SINAMICS G120C s *A5E36420270A* Edition 07/2015 SINAMICS G120C UL supplementary sheet The following information is additional information regarding the specific details of the requirements for Branch Circuit Protection for the SINAMICS G120C converter. Branch circuit protection according to IEC Frame size FSA FSB FSC Rated power 0.55 kW 0.75 kW 1.1 kW 1.5 kW 2.2 kW 3 kW 4 kW 5.5 kW 7.5 kW 11 kW 15 kW 18.5 kW Fuse Motor starter protector Max. rated current of the protection device 3NA3805 3RV2011-4AA.. 16 A 0.03 m3 3NA3812 3RV2021-4EA.. 32 A 0.06 m3 3NA3822 3RV1041-4JA.. 63 A 0.2 m3 Article number Power Module 6SL3210-1KE11-8... 6SL3210-1KE12-3... 6SL3210-1KE13-2... 6SL3210-1KE14-3... 6SL3210-1KE15-8... 6SL3210-1KE17-5... 6SL3210-1KE18-8... 6SL3210-1KE21-3... 6SL3210-1KE21-7... 6SL3210-1KE22-6... 6SL3210-1KE23-2... 6SL3210-1KE23-8... Minimum enclosure volume Siemens 3NA38 series fuses and 3RV series motor starter protectors of a lower current rating than shown may also be used. The inverter must be mounted in a suitable enclosure (e.g. metal equipment cabinet) and if a motor starter protector is used, the enclosure interior volume should not be less than that shown in the table above. Branch circuit protection according to UL standards Use in North America requires protection devices that meet UL standards as detailed in the following tables. The inverter must be mounted in a UL approved enclosure not less than the minimum enclosure volume unless the branch circuit protection is a class AJT fuse by Mersen (Ferraz Shawmut). Overview of the approved protection devices according to UL standards: Protection device Fuses of any manufacturer with faster tripping characteristic than class RK5 and rated 600V AC, e.g. class J, T, CC, G, or CF SIEMENS circuit breaker SIEMENS Type E combination motor controllers UL category JDDZ DIVQ NKJH The inverter is suitable for use on a circuit capable of delivering the short circuit current shown in the tables below when protected by the branch circuit protection indicated. Branch circuit protection with non-semiconductor fuses Class J, T, CC, G, CF (JDDZ) Frame size FSA FSB FSC Rated power 0.55 kW 0.75 kW 1.1 kW 1.5 kW 2.2 kW 3 kW 4 kW 5.5 kW 7.5 kW 11 kW 15 kW 18.5 kW Power Module 6SL3210-1KE11-8... 6SL3210-1KE12-3... 6SL3210-1KE13-2... 6SL3210-1KE14-3... 6SL3210-1KE15-8... 6SL3210-1KE17-5... 6SL3210-1KE18-8... 6SL3210-1KE21-3... 6SL3210-1KE21-7... 6SL3210-1KE22-6... 6SL3210-1KE23-2... 6SL3210-1KE23-8... SINAMICS G120C Supplementary Sheet, A5E36420270A, Edition 07/2015 Max. rated current of the fuse Short-circuit current rating (SCCR) Minimum enclosure volume 10 A 1830 in3 15 A 100 kA, 480 V AC 35 A 3660 in3 60 A 12200 in3 1 Branch circuit protection with circuit breakers (DIVQ) Frame size FSA Rated power Power Module Max. rated current of the circuit breaker 0.55 kW 6SL3210-1KE11-8... 15 A 0.75 kW 6SL3210-1KE12-3... 15 A 1.1 kW 6SL3210-1KE13-2... 15 A 1.5 kW 6SL3210-1KE14-3... 15 A 2.2 kW 6SL3210-1KE15-8... 15 A 3 kW 6SL3210-1KE17-5... 15 A 4 kW 6SL3210-1KE18-8... 15 A 5.5 kW 6SL3210-1KE21-3... 35 A FSB FSC 7.5 kW 6SL3210-1KE21-7... 35 A 11 kW 6SL3210-1KE22-6... 60 A 15 kW 6SL3210-1KE23-2... 60 A 18.5 kW 6SL3210-1KE23-8... 60 A Circuit breaker types 3RV1742, LGG, CED6 3RV2711 3RV1742, LGG, CED6 3RV2711 3RV1742, LGG, CED6 3RV2711 3RV1742, LGG, CED6 3RV2711 3RV1742, LGG, CED6 3RV2711 3RV1742, LGG, CED6 3RV2711 3RV1742, LGG, CED6 3RV2711 NCGA 3RV2721 LGG, CED6, HCGA 3RV1742 3RV2711 NCGA 3RV2721 LGG, CED6, HCGA 3RV1742 3RV2711 NCGA LGG, CED6, HCGA 3RV1742 NCGA LGG, CED6, HCGA 3RV1742 NCGA LGG, CED6, HCGA 3RV1742 Short-circuit current rating (SCCR) 65 kA, 480 V AC 65 kA, 480Y / 277V AC 65 kA, 480 V AC 65 kA, 480Y / 277V AC 65 kA, 480 V AC 65 kA, 480Y / 277V AC 65 kA, 480 V AC 65 kA, 480Y / 277V AC 65 kA, 480 V AC 65 kA, 480Y / 277V AC 65 kA, 480 V AC 65 kA, 480Y / 277V AC 65 kA, 480 V AC 65 kA, 480Y / 277V AC 35 kA, 480 V AC 50 kA, 480Y / 277V AC 65 kA, 480 V AC 65 kA, 480Y / 277V AC* 65 kA, 480Y / 277V AC 35 kA, 480 V AC 50 kA, 480Y / 277V AC 65 kA, 480 V AC 65 kA, 480Y / 277V AC* 65 kA, 480Y / 277V AC 35 kA, 480 V AC 65 kA, 480 V AC 65 kA, 480Y / 277V AC* 35 kA, 480 V AC 65 kA, 480 V AC 65 kA, 480Y / 277V AC* 35 kA, 480 V AC 65 kA, 480 V AC 65 kA, 480Y / 277V AC* Min. enclosure volume 1830 in 3 3660 in3 8780 in3 *65kA, 480V AC for 3RV1742 type with current rating <35 A Branch circuit protection with Type E combination motor controllers (NKJH) Frame size FSA 0.55 kW 6SL3210-1KE11-8... 3RV20_1-1JA.. 0.75 kW 6SL3210-1KE12-3... 3RV20_1-1JA.. 10 A 5 HP 1.1 kW 6SL3210-1KE13-2... 3RV20_1-1JA.. 10 A 5 HP 1.5 kW 6SL3210-1KE14-3... 3RV20_1-1JA.. 10 A 5 HP 3RV20_1-4AA.. 16 A 10 HP 3RV_031-4AA.. 16 A 10 HP 3RV20_1-4AA.. 16 A 10 HP 3RV_031-4AA.. 16 A 10 HP 3RV20_1-4AA.. 16 A 10 HP Power Module 2.2 kW 6SL3210-1KE15-8... 3 kW 6SL3210-1KE17-5... 4 kW 5.5 kW 6SL3210-1KE18-8... 6SL3210-1KE21-3... FSB 7.5 kW 11 kW FSC Rated power of the CMC at 460 VAC 5 HP Max. rated current of the CMC 10 A Rated power 6SL3210-1KE21-7... 6SL3210-1KE22-6... 15 kW 6SL3210-1KE23-2... 18.5 kW 6SL3210-1KE23-8... CMC model no. Short-circuit current rating (SCCR) 65 kA, 480Y / 277V AC 3RV_031-4AA.. 16 A 10 HP 3RV2021-4DA.. 25 A 15 HP 65 kA, 480Y / 277V AC 3RV2021-4EA.. 32 A 20 HP 50 kA, 480Y / 277V AC 3RV_031-4EA.. 32 A 20 HP 65 kA, 480Y / 277V AC 3RV2021-4DA.. 25 A 15 HP 65 kA, 480Y / 277V AC 3RV2021-4EA.. 32 A 20 HP 50 kA, 480Y / 277V AC 3RV_031-4EA.. 32 A 20 HP 65 kA, 480Y / 277V AC 3RV_031-4HA.. 50 A 40 HP 3RV1041-4JA.. 63A 50 HP 3RV_031-4HA.. 50 A 40 HP 3RV1041-4JA.. 63A 50 HP 3RV_031-4HA.. 50 A 40 HP 3RV1041-4JA.. 63A 50 HP 65 kA, 480Y / 277V AC Minimum enclosure volume 1830 in3 3660 in3 12200 in3 Where “_” in the CMC model number can be replaced by “1” or “2” Listed (NKJH) Siemens CMCs of the same type with a current rating lower than that specified in the table, corresponding to G120C drive model number and with a voltage rating of at least 480V AC may also be used. 2 SINAMICS G120C Supplementary Sheet, A5E36420270A, Edition 07/2015