G120C Branch Ciruit Protection

advertisement
SINAMICS G120C
s
*A5E36420270A*
Edition 07/2015
SINAMICS G120C UL supplementary sheet
The following information is additional information regarding the specific details of the requirements for Branch Circuit Protection for the
SINAMICS G120C converter.
Branch circuit protection according to IEC
Frame
size
FSA
FSB
FSC
Rated
power
0.55 kW
0.75 kW
1.1 kW
1.5 kW
2.2 kW
3 kW
4 kW
5.5 kW
7.5 kW
11 kW
15 kW
18.5 kW
Fuse
Motor starter protector
Max. rated
current of the
protection device
3NA3805
3RV2011-4AA..
16 A
0.03 m3
3NA3812
3RV2021-4EA..
32 A
0.06 m3
3NA3822
3RV1041-4JA..
63 A
0.2 m3
Article number
Power Module
6SL3210-1KE11-8...
6SL3210-1KE12-3...
6SL3210-1KE13-2...
6SL3210-1KE14-3...
6SL3210-1KE15-8...
6SL3210-1KE17-5...
6SL3210-1KE18-8...
6SL3210-1KE21-3...
6SL3210-1KE21-7...
6SL3210-1KE22-6...
6SL3210-1KE23-2...
6SL3210-1KE23-8...
Minimum
enclosure volume
Siemens 3NA38 series fuses and 3RV series motor starter protectors of a lower current rating than shown may also be used. The
inverter must be mounted in a suitable enclosure (e.g. metal equipment cabinet) and if a motor starter protector is used, the enclosure
interior volume should not be less than that shown in the table above.
Branch circuit protection according to UL standards
Use in North America requires protection devices that meet UL standards as detailed in the following tables. The inverter must be
mounted in a UL approved enclosure not less than the minimum enclosure volume unless the branch circuit protection is a class AJT
fuse by Mersen (Ferraz Shawmut).
Overview of the approved protection devices according to UL standards:
Protection device
Fuses of any manufacturer with faster tripping characteristic than class RK5 and rated 600V AC, e.g.
class J, T, CC, G, or CF
SIEMENS circuit breaker
SIEMENS Type E combination motor controllers
UL category
JDDZ
DIVQ
NKJH
The inverter is suitable for use on a circuit capable of delivering the short circuit current shown in the tables below when protected by
the branch circuit protection indicated.
Branch circuit protection with non-semiconductor fuses Class J, T, CC, G, CF (JDDZ)
Frame
size
FSA
FSB
FSC
Rated power
0.55 kW
0.75 kW
1.1 kW
1.5 kW
2.2 kW
3 kW
4 kW
5.5 kW
7.5 kW
11 kW
15 kW
18.5 kW
Power Module
6SL3210-1KE11-8...
6SL3210-1KE12-3...
6SL3210-1KE13-2...
6SL3210-1KE14-3...
6SL3210-1KE15-8...
6SL3210-1KE17-5...
6SL3210-1KE18-8...
6SL3210-1KE21-3...
6SL3210-1KE21-7...
6SL3210-1KE22-6...
6SL3210-1KE23-2...
6SL3210-1KE23-8...
SINAMICS G120C
Supplementary Sheet, A5E36420270A, Edition 07/2015
Max. rated current
of the fuse
Short-circuit
current rating
(SCCR)
Minimum enclosure
volume
10 A
1830 in3
15 A
100 kA, 480 V AC
35 A
3660 in3
60 A
12200 in3
1
Branch circuit protection with circuit breakers (DIVQ)
Frame
size
FSA
Rated power
Power Module
Max. rated
current of the
circuit
breaker
0.55 kW
6SL3210-1KE11-8...
15 A
0.75 kW
6SL3210-1KE12-3...
15 A
1.1 kW
6SL3210-1KE13-2...
15 A
1.5 kW
6SL3210-1KE14-3...
15 A
2.2 kW
6SL3210-1KE15-8...
15 A
3 kW
6SL3210-1KE17-5...
15 A
4 kW
6SL3210-1KE18-8...
15 A
5.5 kW
6SL3210-1KE21-3...
35 A
FSB
FSC
7.5 kW
6SL3210-1KE21-7...
35 A
11 kW
6SL3210-1KE22-6...
60 A
15 kW
6SL3210-1KE23-2...
60 A
18.5 kW
6SL3210-1KE23-8...
60 A
Circuit breaker types
3RV1742, LGG, CED6
3RV2711
3RV1742, LGG, CED6
3RV2711
3RV1742, LGG, CED6
3RV2711
3RV1742, LGG, CED6
3RV2711
3RV1742, LGG, CED6
3RV2711
3RV1742, LGG, CED6
3RV2711
3RV1742, LGG, CED6
3RV2711
NCGA
3RV2721
LGG, CED6, HCGA
3RV1742
3RV2711
NCGA
3RV2721
LGG, CED6, HCGA
3RV1742
3RV2711
NCGA
LGG, CED6, HCGA
3RV1742
NCGA
LGG, CED6, HCGA
3RV1742
NCGA
LGG, CED6, HCGA
3RV1742
Short-circuit current
rating (SCCR)
65 kA, 480 V AC
65 kA, 480Y / 277V AC
65 kA, 480 V AC
65 kA, 480Y / 277V AC
65 kA, 480 V AC
65 kA, 480Y / 277V AC
65 kA, 480 V AC
65 kA, 480Y / 277V AC
65 kA, 480 V AC
65 kA, 480Y / 277V AC
65 kA, 480 V AC
65 kA, 480Y / 277V AC
65 kA, 480 V AC
65 kA, 480Y / 277V AC
35 kA, 480 V AC
50 kA, 480Y / 277V AC
65 kA, 480 V AC
65 kA, 480Y / 277V AC*
65 kA, 480Y / 277V AC
35 kA, 480 V AC
50 kA, 480Y / 277V AC
65 kA, 480 V AC
65 kA, 480Y / 277V AC*
65 kA, 480Y / 277V AC
35 kA, 480 V AC
65 kA, 480 V AC
65 kA, 480Y / 277V AC*
35 kA, 480 V AC
65 kA, 480 V AC
65 kA, 480Y / 277V AC*
35 kA, 480 V AC
65 kA, 480 V AC
65 kA, 480Y / 277V AC*
Min.
enclosure
volume
1830 in
3
3660 in3
8780 in3
*65kA, 480V AC for 3RV1742 type with current rating <35 A
Branch circuit protection with Type E combination motor controllers (NKJH)
Frame
size
FSA
0.55 kW
6SL3210-1KE11-8...
3RV20_1-1JA..
0.75 kW
6SL3210-1KE12-3...
3RV20_1-1JA..
10 A
5 HP
1.1 kW
6SL3210-1KE13-2...
3RV20_1-1JA..
10 A
5 HP
1.5 kW
6SL3210-1KE14-3...
3RV20_1-1JA..
10 A
5 HP
3RV20_1-4AA..
16 A
10 HP
3RV_031-4AA..
16 A
10 HP
3RV20_1-4AA..
16 A
10 HP
3RV_031-4AA..
16 A
10 HP
3RV20_1-4AA..
16 A
10 HP
Power Module
2.2 kW
6SL3210-1KE15-8...
3 kW
6SL3210-1KE17-5...
4 kW
5.5 kW
6SL3210-1KE18-8...
6SL3210-1KE21-3...
FSB
7.5 kW
11 kW
FSC
Rated power of
the CMC at 460
VAC
5 HP
Max. rated
current of
the CMC
10 A
Rated
power
6SL3210-1KE21-7...
6SL3210-1KE22-6...
15 kW
6SL3210-1KE23-2...
18.5 kW
6SL3210-1KE23-8...
CMC model no.
Short-circuit current rating
(SCCR)
65 kA, 480Y / 277V AC
3RV_031-4AA..
16 A
10 HP
3RV2021-4DA..
25 A
15 HP
65 kA, 480Y / 277V AC
3RV2021-4EA..
32 A
20 HP
50 kA, 480Y / 277V AC
3RV_031-4EA..
32 A
20 HP
65 kA, 480Y / 277V AC
3RV2021-4DA..
25 A
15 HP
65 kA, 480Y / 277V AC
3RV2021-4EA..
32 A
20 HP
50 kA, 480Y / 277V AC
3RV_031-4EA..
32 A
20 HP
65 kA, 480Y / 277V AC
3RV_031-4HA..
50 A
40 HP
3RV1041-4JA..
63A
50 HP
3RV_031-4HA..
50 A
40 HP
3RV1041-4JA..
63A
50 HP
3RV_031-4HA..
50 A
40 HP
3RV1041-4JA..
63A
50 HP
65 kA, 480Y / 277V AC
Minimum
enclosure
volume
1830 in3
3660 in3
12200 in3
Where “_” in the CMC model number can be replaced by “1” or “2”
Listed (NKJH) Siemens CMCs of the same type with a current rating lower than that specified in the table, corresponding to G120C
drive model number and with a voltage rating of at least 480V AC may also be used.
2
SINAMICS G120C
Supplementary Sheet, A5E36420270A, Edition 07/2015
Download