Annex to Certificate IECEx VTT 14.0021X 1 (5) Rated values Voltage: Max 690 V depending on the terminal type and accessories (see Table 1) Current: Max 35 A according to Tables 3–5 Terminal cross section: According to Table 2 Number of terminals: According to Tables 3–5 Number of cable glands: According to Table 6 Transmitters and proximity transducer amplifiers: Ex n transmitters: Ui = 42.4 V, Li = 0, Ci = 3.6 nF Ex n proximity transducer amplifiers: Ui = -28 V Components Enclosures: ROSE Systemtechnik GmbH, types 34… II 2 G Ex e IIC Gb II 2 D Ex tb IIIC Db, IP66 Tamb = -55 C …+135 C Tamb = -50 C …+100 C (with inspection window) IECEx PTB 07.0059U, PTB 00 ATEX 1101U Ensto Finland Oy, types Cubo X… II 2 G Ex e IIC Gb II 2 D Ex t IIC Db, IP66 Tamb = -55 C …+85 C IECEx DNV 11.0005U, DNV 11 ATEX 98909U IECEx PRE 14.0042U, Presafe 14 ATEX 5378U Terminals: Phoenix Contact; see types, certificates and rated values in Tables 1–2 and the maximum number of terminal blocks in each terminal box type in Tables 3–5. II 2 GD Ex eb IIC Tamb = -60 C …+110 C Annex to Certificate IECEx VTT 14.0021X 2 (5) Table 1: Rated voltage for each Phoenix Contact terminal type included in this certificate. The rated voltage may be lower if skipping jumpers or cut to length bridges are used. Phoenix Contact terminal types ST 1,5 ST 1,5QUATTRO Rated voltage [V] (1 ST 2,5 ST 2,5QUATTRO ST 4 ST 4QUATTRO 440 - with skipping jumper [V] ST 6 ST 10 550 690 (2 - with skipping jumper across type PE [V] 352 (2 (3 275 440 176 - 220 - with cut to length bridge and cover type D [V] - with cut to length bridge and partition plate type (3 ATP [V] UT 6 220 275 275 (1 With or without Phoenix Plug-in bridges (unmodified standard plug-in bridges) With Phoenix Plug-in bridges in which one or more pins are cut off (3 With Phoenix Plug-in bridges that have been cut shorter (2 Table 2: The rated terminal cross sections, allowable cable cross sections and the component certificates for the Phoenix Contact terminal types included in this certificate. In addition, protective conductor terminal blocks (listed types with suffix –PE) are allowed and the same rated terminal cross sections and allowable cable cross sections apply. Phoenix Contact terminal type Cable cross sections [mm2] Rated terminal cross section [mm2] ST 1,5 ST 1,5-QUATTRO ST 2,5 ST 2,5-QUATTRO ST 4 ST 4-QUATTRO ST 6 UT 6 ST 10 Certificates 1.5 0.2–1.5 IECEx KEM 06.0043U, KEMA 01 ATEX 2129U 2.5 0.2–2.5 IECEx KEM 06.0051U, KEMA 00 ATEX 2052U 4 0.2–4 6 6 10 0.2–6 0.2–6 1.5–10 IECEx KEM 06.0050U, KEMA 00 ATEX 2129U IECEx KEM 06.0027U, KEMA 04 ATEX 2048U IECEx KEM 06.0033U, KEMA 01 ATEX 2260U current [A] Table 3: Maximum number of terminal blocks in terminal box types ZWT1 _202012-_BS and ZWT1 _202012-_SS. 3 6 10 16 20 25 35 1,5 32 28 5 cross section [mm2] 2,5 4 26 26 6 22 22 14 6 15 15 15 10 13 13 13 Annex to Certificate IECEx VTT 14.0021X 3 (5) current [A] Table 4: Maximum number of terminal blocks in terminal box types ZWT1 _323220-_BS, ZWT1 _323220-_SS, ZWT1 _323223-_BW and ZWT1 _323223-_SW. 3 6 10 16 20 25 35 1,5 114 28 5 cross section [mm2] 2,5 4 92 58 6 78 36 14 6 55 55 24 10 47 47 15 current [A] Table 5: Maximum number of terminal blocks in terminal box types ZWT1 _505020-_BS and ZWT1 _505020-_SS. 3 6 10 16 20 25 35 1,5 188 28 5 cross section [mm2] 2,5 4 160 58 6 93 36 14 6 90 62 24 10 58 58 15 Note 1. The maximum number of terminal blocks is related only to the current, and thus the actual number of terminals may be lower than given in Tables 3–5 depending on the dimensions of the terminal blocks and the available mounting rail space. When applying the values of Tables 3–5 to determine the maximum number of terminals, simultaneous factors or load factors to IEC 439 may be considered. Mixed equipment with circuits of different cross sections and currents is possible if the various values of the tables are applied proportionally. The values in Tables 3–5 are selected so that the remaining space can be occupied exclusively by control terminals (max. 3 A). The tables for maximum number of terminal blocks are valid only for the Phoenix Contact terminals mentioned in this certificate or for terminals with the same or smaller terminal resistance. For higher terminal resistance values the maximum number of terminal blocks has to be reduced. Annex to Certificate IECEx VTT 14.0021X 4 (5) Cable glands: Hummel AG, type HSK-M-EMV-Ex II 2 G Ex e IIC Gb II 1 D Ex ta IIIC Da, IP 66 Tamb = -60 C …+95 C IECEx KEM 07.0014X, KEMA 99 ATEX 6971X Hawke International, types 501/421 and 501/414 II 2 G Ex e IIC Gb II 2 D Ex tb IIIC Db, IP66 Tamb = -60 C …+80 C IECEx BAS 06.0013X, Baseefa 06 ATEX 0056X Table 6: Maximum number of cable glands. ZWT1 _505020-_BS ZWT1 _505020-_SS PG thread Metric thread NPT thread All side walls Back wall ZWT1 _323220-_BS ZWT1 _323220-_SS ZWT1 _323223-_BW ZWT1 _323223-_SW All side Back wall walls PG 7 or PG9 PG 11 PG 13,5 or PG 16 M12 32 48 18 32 24 48 36 PG 21 PG 29 M25 M32 13 8 PG 36 M40 3/8” NPT 1/2” or 3/4” NPT 1” NPT 1 1/4” NPT 1 1/2” NPT 6 M16 M20 ZWT1 _202012-_BS ZWT1 _202012-_SS Walls with gland plate 8 Back wall 27 Walls without gland plate 8 18 16 27 24 8 5 8 5 6 4 20 12 7 4 11 6 3 2 3 2 2 2 9 3 5 2 0 1 Closing devices (plugs): Hummel Elektrotechnik GmbH, type V-MS-Ex 1.199.****.** II 2 G Ex e II II 1 D Ex tD A20 IP68 Tamb = -60 C …+180 C IECEx BVS 07.0021, DMT 03 ATEX E 049 Hawke International, type 387 II 2 G Ex e IIC Gb II 2 D Ex tb IIIC Db, IP66 Tamb = -60 C …+80 C IECEx BAS 06.0029U, Baseefa 06 ATEX 0118U 6 Annex to Certificate IECEx VTT 14.0021X Adaptors: Hawke International, type 476 II 2 G Ex e IIC Gb II 2 D Ex tb IIIC Db, IP66 Tamb = -60 C …+80 C IECEx BAS 11.0037X, Baseefa 11 ATEX 0067X Transmitters: Rosemount, type 248 II 3 G Ex nA IIC T5 Tamb = -60 C …+80 C IECEx BAS 07.0087U, Baseefa 03 ATEX 0032U In 3 D (dust) applications normal industrial components are allowed. Proximity transducer amplifiers: Bently Nevada Inc, type 3300XL Proximitor Sensor, 330180-51-05 II 3 G Ex nA IIC T4 Gc Tamb = -51 C …+100 C IECEx BAS 04.0057X, Baseefa 07 ATEX 0189X In 3 D (dust) applications normal industrial components are allowed. The above mentioned components, excluding enclosures, may be replaced by equivalent Ex certified components taking into consideration the required equipment group, temperature classification and creepage and clearance distances. Degree of protection IP 66 Documents The equipment is installed in the enclosure as shown in the following principle drawings: ABB Oy: 3AFP 9923019 rev D ABB Oy: 3AFP 9923024 rev D ABB Oy: 3AFP 9923042 rev D ABB Oy: 3AFP 9923044 rev D 5 (5)