCB Description O X O 13-14 X O X 11-12 N.C. Aux O X O 13-14 N.O. Aux Connection Diagram 7 N.O. Aux X O X 21-22 N.C. Aux O X O 13-14 N.O. Aux 13 21 14 22 For Use With 140M-C, D, F 140M-C-AFA10 140M-C, D, F 140M-C-AFA01 140M-C, D, F 140M-C-AFA11 X O 23-24 1 2 3 4 140M-C, D, F O Cat. No. 140M-C-AFA20 N.O. Aux 5 X O X 11-12 N.C. Aux 140M-C, D, F Right Side-Mounted Auxiliary Contact 2-pole Adds 9 mm to the width of the device - 2 per MPCB X O X 21-22 N.C. Aux O X O 33-34 N.O. Aux O X O 43-44 N.O. Aux X O X 31-32 N.C. Aux 140M-C-AFA02 6 140M-C, D, F 140M-C-ASA20 140M-C, D, F 140M-C-ASA02 140M-C, D, F 140M-C-ASA11 7 31 41 32 X O X 41-42 N.C. Aux O X O 33-34 N.O. Aux X O X 41-42 42 N.C. Aux 8 9 9 X = Contact Closed; O = Contact Open 7 10 11 12 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-25 01_140M_Circuit_Breakers_A.qxd 4/22/2008 4:23 PM Page 2-26 Bulletin 140M Motor Protection Circuit Breakers and Motor Circuit Protectors Accessories, Continued Description ! Operator Position 9 OFF 1 O Front-Mounted Trip Contact 2-pole Indicates tripping of device No additional space required 2 X Tripped O Term. No. Description 13-14 N.O. Aux O O X 27-28 N.O. Trip (Short-Circuit & Overload) X O X 11-12 N.C. Aux 27-28 N.O. Trip (Short-Circuit & Overload) 57-58 N.O. Trip (Short-Circuit & Overload) O O O O O X X X 67-68 N.O. Trip 57-58 N.O. Trip (Short-Circuit & Overload) 4 O Right-Side Mounted Trip Contact 2-pole Indicates tripping of Motor Protection Circuit Breaker Adds 9 mm to the width of the circuit breaker - Only 1 per MPCB - A right-side mounted auxiliary contact may be tandem mounted on top of this Trip Contact 5 6 7 8 Connection Diagram 7 O X X X O 65-66 N.C. Trip X X O 55-56 N.C. Trip (Short-Circuit & Overload) O O X 67-68 N.O. Trip X X O 55-56 N.C. Trip (Short-Circuit & Overload) X X O 65-66 N.C. Trip O O X 77-78 N.O. Trip (Short-Circuit) 65-66 N.C. Trip (Short-Circuit) X X O 9 X = Contact Closed; O = Contact Open 7 9 10 11 12 13 Visit our website: www.ab.com/catalogs 2-26 For Use With Cat. No. 140M-C, D, F 140M-C-AFAR10A10 140M-C, D, F 140M-C-AFAR10A01 11 27 O 3 ON Preferred availability cat. nos. are printed in bold 12 28 57 67 I>> 58 140M-C, 140M-C-ASAR10M10 D, F 68 57 65 I>> 140M-C, 140M-C-ASAR10M01 D, F 58 66 140M-C, 140M-C-ASAR01M10 D, F 140M-C, 140M-C-ASAR01M01 D, F 140M-C, D, F 140M-C-ASAM11 02_140M_Circuit_Protectors_A.qxd 4/23/2008 11:05 AM Page 2-27 Bulletin 140M Motor Protection Circuit Breakers and Motor Circuit Protectors Accessories, Continued Description Operator Position9 OFF O ON X ! Tripped O Term. No. Description 13-14 N.O. Aux Connection Diagram7 For Use With Cat. No. 140-CMN 140-CA20 1 Front-Mounted Auxiliary Contact Internal 2-pole -1 per MPCB O X O 23-24 N.O. Aux X O X 11-12 N.C. Aux X O X 21-22 N.C. Aux O X O 13-14 N.O. Aux X O X 21-22 N.C. Aux O O X 37-38 N.O. Trip (Overload) O O X 43-44 N.O. Trip (Short-Circuit) X X O 35-36 N.C. Trip (Overload) X X O 41-42 N.C. Trip (Short-Circuit) 2 140-CMN 140-CA02 11 21 140-CMN 140-CA02 3 12 22 Front-Mounted TripIndicating Auxiliary Contact Internal 2-pole -1 per MPCB X X O 35-36 N.C. Trip (Overload) O O X 43-44 N.O. Trip (Short-Circuit) O O X 37-38 N.O. Trip (Overload) X X O 41-42 N.C. Trip (Short-Circuit) 140-CMN 140-CA11 140-CMN 140-CT10-10 4 5 6 140-CMN 140-CT01-01 7 140-CMN 140-CT01-10 8 9 140-CMN 140-CT10-01 10 9 X = Contact Closed O = Contact Open 7 11 12 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-27 02_140M_Circuit_Protectors_A.qxd 4/23/2008 11:05 AM Page 2-28 Bulletin 140M Motor Protection Circuit Breakers and Motor Circuit Protectors Accessories, Continued Description Connection Diagram9 Trip Rating For Use With 24V, 60 Hz ! Undervoltage Trip Left-side mounted Adds 18 mm to the width of the circuit breaker Automatically trips MPCB/MCP when voltage falls below 35…70% 1 2 3 Undervoltage Trip Left-side mounted 2 early make contacts integrated Adds 18 mm to the width of the circuit breaker Automatically trips MPCB/MCP when voltage falls below 35…70% 4 5 6 Shunt Trip Left-side mounted Adds 18 mm to the width of the circuit breaker Provides remote tripping of the MPCB/MCP 7 8 Undervoltage Trip Unit Internal, front-mounted Integrated short-circuit trip indication Automatically trips MPCB when voltage falls below 35…70% 9 10 Shunt Trip Unit Internal, front-mounted Integrated short-circuit trip indication Provides remote tripping of the MPCB 11 24V, 50 Hz 140M-C-UXK 120V, 60 Hz 140M-C-UXD 110V, 50 Hz 140M-C-UXC 208V, 60 Hz 140M-C-UXH 220…230V, 50 Hz 240…260V, 60 Hz 140M-C, D, F 140M-C-UXF 140M-C-UXA 277V, 60 Hz 140M-C-UXT 380…400V, 50 Hz 140M-C-UXN 480V, 60 Hz/415V, 50 Hz 140M-C-UXB 575V, 60 Hz/500V, 50 Hz 140M-C-UXM 600V, 60 Hz 140M-C-UXVC 24V, 60 Hz 140M-C-UCJ 24V, 50 Hz 140M-C-UCK 120V, 60 Hz 140M-C-UCD 110V, 50 Hz 140M-C-UCC 208V, 60 Hz 140M-C-UCH 220…230V, 50 Hz 240…260V, 60 Hz 140M-C, D, F 140M-C-UCF 140M-C-UCA 277V, 60 Hz 140M-C-UCT 380…400V, 50 Hz 140M-C-UCN 480V, 60 Hz/415V, 50 Hz 140M-C-UCB 575V, 60 Hz/500V, 50 Hz 140M-C-UCM 600V, 60 Hz 140M-C-UCVC 24V, 60 Hz 140M-C-SNJ 24V, 50 Hz 140M-C-SNK 120V, 60 Hz 140M-C-SND 208V, 60 Hz 140M-C-SNH 220…230V, 50 Hz 140M-C-SNF 240…260V, 60 Hz 140M-C-SNA 277V, 60 Hz 140M-C, D, F 380…400V, 50 Hz 140M-C-SNT 140M-C-SNN 480V, 60 Hz/415V, 50 Hz 140M-C-SNB 575V, 60 Hz/500V, 50 Hz 140M-C-SNM 600V, 60 Hz 140M-C-SNVC 24V DC 140M-C-SNZJ 24V, 50/60 Hz 140-CUV-KJ 110V, 50 Hz/120V, 60 Hz 140-CUV-D 140-CMN 220V, 50 Hz/240V, 60 Hz 140-CUV-A 24V, 50/60 Hz 140-CRT-KJ 110V, 50 Hz/120V, 60 Hz 140-CRT-D 140-CMN 220V, 50 Hz/240V, 60 Hz 9 12 13 Visit our website: www.ab.com/catalogs 2-28 Cat. No. 140M-C-UXJ Preferred availability cat. nos. are printed in bold 140-CRT-A 02_140M_Circuit_Protectors_A.qxd 4/23/2008 11:05 AM Page 2-29 Bulletin 140M Motor Protection Circuit Breakers and Motor Circuit Protectors Accessories, Continued Description For Use With Cat. No. ! Anti-Tamper Shield Provides protection against inadvertent adjustment of the current setting Lockable Twist Knob For 1 padlock 4…6 mm (1/4 in.) dia. shackle Can be locked in OFF position 10 pcs/pkg 140M-C, D, F 140M-C-CA Black 140M-C, D, F 140M-C-KN Red/Yellow 140M-C/-D 140M-C-KRY Red/Yellow 140M-F 140M-F-KRY Black Padlockable Operating Knob Accepts 8 mm (5/16 in.) padlock — up to three padlocks Permits padlocking in the off position Door Coupling Handle For 3 padlocks 4…8 mm (5/16 in.) in diameter IP66 Protection/Type 1, 4, 4X, 12 Interlock override capability Can be modified for locking in ON position Ships with coupling — order extension shaft and legend plate separately Mounting depth (adapter-door): 140-C: 105.5 mm ± 5 mm (4.5 in. ± 3/16 in.) 140-D: 114.5 mm ± 5 mm (4.5 in. ± 3/16 in.) 140-F: 137.1 mm ± 5 mm (5.4 in. ± 3/16 in.) Red/Yellow Black Red/Yellow 140-KN 140-CMN 2 140-KRY 140M-C, D, F 140M-C-DN66 140-CMN 140-CDN66 140M-C, D, F 140M-C-DRY66 140-CMN 140-CDRY66 3 4 5 Extension Shaft Cut to required length for mounting depth (adapter-door): 140M-C: 117…338 mm (4.6 in.…13.3 in.) 140M-D: 126…347 mm (5.0 in.…13.7 in.) 140M-F: 149…369 mm (5.4 in.…14.5 in.) 140-CMN: 180…403 mm (7.1 in.…15.9 in.) 140M-C-DN66, 140M-C-DRY66, 140-CDN66, 140-CDRY66 140M-C-DS Extension Shaft (Extended Length) Cut to required length for mounting depth (adapter-door): 140M-C: 117…488 mm (4.6…19.2 in.) 140M-D: 126…497 mm (5.0…19.6 in.) 140M-F: 149…519 mm (5.4…20.4 in.) 140-CMN: 180…553 mm (7.1…21.8 in.) 140M-C-DN66, 140M-C-DRY66, 140-CDN66, 140-CDRY66 140M-C-DSL 140M-C, D, F 140M-C-DNC Coupler Included with Cat. Nos. 140M-C-DN66 and 140M-C-DRY66 6 7 Legend Plate Marking: "Hauptschalter" and "Main Switch" Marking: "Not-Aus" and "Emergency Off" 140-CDN66 140M-C-DFCN 140-CDRY66 140M-C-DFCRY Locking Tag Padlock attachment to the lockable handles Up to three padlocks 4…8 mm (5/16 in.) shackle 140M-C-KN 140M-C-KRY 140M-F-KRY 140M-C-M3 Black Handle 140M-C 198E-AYTG2 Red/Yellow Handle 140M-C 198E-AYTJ2 IP65 Non-Metallic Enclosure Knockouts for M20 and M25 fittings Suitable for flexible cable with internal ground wire or conduit when externally grounded around the outside of the enclosure (no UL approval) 1 8 9 10 11 Terminal Cover For covering of unused commoning link terminals IP2X finger protection 140M-C, 140M-D 140M-C-WS 140M-F 140M-F-WS 12 Screw Adapter For screw arrangement of a Motor Protection Circuit Breaker 10 pcs/pkg 140M-C, D, F 140M-C-N45 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-29 02_140M_Circuit_Protectors_A.qxd 4/23/2008 11:06 AM Page 2-30 Bulletin 140M Motor Protection Circuit Breakers and Motor Circuit Protectors Accessories, Continued Description ECO Connecting Module — 12 A For DOL and reversing starters Eco-starters mount on single DIN Rail (140M on DIN Rail) Electrical and mechanical interconnection of 140M MPCB and 100-K contactors ! ECO Connecting Modules — 25 A Eco-starters mount on single DIN Rail (140M on DIN Rail) Electrical and mechanical interconnection of 140M MPCB and 100-C (with AC coils or 24V DC electronic coils) contactors 1 Connecting Modules — 25 and 45 A Contactor and MPCB MUST BE mounted separately on (2) DIN Rails Electrical interconnection between 140M MPCB and 100-C contactors (with AC coils) 2 Coil Modules — 25 A and 45 A y For use with Bulletin 103T/107T 3-component starters 3 Spacing Adapter Required for Self-Protected combination motor controller (Type E) applications of Bul. 140M-C, -D, and -F MPCBs 4 Compact Busbar Feeder Block Supply of compact busbars Increases terminal capacity Compact Busbar Feeder Terminal For supply of commoning links Top feed — overlaps commoning link Meets UL Type E spacing requirements 5 Three-Phase Compact Busbar for 25 A Motor Protection Circuit Breakers — 63 A Max. Continuous Current 45 mm spacing For use with front-mounted auxiliary contact 6 Three-Phase Compact Busbar for 25 A Motor Protection Circuit Breakers — 63 A Max. Continuous Current 54 mm spacing For use with side-mounted auxiliary contact 7 Three-Phase Compact Busbar for 25 A Motor Protection Circuit Breakers — 63 A Max. Continuous Current 63 mm spacing For use with side-mounted undervoltage trip and shunt trip 8 9 10 Cat. No. 140M-C to 100-K 140M-C-PEK12 140M-C to 100-C09…C23 140M-C-PEC23 140M-D to 100-C09…C23 140M-D-PEC23 140M-C to 100-C09…C23 140M-C-PNC23 140M-D to 100-C09…C23 140M-D-PNC23 140M-D to 100-C30…C37 140M-D-PNC37 140M-F to 100-C30…C37 140M-F-PNC37 140M-F to 100-C43 140M-F-PNC43 140M-C, -D to 100C09…C23 140M-C-PSC23 140M-D, -F to 100C30…C43 140M-F-PSC43 140M-C, -D 140M-C-TE1 140M-F 140M-F-TE 140M-C, -D 140M-C-WBE 140M-F 140M-F-WBE 140M-C, -D 140M-C-WTE 140M-F 140M-F-WTE 2 connections 3 connections 4 connections 140M-C-W452 140M-C, -D 140M-C-W453 140M-C-W454 5 connections 140M-C-W455 2 connections 140M-C-W542 3 connections 4 connections 140M-C, -D 140M-C-W543 140M-C-W544 5 connections 140M-C-W545 2 connections 140M-C-W632 3 connections 4 connections 140M-C, -D 5 connections Jumper for 140M-D to 140M-C Accommodates difference in depth from Bul. 140M-D to 140M-C 54 mm spacing Can be used with all other commoning links 2 connections Three-Phase Compact Busbar for 45 A Motor Protection Circuit Breakers — 115 A Max. Continuous Current 54 mm spacing For use with front-mounted auxiliary contact 3 connections Three-Phase Compact Busbar for 45 A Motor Protection Circuit Breakers — 115 A Max. Continuous Current 63 mm spacing For use with side-mounted auxiliary contact For Use With 140M-C-W634 140M-C-W635 140M-D to 140M-C 2 connections 140M-C-WD542 140M-F-W542 140M-F 4 connections 140M-F-W543 140M-F-W544 2 connections 3 connections 140M-C-W633 140M-F-W632 140M-F 4 connections 140M-F-W633 140M-F-W634 11 DIN (#3) symmetrical Rail 35 mm x 7.5 mm x 1 m long 10 pcs/kg 140M-D 140M-F 199-DR1 12 DIN (#3) Symmetrical Rail 35 mm x 15 mm x 1 m long Top Hat Rail (DIN #3 Symmetrical Rail) 5 pcs/kg 140M-C 140M-D 140M-F 140-CMN 1492-DR9 13 Notes: 1. See Bulletin 140U for Internal and External Accessories for Bulletin 140M-H, J, L and N frames. 2. Bulletin 140M-I frame Accessories such as auxiliaries, alarms, undervoltage and shunt trips are only available as factory installed modifications. See page 33. Visit our website: www.ab.com/catalogs 2-30 Preferred availability cat. nos. are printed in bold 02_140M_Circuit_Protectors_A.qxd 4/23/2008 11:08 AM Page 2-31 Bulletin 140M Motor Protection Circuit Breakers and Motor Circuit Protectors Accessories, Continued Description For Use With Pkg. Quantity Terminal End Cover — 0.25 in. Terminal End Cover — 0.41 in. Cat. No. 140U-I-TC2 140M-I 1 ! 140U-I-TC4 1 Terminal Shields (Plastic) IP20 Ingress Protection 140M-I 1 140U-I-TS1 2 Padlockable Handle Lock Hasp — Off only Padlocking Hasp Lock-OFF only 140M-I End Cap Kit Provides 3-phase connections for terminal or bolt-on connections Metric Hardware 140M-I Phase Barriers Provides additional phase clearance when special connections are required 140M-I Terminal Lugs Steel Terminal Copper/Aluminum wire #4-4/0 AWG Terminal Lugs Stainless Steel Terminal Copper/Aluminum wire #4-4/0 AWG 1 3 1 Operating Mechanism for External Handles 140U-I-ECM 4 2 140U-I-PB 140U-I-TLS1 140M-I 3 5 6 140U-I-TLS2 Rotary Close Couple Handle International Black handle Rotary Close Couple Handle International Red/Yellow handle 140U-I-PL 140U-I-RCB 140M-I 1 140U-I-RCR 140M-I 7 1 198-H2 8 9 External Handles Black/Grey IP66 (Type 3/3R/4/4X/12) 190-HM4 Red/Yellow IP66 (Type 3/3R/4/4X/12) 190-HM4E Black/Grey IP55 (Type 1) 140M-I 10 1 190-HM1 Red/Yellow IP55 (Type 1) 190-HM1E Overload Pre-trip Auxiliary Contact (AX) Opens contactor coil circuit on overload before MPCB trips (Automatic reset) 140M-J, -L (MPCB only) 1 140U-J-ER1RX 11 12 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-31 02_140M_Circuit_Protectors_A.qxd 4/23/2008 11:09 AM Page 2-32 Bulletin 140M Motor Protection Circuit Breakers and Motor Circuit Protectors Accessories, Continued Description For Use With Pkg. Quantity Cat. No. Extension Shafts ! Standard Enclosure Working Depth [mm (in.)] Minimum 203 (8) Maximum 305 (12) 194R-R3 140M-I 1 Extended 1 Minimum 203 (8) Maximum 508 (20) Description 2 For Use With Flex-Cable Operating Mechanism NEMA Type 1/3/12/4/4X Flange-Mount Handle Cat. No. 140U-I-FCX03 4 ft. (1.2 m) Cable 140U-I-FCX04 6 ft. (1.9 m) Cable 140U-I-FCX06 10 ft. (3.0 m) Cable Flex-Cable Operating Mechanism Stainless Steel - Type 4/4X Flange Mount Handle 140U-I-FCX10 140M-I 1 140U-I-FCS03 4 ft. (1.2 m) Cable 140U-I-FCS04 6 ft. (1.9 m) Cable 140U-I-FCS06 10 ft. (3.0 m) Cable 140U-I-FCS10 4 5 6 7 8 9 10 11 12 13 Visit our website: www.ab.com/catalogs 2-32 Pkg. Quantity 3 ft. (0.9 m) Cable 3 ft. (0.9 m) Cable 3 194R-R4 Preferred availability cat. nos. are printed in bold 02_140M_Circuit_Protectors_A.qxd 4/23/2008 11:09 AM Page 2-33 Bulletin 140M Motor Protection Circuit Breakers and Motor Circuit Protectors Factory Modifications 140M Factory Modifications (Open) Note: For modifications add (option code *) for desired features to cat. no. ! g f Aux / Trip Contacts - I, N Miscellaneous 1st Code 2nd Code Code Description Frame Size KN Black Lockable Knob C, D, F, CMN KY Red/Yellow Lockable Knob C, D, F, CMN TE Spacing Adapter for SelfProtected Starters (Type E) C, D, F MT STD Bus Bar Mount, Top C, D, F, H, CMN F 2 N.O. + 2 N.C. F9 2 N.O. + 2 N.C. MU STD Bus Bar Mount, Universal J, K, L N 1 N.O. (SC+OL) + 1 N.C. (SC) N9 1 N.O. (SC+OL) + 1 N.C. (SC) T 1 N.O. + 1 N.C. and 1 N.O. + 1 N.C. (SC+OL) T9 1 N.O. + 1 N.C. and 1 N.O. + 1 N.C. (SC+OL) g Description 2nd Code Left Side Description 1 Right Side X Placeholder X Placeholder C 1 N.O. + 1 N.C. C 1 N.O. + 1 N.C. 3 Description Bottom Front Right Side X Placeholder X Placeholder h A 1 N.C. C 1 N.O. + 1 N.C. UV and Shunt Trips - C, D, F B 1 N.O. D 2 N.O. C 1 N.O. + 1 N.C. E 2 N.C. D 2 N.O. K 1 N.C. (SC+OL) + 1 N.C. (SC) E 2 N.C. L 1 N.O. (SC+OL) + 1 N.O. (SC) 1st Code Description G Undervoltage Trip 2nd Code Left Side 4 Description Voltage J 24V AC, 60 Hz K 24V AC, 50 Hz R 1 N.C. + 1 N.O. (SC+OL) M 1 N.C. (SC+OL) + 1 N.O. (SC) S 1 N.O. + 1 N.O. (SC+OL) N 1 N.O. (SC+OL) + 1 N.C. (SC) D 120V AC, 60 Hz 1 N.O. (SC) + 1 N.C. (SC) C 110V AC, 50 Hz Q g Aux / Trip Contacts - CMN 1st Code Description 2nd Code Bottom Front Description Top Front‡ X Placeholder X Placeholder C 1 N.O. + 1 N.C. K 1 N.C. (OL) + 1 N.C. (SC) D 2 N.O. L 1 N.O. (OL) + 1 NO (SC) E 2 N.C. M 1 N.C. (OL) + 1 N.O. (SC) N 1 N.O. (OL) + 1 N.C. (SC) P Shunt Trip ‡Cannot be combined with option "h". 1st Code 208V AC, 60 Hz F 220…230V AC, 50 Hz A 240V AC, 60 Hz T 277V AC, 50 Hz N 380…400V AC, 50 Hz B 480V AC, 60 Hz and 415V AC, 50 Hz VC 600V AC, 60 Hz M 575V AC, 60 Hz and 500V AC, 50 Hz ZR 9V DC ZQ 12V DC ZJ 24V DC ZW 36V DC ZY 48V DC g ZZ 60V DC ZB 64V DC ZG 72V DC ZE 80V DC 2nd Code Bottom Front X H Aux / Trip Contacts - H, J, L Description Placeholder 2 9 Only available on MCPs. Aux / Trip Contacts - C, D, F 1st Code Description Description 5 6 7 8 9 Right Side X Placeholder C 1 N.O. + 1 N.C. R7 1 N.O. + 1 N.C. (Overload Function) F9 2 N.O. + 2 N.C. N9 1 N.O. (SC+OL) + 1 N.C. (SC) T9 1 N.O. + 1 N.C. and 1 N.O. + 1 N.C. (SC+OL) 10 11 9 Only available on MCPs. 7 J- and L-Frame MPCB only. 12 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-33 02_140M_Circuit_Protectors_A.qxd 4/23/2008 11:09 AM Page 2-34 Bulletin 140M Motor Protection Circuit Breakers and Motor Circuit Protectors Factory Modifications, Continued 140M Factory Modifications (Open); Continued Note: For modifications add (option code *) for desired features to cat. no. ! 1 1st Code 2 h h UV and Shunt Trips - CMN UV and Shunt Trips - I 2nd Code Description Description Top Front‡ G 1st Code Voltage Undervoltage Trip KJ D P ! Shunt Trip A Description 2nd Code Left Front UV Voltage 24V AC, 60 Hz and 24V AC, 50 Hz 120V AC, 60 Hz and 110V AC, 50 Hz G 240V AC, 60 Hz and 220…230V AC, 50 Hz Undervoltage Trip J 24V AC D 110…127V AC A 208…240V AC B 380…480V AC Left Front h P J 12…24V AC/DC D 48…127V AC and 48…60V DC Shunt Trip N 208…380V AC and 110…127V DC B 415…600V AC and 220…250V DC UV and Shunt Trips - H, J, L 4 1st Code Description 2nd Code Left Front G Undervoltage Trip 5 110…127V AC A 208…240V AC B 380…500V AC Left Front 6 Shunt Trip Description 12…60V AC/DC 110…240V AC/DC B 380…600V AC 2nd Code Left Front G Undervoltage Trip 110…127V AC A 208…240V AC B P 380…480V AC Shunt Voltage J 12…24V AC/DC D 110…240V AC and 110…125V DC N 380…440V AC and 220…250V DC B 480…600V AC Shunt Trip 5 24V AC D Left Front 7 Description UV Voltage J Shunt Voltage D 3 UV and Shunt Trips - N 1st Code 525…600V AC J 2 4 h 24V AC/DC D C P Description UV Voltage J 1 Shunt Voltage ‡ Cannot be combined with option "g". 3 Description 6 7 8 8 9 9 10 10 11 11 12 13 Visit our website: www.ab.com/catalogs 2-34 Preferred availability cat. nos. are printed in bold 02_140M_Circuit_Protectors_A.qxd 4/23/2008 11:10 AM Page 2-35 Bulletin 140M Motor Protection Circuit Breakers and Motor Circuit Protectors Specifications IEC Performance Data Cat. No. 140M-C2E- ! 1 2 A16 A25 A40 A63 B10 B16 B25 B40 B63 C10 C16 C20 C25 Rated Operational Current, Ie [A] 0.16 0.25 0.4 0.63 1 1.6 2.5 4 6.3 10 16 20 25 Magnetic Release Current [A] 2.1 3.3 5.2 8.2 13 21 33 52 82 130 208 260 325 0.12 0.18/0.25 0.37 0.25 0.37/0.55 0.75 1.1/1.5 0.25/0.37 0.55/0.75 1.1 1.5/2.2 Switching of Standard Three-Phase Motors 1 AC-2, AC-3 230/240V [kW] — — — 0.06/0.09 400/415V [kW] 0.02 0.06 0.09 0.12/0.18 500V [kW] — — — 0.18 690V ! [kW] — — — 0.25 0.37/0.55 0.75/1.1 0.55/0.75 1.1/1.5 2.2 2.2 3.0/4.0 4.0/5.5 — 3.0/4.0 5.5/7.5 7.5/10 11 2.5/3.0 4.0/6.3 7.5/10 1.8 2.2/3.0 4.0 5.5/7.5 11/13 11 15 15/17 18.5/2 2 2 3 Back-Up Fuses gG, gL, only if Icc≥Icu 3 4 230/240V [A] 9 9 9 9 9 9 9 9 9 9 9 100 100 400/415V [A] 9 9 9 9 9 9 9 9 9 9 80 100 100 440/460V [A] 9 9 9 9 9 9 9 9 9 9 80 80 80 500V [A] 9 9 9 9 9 9 9 9 9 80 80 80 80 690V [A] 9 9 9 9 9 16 20 35 50 50 63 63 63 4 Ultimate Short Circuit Breaking Capacity Icu 5 230/240V [kA] 100 100 100 100 100 100 100 100 100 100 100 50 50 400/415V [kA] 100 100 100 100 100 100 100 100 100 100 65 50 15 440/460V [kA] 100 100 100 100 100 100 100 100 100 50 10 6 6 500V [kA] 100 100 100 100 100 100 100 100 100 50 10 6 6 690V [kA] 100 100 100 100 100 8 8 8 4 4 3 3 3 5 Rated Service Short Circuit Breaking Capacity 6 7 Ics 230/240V [kA] 100 100 100 100 100 100 100 100 100 100 100 50 50 400/415V [kA] 100 100 100 100 100 100 100 100 100 100 50 15 15 440/460V [kA] 100 100 100 100 100 100 100 100 100 50 6 6 6 500V [kA] 100 100 100 100 100 100 100 100 100 50 6 6 6 690V [kA] 100 100 100 100 100 8 8 8 4 4 3 3 3 6 7 9 No back-up fuse required. 8 8 9 9 10 10 11 11 12 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-35 02_140M_Circuit_Protectors_A.qxd 4/23/2008 11:10 AM Page 2-36 Bulletin 140M Motor Protection Circuit Breakers and Motor Circuit Protectors Specifications, Continued IEC Performance Data, Continued ! Cat. No. 140M-D8E- 1 2 Cat. No. 140M-F8E- B25 B40 B63 C10 C16 C20 C25 C10 C16 C20 C25 C32 Rated Operational Current, Ie [A] 2.5 4.0 6.3 10 16 20 25 10 16 20 25 32 C45 45 Magnetic Release Current [A] 33 52 82 130 208 260 325 130 208 260 325 416 585 Switching of Standard Three-Phase Motors AC-2, AC-3 230/240V [kW] 0.37 400/415V [kW] 0.75 0.55/0.75 1.1/1.5 1.1/1.5 2.2 2.2 3.0/4.0 4.0/5.5 — 2.2 3.0/4.0 4.0/5.5 5.5/6.3 7.5 11/13 3.0/4.0 5.5/7.5 7.5/10 11 3.0/4.0 5.5/7.5 7.5/10 11 15 18.5/22 500V [kW] 1.1 1.5/2.2 690V [kW] 1.8 2.2/3.0 2.5/3.0 4.0/6.3 7.5/10 11 15 4.0/6.3 7.5/10 11 15 15/20 22/30 4.0 5.5/7.5 11/13 15/17 18.5/22 5.5/7.5 11/13 15/17 18.5/22 22/25 30/40 Back-Up Fuses gG, gL, only if Icc≥Icu 3 4 230/240V [A] 9 9 9 9 9 9 9 9 9 9 9 9 9 400/415V [A] 9 9 9 9 9 100 100 80 100 100 100 125 125 440/460V [A] 9 9 9 9 9 100 100 80 100 100 100 125 125 500V [A] 9 9 9 9 80 100 100 80 100 100 100 125 125 690V [A] 20 35 50 50 63 63 63 63 80 80 80 100 100 100 Ultimate Short Circuit Breaking Capacity Icu 5 230/240V [kA] 100 100 100 100 100 100 100 100 100 100 100 100 400/415V [kA] 100 100 100 100 100 65 65 65 65 65 65 65 65 440/460V [kA] 100 100 100 100 65 65 65 65 65 65 65 65 50 500V [kA] 100 100 100 100 50 50 50 50 50 50 50 50 50 690V [kA] 10 10 10 6 6 6 6 10 10 10 10 10 10 Rated Service Short Circuit Breaking Capacity 6 7 Ics 230/240V [kA] 100 100 100 100 100 100 100 100 100 100 100 100 100 400/415V [kA] 100 100 100 100 50 25 25 50 50 50 50 50 50 440/460V [kA] 100 100 100 100 50 25 25 50 50 50 50 50 50 500V [kA] 100 100 100 100 50 25 25 50 50 50 50 50 50 690V [kA] 10 10 10 6 4 4 4 10 10 10 10 6 6 8 9 10 11 12 13 Visit our website: www.ab.com/catalogs 2-36 Preferred availability cat. nos. are printed in bold 02_140M_Circuit_Protectors_A.qxd 4/23/2008 11:10 AM Page 2-37 Bulletin 140M Motor Protection Circuit Breakers and Motor Circuit Protectors Specifications, Continued IEC Performance Data, Continued ! 140-CMN-… Cat. No. Rated Operational Current, Ie [A] -2500 25 -4000 40 -6300 63 -9000 90 350 560 890 1260 [kW] 5.5/7.5 10/11 13/20 22/25 Magnetic Release Current [A] Switching of Standard Three-Phase Motors AC-2, AC-3 230/240V7 1 400/415V7 [kW] 7.5/13 15/22 25/32 37/45 500V7 [kW] 11/15 18.5/25 30/40 45/55 690V7 [kW] 15/22 25/30 37/55 63/75 2 Back-up fuses gG, gL,, only if Icc ≥ Icu 230/240V [A] 9 9 9 9 400/415V [A] 160 160 160 160 500V [A] 160 160 160 160 690V [A] 160 160 160 160 3 Ultimate short-circuit breaking capacity Icu 230/240V [kA] 100 100 100 100 400/415V [kA] 65 65 65 50 500V [kA] 50 30 30 25 690V [kA] 15 8 8 6 4 Rated service short-circuit breaking capacity Ics 230/240V [kA] 100 100 100 100 400/415V [kA] 65 50 50 25 500V [kA] 50 25 25 13 690V [kA] 15 8 6 6 5 6 9 No back-up fuse required. 7 Power ratings: Preferred values according to IEC 60072-1. 7 8 9 10 11 12 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-37 02_140M_Circuit_Protectors_A.qxd 4/23/2008 11:10 AM Page 2-38 Bulletin 140M Motor Protection Circuit Breakers and Motor Circuit Protectors Specifications, Continued IEC Performance Data, Continued ! A16 A25 A40 Cat. No. 140M-C2NA63 B10 B16 B25 0.16 0.25 0.4 0.63 1 1.6 2.5 Magnetic Release Current [A] 2.1 Switching of Standard Three-Phase Motors AC-2, AC-3 3.3 5.2 8.2 13 21 32 Rated Operational Current, Ie 1 2 [A] 230/240V [kW] — — — 0.06/0.09 0.12 0.18/0.25 0.37 400/415V [kW] 0.02 0.06 0.09 0.12/0.18 0.25 0.37/0.55 0.75 500V [kW] — — — 0.18 0.25/0.37 0.55/0.75 1.1 690V [kW] — — — 0.25 0.37/0.55 0.75/1.1 1.8 230/240V [A] 9 9 9 9 9 9 9 400/415V [A] 9 9 9 9 9 9 9 440/460V [A] 9 9 9 9 9 9 9 500V [A] 9 9 9 9 9 9 9 690V [A] 9 9 9 9 9 16 20 Back-Up Fuses gG, gL, only if Icc≥Icu9 3 Ultimate Short Circuit Breaking Capacity 4 5 Icu 230/240V [kA] 100 100 100 100 100 100 100 400/415V [kA] 100 100 100 100 100 100 100 440/460V [kA] 100 100 100 100 100 100 100 500V [kA] 100 100 100 100 100 100 100 690V [kA] 100 100 100 100 100 10 8 Rated Service Short Circuit Breaking Capacity Ics 6 7 230/240V [kA] 100 100 100 100 100 100 100 400/415V [kA] 100 100 100 100 100 100 100 440/460V [kA] 100 100 100 100 100 100 100 500V [kA] 100 100 100 100 100 100 100 690V [kA] 100 100 100 100 100 8 8 9 No back-up fuse required. 8 9 10 11 12 13 Visit our website: www.ab.com/catalogs 2-38 Preferred availability cat. nos. are printed in bold 02_140M_Circuit_Protectors_A.qxd 4/23/2008 11:11 AM Page 2-39 Bulletin 140M Motor Protection Circuit Breakers and Motor Circuit Protectors Specifications, Continued IEC Performance Data, Continued Cat. No. 140M-D8NB25 B40 B63 C10 Cat. No. 140M-F8NC16 C25 C25 C32 C45 Rated Operational Current, Ie [A] 2.5 4.0 6.3 10 16 25 25 32 45 Magnetic Release Current [A] 32 52 82 130 208 325 325 416 585 Switching of Standard Three-Phase Motors ! 1 AC-2, AC-3 230/240V [kW] 0.37 0.55/0.75 1.1/1.5 2.2 3.0/4.0 — 5.5/6.3 7.5 11/13 400/415V [kW] 0.75 1.1/1.5 2.2 3.0/4.0 5.5/7.5 11 11 15 18.5/22 500V [kW] 1.1 1.5/2.2 2.5/3.0 4.0/6.3 7.5/10 15 15 15/20 22/30 690V [kW] 1.8 2.2/3.0 4.0 5.5/7.5 11/13 18.5/22 18.5/22 22/25 30/40 2 Back-Up Fuses gG, gL, only if Icc≥Icu 230/240V [A] 9 9 9 9 9 9 100 125 125 400/415V [A] 9 9 9 9 9 100 100 125 125 440/460V [A] 9 9 9 9 80 100 100 125 125 500V [A] 9 9 9 9 80 80 100 125 125 690V [A] 20 35 50 50 63 63 80 100 100 3 4 Ultimate Short Circuit Breaking Capacity Icu 230/240V [kA] 100 100 100 100 100 100 100 100 400/415V [kA] 100 100 100 100 100 50 65 65 100 65 440/460V [kA] 100 100 100 100 50 50 65 65 50 500V [kA] 100 100 100 100 50 25 50 50 50 690V [kA] 10 10 10 6 6 6 10 10 10 5 Rated Service Short Circuit Breaking Capacity Ics 230/240V [kA] 100 100 100 100 100 100 100 100 100 400/415V [kA] 100 100 100 100 50 25 50 50 50 440/460V [kA] 100 100 100 100 50 25 50 50 50 500V [kA] 100 100 100 100 50 25 50 50 50 690V [kA] 10 10 10 6 4 4 10 6 6 6 7 9 No back-up fuse required. 8 9 10 11 12 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-39 02_140M_Circuit_Protectors_A.qxd 4/23/2008 11:11 AM Page 2-40 Bulletin 140M Motor Protection Circuit Breakers and Motor Circuit Protectors Specifications, Continued IEC Performance Data, Continued ! Cat. No. 140M-D8T- 1 2 Cat. No. 140M-F8T- C16 C20 C25 C32 Rated Operational Current, Ie [A] 16 20 25 32 Magnetic Release Current [A] 260 325 416 585 7.5 Switching of Standard Three-Phase Motors AC-2, AC-3 230/240V 7 [kW] 3.0/4.0 4.0/5.5 5.5/6.3 400/415V 7 [kW] 5.5/7.5 7.5/10 11 15 500V 7 [kW] 7.5/10 11 15 15/20 690V 7 [kW] 11/13 15/17 18.5/22 22/25 Back-up fuses gG, gL,, only if Icc ≥ Icu 3 4 5 230/240V [A] 9 9 9 9 400/415V [A] 80 100 100 125 440/460V [A] 80 100 100 125 500V [A] 80 80 100 125 690V [A] 63 63 80 100 Ultimate short-circuit breaking capacity Icu 230/240V [kA] 100 100 100 100 400/415V [kA] 65 65 65 65 440/460V [kA] 65 65 65 65 500V [kA] 50 25 50 50 690V [kA] 6 6 10 10 Rated service short-circuit breaking capacity Ics 6 7 Ics 230/240V [kA] 100 100 100 100 400/415V [kA] 25 25 50 50 440/460V [kA] 25 25 50 50 500V [kA] 25 25 50 50 690V [kA] 4 4 6 6 9 No back-up fuse required. 7 Consult your local Rockwell Automation sales office or Allen-Bradley distributor. 8 9 10 11 12 13 Visit our website: www.ab.com/catalogs 2-40 Preferred availability cat. nos. are printed in bold 02_140M_Circuit_Protectors_A.qxd 4/23/2008 11:11 AM Page 2-41 Bulletin 140M Motor Protection Circuit Breakers and Motor Circuit Protectors Specifications, Continued IEC Performance Data, Continued Cat. No. 140M-C2TA16 A25 A40 A63 B10 B16 B25 B40 B63 C10 C16 Rated Operational Current, Ie [A] 0.16 0.25 0.40 0.63 1.0 1.6 2.5 4.0 6.3 10 16 Magnetic Release Current [A] 3.2 5.2 8.2 13 21 32 52 82 130 208 260 Switching of Standard Three-Phase Motors ! 1 AC-2, AC-3 230/240V [kW] — — — 0.06/0.09 0.12 0.18/0.25 0.37 0.55/0.75 1.1/1.5 2.2 3.0/4.0 400/415V [kW] 0.02 0.06 0.09 0.12/0.18 0.25 0.37/0.55 0.75 1.1/1.5 2.2 3.0/4.0 5.5/7.5 500V [kW] — — — 0.18 0.25/0.37 0.55/0.75 1.1 1.5/2.2 2.5/3.0 4.0/6.3 7.5/10 690V [kW] — — — 0.25 0.37/0.55 0.75/1.1 1.8 2.2/3.0 4.0 5.5/7.5 11/13 230/240V [A] 9 9 9 9 9 9 9 9 9 9 9 400/415V [A] 9 9 9 9 9 9 9 9 9 9 80 440/460V [A] 9 9 9 9 9 9 9 9 9 9 80 500V [A] 9 9 9 9 9 9 9 9 9 80 80 690V [A] 9 9 9 9 9 16 20 35 50 50 63 2 Back-Up Fuses gG, gL, only if Icc≥Icu Ultimate Short Circuit Breaking Capacity 3 4 Icu 230/240V [kA] 100 100 100 100 100 100 100 100 100 100 100 400/415V [kA] 100 100 100 100 100 100 100 100 100 100 50 440/460V [kA] 100 100 100 100 100 100 100 100 100 50 10 500V [kA] 100 100 100 100 100 100 100 100 100 50 10 690V [kA] 100 100 100 100 100 8 8 8 4 4 3 5 Rated Service Short Circuit Breaking Capacity Ics 230/240V [kA] 100 100 100 100 100 100 100 100 100 100 100 400/415V [kA] 100 100 100 100 100 100 100 100 100 100 15 440/460V [kA] 100 100 100 100 100 100 100 100 100 50 6 500V [kA] 100 100 100 100 100 100 100 100 100 50 6 690V [kA] 100 100 100 100 100 8 8 8 4 4 3 6 7 9 No back-up fuse required. 8 9 10 11 12 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-41 02_140M_Circuit_Protectors_A.qxd 4/23/2008 11:12 AM Page 2-42 Bulletin 140M Motor Protection Circuit Breakers and Motor Circuit Protectors Specifications, Continued General Data Cat. No. ! 140M-C 140M-D 140M-F 140-CMN Rated Insulation Voltage Ui 1 IEC, SEV, VDE 0660 [V] 690 690 UL, CSA [V] 600 600 Rated Impulse Withstand Voltage Uimp Pollution degree Main circuits Uimp /Overvoltage Category Auxiliary circuits Uimp /Overvoltage Category Rated Frequency 2 [Hz] 3 3 6 kV/III 6 kV/III 6 kV/III 6 kV/III 50/60 40…60 Utilization Category IEC 60947-2 (Circuit breaker) A A IEC 60947-4-1 (Motor starter) AC-3 AC-3 Life Span 3 Mechanical Electrical (Ie max.) Switching Frequency [operations] 100 000 [operations] 100 000 [operations/h] 30 000 30 000 30 000 10 000 (up to 63 A) 5 000 (up to 90 A) max. 25 (motor starts) max. 20 -40 … +80 -25… +80 Ambient Temperature 4 Storage [°C] Operation [°C] -25… +60 Resistance to Climatic Change IEC 68-2 Moisture/heat resistance 5 Moisture/change resistance Site Altitude 23 °C, 83%/40 °C, 92%, 50 cycles [m] to 2000 N.N. Protection Class Resistance to Shock 6 IP20, when wired [g] 30, 11 ms Resistance to Vibration Frequency range in all directions C IV (acc. to IEC 68) 40 °C, 92% relative humidity, 56 days 30, 11 ms IEC 68-2 [Hz] 10…150 [g] under testing Rated Thermal Current Ith 7 IEC, SEV, VDE 0660 up to 40 °C ambient temperature [A] 0.1…25 1.6…25 6.3…45 up to 60 °C ambient temperature [A] 0.1…25 1.6…25 6.3…45 16… 90 Rated Supply Current Ie [A] 0.1…25 1.6…25 6.3…45 16… 90 13 7 6 4 Number of setting ranges 8 9 Dependence on Temperature 40 °C [A] no reduction 50 °C [A] no reduction 60 °C [A] no reduction 70 °C [A] 15 % current reduction of the upper rated current Ie Overload Protection IEC 60947-4-1 Motor protection (except Cat. Nos. 140M-C2N, 140M-D8N, 140M-F8N) Characteristics Ambient Temperature Compensation 10 [°C] IEC 60947-4-1 Motor protection -20 …+60 Phase-loss Protection Differential release Trip class 11 16… 90 Magnetic Release Release current 10 (except Cat. Nos. 140M-C2N, 140M-D8N, 140M-F8N) fixed setting 10 fixed setting 13 x Ie max. (for 140M-C2E, 140M-D8E, 140M-F8E, 140MC2N, 140M-D8N, 140M-F8N) 16…20 x Ie max. (for 140M-C2T, 140M-D8T, 140M-F8T) Ie max. = maximum values of setting ranges fixed setting 14 x Ie max. Total Power loss Pv Circuit Breaker at rated load operating temperature 12 Main Circuit Breaker Application [W] 6…8 6…8 13 Visit our website: www.ab.com/catalogs 2-42 9…16 33 Usable as main circuit breaker according to IEC 204 with corresponding accessories Preferred availability cat. nos. are printed in bold 02_140M_Circuit_Protectors_A.qxd 4/23/2008 11:12 AM Page 2-43 Bulletin 140M Motor Protection Circuit Breakers and Motor Circuit Protectors Specifications, Continued General Data, Continued Cat. No. 140M-C… 140M-D… Conformity to Standards 140M-F… 140-CMN IEC 60947-1; -2; -4-1; EN 60947-1; -2; -4-1; UL 508; CSA 22.2, No. 14 IEC 60947-1; -2; -4-1; EN 60947-1; -2; -4-1; UL 508; CSA 22.2, No. 14 CE, UL, CSA CE, UL, CSA Approvals 1 Terminal Parts Type of terminals Screwdriver Pozidriv No. 2/Blade No. 3 Pozidriv No. 2/Blade No. 3 1. conductor 2. conductor [mm2 ]/[AWG] [mm2 ]/[AWG] 1…4/No. 16…10 1…4/No. 16…10 2.5…16/No. 14…4 2.5…10/No. 14…4 2.5…35 1. conductor 2. conductor [mm2 ]/[AWG] [mm2 ]/[AWG] 1.5…6/No. 16…8 1.5…6/No. 16…8 2.5…16/No. 14…4 2.5…10/No. 14…4 4…50 / 12…2 1. conductor 2. conductor [mm2 ]/[AWG] [mm2 ]/[AWG] 1…6/No. 16…10 1…6/No. 16…10 2.5…25/No. 14…4 2.5…16/No. 14…4 4…50 / 12…2 2…2.5/18…22 3…3.5/27…30 6…10/55…90 Tightening torque ! [Nm]/[lb•in] 2 3 Accessories for Bulletin 140M Motor Protection Circuit Breakers Auxiliary Contact Blocks for Front Mounting Cat. No. 140M-C-AFA…, 140M-C-AFAR… Auxiliary Contact Blocks for Right-Side Mounting Cat. No. 140M-C-ASA…, 140M-C-ASAR… [A] [A] 5 4 10 6 (UL/CSA Standards) AC DC B 300 Q 300 B 600 Q 600 Back-Up Fuses gG, gL [A] 10 10 Rated Thermal Current Ith at 40 °C ambient temperature at 60 °C ambient temperature 4 5 Contact Class Coordination According to NEMA Rated Supply Current 6 [V] 24 120 240 24 120 240 415 690 AC-15 [A] 4 3 1.5 6 5 3 2 0.7 DC-13 [V] 24 120 240 24 120 240 415 [A] 2 0.5 0.25 2 0.5 0.25 0.15 7 Terminal Parts Type of terminals Screwdriver Pozidriv No. 2/Blade No. 3 1. conductor 2. conductor [mm2]/[AWG] [mm2]/[AWG] 0.5…1.5/18…14 0.75…1.5/18…14 0.5…2.5/18…14 0.75…2.5/18…14 1. conductor 2. conductor [mm2]/[AWG] [mm2]/[AWG] 0.75…1.5/18…14 0.75…1.5/18…14 0.75…2.5/18…14 0.75…2.5/18…14 1. conductor 2. conductor [mm2]/[AWG] [mm2]/[AWG] 0.75…1.5/18…14 0.75…1.5/18…14 0.75…2.5/18…14 0.75…2.5/18…14 [N•m]/[lb•in] 1.2…1.5/10.6…13 1.2…1.5/10.6…13 Tightening torque 8 9 10 11 12 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-43 02_140M_Circuit_Protectors_A.qxd 4/23/2008 11:12 AM Page 2-44 Bulletin 140M Motor Protection Circuit Breakers and Motor Circuit Protectors Specifications, Continued Accessories for Bulletin 140M Motor Protection Circuit Breakers, Continued ! 1 Actuating Voltage Pull-in Drop-out Rated Control Voltage min. max. Undervoltage Trip for Left-Side Mounting Cat. No. 140M-C-UX… Undervoltage Trip with 2 Auxiliary Contacts for Left-Side Mounting Cat. No. 140M-C-UC… 0.85…1.1 x Us 0.7…0.35 x Us 0.85…1.1 x Us 0.7…0.35 x Us 0.7…1.1 x Us 21V 50 Hz, 24V 60 Hz 600V 50 Hz 21V 50 Hz, 24V 60 Hz 600V 50 Hz 21V 50 Hz, 24V 60 Hz 600V 50 Hz On-Time 2 Coil Rating Pull-in Hold Shunt Trip for Left-Side Mounting Cat. No. 140M-C-SN… 100% 100% 100% 8.5 VA, 6 W 3 VA, 1.2 W 8.5 VA, 6 W 3 VA, 1.2 W 8.5 VA, 6 W 3 VA, 1.2 W Terminal Parts Type of terminals 3 Screwdriver 4 Pozidriv No. 2/Blade No. 3 1. conductor 2. conductor [mm2]/[AWG] [mm2]/[AWG] 0.5…2.5/No. 18…14 0.75…2.5/No. 18…14 1. conductor 2. conductor [mm2]/[AWG] [mm2]/[AWG] 0.75…2.5/No. 18…14 0.75…2.5/No. 18…14 1. conductor 2. conductor [mm2]/[AWG] [mm2]/[AWG] 0.75…2.5/No. 18…14 0.75…2.5/No. 18…14 [N•m]/[lb•in] 1.25…1.5/10.6…13.3 Tightening torque 5 Commoning Link Feeder Terminal 140M-C-WTE Rated Thermal Current Ith at 60 °C ambient temperature 6 [A] 140M-F-WTE 140M-C-W 140M-F-W 64 120 64 120 1. conductor [mm2]/[AWG] 1.5…16 4…50/12…110 ⎯ ⎯ 1. conductor [mm2]/[AWG] 1.5…25/No. 14…4 2.5…50/12…110 ⎯ ⎯ 1. conductor [mm2]/[AWG] 1.5…25/No. 14…4 ⎯ ⎯ [N•m]/[lb•in] 3/27 ⎯ ⎯ Tightening torque 5…6/45…54 7 8 9 10 11 12 13 Visit our website: www.ab.com/catalogs 2-44 Commoning Link 140M-C-WTE Preferred availability cat. nos. are printed in bold 02_140M_Circuit_Protectors_A.qxd 4/23/2008 11:12 AM Page 2-45 Bulletin 140M Motor Protection Circuit Breakers and Motor Circuit Protectors Specifications, Continued Weights Description Motor Protection Circuit Breakers Weight [g] Cat.No. 317 140M-C2E-… 373 140M-D8E-… 782 140M-F8E-… 315 140M-C2N-… 365 140M-D8N-… 782 140M-F8N-… 315 140M-C2T-… 365 140M-D8T-… 782 140M-F8T-… 1845 140-CMN-… ! 1 2 140M-C-AFA10 140M-C-AFA01 10 3 140M-C-AFA11 140M-C-AFA20 Auxiliary Contacts 140M-C-ASA… 140M-C-AFAR10A… 15 140M-C-ASAR…M… 4 140M-C-ASAM11 31 Undervoltage Trip 140-CA… 108 140M-C-UX… 110 140M-C-SN… 116 140M-C-UC… 94 140-CUV… Trip Contact Blocks 31 140-CT… Shunt Trip 94 140-CRT… Weight [g] Cat.No. ` Anti-Tamper Cover 2 140M-C-CA 5 Locking Tag 30 Door Coupling Handle 123 Extension Shaft 46 140M-C-DS Legend Plate 4 140M-C-DFC… Commoning Links 172 6 140M-C-KN Lockable Twist Knob Feeder Terminal 5 140M-C-KRY 7 140M-C-M3 140M-C-DN66 140M-C-NRY66 8 140M-C-WT 140M-F-WT 47 140M-C-W452 80 140M-C-W453 104 140M-C-W454 132 140M-C-W455 52 140M-C-W542 86 140M-C-W543 118 140M-C-W544 154 140M-C-W545 56 140M-C-W632 92 140M-C-W633 134 140M-C-W634 170 140M-C-W635 9 10 11 12 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-45 02_140M_Circuit_Protectors_A.qxd 4/23/2008 11:12 AM Page 2-46 Bulletin 140M Motor Protection Circuit Breakers and Motor Circuit Protectors Specifications, Continued Accessories for Bulletin 140-CMN Circuit Breakers ! Cat. No. 140-CT Trip Contact Block for Flush Mounting on Cat. No. 140-CMN Circuit Breakers 1 2 Rated Thermal Current Ith up to 40 °C ambient temperature up to 60 °C ambient temperature NEMA contact class (UL/CSA-Approval) Cat. No. 140-CRT, 140-CUV Undervoltage Trip and Shunt Trip for Flush Mounting on Cat. No. 140-CMN Circuit Breakers 2 2 [A] [A] 10 6 AC DC B 600 Standard Pilot Duty R 300 Light Pilot Duty Make/Break max. voltage 432 VA72 VA480 V 28 VA28 VA250 V 16 A 16 A Back-Up Fuse gG, gL Rated Current Ie 3 AC-15: [V] [A] 230 3 400 2.5 500 1.5 690 0.75 DC-13: [V] [A] 24 2 48 0.6 110 0.2 230 0.1 440 0.04 AC-14: 24 1.5 110 1.5 230 1.0 400 1.0 DC 13: 24 1.5 48 0.5 60 0.4 110 0.2 500 0.75 Terminals 4 Screwdriver 5 1.conduct or 2.conduct or [mm2]/[AWG] [mm2]/[AWG] 0.75… 2.5/No. 18… 14 0.75… 2.5/No. 18… 14 0.75… 2.5/No. 18… 14 0.75… 2.5/No. 18… 14 1.conduct or 2.conduct or [mm2]/[AWG] [mm2]/[AWG] 0.75… 2.5/No. 18… 14 0.75… 2.5/No. 18… 14 0.75… 2.5/No. 18… 14 0.75… 2.5/No. 18… 14 [N•m]/[lb•in] 1… 1.5/8.8… 10.3 1… 1.5/8.8… 10.3 Tightening torque 6 Cat. No. 140-CUV… Undervoltage Trip Unit for Right-Side Mounting on Cat. No. 140-CMN Circuit Breakers Cat. No. 140-CRT... Shunt Trip for Flush Mounting on Cat. No. 140-CMN Circuit Breakers Pick-up 0.8… 1.1 x Us 0.7… 1.1 x Us Drop-out 0.7… 0.35 x Us ⎯ Duty cycle 100 % ED 100 % ED min. 12 V 50 Hz/14 V 60 Hz 12 V 50 Hz/14 V 60 Hz max. 600 V 50 Hz 600 V 50 Hz [VA/W] [VA/W] 11 / 8 4/1 12 / 7 6/2 Fine-stranded [mm2] 2 x 0.75…2.5 2 x 0.75…2.5 Coarse-stranded [mm2] 2 x 0.75…2.5 2 x 0.75…2.5 1… 1.5 1… 1.5 Coarse-stranded [AWG] No. 18…. 14 No. 18…. 12 [lb•in] 8.8… 10.3 8.8… 10.3 7 Operating Voltage 8 Control Voltage 9 Coil Performance Pick-up Drop-out 10 11 Terminals Terminal type Tightening torque Tightening torque [Nm] 12 13 Visit our website: www.ab.com/catalogs 2-46 Preferred availability cat. nos. are printed in bold 02_140M_Circuit_Protectors_A.qxd 4/23/2008 11:12 AM Page 2-47 Bulletin 140M Motor Protection Circuit Breakers and Motor Circuit Protectors Specifications, Continued Cut-off current ! asymmetrical symmetrical 1 The Bulletin 140-M limits solid short-circuit current Icc (prospective short-circuit current). ID is the maximum cut-off current (highest instantaneous value of the limited short-circuit current). This value is indicated in the following diagrams as a function of the progressive system short-circuit current. 2 Bulletin 140M-C Circuit Breaker Maximum cut-off current Rated operating voltage 415V Maximum forward energy Rated operating voltage 415V 3 4 5 6 7 Bulletin 140M-D Circuit Breaker Maximum cut-off current Rated operating voltage 415V 8 Maximum cut-off current Rated operating voltage 415V 9 max. forward energy max. cut-off current ID [kA] 10 11 12 Prospective short-circuit current Icc [kA] Prospective short-circuit current Icc [kA] 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-47 02_140M_Circuit_Protectors_A.qxd 4/23/2008 11:12 AM Page 2-48 Bulletin 140M Motor Protection Circuit Breakers and Motor Circuit Protectors Specifications, Continued Bulletin 140M-F Circuit Breaker ! Maximum cut-off current Rated operating voltage 415V Maximum cut-off current Rated operating voltage 415V 3 max. forward energy 2 max. cut-off current ID [kA] 1 4 Prospective short-circuit current Icc [kA] Prospective short-circuit current Icc [kA] 5 Time-Current Characteristic Bulletin 140M-C, -D, -F Motor Protection Circuit Breakers Bulletin 140-CMN Motor Protector 10 000 1h 6 1 000 100 1 7 Release Time [s] 8 10 1 2 0.1 0.01 9 0.001 0.8 1 2 4 6 10 20 40 60 100 Multiple of the set current IeF 10 1) Thermal Release Trip Current The adjustable current-dependent delayed bimetal release protects motors against overload. The curve shows the mean operating current at an ambient temperature of 20 °C starting from the cold state. Careful testing and setting ensures effective motor protection even in the case of single-phasing. The overload characteristic is also valid for transformer protection. 11 2) Magnetic Release Trip Current The instantaneous magnetic trip has a fixed operating current setting. This corresponds to 13 times the maximum value of setting range. (Transformer protection up to 20 x Ie max.) At a lower setting it is correspondingly higher. 12 13 Current Setting IeF The overload trip corresponds to a thermal overload relay in a motor starter conforming to IEC947-4-1. If a different value is prescribed (e.g., reduced Ie for cooling medium having a temperature higher than 40 °C or a place of installation higher than 2000 m above sea level), the setting current is equal to the reduced rated current Ie of the motor. Visit our website: www.ab.com/catalogs 2-48 Preferred availability cat. nos. are printed in bold 02_140M_Circuit_Protectors_A.qxd 4/23/2008 11:12 AM Page 2-49 Bulletin 140M Motor Protection Circuit Breakers and Motor Circuit Protectors Approximate Dimensions Cat. No. 140M-C, -D, -F ! Dimensions are shown in millimeters. Dimensions are not intended to be used for manufacturing purposes. Cat. No. 140M-C2… Cat. No. 140M-D8… 65 1 2 45 92 90 91 45 92 45 45 4.5 4.5 90 91 45 5 5 45 54.9 24.8 18 45 9 4.5 § 44 62 8 24.8 18 70 45 § 9 4.5 54 3 8 72 80 4 55 Cat. No. 140M-F8… Mounting on 35 mm DIN Rail § Auxiliary contact (side mounted) Undervoltage/shunt trip Auxiliary contact (front mounted) 5 45 111.4 55.7 4.5 6 18 § 29.4 4.5 7 91 9 54 8 102 110 54.9 8 64.9 43.9 53.9 44.7 42.4 34.8 42.4 13.9 10 23.9 5 L3 5 3 L2 55 5 L3 3 L2 1 L1 9 10 3 L2 5 L3 5 L3 3 L2 1 L1 (10) (10) 1 L1 Cat. No. 140M-C-TE1 Type E adapter on Cat. No. 140M-C2E… (55) 44.9 5 L3 5 L3 3 L2 3 L2 1 L1 1 L1 (55) 45 44.9 44.9 5 5 L3 5 L3 3 L2 3 L2 1 L1 1 L1 1 L1 10 24.8 55 44.7 11 12 Cat. No. 140M-C-TE1 Type E adapter on Cat. No. 140M-D8E… 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-49 02_140M_Circuit_Protectors_A.qxd 4/23/2008 11:12 AM Page 2-50 Bulletin 140M Motor Protection Circuit Breakers and Motor Circuit Protectors Approximate Dimensions, Continued Dimensions are shown in millimeters. Dimensions are not intended to be used for manufacturing purposes. ° 90 90 30° 0° ° 12 d ! d 1 2 Mounting position/safety clearance of Cat. No. 140M-C…, 140M-D…, 140M-F… 3 4 4.5 min. 100 1.5...5 5 3.5 35...45 b 53.5 6 53.5 140M-C-DS 140M-C-DSL a 7 c1 + 5 mm 4...8 + 5 mm c2 4.5 8 9 2.4 140M-C-D…66 10 With Cat. No. 140-M-C-DS Shaft 11 With Cat. No. 140-M-C-DSL Shaft Cat. No. a b c1 c2 d Cat. No. a b c1 c2 d 140M-C 117…338 105.5 ±5 49.5 40.5 25 140M-C 117…438 105.5 ±5 49.5 40.5 25 140M-D 126…347 114.5 ±5 49.5 40.5 25 140M-D 126…497 114.5 ±5 49.5 40.5 25 140M-F 148.6…369.6 137.1 ±5 59.35 50.35 30 140M-F 148.6…519 137.1 ±5 59.35 50.35 30 12 13 Visit our website: www.ab.com/catalogs 2-50 Preferred availability cat. nos. are printed in bold 02_140M_Circuit_Protectors_A.qxd 4/23/2008 11:12 AM Page 2-51 Bulletin 140M Motor Protection Circuit Breakers and Motor Circuit Protectors Approximate Dimensions, Continued Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. ! Cat. No. 198E… 1 2 3 4 5 6 198E-AYT… 7 8 9 10 140M-C-WB 11 12 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-51 02_140M_Circuit_Protectors_A.qxd 4/23/2008 11:12 AM Page 2-52 Bulletin 140M Motor Protection Circuit Breakers and Motor Circuit Protectors Approximate Dimensions, Continued Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. ! Cat. No. 140-CMN… 1 2 3 4 5 140-CMN 70 6 90 ° 90 ° ° 90 30° 70 7 8 Mounting position/safety clearance of Cat. No. 140-CMN 9 140-CD… 10 Note: See Bulletin 140U-H, J, L and N for dimensions of 140M-H, J, L and N frames. 11 12 13 Visit our website: www.ab.com/catalogs 2-52 Preferred availability cat. nos. are printed in bold 02_140M_Circuit_Protectors_A.qxd 4/23/2008 11:13 AM Page 2-53 Bulletin 140M Motor Protection Circuit Breakers and Motor Circuit Protectors Approximate Dimensions, Continued Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. Cat. Nos. 140M-H, -I, -J, -L, -N A ! G C E D 1 F B 2 3 4 5 E 7 H H 6 E E E 8 E A B C D E F G H H-Frame 77 (3) 140 (5-1/2) 88 (3-1/2) 75 (3) 25.4 (1) 96.8 (3-13/16) 24.6 (31/32) 22.4 (7/8) I-Frame 105 (4-1/8) 152 (6) 105 (4-1/8) 88 (3-1/2) 35 (1-3/8) 114 (4-1/2) 19 (3/4) 40 (1-9/10) J-Frame 105 (4-1/8) 178 (7) 113 (4-29/64) 88 (3-1/2) 35 (1-3/8) 139.7 (5-1/2) 19.8 (25/32) 20.6 (13/16) L-Frame 140 (5-1/2) 258 (10-5/32) 138 (5-7/16) 110 (4-21/64) 43.7 (1-23/32) 214.4 (8-7/16) 21.3 (27/32) 24.7 (31/32) N-Frame 210 (8-17/64) 407 (16-1/64) 183 (7-13/64) 140 (5-1/2) 69.9 (2-3/4) 374.7 (14-3/4) 16 (5/8) 29.5 (1-5/32) 9 10 11 12 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-53 01_140U_100A_G_Frame.qxd 4/23/2008 11:53 AM Page 2-54 Bulletin 140U Molded Case Circuit Breakers Product Overview ! ! 1 2 3 Bulletin 140U Molded Case Circuit Breakers Table of Contents y 15…1200 A Molded Case Circuit Breakers − Thermal-Magnetic 15…800 A − Electronic 70…1200 A y LS — Long Time/Short Time y LSI — Long Time/Short Time/High Instantaneous y LSG — Long Time/Short Time/Ground Fault y LSIG — Long Time/Short Time/High Instantaneous/Ground Fault − Molded Case Switches 125…1200 A y Factory- or field-installed accessories y Flex cable operating mechanisms y Rotary variable-depth operating mechanisms y High interrupting ratings in compact dimensions y Globally rated and approved product line for worldwide application Product Selection — 100 A, G-Frame.......... 2-57 Product Selection — 125 A, H-Frame.......... 2-60 Product Selection — 250 A, J-Frame........... 2-69 Product Selection — 400 A, K-Frame .......... 2-74 Product Selection — 600 A, L-Frame........... 2-79 Product Selection — 800 A, M-Frame ......... 2-84 Product Selection — 1200 A, N-Frame ....... 2-88 Certifications Standards Compliance UL Listed CSA Certified CE Marked KEMA-KEUR UL 489 CSA 22.2, No. 5 EN/IEC 60947-2 4 Product Line Overview 5 6 7 8 G-Frame H-Frame J-Frame K-Frame L-Frame M-Frame Max. Current In Frame Reference 100 A 125 A 250 A 400 A 600 A 800 A 1200 A Current Range 15…100 A 15…125 A 70…250 A 100…400 A 300…600 A 300…800 A 600…1200 A 9 9 9 9 9 9 — LS — — 9 9 9 9 9 LSI — — 9 9 9 9 9 LSG — — 9 9 9 9 9 LSIG — — 9 9 9 9 9 Thermal Magnetic N-Frame Electronic: Interrupting Ratings: 9 10 11 12 13 380…415V (Icu) 14 22 480V 14 22 600V — 690V (Icu) — 25 25 40 35 18 65 22 3 70 25 40 70 100 40 65 100 45 70 100 50 70 50 70 100 100 25 35 65 100 35 65 100 35 65 100 50 65 50 65 100 35 18 18 25 35 25 35 50 25 35 50 25 35 25 35 50 6 6 7 12 10 13 18 20 25 15 20 25 20 25 30 25 4 6 Molded Case Switches 9 9 9 9 9 9 9 Flex Cable Operators 9 9 9 9 9 9 9 Rotary Operators 9 9 9 9 9 9 9 Internal Control Modules (Field installed) 9 9 9 9 9 9 9 UL 489 9 9 9 9 9 9 9 UL File E197878, Guide No. DIV Q 9 9 9 9 9 9 9 CSA 22.2, No. 5 9 9 9 9 9 9 9 CSA File Nos. 216034, 216035, 219884 Class No. 1432-01 9 9 9 9 9 9 9 IEC 60947-2 9 9 9 — 9 9 9 CE 9 9 9 — 9 9 9 KEMA-KEUR 9 9 9 9 9 9 9 Standards Compliance Visit our website: www.ab.com/catalogs 2-54 Preferred availability cat. nos. are printed in bold 01_140U_100A_G_Frame.qxd 4/23/2008 11:53 AM Page 2-55 Bulletin 140U Molded Case Circuit Breakers Catalog Number Explanation Examples given in this section are for reference purposes. This basic explanation should not be used for product selection; not all combinations will produce a valid cat. no. Refer to the tables on the following pages for descriptions of options. ! Complete Circuit Breaker Assemblies 140U – H 6 C 3 – C50 – H b c d e f g a 1 h a d g Bulletin No. Protection Type Internal Control Modules Code Description Code Description Code 140U Molded Case Circuit Breaker C Fixed Thermal/Fixed Magnetic A 1 Auxiliary contact D Fixed Thermal/Adjust Magnetic B 2 Auxiliary contacts 2 Description b E Adjust Thermal/Fixed Magnetic D 1 Alarm contact Frame/Rating F Adjust Thermal/Adjust Magnetic F 1 Auxiliary + 1 Alarm contact G Electronic (LSG — Long, short, ground fault) G Undervoltage release only H Electronic (LSI — Long, short, high instant) I Electronic (LSIG — Long, short, high instant, ground fault) Code Description H 125 A J 250 A K 400 A L 600 A Description H 1 Auxiliary contact + undervoltage release J 2 Auxiliary contacts + undervoltage release L e 1 Auxiliary + 1 Alarm contact + undervoltage release N 1 Alarm contact + undervoltage release 800 A L Electronic (LS — Long and Short time) N 1200 A S Molded Case Switch (Isolator) Interrupting Rating/Breaking Capacity (based on Ic at 480V) Shunt trip only Control Module Combinations Code M c P Poles Q 1 Auxiliary contact + shunt trip Code Description R 2 Auxiliary contacts + shunt trip Code Description 1 1 poles 2 20…29 kA T 1 Auxiliary + 1 Alarm contact + shunt trip 2 2 poles 3 30…39 kA V 1 Alarm contact + shunt trip 3 3 poles 5 50…59 kA 6 60…69 kA 8 80…89 kA 0 ≥100 kA f Current Range Code Description C 10 rr. A D 100 rr0 A E 1000 rr00 A 3 4 5 6 h Voltage Code 7 See the following pages for voltage code descriptions: All frame sizes Page 2-92 8 9 10 11 12 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-55 01_140U_100A_G_Frame.qxd 4/23/2008 11:53 AM Page 2-56 Bulletin 140U Molded Case Circuit Breakers Catalog Number Explanation, Continued Examples given in this section are for reference purposes. This basic explanation should not be used for product selection; not all combinations will produce a valid cat. no. Refer to the tables on the following pages for descriptions of options. ! ! Frames 140U – 1 2 3 4 a J 3 X 3 b c d e a c d Bulletin No. Interrupting Rating/Breaking Capacity (based on Ic at 480V) Protection Type Code Description 140U Molded Case Circuit Breaker Code Description X Frame Only Code Description 2 20…29 kA b 3 30…39 kA e Frame/Rating 5 50…59 kA Poles Code Description 6 60…69 kA Code Description J 250 A 8 80…89 kA 3 3 poles K 400 A 0 ≥100 kA Q 600 A M 800 A Trip Units 140U – 5 a 6 T D 3 b c d e – D25 f a c e Bulletin No. Trip Unit Poles Code Description Code Description Code Description 140U Molded Case Circuit Breaker T Trip Unit 3 3 poles 7 8 J b d f Frame/Rating Protection Type Current Range Code Description Code Description Code J 250 A C Fixed Thermal/Fixed Magnetic C 10 rr. A K 400 A D Fixed Thermal/Adjust Magnetic D 100 rr0 A L 600 A E Adjust Thermal/Fixed Magnetic E 1000 rr00 A M 800 A F Adjust Thermal/Adjust Magnetic G Electronic (LSG — Long, short, ground fault) H Electronic (LSI — Long, short, high instant) I Electronic (LSIG — Long, short, high instant, ground fault) L Electronic (LS — Long and Short time) S Molded Case Switch (isolator) 9 10 11 12 13 Visit our website: www.ab.com/catalogs 2-56 Preferred availability cat. nos. are printed in bold Description 01_140U_100A_G_Frame.qxd 4/23/2008 11:53 AM Page 2-57 Bulletin 140U Molded Case Circuit Breakers Product Selection — 100 A, G-Frame/Accessories y UL 489 y CSA 22.2, No. 5 Note: Terminal box lugs provided as standard ! Note: Accessories cannot be field installed to the G-Frame circuit breakers. Circuit breakers with 1 auxiliary contact are also available. 14 kA, Thermal-Magnetic, Fixed Thermal-Fixed Magnetic Rated Current In [A] Thermal Trip [A] Ir = In (Fixed) Magnetic Trip [A] Im = 10 x In 15 20 25 30 35 40 45 50 15 20 25 30 35 40 45 50 150 200 250 300 350 400 450 500 Interrupt Rating (50/60 Hz) Icu /Ics [kA] 208V AC 65 65 65 65 65 65 65 65 240V AC 65 65 65 65 65 65 65 65 480V AC 14 14 14 14 14 14 14 14 2 Poles Interrupt Rating [kA] 9 125/250V DC Cat. No. 140U-G1C2-C15 10 10 140U-G1C2-C20 140U-G1C2-C25 10 140U-G1C2-C30 10 140U-G1C2-C35 10 140U-G1C2-C40 10 140U-G1C2-C45 10 140U-G1C2-C50 10 2 Poles w/ 1 aux. contact Cat. No. 140U-G1C2-C15-A 140U-G1C2-C20-A 140U-G1C2-C25-A 140U-G1C2-C30-A 140U-G1C2-C35-A 140U-G1C2-C40-A 140U-G1C2-C45-A 140U-G1C2-C50-A 1 2 3 9 Time constant is 8 ms min. 22 kA, Thermal-Magnetic, Fixed Thermal-Fixed Magnetic Rated Current In [A] Thermal Trip [A] Ir = In (Fixed) Magnetic Trip [A] Im = 10 x In 15 20 25 30 35 40 45 50 60 70 80 90 100 15 20 25 30 35 40 45 50 60 70 80 90 100 150 200 250 300 350 400 450 500 600 700 800 900 1000 Interrupt Rating (50/60 Hz) Icu /Ics [kA] 208V AC 65 65 65 65 65 65 65 65 65 65 65 65 65 240V AC 65 65 65 65 65 65 65 65 65 65 65 65 65 480V AC 22 22 22 22 22 22 22 22 22 22 22 22 22 3 Poles Interrupt Rating [kA] 9 125/250V DC Cat. No. 140U-G2C3-C15 10 10 140U-G2C3-C20 10 140U-G2C3-C25 140U-G2C3-C30 10 10 140U-G2C3-C35 140U-G2C3-C40 10 140U-G2C3-C45 10 140U-G2C3-C50 10 140U-G2C3-C60 10 140U-G2C3-C70 10 140U-G2C3-C80 10 140U-G2C3-C90 10 140U-G2C3-D10 10 3 Poles w/ 1 aux. contact Cat. No. 140U-G2C3-C15-A 140U-G2C3-C20-A 140U-G2C3-C25-A 140U-G2C3-C30-A 140U-G2C3-C35-A 140U-G2C3-C40-A 140U-G2C3-C45-A 140U-G2C3-C50-A 140U-G2C3-C60-A 140U-G2C3-C70-A 140U-G2C3-C80-A 140U-G2C3-C90-A 140U-G2C3-D10-A 4 5 6 7 9 Time constant is 8 ms min. and 2 poles of a 3-pole circuit breaker. 8 Accessories External Accessories Description Rotary, Variable-Depth Operating Mechanism UL Type 3/12/4/4X, IP 66 Rotary handle 12 in. (30.48 cm) operating rod Cat. No. Black Handle 140U-G-RVM12B Red/Yellow Handle 140U-G-RVM12R 9 10 DIN Rail Adapter Allows 2-pole G-frame MCCB to mount to 35 mm DIN Rail Qty: 1 140U-G-DRA2 11 DIN Rail Adapter Allows 3-pole G-frame MCCB to mount to 35 mm DIN Rail Qty: 1 140U-G-DRA3 12 Padlock Kit Padlocking Hasp Lock-OFF only Qty: 1 140U-G-PL Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-57 13 01_140U_100A_G_Frame.qxd 4/23/2008 11:53 AM Page 2-58 Bulletin 140U Molded Case Circuit Breakers Approximate Dimensions — 100 A, G-Frame 3-Pole Dimensions ! .84 [ 21,3 ] 1 .36 [ 9,1 ] .45 [ 11,4 ] 2 3 3.00 [ 76,2 ] 4 3.21 [ 81,4 ] Ø.16 [ 4,1 ] 1.00 [ 25,4 ] 5 6 4.88 [ 123,8 ] 140U G FRAME 3.22 [ 81,7 ] 7 8 9 1.00 [ 25,4 ] 1.00 [ 25,4 ] 2.41 [ 61,2 ] 10 .45 [ 11,4 ] 11 .36 [ 9,1 ] 2.83 [ 71,8 ] 1.22 [ 31 ] 12 13 Visit our website: www.ab.com/catalogs 2-58 Preferred availability cat. nos. are printed in bold 01_140U_100A_G_Frame.qxd 4/23/2008 11:54 AM Page 2-59 Bulletin 140U Molded Case Circuit Breakers Approximate Dimensions — 100 A, G-Frame, Continued Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes. 2-Pole Dimensions ! 15-100 AMP, PRESSURE COLLAR TERMINALS 1 .84 [ 21,4 ] 2 .49 [ 12,5 ] 3 2.00 [ 50,8 ] Ø.14 [ 3,6 ] 1.00 [ 25,4 ] 4 2.42 [ 61,5 ] 5 .97 [ 24,6 ] 6 7 3.22 [ 81,8 ] 8 9 1.00 [ 25,4 ] 3.21 [ 81,5 ] 10 .49 [ 12,4 ] 11 12 1.22 [ 30,9 ] 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-59 02_140U_125A_H_Frame.qxd 4/23/2008 11:59 AM Page 2-60 Bulletin 140U Molded Case Circuit Breakers Product Selection — 125 A, H-Frame Product Selection — 125 A, H-Frame ! ! 1 2 3 4 5 y UL 489 y CSA 22.2, No. 5 y IEC 60947-2 y CE y KEMA-KEUR Note: Terminal box lugs provided as standard 1-Pole 25/18 kA, Thermal-Magnetic, Fixed Thermal-Fixed Magnetic Breaking Capacity (50 Hz) Icu /Ics [kA] Interrupting Rating (60 Hz) [kA] Rated Current In [A] Magnetic Trip [A] Im = 10 x In 240V 277V Cat. No. 15 500 25 25 25 18 140U-H1C1-C15 20 500 25 25 25 18 140U-H1C1-C20 25 500 25 25 25 18 140U-H1C1-C25 30 500 25 25 25 18 140U-H1C1-C30 35 500 25 25 25 18 140U-H1C1-C35 40 500 25 25 25 18 140U-H1C1-C40 45 500 25 25 25 18 140U-H1C1-C45 50 500 25 25 25 18 140U-H1C1-C50 60 600 25 25 25 18 140U-H1C1-C60 70 700 25 25 25 18 140U-H1C1-C70 80 800 25 25 25 18 140U-H1C1-C80 90 900 25 25 25 18 140U-H1C1-C90 100 1000 25 25 25 18 140U-H1C1-D10 110 1100 25 25 25 18 140U-H1C1-D11 125 1250 25 25 25 18 140U-H1C1-D12 220…240V 2-Pole 25/25 kA, Thermal-Magnetic, Fixed Thermal-Fixed Magnetic 6 7 8 9 10 Breaking Capacity (50 Hz) Icu /Ics [kA] Interrupting Rating (60 Hz) [kA] Rated Current In [A] Magnetic Trip [A] Im = 10 x In 240V 480V 600/347V Cat. No. 15 500 35 35 25 25 — — — — 35 25 18 140U-H2C2-C15 20 500 35 35 25 25 — — — — 35 25 18 140U-H2C2-C20 25 500 35 35 25 25 — — — — 35 25 18 140U-H2C2-C25 30 500 35 35 25 25 — — — — 35 25 18 140U-H2C2-C30 35 500 35 35 25 25 — — — — 35 25 18 140U-H2C2-C35 40 500 35 35 25 25 — — — — 35 25 18 140U-H2C2-C40 45 500 35 35 25 25 — — — — 35 25 18 140U-H2C2-C45 50 500 35 35 25 25 — — — — 35 25 18 140U-H2C2-C50 60 600 35 35 25 25 — — — — 35 25 18 140U-H2C2-C60 70 700 35 35 25 25 — — — — 35 25 18 140U-H2C2-C70 80 800 35 35 25 25 — — — — 35 25 18 140U-H2C2-C80 140U-H2C2-C90 220…240V 380…415V 500V 690V 90 900 35 35 25 25 — — — — 35 25 18 100 1000 35 35 25 25 — — — — 35 25 18 140U-H2C2-D10 110 1100 35 35 25 25 — — — — 35 25 18 140U-H2C2-D11 125 1250 35 35 25 25 — — — — 35 25 18 140U-H2C2-D12 11 12 13 Visit our website: www.ab.com/catalogs 2-60 Preferred availability cat. nos. are printed in bold 02_140U_125A_H_Frame.qxd 4/23/2008 12:00 PM Page 2-61 Bulletin 140U Molded Case Circuit Breakers Product Selection — 125 A, H-Frame, Continued 2-Pole 40/35 kA, Thermal-Magnetic, Fixed Thermal-Fixed Magnetic Rated Current In [A] Thermal Trip [A] Ir = In (Fixed) Magnetic Trip [A] Im = 10 x In 15 Fixed 20 Fixed 25 Breaking Capacity (50 Hz) Icu /Ics [kA] Interrupting Rating (60 Hz) [kA] 220…240V 380…415V 500V 690V 500 85 43 40 30 — — — 500 85 43 40 30 — — — Fixed 500 85 43 40 30 — — 30 Fixed 500 85 43 40 30 — 35 Fixed 500 85 43 40 30 40 Fixed 500 85 43 40 30 45 Fixed 500 85 43 40 50 Fixed 500 85 43 60 Fixed 600 85 70 Fixed 700 80 Fixed 800 90 Fixed 100 ! 240V 480V 600/347V Cat. No. — 85 35 22 140U-H3C2-C15 — 85 35 22 140U-H3C2-C20 — — 85 35 22 140U-H3C2-C25 — — — 85 35 22 140U-H3C2-C30 — — — — 85 35 22 140U-H3C2-C35 — — — — 85 35 22 140U-H3C2-C40 30 — — — — 85 35 22 140U-H3C2-C45 40 30 — — — — 85 35 22 140U-H3C2-C50 43 40 30 — — — — 85 35 22 140U-H3C2-C60 85 43 40 30 — — — — 85 35 22 140U-H3C2-C70 85 43 40 30 — — — — 85 35 22 140U-H3C2-C80 900 85 43 40 30 — — — — 85 35 22 140U-H3C2-C90 Fixed 1000 85 43 40 30 — — — — 85 35 22 140U-H3C2-D10 110 Fixed 1100 85 43 40 30 — — — — 85 35 22 140U-H3C2-D11 125 Fixed 1250 85 43 40 30 — — — — 85 35 22 140U-H3C2-D12 Thermal Trip [A] Ir = In (Fixed) Magnetic Trip [A] Im = 10 x In 15 Fixed 500 Breaking Capacity (50 Hz) Icu /Ics [kA] 220…240V 100 50 380…415V 70 35 690V — — — 240V 480V 600/347V Cat. No. 100 65 25 140U-H6C2-C15 20 Fixed 500 100 50 70 35 — — — — 100 65 25 140U-H6C2-C20 25 Fixed 500 100 50 70 35 — — — — 100 65 25 140U-H6C2-C25 30 Fixed 500 100 50 70 35 — — — — 100 65 25 140U-H6C2-C30 35 Fixed 500 100 50 70 35 — — — — 100 65 25 140U-H6C2-C35 40 Fixed 500 100 50 70 35 — — — — 100 65 25 140U-H6C2-C40 45 Fixed 500 100 50 70 35 — — — — 100 65 25 140U-H6C2-C45 50 Fixed 500 100 50 70 35 — — — — 100 65 25 140U-H6C2-C50 60 Fixed 600 100 50 70 35 — — — — 100 65 25 140U-H6C2-C60 70 Fixed 700 100 50 70 35 — — — — 100 65 25 140U-H6C2-C70 80 Fixed 800 100 50 70 35 — — — — 100 65 25 140U-H6C2-C80 90 Fixed 900 100 50 70 35 — — — — 100 65 25 140U-H6C2-C90 100 Fixed 1000 100 50 70 35 — — — — 100 65 25 140U-H6C2-D10 110 Fixed 1100 100 50 70 35 — — — — 100 65 25 140U-H6C2-D11 125 Fixed 1250 100 50 70 35 — — — — 100 65 25 140U-H6C2-D12 3-Pole 25/25 kA, Thermal-Magnetic, Fixed Thermal-Fixed Magnetic Rated Current In [A] 15 20 25 30 35 40 45 50 60 70 80 90 100 110 125 Thermal Trip [A] Ir = In (Fixed) 15 20 25 30 35 40 40 50 60 70 80 90 100 110 125 Magnetic Trip [A] Im = 10 x In 500 500 500 500 500 500 500 500 600 700 800 900 1000 1100 1250 Breaking Capacity (50 Hz) Icu /Ics [kA] 220…240V 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 380…415V 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 525V 22 22 22 22 22 22 22 22 22 22 22 22 22 22 18 3 Interrupting Rating (60 Hz) [kA] 500V — 2 4 2-Pole 70/65 kA, Thermal-Magnetic, Fixed Thermal-Fixed Magnetic Rated Current In [A] 1 690V 17 17 17 17 17 17 17 17 17 17 17 17 17 17 17 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Interrupting Rating (60 Hz) [kA] 240V 480V 600/347V 35 25 18 35 25 18 35 25 18 35 25 18 35 25 18 35 25 18 35 25 18 35 25 18 35 25 18 35 25 18 35 25 18 35 25 18 35 25 18 35 25 18 35 25 18 5 6 7 8 9 Cat. No. 140U-H2C3-C15 140U-H2C3-C20 140U-H2C3-C25 140U-H2C3-C30 140U-H2C3-C35 140U-H2C3-C40 140U-H2C3-C45 140U-H2C3-C50 140U-H2C3-C60 140U-H2C3-C70 140U-H2C3-C80 140U-H2C3-C90 140U-H2C3-D10 140U-H2C3-D11 140U-H2C3-D12 10 11 12 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-61 02_140U_125A_H_Frame.qxd 4/23/2008 12:01 PM Page 2-62 Bulletin 140U Molded Case Circuit Breakers Product Selection — 125 A, H-Frame, Continued 3-Pole 40/35 kA, Thermal-Magnetic, Fixed Thermal-Fixed Magnetic ! ! 1 2 3 Rated Current In [A] 15 20 25 30 35 40 45 50 60 70 80 90 100 110 125 Thermal Trip [A] Ir = In (Fixed) 15 20 25 30 35 40 45 50 60 70 80 90 100 110 125 Magnetic Trip [A] Im = 10 x In 500 500 500 500 500 500 500 500 600 700 800 900 1000 1100 1250 Breaking Capacity (50 Hz) Icu /Ics [kA] 220…240V 85 43 85 43 85 43 85 43 85 43 85 43 85 43 85 43 85 43 85 43 85 43 85 43 85 43 85 43 85 43 380…415V 40 30 40 30 40 30 40 30 40 30 40 30 40 30 40 30 40 30 40 30 40 30 40 30 40 30 40 30 40 30 525V 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Interrupting Rating (60 Hz) [kA] 240V 480V 600/347V 85 35 22 85 35 22 85 35 22 85 35 22 85 35 22 85 35 22 85 35 22 85 35 22 85 35 22 85 35 22 85 35 22 85 35 22 85 35 22 85 35 22 85 35 22 Cat. No. 140U-H3C3-C15 140U-H3C3-C20 140U-H3C3-C25 140U-H3C3-C30 140U-H3C3-C35 140U-H3C3-C40 140U-H3C3-C45 140U-H3C3-C50 140U-H3C3-C60 140U-H3C3-C70 140U-H3C3-C80 140U-H3C3-C90 140U-H3C3-D10 140U-H3C3-D11 140U-H3C3-D12 3 3 3 3 3 3 3 3 3 3 3 3 3 Interrupting Rating (60 Hz) [kA] 240V 480V 600/347V 100 65 25 100 65 25 100 65 25 100 65 25 100 65 25 100 65 25 100 65 25 100 65 25 100 65 25 100 65 25 100 65 25 100 65 25 100 65 25 Cat. No.‡ 140U-H6C3-C15 140U-H6C3-C20 140U-H6C3-C25 140U-H6C3-C30 140U-H6C3-C40 140U-H6C3-C50 140U-H6C3-C60 140U-H6C3-C70 140U-H6C3-C80 140U-H6C3-C90 140U-H6C3-D10 140U-H6C3-D11 140U-H6C3-D12 6 6 6 6 6 6 6 6 6 6 6 6 6 Interrupting Rating (60 Hz) [kA] 240V 480V 600/347V 200 100 35 200 100 35 200 100 35 200 100 35 200 100 35 200 100 35 200 100 35 200 100 35 200 100 35 200 100 35 200 100 35 200 100 35 200 100 35 Cat. No.‡ 140U-H0C3-C15 140U-H0C3-C20 140U-H0C3-C25 140U-H0C3-C30 140U-H0C3-C40 140U-H0C3-C50 140U-H0C3-C60 140U-H0C3-C70 140U-H0C3-C80 140U-H0C3-C90 140U-H0C3-D10 140U-H0C3-D11 140U-H0C3-D12 690V 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 3-Pole 70/65 kA, Thermal-Magnetic, Fixed Thermal-Fixed Magnetic 4 5 6 7 Rated Current In [A] 15 20 25 30 40 50 60 70 80 90 100 110 125 Thermal Trip [A] Ir = In (Fixed) Fixed Fixed Fixed Fixed Fixed Fixed Fixed Fixed Fixed Fixed Fixed Fixed Fixed Magnetic Trip [A] Im = 10 x In 500 500 500 500 500 500 600 700 800 900 1000 1100 1250 Breaking Capacity (50 Hz) Icu /Ics [kA] 220…240V 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 380…415V 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 525V 25 25 25 25 25 25 25 25 25 25 25 25 25 690V 13 13 13 13 13 13 13 13 13 13 13 13 13 6 6 6 6 6 6 6 6 6 6 6 6 6 ‡ Current Limiting 3-Pole 100/100 kA, Thermal-Magnetic, Fixed Thermal-Fixed Magnetic 8 9 10 11 12 Rated Current In [A] 15 20 25 30 40 50 60 70 80 90 100 110 125 Thermal Trip [A] Ir = In (Fixed) Fixed Fixed Fixed Fixed Fixed Fixed Fixed Fixed Fixed Fixed Fixed Fixed Fixed Magnetic Trip [A] Im = 10 x In 500 500 500 500 500 500 600 700 800 900 1000 1100 1250 Breaking Capacity (50 Hz) Icu /Ics [kA] 220…240V 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 380…415V 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 525V 35 35 35 35 35 35 35 35 35 35 35 35 35 690V 18 18 18 18 18 18 18 18 18 18 18 18 18 8 8 8 8 8 8 8 8 8 8 8 8 8 ‡ Current Limiting Molded Case Switch — UL 1087 Rated Current In [A] 125 Thermal Trip [A] Ir = In (Fixed) — Magnetic Trip [A] Im = 10 x In 1250 Breaking Capacity (50 Hz) Icu /Ics [kA] 220…240V 100 50 380…415V 70 35 525V 35 690V 18 6 3 13 Visit our website: www.ab.com/catalogs 2-62 Preferred availability cat. nos. are printed in bold Interrupting Rating (60 Hz) [kA] 240V 480V 600/347V 100 65 25 Cat. No. 140U-H6S3-D12 02_140U_125A_H_Frame.qxd 4/23/2008 12:01 PM Page 2-63 Bulletin 140U Molded Case Circuit Breakers Accessories — 125 A, H-Frame Accessories — 125 A, H-Frame ! Internal Control Modules — Field Installed Description Auxiliary Contact (AX) Electrically indicates "ON/OFF" status of breakers Diagram Mounting Location (1) 1a-1b (2) 1a-1b Cat. No. 140U-H-EA1 Left AND Right side 1 140U-H-EA2 2 Alarm Contact (AL) Electrically indicates when the breaker is in the "TRIPPED" state (1) 1M (make)1B (break) 140U-H-ER1 3 Right side ONLY Auxiliary/Alarm Contact (AX/AL) Combination Combination of auxiliary contact and alarm contact (1) 1a-1b (1) 1M (make)1B (break) 140U-H-EA1R1 4 Right side ONLY Shunt Trip (SNT) Provides remote tripping of the circuit breaker Undervoltage trip not available when shunt trip is used 12V DC 140U-H-SNZQ 24…60V, 50/60/DC 140U-H-SNJ 110…240V, 50/60/DC 140U-H-SND 380…440V AC, 220…250V DC 140U-H-SNN 380…600V, 50/60 Hz Undervoltage Release (UVT) Automatically trips breaker when voltage falls between preset value, 35…70% Shunt trip is not available when undervoltage release is used Left side ONLY 140U-H-SNB 24V, 50/60 Hz 140U-H-UJ 110…127V, 50/60 Hz 140U-H-UD 208…240V, 50/60 Hz 140U-H-UA 380…500V, 50/60 Hz 140U-H-UB 525…600V, 50/60 Hz Left side ONLY 5 6 7 140U-H-UC 8 Note: For Factory-Installed internal control modules, please see page 2-92 9 10 11 12 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-63 02_140U_125A_H_Frame.qxd 4/23/2008 12:01 PM Page 2-64 Bulletin 140U Molded Case Circuit Breakers Accessories — 125 A, H-Frame, Continued 125 A, H-Frame, Continued ! ! External Accessories Description 1 Cat. No. Terminal End Cover 6.4 mm (0.25 in.) diameter cable entry 140U-H-TC2 Terminal End Cover 10.4 mm (0.41 in.) diameter cable entry 140U-H-TC4 Terminal Shields IP20 Ingress Protection Rating 2 140U-H-TS Flex-Cable Operating Mechanism Includes handle, cable, operating, and bail mechanism Pre-assembled and adjusted Non-Metallic - UL IP66, Type 1/3/12/4/4X Flange Mount Operating Handle 3 Flex-Cable Operating Mechanism Includes handle, cable, operating, and bail mechanism Pre-assembled and adjusted Stainless Steel - Type 4/4X Flange Mount Operating Handle 4 Rotary, Variable-Depth Operating Mechanism UL Type 3/12/4/4X, IP 66 Rotary handle 12 in. (30.48 cm) operating rod 140U-H-FCX06 10 ft (3.0 m) Cable 140U-H-FCX10 3 ft (0.9 m) Cable 140U-H-FCS03 4 ft (1.2 m) Cable 140U-H-FCS04 6 ft (1.9 m) Cable 140U-H-FCS06 10 ft (3.0 m) Cable 140U-H-FCS10 Black Handle 140U-H-RVM12B 140U-H-RVM12R 140U-H-RVM21B Red/Yellow Handle 140U-H-RVM21R Black Handle 140U-H-NVM12B Red/Yellow Handle 140U-H-NVM12R Black Handle 140U-H-NVM21B Red/Yellow Handle 140U-H-NVM21R Motor Operator Remotely opens, closes, and resets the circuit breaker 110…240V AC For use with 3- or 4Pole MCCBs, 110…240V AC/DC 140U-H-EOPD Motor Operator Remotely opens, closes, and resets the circuit breaker 24V DC For use with 3- or 4Pole MCCBs, 24V DC 140U-H-EOPZ Mounting Hardware (4) M4 - 0.7 x 75 mm For use with 3- or 4Pole MCCBs 140U-H-MHM Rotary, Variable-Depth Operating Mechanism with Internal NFPA 79 Operating Handle Type 3/4/4X/12 IP66 Rotary Handle 21 in. (53.34 cm) operating rod 7 140U-H-FCX04 6 ft (1.9 m) Cable Black Handle Rotary, Variable-Depth Operating Mechanism with Internal NFPA 79 Operating Handle Type 3/4/4X/12 IP66 Rotary Handle 12 in. (30.48 cm) operating rod 6 140U-H-FCX03 Red/Yellow Handle Rotary, Variable-Depth Operating Mechanism UL Type 3/12/4/4X, IP 66 Rotary handle 21 in. (53.34 cm) operating rod 5 3 ft (0.9 m) Cable 4 ft (1.3 m) Cable 8 9 10 11 12 13 Visit our website: www.ab.com/catalogs 2-64 Preferred availability cat. nos. are printed in bold 02_140U_125A_H_Frame.qxd 4/23/2008 12:01 PM Page 2-65 Bulletin 140U Molded Case Circuit Breakers Accessories — 125 A, H-Frame, Continued 125 A, H-Frame, Continued ! External Accessories, Continued Description Cat. No. Black Handle 140U-H-RCB Red/Yellow Handle 140U-H-RCR End Cap Kit Provides three-phase connections for terminal or bolt-on connections Metric hardware provided Qty: 1 140U-H-ECM 2 Phase Barriers Provides additional phase clearance when special connections that extend past the circuit breaker housing are required Qty: 2 140U-H-PB 3 Padlock Kit Padlocking hasp Lock-OFF only Qty: 1 140U-H-PL Rotary, Direct Couple Operating Mechanism Rotary handle - IP42 UL Type 1 Breaker mounted 1 4 Plug-in Base Adapters Plug-in provides power terminations and adapter for applications where the ability to quickly remove or replace the circuit breakers is required Plug-in Base Auxiliary Contacts Provides auxiliary contact functions to detect breaker installation status 5 For use with 3-Pole MCCBs Qty: 1 140U-H-PAD3 6 For use with 3- or 4-Pole MCCBs Qty: 1 140U-H-PDK 7 DIN Rail Adapter Allows H-frame MCCB to mount to 35 mm DIN Rail For use with 3-Pole H-Frame MCCBs Qty: 1 140U-H-DRA 8 Multi-Tap Terminal Lug Kit — with IP20 terminal cover Cat. No. 140U-H-MTL3AN Multi-Tap Terminal Lug Kit — with IP20 terminal cover Qty: 3 with terminal shield 140U-H-MTL3A Qty: 3 140U-H-MTL3AN (6) #14…6 AWG or (6) 2.5…10 mm2 Qty: 3 with terminal shield 140U-H-MTL6A (6) #14…6 AWG or (6) 2.5…10 mm2 Qty: 3 140U-H-MTL6AN (3) #14…2 AWG or (3) 2.5…35 mm2 9 10 11 12 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-65 02_140U_125A_H_Frame.qxd 4/23/2008 12:01 PM Page 2-66 Bulletin 140U Molded Case Circuit Breakers Approximate Dimensions — 125 A, H-Frame Dimensions are in inches. Dimensions are not intended to be used for manufacturing purposes. ! ! 1-Pole Molded Case Circuit Breakers 0.907 1 TOP 2 3 FNT 2.497 0.984 4 FNT 5 6 8 5.50 3.812 7 RGT RGT 9 TOP 2.913 10 3.476 11 12 13 Visit our website: www.ab.com/catalogs 2-66 Preferred availability cat. nos. are printed in bold 02_140U_125A_H_Frame.qxd 4/23/2008 12:01 PM Page 2-67 Bulletin 140U Molded Case Circuit Breakers Approximate Dimensions — 125 A, H-Frame, Continued Dimensions are in inches. Dimensions are not intended to be used for manufacturing purposes. ! 2-Pole Molded Case Circuit Breakers 0.8524 1 0.4179 TOP 2 3.414 FNT 3 1.973 FNT 4 0.168 5 RGT RGT 3.812 6 7 TOP 1.007 8 FNT 2.9725 TOP 9 10 11 12 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-67 02_140U_125A_H_Frame.qxd 4/23/2008 12:01 PM Page 2-68 Bulletin 140U Molded Case Circuit Breakers Approximate Dimensions — 125 A, H-Frame, Continued Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes. ! !! 3-Pole Molded Case Circuit Breakers 4 Ð .17 (4.32) x .19 (4.83) Dia. Slot for #6 Mounting Screws Line End .50 .50 (12.70) (12.70) .45 (11.43) 6 Ð .35 (8.90) Dia. 11 .78 (19.81) .09 (2.29) .58 (14.73) .56 (14.22) .22 (5.59) 22 Attachment Leads Side Exit Point 5.50 (139.70) 33 Push to Trip Button 3.81 (96.78) 44 3.03 (76.96) .17 (4.32) 55 C L .15 (3.81) E D 1.38 (35.05) A .57 (14.48) 1.08 (27.43) .72 (18.29) .20 (5.08) Dia. Thru Conductors 2.18 (55.37) .22 (5.59) B .17 (4.32) 66 Handle R2.13 1.73 (43.94) .09 (2.29) .55 (13.97) 2.77 (70.36) 2.93 2.99 (74.42) (75.95) C 1.00 (25.40) 1.00 (25.40) 77 .03 (0.76) .77 (19.56) 1.42 (36.07) 1.21 (30.73) 3.00 (76.20) 1.50 (38.10) 88 .94 (23.88) .44 (11.18) .47 (11.94) Attachment Leads Rear Exit Point 99 10 10 Breaker Status Dimension A B C D E On 2.71 (68.83) 2.53 (64.26) 3.46 (87.88) 2.83 (71.88) 2.75 (69.85) Off 1.54 (39.12) 1.62 (41.15) 3.46 (87.88) 1.66 (42.16) 1.84 (46.74) Tripped 2.33 (59.18) 2.23 (56.64) 3.54 (89.92) 2.46 (67.48) 2.45 (62.23) Reset 1.39 (35.31) 1.49 (37.85) 3.42 (86.87) 1.52 (38.61) 1.70 (43.18) 1.44 (36.58) 11 11 .67 (17.02) 12 13 Visit our website: www.ab.com/catalogs 2-68 Preferred availability cat. nos. are printed in bold 03_140U_250A_J_Frame.qxd 4/23/2008 12:10 PM Page 2-69 Bulletin 140U Molded Case Circuit Breakers Product Selection — 250 A, J-Frame y UL 489 y CSA 22.2, No. 5 y IEC 60947-2 y CE y KEMA-KEUR (Pending) Note: Terminal box lugs must be ordered separately. See page 2-72 ! Breaker Frames 1 Breaking Capacity (50 Hz) Icu /Ics [kA] Rated Current In [A] 220…240V 65 250 380…415V Interrupting Rating (60 Hz) [kA] 525V 690V 65 25 25 18 12 12 6 240V 480V 600V Cat. No. 65 25 18 140U-J2X3 2 85 85 45 45 18 12 12 6 85 35 18 100 100 70 70 25 13 14 7 100 65 25 ‡ 140U-J6X3 200 200 100 100 35 18 16 12 200 100 35 ‡ 140U-J0X3 140U-J3X3 ‡ Current Limiting 3 Trip Units Thermal-Magnetic Electronic Adjustment Range [A] Rated Current In [A] Thermal Trip Ιr = Ιn (Fixed) Adjustment Range [A] Magnetic Trip Ιm = 5…10 x Ιr Cat. No. Rated Current In [A] Thermal Trip Ιr = 0.4…1.0 x Ιn Magnetic Trip Ιm = 2…14 x Ιr Protection Type Cat. No. 90 90 450…900 140U-JTD3-C90 50 20…50 40…700 LS 140U-JTL3-C50 100 100 500…1000 140U-JTD3-D10 50 20…50 40…700 LSI 140U-JTH3-C50 125 125 600…1250 140U-JTD3-D12 50 20…50 40…700 LSG 140U-JTG3-C50 150 150 750…1500 140U-JTD3-D15 50 20…50 40…700 LSIG 140U-JTI3-C50 175 175 875…1750 140U-JTD3-D17 100 40…100 80…1400 LS 140U-JTL3-D10 200 200 1000…2000 140U-JTD3-D20 100 40…100 80…1400 LSI 140U-JTH3-D10 225 225 1125…2250 140U-JTD3-D22 100 40…100 80…1400 LSG 140U-JTG3-D10 250 250 1250…2500 140U-JTD3-D25 100 40…100 80…1400 LSIG 140U-JTI3-D10 160 63…160 126…2240 LS 140U-JTL3-D16 160 63…160 126…2240 LSI 140U-JTH3-D16 160 63…160 126…2240 LSG 140U-JTG3-D16 160 63…160 126…2240 LSIG 140U-JTI3-D16 250 100…250 200…3500 LS 140U-JTL3-D25 250 100…250 200…3500 LSI 140U-JTH3-D25 250 100…250 200…3500 LSG 140U-JTG3-D25 250 100…250 200…3500 LSIG 140U-JTI3-D25 4 5 6 7 8 Assembled Circuit Breakers with Thermal-Magnetic Trip Units Breaking Capacity/ Interrupting Rating [kA]7 Breaking Capacity/ Interrupting Rating [kA]7 Breaking Capacity/ Interrupting Rating [kA]7 Rated Current In [A] 400V 480V Cat. No. 400V 480V Cat. No. 400V 480V Cat. No. 140U-J6D3-C90 90 25 25 140U-J2D3-C90 40 35 140U-J3D3-C90 70 65 100 25 25 140U-J2D3-D10 40 35 140U-J3D3-D10 70 65 140U-J6D3-D10 125 25 25 140U-J2D3-D12 40 35 140U-J3D3-D12 70 65 140U-J6D3-D12 150 25 25 140U-J2D3-D15 40 35 140U-J3D3-D15 70 65 140U-J6D3-D15 175 25 25 140U-J2D3-D17 40 35 140U-J3D3-D17 70 65 140U-J6D3-D17 200 25 25 140U-J2D3-D20 40 35 140U-J3D3-D20 70 65 140U-J6D3-D20 225 25 25 140U-J2D3-D22 40 35 140U-J3D3-D22 70 65 140U-J6D3-D22 250 25 25 140U-J2D3-D25 40 35 140U-J3D3-D25 70 65 140U-J6D3-D25 9 10 11 7 Full ratings are found in the breaker frames table on this page 12 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-69 03_140U_250A_J_Frame.qxd 4/23/2008 12:10 PM Page 2-70 Bulletin 140U Molded Case Circuit Breakers Product Selection — 250 A, J-Frame, Continued Assembled Circuit Breakers with Electronic Trip Units Breaking Capacity/ Interrupting Rating [kA]7 ! Breaking Capacity/ Interrupting Rating [kA]7 Breaking Capacity/ Interrupting Rating [kA]7 Rated Current In [A] Protection Type 400V 480V Cat. No. 400V 480V Cat. No. 400V 480V Cat. No. 50 LS 25 25 140U-J2L3-C50 40 35 140U-J3L3-C50 70 65 140U-J6L3-C50 1 2 3 4 50 LSI 25 25 140U-J2H3-C50 40 35 140U-J3H3-C50 70 65 140U-J6H3-C50 50 LSG 25 25 140U-J2G3-C50 40 35 140U-J3G3-C50 70 65 140U-J6G3-C50 50 LSIG 25 25 140U-J2I3-C50 40 35 140U-J3I3-C50 70 65 140U-J6I3-C50 100 LS 25 25 140U-J2L3-D10 40 35 140U-J3L3-D10 70 65 140U-J6L3-D10 100 LSI 25 25 140U-J2H3-D10 40 35 140U-J3H3-D10 70 65 140U-J6H3-D10 100 LSG 25 25 140U-J2G3-D10 40 35 140U-J3G3-D10 70 65 140U-J6G3-D10 100 LSIG 25 25 140U-J2I3-D10 40 35 140U-J3I3-D10 70 65 140U-J6I3-D10 160 LS 25 25 140U-J2L3-D16 40 35 140U-J3L3-D16 70 65 140U-J6L3-D16 160 LSI 25 25 140U-J2H3-D16 40 35 140U-J3H3-D16 70 65 140U-J6H3-D16 160 LSG 25 25 140U-J2G3-D16 40 35 140U-J3G3-D16 70 65 140U-J6G3-D16 160 LSIG 25 25 140U-J2I3-D16 40 35 140U-J3I3-D16 70 65 140U-J6I3-D16 250 LS 25 25 140U-J2L3-D25 40 35 140U-J3L3-D25 70 65 140U-J6L3-D25 250 LSI 25 25 140U-J2H3-D25 40 35 140U-J3H3-D25 70 65 140U-J6H3-D25 250 LSI 25 25 140U-J2G3-D25 40 35 140U-J3H3-D25 70 65 140U-J6G3-D25 250 LSIG 25 25 140U-J2I3-D25 40 35 140U-J3I3-D25 70 65 140U-J6I3-D25 7 Full ratings are found in the breaker frames table on page 2-69 5 6 Molded Case Switch — UL 489 Rated Current In [A] Thermal Trip Ιr = Ιn [A] Magnetic Trip [A] Ιm = 10 x Ιn 250 — 2500 Breaking Capacity (50 Hz) Ιcu /Ιcs [kA] 220…240V 100 100 380…415V 70 70 Interrupting Rating (60 Hz) [kA] 500V 42 690V 20 7 7 8 9 10 11 12 13 Visit our website: www.ab.com/catalogs 2-70 Preferred availability cat. nos. are printed in bold 3 240V 100 480V 65 600V 25 Cat. No. 140U-J6S3-D25 03_140U_250A_J_Frame.qxd 4/23/2008 12:10 PM Page 2-71 Bulletin 140U Molded Case Circuit Breakers Accessories — 250 A, J-Frame Internal Control Modules — Field Installed Description Auxiliary Contact (AX) Electrically indicates "ON/OFF" status of breakers Diagram Mounting Location (1) 1a-1b ! 140U-H-EA1 (2) 1a-1b Alarm Contact (AL) Electrically indicates when the breaker is in the "TRIPPED" state Cat. No. Left AND Right side (1) 1M (make)-1B (break) 140U-H-EA2 140U-J-ER1 1 2 Right side ONLY Auxiliary/Alarm Contact (AX/AL) Combination Combination of auxiliary contact and alarm contact 3 (1) 1a-1b (1) 1M (make)-1B (break) 140U-J-EA1R1 Right side ONLY Shunt Trip (SNT) Provides remote tripping of the circuit breaker Undervoltage trip not available when shunt trip is used 12V DC 140U-H-SNZQ 24…60V, 50/60/DC 140U-H-SNJ 110…240V, 50/60/DC 140U-H-SND 380…440V AC, 220…250V DC 140U-H-SNN 140U-H-SNB 380…600V, 50/60 Hz 12V DC Undervoltage Release (UVT) Automatically trips breaker when voltage falls between preset value, 35…70% Shunt trip is not available when undervoltage release is used Left side ONLY 24V, 50/60 Hz 140U-H-UJ 140U-H-UD 208…240V, 50/60 Hz 140U-H-UA 380…500V, 50/60 Hz 140U-H-UB Left side ONLY 5 140U-H-SNZQ 110…127V, 50/60 Hz 525…600V, 50/60 Hz 4 6 140U-H-UC 7 Note: For Factory-Installed internal control modules, please see page 2-92 Terminal Lugs Description Terminal Lugs Aluminum lugs, Al or Cu wire (1) 4…350 MCM or (1) 25…185 mm2 Stainless Steel Box Lugs, Cu wire Only (1) 4…350 MCM or (1) 25…185 mm2 Frame Size Cat. No. Qty: 1 J 140U-J-TLA1 Qty: 1 J 140U-J-TLS1 8 9 10 11 12 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-71 03_140U_250A_J_Frame.qxd 4/23/2008 12:11 PM Page 2-72 Bulletin 140U Molded Case Circuit Breakers Accessories — 250 A, J-Frame, Continued External Accessories Description ! Cat. No. Terminal Shields IP20 Ingress Protection Rating 140U-J-TS Flex-Cable Operating Mechanism Includes handle, cable, operating, and bail mechanism Pre-assembled and adjusted Non-Metallic - UL IP66, Type 1/3/12/4/4X Flange Mount Operating Handle 1 Flex-Cable Operating Mechanism Stainless Steel IP66/ UL Type 1/3/12/4/4X Flange-Mount Operating Handle 2 Rotary, Variable-Depth Operating Mechanism UL Type 3/12/4/4X, IP 66 Rotary handle 12 in. (30.48 cm) operating rod 3 4 140U-J-FCX03 140U-J-FCX04 6 ft (1.9 m) Cable 140U-J-FCX06 10 ft (3.0 m) Cable 140U-J-FCX10 3 ft (0.9 m) Cable 140U-J-FCS03 4 ft (1.2 m) Cable 140U-J-FCS04 6 ft (1.9 m) Cable 140U-J-FCS06 10 ft (3.0 m) Cable 140U-J-FCS10 Black Handle 140U-J-RVM12B Red/Yellow Handle 140U-J-RVM12R Rotary, Variable-Depth Operating Mechanism UL Type 3/12/4/4X, IP 66 Rotary handle 21 in. (53.34 cm) operating rod Black Handle 140U-J-RVM21B Red/Yellow Handle 140U-J-RVM21R Rotary, Variable-Depth Operating Mechanism with Internal NFPA 79 Operating Handle Type 3/4/4X/12 IP66 Rotary Handle 12 in. (30.48 cm) operating rod Black Handle 140U-J-NVM12B Red/Yellow Handle 140U-J-NVM12R Black Handle 140U-J-NVM21B Red/Yellow Handle 140U-J-NVM21R Black Handle 140U-J-RCB Red/Yellow Handle 140U-J-RCR Rotary, Variable-Depth Operating Mechanism with Internal NFPA 79 Operating Handle Type 3/4/4X/12 IP66 Rotary Handle 21 in. (53.34 cm) operating rod 5 Rotary, Direct Couple Operating Mechanism Breaker mounted 6 3 ft (0.9 m) Cable 4 ft (1.3 m) Cable End Cap Kit Provides 3-phase connections for terminal or bolt-on connections Metric hardware 7 8 140U-J-ECM Phase Barriers Provides additional phase clearance when special connections that extend past the circuit breaker housing are required Qty: 2 140U-J-PB Padlock Kit Padlocking hasp Lock-OFF only Qty: 1 140U-J-PL (3) #14…#2 AWG or (3) 2.5…25 mm2 Qty: 3 140U-J-MTL3A (6) #14…#6 AWG or (6) 2.5…10 mm2 Qty: 3 140U-J-MTL6A 150 A For use with J-Frame 3 pole MCCBs up to 150 A 140U-J-GFP1503 250 A For use with J-Frame 3-pole MCCBs up to 250 A 140U-J-GFP2503 For use with 3- or 4-Pole MCCBs, 110…240V AC/DC 140U-J-EOPD For use with 3- or 4-Pole MCCBs, 24V DC 140U-J-EOPZ For use with 3- or 4-Pole MCCBs 140U-J-MHM Multi-Tap Terminal Lug Kit — with IP20 terminal cover 9 Ground Fault Leakage Module Current pickup settings are selectable from 0.03…10 A with time delays up to. Time delays are also selectable from Instantaneous…1.0 s for 0.10 A settings and above. A current pickup setting of 0.03 A defaults to an Instantaneous time setting regardless of the time dial’s position. Two alarm contacts come as standard: a 50% pretrip and a 100% after trip contact, both based only on earth leakage current levels. 10 11 Motor Operator Remotely opens, closes, and resets the circuit breaker 110…240V AC 12 Mounting Hardware (4) M4 - 0.7 x 90 mm 13 Visit our website: www.ab.com/catalogs 2-72 Preferred availability cat. nos. are printed in bold 03_140U_250A_J_Frame.qxd 4/23/2008 12:11 PM Page 2-73 Bulletin 140U Molded Case Circuit Breakers Approximate Dimensions — 250 A, J-Frame Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes. 5.048 .170 ! 4.125 6.000 2.062 4.453 #8-32 TAP 4 HOLES 5.642 1.541 .281 THERMAL ADJUSTMENT 5.500 .256 3.922 .110 X .310 DEEP R TYP(4) Ø.145 7.000 5.500 4 HOLES 1 BREAKER HANDLE H .688 2.750 4.125 1.375 .664 2.062 .688 .203 1.375 2 FRONT CONNECTED DRILL PLAN GNETIC ADJUST PUSH TO TRIP 2.906 .897 Ø.650 TYP(6) 4.125 3.978 .500 2.062 Ø.625 6 HOLES û 1.188 TRIP .594 R2.656 4.0û .500 3 7.000 û BREAKER HANDLE 6.000 4.427 3.570 3.440 3.344 1.375 3.344 3.194 1.906 REF 2.750 .187 .188 4 REAR CONNECTED STUDS 1.771 .624 2.062 .125 Ø.198 .625 .625 1.000 .125 7.000 R.188 1.875 3.922 .173 .949 4.938 BREAKER K HANDLE 5 .859 1.062 .949 .500 6 .281 2.000 4.000 .260 7 8 9 10 11 12 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-73 04_140U_400A_K_Frame.qxd 4/23/2008 12:05 PM Page 2-74 Bulletin 140U Molded Case Circuit Breakers Product Selection — 400 A, K-Frame y UL 489 y CSA 22.2, No. 5 y IEC 157-1 y KEMA-KEUR ! 1 Note: Terminal lugs must be ordered separately. See page 2-75 Breaker Frames Breaking Capacity (50 Hz) Icu /Ics [kA] Rated Current In [A] 2 220…240V 400 380…415V 65 65 100 100 200 200 Interrupting Rating (60 Hz) [kA] 240V 480V 600V Cat. No. 40 30 30 10 5 65 35 25 140U-K3X3 35 35 50 38 13 6 100 65 35 140U-K6X3 100 100 65 49 18 9 200 100 50 140U-K0X3 40 500V 690V Trip Units and Rating Plugs 3 Thermal-Magnetic Electronic Adjustment Range [A] Rated Current Thermal Trip [A] Ir = In (Fixed) In [A] 4 5 6 Magnetic Trip Im = 5…10 x In Cat. No. Rated Current In [A] Adjustment Range [A] Thermal Trip Ir = 0.5…1.0 x In Magnetic Trip Im = 2…8 x Ir Protection Type Cat. No. LS 140U-KTL3-D40 100 100 500…1000 140U-KTD3-D10 125 125 625…1250 140U-KTD3-D12 150 150 750…1500 140U-KTD3-D15 175 175 895…1750 140U-KTD3-D17 200 200 1000…2000 140U-KTD3-D20 225 225 1125…2250 140U-KTD3-D22 250 250 1250…2500 140U-KTD3-D25 Thermal Trip Ιn Cat. No. Thermal Trip Ιn[A] Cat. No. 300 300 1500…3000 140U-KTD3-D30 200 140U-KRP3-D20 300 140U-KRP3-D30 350 350 1750…3500 140U-KTD3-D35 225 140U-KRP3-D22 350 140U-KRP3-D35 400 400 2000…4000 140U-KTD3-D40 250 140U-KRP3-D25 400 140U-KRP3-D40 400 200…4009 400…3200 LSI 140U-KTH3-D40 LSG 140U-KTG3-D40 LSIG 140U-KTI3-D40 Rating Plugs Assembled Circuit Breakers, Thermal-Magnetic Trip Units 7 8 9 10 Breaking Capacity/ Interrupting Rating [kA]7 Breaking Capacity/ Interrupting Rating [kA]7 Breaking Capacity/ Interrupting Rating [kA]7 Rated Current In [A] 400V 480V Cat. No. 400V 480V Cat. No. 400V 480V Cat. No. 100 40 35 140U-K3D3-D10 65 65 140U-K6D3-D10 100 100 140U-K0D3-D10 125 40 35 140U-K3D3-D12 65 65 140U-K6D3-D12 100 100 140U-K0D3-D12 150 40 35 140U-K3D3-D15 65 65 140U-K6D3-D15 100 100 140U-K0D3-D15 175 40 35 140U-K3D3-D17 65 65 140U-K6D3-D17 100 100 140U-K0D3-D17 200 40 35 140U-K3D3-D20 65 65 140U-K6D3-D20 100 100 140U-K0D3-D20 225 40 35 140U-K3D3-D22 65 65 140U-K6D3-D22 100 100 140U-K0D3-D22 250 40 35 140U-K3D3-D25 65 65 140U-K6D3-D25 100 100 140U-K0D3-D25 300 40 35 140U-K3D3-D30 65 65 140U-K6D3-D30 100 100 140U-K0D3-D30 350 40 35 140U-K3D3-D35 65 65 140U-K6D3-D35 100 100 140U-K0D3-D35 400 40 35 140U-K3D3-D40 65 65 140U-K6D3-D40 100 100 140U-K0D3-D40 Assembled circuit breakers can be created by adding a trip unit and rating plugs (electronic only) to a circuit breaker frame. Example: Cat. No. 140U-K3X3 + 140U-KTL3-D40 + 140U-KRP3-D35 7 Full ratings are found in the breaker frames table on this page 11 12 13 Visit our website: www.ab.com/catalogs 2-74 Preferred availability cat. nos. are printed in bold 04_140U_400A_K_Frame.qxd 4/23/2008 12:05 PM Page 2-75 Bulletin 140U Molded Case Circuit Breakers Product Selection — 400 A, K-Frame, Continued Assembled Circuit Breakers, Electronic Trip Units Breaking Capacity/ Interrupting Rating [kA]7 Breaking Capacity/ Interrupting Rating Rated [kA]7 Thermal Trip Protection Current In Ιr = 0.5…1.0 x Ιn [A] 400V 480V Type LS 400 40 35 Breaking Capacity/ Interrupting Rating [kA]7 ! Cat. No. 400V 480V Cat. No. 400V 480V Cat. No. 140U-K3L3-D40 65 65 140U-K6L3-D40 100 100 140U-K0L3-D40 LSI 40 35 140U-K3H3-D40 65 65 140U-K6H3-D40 100 100 140U-K0H3-D40 LSG 40 35 140U-K3G3-D40 65 65 140U-K6G3-D40 100 100 140U-K0G3-D40 100…4009 1 9 Select proper rating plug to cover thermal trip requirement. 7 Full ratings are found in the breaker frames table on page 2-74 2 Molded Case Switch — UL 489 Breaking Capacity (50 Hz) Ιcu /Ιcs [kA] Magnetic Trip Rated 10 x Ιn Current In [A] 400 4000 220…240V 100 100 380…415V 65 65 Interrupting Rating (60 Hz) [kA] 500V 50 690V 38 13 6 240V 100 480V 65 600V 35 Cat. No. 140U-K6S3-D40 3 Optional Terminal Lug Kits Description Pkg. Quantity Aluminum lug, Al or Cu wire (1) 3…350 MCM or (1) 30…185 mm2 Terminal Lugs Aluminum lug, Al or Cu wire (1) 250…500 MCM or (1) 120…240 mm2 Aluminum lug, Al or Cu wire (2) 3/0…250 MCM or (2) 95…120 mm2 Copper lug, Cu wire only (1) 3…350 MCM or (1) 30…185 mm2 Copper lug, Cu wire only (1) 250…500 MCM or (1) 120…240 mm2 Terminal Lugs Copper lug, Cu wire only (2) 3/0…250 MCM or (2) 95…120 mm2 Aluminum lug, Al or Cu wire (2) 2/0…250 MCM or (1) 2/0…500 MCM, (2) 70…120 mm2 or (1) 70…240 mm2 140U-K-TLA1A Multi-Tap Terminal Lug Kit — with IP20 terminal cover 4 1 140U-K-TLA1 3 (includes shield) 140U-K-TLA2 5 140U-K-TLC1A 1 140U-K-TLC1 3 (includes shield) 6 140U-K-TLC2 7 140U-K-TLA2A 3 (includes shield) Aluminum lug, Al or Cu wire (1) 500…750 MCM or (1) 300…400 mm2 Terminal Lugs Cat. No. 140U-K-TLA1B Copper lug, Cu wire only (1) 500…750 MCM or (1) 300…400 mm2 3 (includes shield) 140U-K-TLC1B (3) #12…2/0 AWG or (3) 4…67 mm2 3 140U-K-MTL3A (6) #14…#2 AWG or (6) 2.5…33 mm2 3 140U-K-MTL6A 8 9 10 11 12 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-75 04_140U_400A_K_Frame.qxd 4/23/2008 12:06 PM Page 2-76 Bulletin 140U Molded Case Circuit Breakers Accessories — 400 A, K-Frame Internal Control Modules — Field Installed ! ! Description Auxiliary Contact (AX) Electrically indicates "ON/OFF" status of breakers 1 Diagram (1) 1a-1b (2) 1a-1b Alarm Contact (AL) Electrically indicates when the breaker is in the "TRIPPED" state 2 Mounting Location Cat. No. 140U-K-EA1 Left AND Right side (1) 1M (make)-1B (break) 140U-K-EA2 140U-K-ER1 Right side ONLY 3 Auxiliary/Alarm Contact (AX/AL) Combination Combination of auxiliary contact and alarm contact 4 Right side ONLY 5 Shunt Trip (SNT) Provides remote tripping of the circuit breaker Undervoltage trip not available when shunt trip is used 6 Undervoltage Release (UVT) Automatically trips breaker when voltage falls between preset value, 35…70% Shunt trip is not available when undervoltage release is used 7 8 140U-KEA1R1 (1) 1a-1b (1) 1M (make)-1B (break) 12…24V, 50/60/DC 140U-K-SNJ 110…240V AC, 110…125V DC 140U-K-SND 380…440V AC, 220…250V DC 140U-K-SNN 480…600V, 50/60 Hz 140U-K-SNB 140U-K-UJ 110…127V, 50/60 Hz 140U-K-UD 208…240V, 50/60 Hz 140U-K-UA 380…500V, 50/60 Hz Note: For Factory-Installed internal control modules, please see page 2-92 9 10 11 12 13 Visit our website: www.ab.com/catalogs 2-76 Left side ONLY 24V, 50/60 Hz Preferred availability cat. nos. are printed in bold Left side ONLY 140U-K-UB 04_140U_400A_K_Frame.qxd 4/23/2008 12:07 PM Page 2-77 Bulletin 140U Molded Case Circuit Breakers Accessories — 400 A, K-Frame, Continued External Accessories Description Cat. No. Terminal Shields 140U-K-TS Flex-Cable Operating Mechanism Includes handle, cable, operating, and bail mechanism Pre-assembled and adjusted UL Type 1/3/12/4/4X Flange-Mount Operating Handle Non-Metallic Flex-Cable Operating Mechanism Includes handle, cable, operating, and bail mechanism Pre-assembled and adjusted UL Type 4/4X Flange-Mount Operating Handle Stainless Steel 4 ft (1.3 m) Cable 140U-K-FCX04 6 ft (1.9 m) Cable 140U-K-FCX06 1 10 ft (3.0 m) Cable 140U-K-FCX10 4 ft (1.2 m) Cable 140U-K-FCS04 6 ft (1.9 m) Cable 140U-K-FCS06 10 ft (3.0 m) Cable 140U-K-FCS10 Rotary, Variable-Depth Operating Mechanism UL Type 3/12/4/4X, IP 66 Rotary handle 12 in. (30.48 cm) operating rod Black Handle 140U-K-RVM12B Red/Yellow Handle 140U-K-RVM12R Rotary, Variable-Depth Operating Mechanism UL Type 3/12/4/4X, IP 66 Rotary handle 21 in. (53.34 cm) operating rod Black Handle 140U-K-RVM21B Red/Yellow Handle 140U-K-RVM21R Black Handle 140U-K-NVM12B Red/Yellow Handle 140U-K-NVM12R Black Handle 140U-K-NVM21B Rotary, Variable-Depth Operating Mechanism with Internal NFPA 79 Operating Handle UL Type 3/12/4/4X, IP 66 Rotary Handle 12 in. (30.48 cm) operating rod Rotary, Variable-Depth Operating Mechanism with Internal NFPA 79 Operating Handle UL Type 3/12/4/4X, IP 66 Rotary Handle 21 in. (53.34 cm) operating rod ! Red/Yellow Handle 140U-K-NVM21R Rotary, Direct Couple Operating Mechanism Type 1 Rotary Handle Breaker Mounted Black Handle 140U-K-RCG Rotary, Direct Couple Operating Mechanism Type 1 Rotary Handle Breaker Mounted Red/Yellow Handle 140U-K-RCR End Cap Kit Provides 3-phase connections for terminal or bolt-on connections Metric Hardware Qty: 1 140U-K-ECM Phase Barriers Provides additional phase clearance when special connections that extend past the circuit breaker housing are required Qty: 2 140U-K-PB 1 140U-K-MHM 2 3 4 5 6 7 8 Mounting Hardware (4) M6 - 1.0 x 45 mm 9 10 11 12 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-77 04_140U_400A_K_Frame.qxd 4/23/2008 12:07 PM Page 2-78 Bulletin 140U Molded Case Circuit Breakers Approximate Dimensions — 400 A, K-Frame Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes. Front View Side View 5.490(139.43) .500 (12.70) 1 .844 (21.44) 1.719 (43.66) 2.813 (71.45) 1.719 (43.66) 2 2.063 (52.39) .125 (3.18) 4.125 (104.78) 3 .093 R (2.36) R 3.75 (9.52) ON .375 (9.52) Contact Position Indicators Red/1 - On Green/O - Off White - T rip 2.438 (61.89) .750 (19.05) CL 10.125 (257.18) .063 (1.60) 1.063 (27.00) 3.875 R (98.42) R Handle .500 (12.70) 1.219 (30.96) 1.625 (41.28) 1.625 (41.28) D .250 (6.35) 1.250 (31.75) .062 (1.57) .500 (12.70) 8.438 (214.33) 8.875 (225.43) OFF .250 R (6.35) R 5 43û 4.000 (101.60) 3.563 (90.50) 1.000 (25.40) 3.813 (96.85) .125 (3.18) Wide x .750 (19.05) Slots for Attachment Leads .188 (4.77) R 7.406 (112.70) .694 (17.63) .188 (4.77) Dia. C'Bore x .031 (.79) DP .147 (12.7) Dia. Hole x .500 DP to Accept #8 (M4) Thread Cutting Screws (8 Places) .860 (21.84) 4.437 (65.10) .500 (12.70) Trough for Attachment Leads 2.563 (12.70) 4 Line End .625 (15.88) C B .209 (5.31) .188 (4.77) A 1.734 (44.04) 2.391 (60.73) 39û 4.782(121.46) .698 .547 (13.89) (17.73) .188 R (4.77) R .500 (12.70) 6 1.160 (29.49) Dimensions for Extended Terminals and Barrier Style Nos. 4212B60G02, 4212B61G02 and 1492D24H01 7 .063 (1.60) .937 (23.80) 8 .875 (22.25) .438 (11.13) .250 (6.35) R 1.063 (27.00) .750 (19.05) Wide Conductor with .391 (9.93) Dia Hole Line and Load End 3.812 (96.82) .188 (4.77) 9 .766 (19.46) 2.375 (60.33) .500 (12.70) Load End .281 (7.14) Dia. Mounting Holes 4 Holes for .250-20 (M6) x 1.50 (38) Mounting Screws .500 (12.70) Dia. C'Bore from T op 2.875 (73.03) Deep Load End 2.625 (66.68) Deep Line End .438 (11.13) Dia C'Bore .750 (10.05) Deep from Bottom F Breaker Status Dimensions A B C D E F Handle Force➀ On 5.39 (136.9) 5.20 (132.1) 5.69 (144.5) 5.61 (142.5) 4.72 (119.9) 4.77 (121.2) Tripped 4.77 (121.2) 4.69 (119.1) 5.08 (129.0) 5.11 (129.8) 4.89 (124.2) 4.89 (124.2) N/A Off 4.16 (105.7) 4.21 (106.9) 4.46 (113.3) 4.64 (117.9) 4.95 (125.7) 4.91 (124.7) 25 lbs. (11.34 kgs.) Reset 4.07 (103.4) 4.14 (105.2) 4.57 (116.1) 4.56 (115.8) 4.95 (125.7) 4.90 (124.5) 35 lbs. (15.87 kgs.) ➀ All handle forces measured approximately 0.125 (3.17) from top of handle. 10 11 12 13 Visit our website: www.ab.com/catalogs 2-78 .062 (1.57) 4.062 (103.17) E Preferred availability cat. nos. are printed in bold 30 lbs. (13.61 kgs.) 5.966(151.54) .625 (15.88) 6 Holes 4.313 (109.55) .110 (2.79) Dia. x .297 (7.54) Deep, 4 Holes Accept #6 (M3) Thread Cutting Screws 3.438 (87.32) 5.000(127.00) ! 5.766(146.46) ! 06_140U_600A_L_Frame.qxd 4/3/2008 11:50 AM Page 2-79 Bulletin 140U Molded Case Circuit Breakers Product Selection — 600 A, L-Frame y UL 489 y CSA 22.2, No. 5 y IEC 60947-2 y CE y KEMA-KEUR ! Note: Terminal box lugs must be ordered separately. See page 2-80 1 2 Breaker Frames Rated Current In [A] 220…240V 85 600 Interrupting Rating (60 Hz) [kA] Breaking Capacity (50 Hz) Icu /Ics [kA] 380…415V 85 45 525V 45 25 690V 13 20 10 240V 480V 600V Cat. No. 65 35 25 140U-L3X3 3 100 100 70 70 35 18 25 13 100 65 35 ‡ 140U-L6X3 200 200 100 100 50 25 30 15 200 100 50 ‡ 140U-L0X3 4 ‡ Current Limiting Trip Units and Rating Plugs Thermal-Magnetic Electronic Adjustment Range [A] Thermal Trip Rated Current In [A] Ιr = Ιn (Fixed) 5 Adjustment Range [A] Magnetic Trip Ιm = 5…10 x Ιn Cat. No. 250 250 1250…2500 140U-LTD3-D25 300 300 1500…3000 140U-LTD3-D30 350 350 1750…3500 140U-LTD3-D35 400 400 2000…4000 140U-LTD3-D40 500 500 2500…5000 140U-LTD3-D50 600 600 3000…6000 140U-LTD3-D60 Rated Current In [A] 250 400 600 Thermal Trip Ιr = 0.5…1.0 x Ιn Magnetic Trip Ιm = 2…10 x Ιn 100…250 200…2500 160…400 320…4000 240…600 480…6000 Protection Type Cat. No. LS 140U-LTL3-D25 LSI 140U-LTH3-D25 LSG 140U-LTG3-D25 LSIG 140U-LTI3-D25 LS 140U-LTL3-D40 LSI 140U-LTH3-D40 LSG 140U-LTG3-D40 LSIG 140U-LTI3-D40 LS 140U-LTL3-D60 LSI 140U-LTH3-D60 LSG 140U-LTG3-D60 LSIG 140U-LTI3-D60 6 7 8 Assembled Circuit Breakers, Thermal-Magnetic Trip Units 9 Breaking Capacity/Interrupting Rating [kA]7 Breaking Capacity/Interrupting Rating [kA]7 Rated Current Thermal Trip Ιr = Ιn In [A] 400V 480V Cat. No. 400V 480V Cat. No. 140U-L3D3-D25 70 65 140U-L6D3-D25 35 140U-L3D3-D30 70 65 140U-L6D3-D30 35 140U-L3D3-D35 70 65 140U-L6D3-D35 250 250 45 35 300 300 45 350 350 45 400 400 45 35 140U-L3D3-D40 70 65 140U-L6D3-D40 500 500 45 35 140U-L3D3-D50 70 65 140U-L6D3-D50 600 600 45 35 140U-L3D3-D60 70 65 140U-L6D3-D60 10 11 7 Full ratings are found in the breaker frames table on this page 12 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-79 06_140U_600A_L_Frame.qxd 4/3/2008 11:50 AM Page 2-80 Bulletin 140U Molded Case Circuit Breakers Product Selection — 600 A, L-Frame, Continued ! ! 1 2 Assembled Circuit Breakers, Electronic Trip Units 3 Thermal Trip Ιr = 0.5…1.0 x Ιn Rated Current In [A] LS 4 250 5 100…250 400 6 160…400 600 Breaking Capacity/ Interrupting Rating [kA]7 Breaking Capacity/ Interrupting Rating [kA]7 Protection 400V 480V Type 240…600 45 35 Cat. No. 400V 480V Cat. No. 140U-L3L3-D25 70 65 140U-L6L3-D25 LSI 45 35 140U-L3H3-D25 70 65 140U-L6H3-D25 LSG 45 35 140U-L3G3-D25 70 65 140U-L6G3-D25 LSIG 45 35 140U-L3I3-D25 70 65 140U-L6I3-D25 LS 45 35 140U-L3L3-D40 70 65 140U-L6L3-D40 LSI 45 35 140U-L3H3-D40 70 65 140U-L6H3-D40 LSG 45 35 140U-L3G3-D40 70 65 140U-L6G3-D40 LSIG 45 35 140U-L3I3-D40 70 65 140U-L6I3-D40 LS 45 35 140U-L3L3-D60 70 65 140U-L6L3-D60 LSI 45 35 140U-L3H3-D60 70 65 140U-L6H3-D60 LSG 45 35 140U-L3G3-D60 70 65 140U-L6G3-D60 LSIG 45 35 140U-L3I3-D60 70 65 140U-L6I3-D60 7 Full ratings are found in the breaker frames table on page 2-79 7 8 Molded Case Switch — UL 489 Rated Current In [A] Magnetic Trip Im = 10 x In [A] 600 6000 Breaking Capacity (50 Hz) Icu /Ics [kA] 220…240V 100 100 380…415V 70 70 Interrupting Rating (60 Hz) [kA] 500V 50 690V 38 25 13 240V 480V 600V Cat. No. 100 65 35 140U-L6S3-D60 Terminal Lugs Description 9 Terminal Lugs 10 11 Terminal Lugs Qty: 3 (includes shield) 140U-L-TL6A1 Copper lug, Cu wire only (1) 500…750 MCM or (1) 240…380 mm2 Qty: 3 (includes shield) 140U-L-TL6C1 Aluminum lug, Al or Cu wire (2) 2…500 MCM or (2) 35…240 mm2 Qty: 3 (includes shield) 140U-L-TL6A2 Copper lug, Cu wire only (2) 2…500 MCM or (2) 35…240 mm2 Qty: 3 (includes shield) 140U-L-TL6C2 Aluminum lug, Al or Cu wire (1) 2…500 MCM or (1) 35…240 mm2 Qty: 1 140U-L-TL4A1 Copper lug, Cu wire only (1) 2…500 MCM or (1) 35…240 mm2 Qty: 1 140U-L-TL4C1 12 13 Visit our website: www.ab.com/catalogs 2-80 Cat. No. Aluminum lug, Al or Cu wire (1) 500…750 MCM or (1) 240…380 mm2 Preferred availability cat. nos. are printed in bold 06_140U_600A_L_Frame.qxd 4/3/2008 11:51 AM Page 2-81 Bulletin 140U Molded Case Circuit Breakers Accessories — 600 A, L-Frame Internal Control Modules — Field Installed Description Diagram Auxiliary Contact (AX) Electrically indicates "ON/OFF" status of breakers Mounting Location (1) 1a-1b (2) 1a-1b Alarm Contact (AL) Electrically indicates when the breaker is in the "TRIPPED" state Cat. No. ! 140U-H-EA1 Left AND Right side (1) 1M (make)-1B (break) 140U-H-EA2 140U-J-ER1 1 2 Right side ONLY 3 Auxiliary/Alarm Contact (AX/AL) Combination Combination of auxiliary contact and alarm contact (1) 1a-1b (1) 1M (make)-1B (break) 140U-J-EA1R1 4 Right side ONLY Shunt Trip (SNT) Provides remote tripping of the circuit breaker Undervoltage trip not available when shunt trip is used Undervoltage Release (UVT) Automatically trips breaker when voltage falls between preset value, 35…70% Shunt trip is not available when undervoltage release is used 24…60V, 50/60/DC 140U-H-SNJ 110…240V, 50/60/DC 140U-H-SND 380…440V AC, 220…250V DC 140U-H-SNN 380…600V, 50/60 Hz Left side ONLY 140U-H-SNB 24V, 50/60 Hz 140U-H-UJ 110…127V, 50/60 Hz 140U-H-UD 208…240V, 50/60 Hz 140U-H-UA 380…500V, 50/60 Hz 140U-H-UB 525…600V, 50/60 Hz Left side ONLY 5 140U-H-UC 6 7 Note: For Factory-Installed internal control modules, please see page 2-92 8 9 10 11 12 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-81 06_140U_600A_L_Frame.qxd 4/3/2008 11:53 AM Page 2-82 Bulletin 140U Molded Case Circuit Breakers Accessories — 600 A, L-Frame, Continued External Accessories ! Description ! Cat. No. Terminal Shields IP20 Ingress Protection Rating 1 140U-L-TS Flex-Cable Operating Mechanism Includes handle, cable, operating, and bail mechanism Pre-assembled and adjusted UL Type 1/3/12/4/4X Flange-Mount Operating Handle Non-Metallic 2 Flex-Cable Operating Mechanism Includes handle, cable, operating, and bail mechanism Pre-assembled and adjusted UL Type 4/4X Flange-Mount Operating Handle Stainless Steel 3 Rotary, Variable-Depth Operating Mechanism UL Type 3/12/4/4X, IP 66 Rotary handle 12 in. (30.48 cm) operating rod 4 Rotary, Variable-Depth Operating Mechanism UL Type 3/12/4/4X, IP 66 Rotary handle 21 in. (53.34 cm) operating rod 5 6 8 10 4 ft (1.2 m) Cable 140U-L-FCS04 6 ft (1.9 m) Cable 140U-L-FCS06 10 ft (3.0 m) Cable 140U-L-FCS10 Black Handle 140U-L-RVM12B Red/Yellow Handle 140U-L-RVM12R Black Handle 140U-L-RVM21B Red/Yellow Handle 140U-L-RVM21R Black Handle 140U-L-NVM12B Red/Yellow Handle 140U-L-NVM12R Black Handle 140U-L-NVM21B Red/Yellow Handle 140U-L-NVM21R 140U-L-RMX End Cap Kit Provides 3-phase connections for terminal or bolt-on connections Metric hardware provided Qty: 1 140U-L-ECM Phase Barriers Provides additional phase clearance when special connections that extend past the circuit breaker housing are required Qty: 2 140U-K-PB 400 A For use with LFrame 3-pole MCCBs up to 400 A 140U-L-GFP4003 600 A For use with LFrame 3-pole MCCBs up to 600 A 140U-L-GFP6003 For use with 3- or 4Pole MCCBs, 110…240V AC/DC 140U-L-EOPD For use with 3- or 4Pole MCCBs, 24V DC 140U-L-EOPZ For use with 3- or 4Pole MCCBs 140U-L-MHM Mounting Hardware (4) M5 - 0.8 x 100 mm 12 13 Visit our website: www.ab.com/catalogs 2-82 140U-L-FCX10 Black Handle Motor Operator Remotely opens, closes, and resets the circuit breaker 110…240V AC 11 10 ft (3.0 m) Cable Rotary, Variable-Depth Operating Mechanism with Internal NFPA79 Operating Handle UL Type 3/12/4/4X, IP 66 Rotary Handle 21 in. (53.34 cm) operating rod Ground Fault Leakage Module Current pickup settings are selectable from 0.03…30 A with time delays up to1.0 s. Time delays are also selectable from Instantaneous…1.0 s for 0.10 A settings and above. A current pickup setting of 0.03 A defaults to an Instantaneous time setting regardless of the time dial’s position. Two alarm contacts come as standard: a 50% pretrip and a 100% after trip contact, both based only on earth leakage current levels. 9 140U-L-FCX04 140U-L-FCX06 Rotary, Variable-Depth Operating Mechanism with Internal NFPA79 Operating Handle UL Type 3/12/4/4X, IP 66 Rotary Handle 12 in. (30.48 cm) operating rod Rotary, Direct Couple Operating Mechanism Breaker Mounted 7 4 ft (1.3 m) Cable 6 ft (1.9 m) Cable Preferred availability cat. nos. are printed in bold 06_140U_600A_L_Frame.qxd 4/3/2008 11:53 AM Page 2-83 Bulletin 140U Molded Case Circuit Breakers Approximate Dimensions — 600 A, L-Frame Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes. 5.48 [ 139,2 ! ] 1.72 [ 43,6 ] 3.36 [ 85,3 ] Ø.22 [ 5,5 ] 1 2 3 10.13 [ 257,2 8.44 [ 214,4 ] 4 ] 5 6 1.72 [ 43,7 ] 7 1.72 [ 43,7 ] 5.43 [ 137,9 ] 8 9 10 .25 [ 6,4 ] .97 [ 24,6 ] 11 1.34 [ 34,1 ] 12 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-83 07_140U_800A_M_Frame.qxd 4/23/2008 11:37 AM Page 2-84 Bulletin 140U Molded Case Circuit Breakers Product Selection — 800 A, M-Frame ! ! y UL 489 y CSA 22.2, No. 5 y IEC 60947-2 y CE y KEMA-KEUR 1 Breaker Frames Breaking Capacity (50 Hz) Icu /Ics [kA] Rated Current In [A] 2 Note: Terminal box lugs must be ordered separately. See page 2-86 220…240V 800 380…415V Interrupting Rating (60 Hz) [kA] 525V 690V 240V 480V 600V Cat. No. 65 65 50 50 50 25 20 10 65 50 25 140U-M5X3 100 100 70 70 70 50 25 13 100 65 35 140U-M6X3 Trip Units and Rating Plugs 3 4 5 Thermal-Magnetic Electronic Adjustment Range [A] Adjustment Range [A] Rated Current In [A] Thermal Trip Ιr = Ιn Magnetic Trip Ιm = 5…10 x Ιn Cat. No. 300 300 1500…3000 140U-MTD3-D30 350 350 1750…3500 140U-MTD3-D35 400 400 2000…4000 140U-MTD3-D40 450 450 2250…4500 140U-MTD3-D45 500 500 2500…5000 140U-MTD3-D50 600 600 3000…6000 140U-MTD3-D60 700 700 3500…7000 140U-MTD3-D70 800 800 4000…8000 140U-MTD3-D80 Rated Current In [A] 800A Thermal Trip Ir = 0.5… 1.0 x In Magnetic Trip Im = 2…8 x In 400…8009 800…6400 Cat. No. 400…800 A LS Electronic Trip Unit 140U-MTL3-D80 400…800 A LSI Electronic Trip Unit 140U-MTH3-D80 400…800 A LSG Electronic 140U-MTG3-D80 Trip Unit 400…800 A LSIG Electronic 140U-MTI3-D80 Trip Unit Rating Plugs 6 Protection Type Thermal Trip In [A] Cat. No. Thermal Trip In [A] Cat. No. 400 140U-MRP3-D40 700 140U-MRP3-D70 500 140U-MRP3-D50 800 140U-MRP3-D80 600 140U-MRP3-D60 — — 7 Assembled Circuit Breakers, Thermal-Magnetic Trip Units 8 Rated Current In [A] Thermal Trip Ιr = Ιn 300 300 9 10 11 400V 480V Cat. No. 400V 480V Cat. No. 50 50 140U-M5D3-D30 70 65 140U-M6D3-D30 350 350 50 50 140U-M5D3-D35 70 65 140U-M6D3-D35 400 400 50 50 140U-M5D3-D40 70 65 140U-M6D3-D40 450 450 50 50 140U-M5D3-D45 70 65 140U-M6D3-D45 500 500 50 50 140U-M5D3-D50 70 65 140U-M6D3-D50 600 600 50 50 140U-M5D3-D60 70 65 140U-M6D3-D60 700 700 50 50 140U-M5D3-D70 70 65 140U-M6D3-D70 800 800 50 50 140U-M5D3-D80 70 65 140U-M6D3-D80 7 Full ratings are found in the breaker frames table on this page Assembled Circuit Breakers, Electronic Trip Units Breaking Capacity/ Interrupting Rating [kA]7 Breaking Capacity/ Interrupting Rating [kA]7 Thermal Trip Rated Current In [A] Ιr = 0.5…1.0 x Ιn 12 Breaking Capacity/Interrupting Rating [kA]7 Breaking Capacity/Interrupting Rating [kA]7 800 200…8009 Protection Type 400V 480V Cat. No. 400V 480V Cat. No. LS 50 50 140U-M5L3-D80 70 65 140U-M6L3-D80 LSI 50 50 140U-M5H3-D80 70 65 140U-M6H3-D80 LSG 50 50 140U-M5G3-D80 70 65 140U-M6G3-D80 9 Select proper rating plug to cover thermal trip requirement. 13 7 Full ratings are found in the breaker frames table on this page Visit our website: www.ab.com/catalogs 2-84 Preferred availability cat. nos. are printed in bold 07_140U_800A_M_Frame.qxd 4/23/2008 11:37 AM Page 2-85 Bulletin 140U Molded Case Circuit Breakers Product Selection, Continued/Accessories — 800 A, M-Frame Molded Case Switch — UL 489 Rated Current In [A] Magnetic Trip [A] Im = 10 x In 800 8000 Breaking Capacity (50 Hz) Icu /Ics [kA] 220…240V 380…415V 100 70 100 70 500V 70 50 Interrupting Rating (60 Hz) [kA] 690V 25 240V 480V 600V Cat. No. 100 65 35 140U-M6S3-D80 13 ! 1 Αχχεσσοριεσ Internal Control Modules — Field Installed Description Auxiliary Contact (AX) Electrically indicates "ON/OFF" status of breakers Mounting Location (1) 1a-1b (2) 1a-1b Alarm Contact (AL) Electrically indicates when the breaker is in the "TRIPPED" state Diagram Cat. No. 140U-M-EA1 Left AND Right Side (1) 1M (make)-1B (break) 140U-M-EA2 3 140U-M-ER1 4 Right Side Only Auxiliary/Alarm Contact (AX/AL) Combination Combination of auxiliary contact and alarm contact 2 140U-MEA1R1 (1) 1a-1b (1) 1M (make)-1B (break) 5 Right Side Only 6 Shunt Trip (SNT) Provides remote tripping of the circuit breaker Undervoltage trip not available when shunt trip is used Undervoltage Release (UVT) Automatically trips breaker when voltage falls between preset value, 35…70% Shunt trip is not available when undervoltage release is used 12…24V, 50/60/DC 140U-M-SNJ 110…240V AC, 110…125V DC 140U-M-SND 380…440V AC, 220…250V DC 480…600V, 50/60 Hz 140U-M-SNN Left Side Only 24V, 50/60 Hz 140U-M-UJ 110…127V, 50/60 Hz 140U-M-UD 208…240V, 50/60 Hz 140U-M-UA 380…500V, 50/60 Hz Left Side Only 7 140U-M-SNB 8 140U-M-UB 9 10 11 12 Note: For Factory-Installed internal control modules, please see page 2-92 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-85 07_140U_800A_M_Frame.qxd 4/23/2008 11:38 AM Page 2-86 Bulletin 140U Molded Case Circuit Breakers Accessories — 800 A, M-Frame, Continued External Accessories ! Description ! Flex-Cable Operating Mechanism Includes handle, cable, operating, and bail mechanism Pre-assembled and adjusted UL Type 1/3/12/4/4X Flange-Mount Operating Handle Non-Metallic 1 Flex-Cable Operating Mechanism Includes handle, cable, operating, and bail mechanism Pre-assembled and adjusted UL Type 4/4X Flange-Mount Operating Handle Stainless Steel 2 Rotary, Variable-Depth Operating Mechanism UL Type 3/12/4/4X, IP 66 Rotary Handle 12 in. (30.48 cm) operating rod Rotary, Variable-Depth Operating Mechanism UL Type 3/12/4/4X, IP 66 Rotary Handle 21 in. (53.34 cm) operating rod 3 140U-M-FCX06 10 ft (3.0 m) Cable 140U-M-FCX10 4 ft (1.3 m) Cable 140U-M-FCS04 6 ft (1.8 m) Cable 140U-M-FCS06 10 ft (3.0 m) Cable 140U-M-FCS10 Black Handle 140U-M-RVM12B Red/Yellow Handle 140U-M-RVM12R Black Handle 140U-M-RVM21B 140U-M-RVM21R 140U-M-NVM12B Red/Yellow Handle 140U-M-NVM12R Black Handle 140U-M-NVM21B Red/Yellow Handle 140U-M-NVM21R Copper lug, Cu wire Only (3) 3/0…300 MCM or (3) 95…135 mm2 Qty: 1 140U-M-TLC3 Aluminum lug, Al or Cu wire (3) 3/0…400 MCM or (3) 95…185 mm2 Qty: 1 140U-M-TLA3 Aluminum lug, Al or Cu wire (2) 1…500 MCM or (2) 50…240 mm2 Qty: 1 140U-M-TLA2 Aluminum lug, Al or Cu wire (2) 500…750 MCM or (2) 240…400 mm2 Qty: 1 140U-M-TLA2A Copper lug, Cu wire only (2) 2/0…500 MCM or (2) 70…240 mm2 Qty: 1 140U-M-TLC2 Phase Barriers Provides additional phase clearance when special connections that extend past the circuit breaker housing are required Qty: 2 140U-M-PB Padlock Kit Padlocking Hasp Lock-OFF only Qty: 1 140U-M-PL For use with 3- or 4-Pole MCCBs 140U-M-MHM Terminal Lugs 6 Terminal Lugs 7 6 ft (1.8 m) Cable Black Handle Rotary, Variable-Depth Operating Mechanism with Internal NFPA79 Operating Handle UL Type 3/12/4/4X, IP 66 Rotary Handle 21 in. (53.34 cm) operating rod 5 140U-M-FCX04 Red/Yellow Handle Rotary, Variable-Depth Operating Mechanism with Internal NFPA79 Operating Handle UL Type 3/12/4/4X, IP 66 Rotary Handle 12 in. (30.48 cm) operating rod 4 Cat. No. 4 ft (1.3 m) Cable 8 9 10 Mounting Hardware (4) M8 - 1 x 35 mm 11 12 13 Visit our website: www.ab.com/catalogs 2-86 Preferred availability cat. nos. are printed in bold 07_140U_800A_M_Frame.qxd 4/23/2008 11:38 AM Page 2-87 Bulletin 140U Molded Case Circuit Breakers Approximate Dimensions — 800 A, M-Frame Αππροξιματε Διμενσιονσ Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes. ! C L Handle Pivot Line End 2.018 (51.26) .375 (9.53) Dia. 4-Holes for .312 (7.92) 16 (406.40) x 1.75 (44.45) Large Mounting Screws. .500 (12.70) 1.411 (35.84) Max. .547 (13.89) 1 2 8.302 (210.87) 7.677 (195.00) 6.052 (153.72) On/I .415 (10.54) 3 Tripped 0.2û 11.500 (292.10) On/I On 14.7û C L Handle Pivot 14.750 (374.65) 4 Off 19.2û Off/O Off/O Reset 24.2û 16.000 (406.40) 5 Dim. B Dim. A 6 1.375 (34.93) .500 (12.70) - 13 Tap Thru. .500 (12.70) 2.750 (69.85) .531 (13.49) 2.531 (64.29) 7 4.062 (103.17) 2.750 (69.85) 5.500 (139.70) 4.375 (111.13) 4.250 (107.95) 8.250 (209.55) Load End 3.250 (82.55) 1.625 (41.28) 1.625 (41.28) .813 (20.65) 1.874 (47.60) Breaker Status Dimension A 8 Dimension B On 8.72 (221.49) 9.17 (232.92) Off 6.72 (170.69) 7.14 (181.36) Tripped 7.86 (199.64) 8.30 (210.82) Reset 6.44 (163.58) 6.84 (173.74) 9 10 11 12 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-87 08_140U_1200A_N_Frame.qxd 4/3/2008 3:21 PM Page 2-88 Bulletin 140U Molded Case Circuit Breakers Product Selection — 1200 A, N-Frame ! ! y UL 489 y CSA 22.2, No. 5 y IEC 60947-2 y CE y KEMA-KEUR 1 Assembled Circuit Breakers, Electronic Trip Units Note: Terminal box lugs must be ordered separately. See page 2-90 Adjustment Range Ir [A] 2 Rated Current In [A] 1200 1200 Thermal Trip Ir = 0.5…1.0 x In 600…12009 600…1200 Breaking Capacity (50 Hz) Magnetic Trip Im = 2…8 x In 4 600…12009 220…240V 380…415V LS 1200…10600 1200…10600 3 1200 Icu /Ics [kA] Protection Type 1200…10600 85 85 50 50 Interrupting Rating (60 Hz) [kA] 500V 40 20 690V 20 10 240V 480V 600V Cat. No. 65 50 25 140U-N5L3-E12 LS 100 100 70 50 50 25 25 13 100 65 35 140U-N6L3-E12 LSI 100 100 70 50 50 25 25 13 100 65 35 140U-N6H3-E12 140U-N6G3-E12 LSG 100 100 70 50 50 25 25 13 100 65 35 LSIG 100 100 70 50 50 25 25 13 100 65 35 140U-N6I3-E12 LS 200 100 100 50 65 33 35 18 200 100 50 140U-N0L3-E12 LSI 200 100 100 50 65 33 35 18 200 100 50 140U-N0H3-E12 LSG 200 100 100 50 65 33 35 18 200 100 50 140U-N0G3-E12 LSIG 200 100 100 50 65 33 35 18 200 100 50 140U-N0I3-E12 9 Select proper rating plug to cover thermal trip equipment. Rating Plugs Rated Current In [A] Cat. No. Rated Operational Current In [A] 600 140U-NRP3-D60 900 140U-NRP3-D90 700 140U-NRP3-D70 1000 140U-NRP3-E10 800 140U-NRP3-D80 1200 140U-NRP3-E12 5 6 Cat. No. Molded Case Switch — UL 489 7 Breaking Capacity (50 Hz) Ιcu /Ιcs [kA] Magnetic Trip Rated 10 x Ιn Current In [A] 1200 12000 220…240V 100 100 380…415V 70 50 500V 50 Interrupting Rating (60 Hz) [kA] 690V 25 25 13 240V 100 8 9 10 11 12 13 Visit our website: www.ab.com/catalogs 2-88 Preferred availability cat. nos. are printed in bold 480V 65 600V 35 Cat. No. 140U-N6S3-E12 08_140U_1200A_N_Frame.qxd 4/3/2008 3:21 PM Page 2-89 Bulletin 140U Molded Case Circuit Breakers Accessories — 1200 A, N-Frame Internal Control Modules — Field Installed Description Auxiliary Contact (AX) Electrically indicates "ON/OFF" status of breakers Mounting Location (1) 1a-1b (2) 1a-1b Alarm Contact (AL) Electrically indicates when the breaker is in the "TRIPPED" state Diagram Cat. No. ! 140U-N-EA1 Left AND Right side 140U-N-EA2 140U-N-ER1 (1) 1M (make)-1B (break) 1 2 Right side ONLY Auxiliary/Alarm Contact (AX/AL) Combination Combination of auxiliary contact and alarm contact Shunt Trip (SNT) Provides remote tripping of the circuit breaker Undervoltage trip not available when shunt trip is used Undervoltage Release (UVT) Automatically trips breaker when voltage falls between preset value, 35…70% Shunt trip is not available when undervoltage release is used 3 (1) 1a-1b (1) 1M (make)-1B (break) 140U-NEA1R1 4 Right side ONLY 12…24V, 50/60/DC 140U-N-SNJ 110…240V AC, 110…125V DC 140U-N-SND 380…440V AC, 220…250V DC 140U-N-SNN 480…600V, 50/60 Hz Left side ONLY 140U-N-SNB 24V, 50/60 Hz 140U-N-UJ 110…127V, 50/60 Hz 140U-N-UD 208…240V, 50/60 Hz 140U-N-UA 380…500V, 50/60 Hz Left side ONLY 5 140U-N-UB Note: For Factory-Installed internal control modules, please see page 2-92 6 7 8 9 10 11 12 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-89 08_140U_1200A_N_Frame.qxd 4/3/2008 3:22 PM Page 2-90 Bulletin 140U Molded Case Circuit Breakers Accessories — 1200 A, N-Frame, Continued External Accessories ! Description ! Cat. No. 4 ft. (1.2 m) Cable 140U-N-FCX04 6 ft. (1.9 m) Cable 140U-N-FCX06 10 ft. (3.0 m) Cable 140U-N-FCX10 Black Handle 140U-N-RM12B Phase Barriers Provides additional phase clearance when special connections that extend past the circuit breaker housing are required Qty: 2 140U-N-PB Padlock Kit Padlocking Hasp Lock-OFF only Qty: 1 140U-N-PL Motor Operator Remotely opens, closes, and resets the circuit breaker 110…240V AC Qty: 1 140U-N-EOPD 7 Motor Operator, 230..240V AC Qty: 1 140U-N-EOPA 8 Mounting Hardware (4) M8 - 1 x 35 mm For use with 3- or 4-Pole MCCBs 140U-M-MHM Flex-Cable Operating Mechanism NEMA Type 1/3/12/4/4X Flange-Mount Handle 1 2 Rotary, Variable-Depth Operating Mechanism Type 1/12 Rotary Handle 12 in. (30.48 cm) operating rod 3 4 5 6 Terminal Lugs 9 Description 10 11 Terminal Lugs 12 13 Pkg. Quantity Cat. No. Aluminum lug, Al or Cu wire (2) 1…500 MCM or (2) 50…240 mm2 Qty: 1 140U-N-TLA2 Aluminum lug, Al or Cu wire (3) 3/0…400 MCM or (3) 95…185 mm2 Qty: 1 140U-N-TLA3 Aluminum lug, Al or Cu wire (4) 4/0…500 MCM or (4) 120…300 mm2 Qty: 1 140U-N-TLA4 Aluminum lug, Al or Cu wire (3) 500…750 MCM or (3) 300…400 mm2 Qty: 1 140U-N-TLA3A Copper lug, Cu wire only (2) 2/0…500 MCM or (2) 70…240 mm2 Qty: 1 140U-N-TLC2 Copper lug, Cu wire only (3) 3/0…500 MCM or (3) 95…240 mm2 Qty: 1 140U-N-TLC3 Copper lug, Cu wire only (4) 3/0…400 MCM or (4) 95…185 mm2 Qty: 1 140U-N-TLC4 Visit our website: www.ab.com/catalogs 2-90 Preferred availability cat. nos. are printed in bold 08_140U_1200A_N_Frame.qxd 4/3/2008 3:22 PM Page 2-91 Bulletin 140U Molded Case Circuit Breakers Approximate Dimensions — 1200 A, N-Frame Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes. Removable T erminal Cover Must Be in Place While in Service ! .344 (8.738) Dia. Mounting Holes .703 (17.856) Dia. C'Bore 4.453 (113.106) Deep from Top .594 (15.088) Dia C'Bore .359 (9.119) Deep from Bottom 1.062 (26.987) .531 (13.481) 1.157(29.388) .532(13.513) .500-13 (12 X 1.75) Tap 12-Holes 1 .062 (1.575) Line End 3.236 (82.194) Trough for Attachment Lead .250 R (6.350) R 7.000 (177.774) 9.250 (234.950) 14.750(374.650) 8.625(219.075) 115.00 (292.075) 11.431 (290.348) .062 R (1.575) R .094 R (2.388) R .297 (7.544) 2 .125 X .750 (3.175 X 19.050) Slots for Attachment Leads 3.850 R 3 21û±2û ON/I ON .353 (6.331) 0û±2û TRIPPED 15û±2û .946 (24.022) .750(19.050) .375(9.525) OFF/O .188R (4.762)R 2.511 (63.786) 1.375 (34.925) 2.750 (69.850) 2.344 3.187 (59.541) (80.950) 6.375 (161.925) 4.124 (104.750) .062 (1.575) .532 (13.513) 1.095(27.813) 3.344 (84.938) 5.188(131.769) 2.750 Ref. (69.850) Ref. 2.000 (50.800) 1.000 (25.400) Breaker Status 6.000(152.400) A B On 7.90 (200.66) 8.30 (210.82) Tripped 6.50 (165.10) 6.90 (175.26) Off 5.70 (144.78) 6.10 (154.94) Reset 5.60 (142.24) 6.00 (152.40) 7.132(181.146) Handle Forces (At Handle C)L 3.906 (99.187) On 130 lbs. (58.97 kgs.) Off 105 lbs. (47.63 kgs.) Reset 160 lbs. (72.57 kgs.) 1.500 Ref (38.100) Ref 7 8 3.819 (96.723) 4.875 (123.799) .062 (1.575) 6 5.500(139.687) Dimensions .781 (19.844) .062 (1.588) R Load End 5.248(133.293) 1.688 (42.863) .062 (1.588) R 5 Removable Terminal Cover Must Be in Place While in Service 3.375 (85.725) 1.562 (39.687) 4 1.034 (33.281) Handle Pivot Contact Position Indicator Red-I/ON Green-O/OFF White-TRIPPED 8.250 (209.550) 2.000 (50.800) 2.982 (75.743) B A .147 (3.734) Dia. Hole .500 (12.70) Deep to Accept a #8Thread Cutting Screw 6-Places 3.808 (96.723) 2.798 (71.057) .375 (9.525) RESET 1.500 (38.100) .312 R (7.925)R 13û±2ûOFF CL Push To Trip 16.000 (406.401) CL Handle For 2-Pole Breaker Omit Current Carrying Parts from Center Pole 9 2.493 (63.792) 6.375 Ref (161.925) Ref 10 11 12 13 Visit our website: www.ab.com/catalogs Preferred availability cat. nos. are printed in bold 2-91 09_140U_mods.qxd 4/23/2008 11:54 AM Page 2-92 Bulletin 140U Molded Case Circuit Breakers Factory-Installed Modifications Internal Control Modules — Factory Installed For use with G-Frame Molded Case Circuit Breakers ! 2-Pole Breaker Mounting Location Left side only Right side only 1 (1) Auxiliary contact (AX) 2 3 4 5 6 3-Pole Breaker Mounting Location Left side only Right side only (1) Auxiliary contact (AX) or (1) Alarm contact (AL) or (1) Alarm contact (AL) + Auxiliary contact (AX) Auxiliary and Alarm Contacts 2-Pole 3-Pole (1) AX -A -A (1) Shunt Trip (SNT) or (1) Undervoltage Release (UVT) Suffix Internal Control Modules — Factory Installed For use with H-, J-, K-, L-, M-, and N-Frame Molded Case Circuit Breakers Mounting Location 7 8 9 10 Left side only Right side only (1) Shunt Trip (SNT) or (1) Undervoltage Release (UVT) (1) Auxiliary contact (AX) or (2) Auxiliary contacts (AX) or (1) Alarm contact (AL) or (1) Alarm contact (AL) + Auxiliary contact (AX) Auxiliary and Alarm Contacts -A (2) AX -B (1) AX + (1) AL Suffix Shunt Trip Combinations (1) UVT only - G⊗ (1) SNT only - P⊗ (1) AX + (1) UVT - H⊗ (1) AX + (1) SNT - Q⊗ - R⊗ Suffix (1) AX (1) AL Undervoltage Release Combinations -D -F (2) AX + (1) UVT - J⊗ (2) AX + (1) SNT (1) AX + (1) AL + (1) UVT - L⊗ (1) AX + (1) AL + (1) SNT - T⊗ (1) AL + (1) UVT - N⊗ (1) AL + (1) SNT - V⊗ ⊗Standard Voltage Suffix Codes9 Voltage [V] 11 24 ⊗Standard Voltage Suffix Codes9 110…127 208…240 380…480 Voltage [V] 12…24 110…240 380…600 J D B AC, 50/60 Hz J D A B AC, 50/60 Hz Voltage [V] — — — — Voltage [V] 12…24 110…125 — DC — — — — DC J D — 12 9 For additional voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor. 13 Visit our website: www.ab.com/catalogs 2-92 Suffix Preferred availability cat. nos. are printed in bold