TM DuraLife FPL UL 2196 Fire Rated Alarm Cables UL LISTED FPL FIRE ALARM CABLES; 2-HOUR FIRE RATED Unshielded - 16 AWG - 14 AWG; 2-conductor NEC Type FPL; for use in Electrical Circuit Integrity System FHIT.28A. Installation Guide Authorities Having Jurisdiction should be consulted before installation. 7_14 DuraLifeTM FPL UL 2196 Fire Rated Alarm Cables ! INDEX CRITICAL INSTALLATION INFORMATION Radix DuraLifeTM FPL fire rated cables must be installed in accordance with ALL requirements of the UL 2196 Electrical Circuit Protective System Listing, plus national and local codes. INSTALLATION OVERVIEW.................................. 2 CABLE RATINGS/APPROVALS..... 2 Read carefully and follow the installation instructions in this booklet. CERTIFICATIONS & EMT FILL LISTING ................... 2 • Ensure that cable is stored properly in a moisturefree environment and that cable jacket is in good condition prior to installation. DURALIFETM FPL CABLE OVERVIEW....................... 3 APPLICATIONS/ COMPLIANCE ............................. 3 • Take all precautions when installing cables by following OSHA and other applicable regulations. CABLE STORAGE & HANDLING ......................... 4-5 • Store pull ropes in a clean, dry area, out of direct sunlight and away from extreme heat. PRE-INSTALLATION.................... 6 • While cables are exposed and during cable pulling activities, protect cables from nearby or overhead work to prevent damage to the cable jacket or insulation. INSTALLATION........................ 6-8 SPLICE PROCEDURE FOR FIRE ALARM CABLES...... 9-12 • Do not pull cables around corners with sharp edges as this may damage cable jacket/insulation. PULL-BOX AND SPLICE INSTALLATION EXAMPLES ....... 13 • Pull cable only into clean EMT tubing. Visually check for debris, abrasions or sharp edges that might damage the cable prior to cable installation. TESTING ................................... 13 • Use only steel support systems. No other materials are acceptable. • Support the cable in the manner and intervals detailed in the Electrical Circuit Protective System listing. © 2014 Radix Wire. All rights reserved. DuraLifeTM is a registered trademark of Radix Wire. Made in USA 1 DuraLifeTM FPL UL 2196 Fire Rated Alarm Cables INSTALLATION OVERVIEW / CABLE RATINGS & APPROVALS CERTIFICATIONS & EMT FILL UL 2196 System Requirements Certifications & EMT Fill Listings The reliability of a fire rated cable system depends on correct system design, installation and use of approved components/materials. ! CERTIFICATIONS Solid Conductor 16 AWG 14 AWG Single-Cable EMT Horizontal - ¾” - 2” Wheatland 3 ¾” - 2” Wheatland Multi-Cable EMT Vertical & Horizontal ¾” to 2” Wheatland ¾” to 2” Wheatland 7-Strand Conductor Failure to comply with these specific guidelines may result in a system that fails in fire conditions. Single-Cable EMT Vertical •Radix DuraLifeTM FPL cables must be installed in Wheatland FasTrak Plus EMT tubing. Additional UL 2196 System Components include: •Halex or Raco EMT Compression Couplings •Hubbell Set-Screw Fittings ½” to 2” Wheatland 3 ½” to 2” Wheatland FILL RATES 16 AWG 14 AWG ¾” EMT Horizontal 1 cable Up to 2 cables ½” EMT Vertical •Cooper Crouse-Hinds Compression Fittings 3 1 cable 1 cable 1” EMT Horizontal Up to 2 cables Up to 2 cables •Cooper B-Line NEMA 1 Splice Enclosure/Pull Box ¾” - 1” EMT Up to 3 cables Up to 2 cables Vertical •Penn-Union Copper Off-Set Fixed Lug Connector with 1/4-20 Set-Screw 1¼” EMT Up to 4 cables Up to 3 cables Vertical & Horizontal •Polywater J Lubricant 1½” EMT Up to 6 cables Up to 4 cables Vertical & Horizontal Ratings & Approvals •UL 2196 Certified/UL 1424 Listed 2” EMT Vertical & Horizontal •FHIT SYSTEM No. 28A •Low-Smoke, Zero-Halogen •Unshielded 16 AWG - 14 AWG; 2-Conductor ! •Maximum Voltage Rating: 72V (for fire applications) Up to 10 cables Up to 8 cables DuraLife FPL cables of different gauge sizes can be installed together in a single conduit up to the maximum allowed by the 14 AWG cable. No other cables or wires can be installed in the same conduit with DuraLife FPL cables. •NEC Type FPL; for Use in Protective Electrical System (EMT) Authorities Having Jurisdiction should be consulted before installation 2 DuraLifeTM FPL UL 2196 Fire Rated Alarm Cables DURALIFETM FPL CABLE OVERVIEW APPLICATIONS Radix DuraLifeTM FPL fire rated power cables are designed to be flexible for easier installation. Radix DuraLifeTM FPL fire rated power cables are constructed and approved for the following applications: Oxygen-free bare copper (OFHC) conductors, solid and stranded •Fire alarm circuit integrity (NEC Article 760). •Emergency systems (NEC Articles 700 and 517). Radix proprietary ceramifiable silicone rubber insulation; color-coded black and red insulation on leads •Suitable for 2-hr. certified fire-resistive applications in Wheatland EMT tubing. •Fire-resistive certified for Power-Limited system use at 72V phase-to-phase utilization voltage. Maximum cable voltage rating: 300V •Meets fire alarm survivability circuit requirements in the National Fire Protection Code (NFPA 72) . •UL 1424 Listed FPL for Power-Limited Fire Alarm Circuits; 300V/90°C classified. Low-smoke zero-halogen FRPE outer jacket. Red jacket standard. Black jacket available at an additional charge. •UL Certified to UL 2196 2-hour fire rating in FHIT System 28A. PRINT LEGEND: RADIX WIRE-II DURALIFE ™ X/C #Y AWG FPL 90C / (UL) CLASSIFIED FIRE-RESISTIVE CABLE FOR USE IN ELECTRICAL CIRCUIT INTEGRITY SYSTEM #28A. SEE UL FIRE RESISTANCE DIRECTORY R21213 (MONTH/YEAR). [where, X is the number of conductors and Y is the size of the cable in AWG]. COMPLIANCE •UL 1424 Listed FPL for Power-Limited Fire Alarm Circuits; 300V/90°C classified; •UL Certified to UL 2196 2-hour fire rating in FHIT System 28A •Meets fire alarm survivability circuit requirements in the National Fire Protection Code (NFPA 72). •Meets vertical flame requirement for cable tray rating per UL 1685. 3 DuraLifeTM FPL UL 2196 Fire Rated Alarm Cables CABLE STORAGE & HANDLING Radix DuraLifeTM FPL fire rated power cables are designed for durability. However, proper cable handling procedures must be followed to ensure the cable is not damaged prior to installation. Storage Procedure Store 1000’ and 2000’ reels on sides to avoid damaging reels. Store 5000’ reels upright on flanges. Do not stack reels. Handle reels carefully to avoid physical damage to reel and cable. Store cables on a firm, dry surface or on planking in an area with good drainage. Protect from Damage Choose a storage area that is cool, dry and protected from weather, construction activities, equipment collisions, falling objects, chemical spills, moving vehicles and other related hazards. Arbor Hole Reel Flange Protective Reel Wrap Initial Inspection When cable reels are first received, inspect the protective reel wrap for evidence of shipment damage. Whenever possible, leave the Radix factory-applied protective cover in place until just before installation. Radix highly recommends the use of additional covering to protect cable reels when stored outdoors or in dirty, dust-prone areas. Use a cover that is resistant to moisture and shields cables from the sun. If possible, provide ventilation to avoid excessive heat in the storage area. Always store and transport reels as shown below. To avoid reel damage, do not stack. 1000’ and 2000’ Reels 3Stored on Side 5000’ Reel Packaging: Available on 1,000 ft., 2,000 ft. and 5,000 ft. reels. 3Stored Upright on Flange Smaller length reels may be available from Radix Wire distribution partners. Radix highly recommends storing cable reels indoors or in a weather-protected enclosure. 4 DuraLifeTM FPL UL 2196 Fire Rated Alarm Cables CABLE STORAGE & HANDLING Moving Reels A Radix DuraLifeTM cable reel, depending on gauge and reel size, weighs 60 - 400 pounds, so handle carefully by using equipment designed specifically for this task. Recommended Reel Rolling Method It is a natural instinct to roll cable reels. However, Radix recommends only doing so for short distances over firm, level and dry surfaces. Roll reels in direction the cable is wound (see below) to keep the cable winding tight. Rolling in the wrong direction loosens the winding and may damage the cable or make it more difficult to deploy. • Make sure the lifting/handling device does not come in direct contact with the cable or its protective covering. Secure end of cable with tape or thread through flange hole and knot before rolling. • Take care to ensure that the flange of one reel does not impact cable on another reel. Always roll reels at a slow speed to maintain control and prevent collisions with equipment, other reels or personnel. • Do not drop reels from any height, especially from trucks or transport equipment. If any of these situations occur, immediately examine the DuraLifeTM cable for damage. Flange Hole Recommended Lifting Methods • Crane or boom-type equipment - Insert a suitably strong, properly secured shaft through the reel arbor hole and lift with slings. Arbor Hole - Use a spreader or other device to minimize sling pressure against the reel flange. • Forklift - Place fork tines so that lifting pressure is on both reel flanges, not the cable. Secure Loose Cable End with Tape Prior to Rolling 5 DuraLifeTM FPL UL 2196 Fire Rated Alarm Cables PRE-INSTALLATION INSTALLATION Radix DuraLifeTM FPL fire rated power cables must be installed in accordance with ALL requirements of the UL 2196 Electrical Circuit Protective System Listing, plus national and local codes. ! Radix recommends you follow the installation guidelines documented in the new NEC 2014 Article 728, Fire-Resistive Cable Systems. Article 728 covers the installation of fire-resistive cables, fire-resistive conductors and other system components used for survivability of critical circuits to ensure continued operation during a specified time under fire conditions as required in this Code. UL Electrical Circuit Integrity Systems (FHIT) Prior to installation, Radix highly recommends you visit www.UL.com and reference the Fire-Resistive and Circuit Integrity Cables section for the latest information and updates on UL Electrical Circuit Integrity Systems (FHIT). Checklist • Check cable for presence of moisture or evidence of damage that may have occurred in storage. Wheatland EMT Tubing Installation • Take precautions if system routing comes in close proximity to abnormally high heat sources such as pipes. Long-term exposure to high heat could cause damage to cable jacket. ! • Inspect cable entry and exit points for any sharp, jagged edges which could damage cable jacket in pulling process. WEIGHT/1000 FT (LBS) 14 AWG 7-Strand Conductor 73.28 16 AWG Solid 2-Conductor 14 AWG Solid 2-Conductor Wheatland EMT support brackets must be installed no further apart than 72” in vertical orientation and 60” in horizontal orientation. These maximum support dimensions apply to all EMT tubing sizes. For complete overview of Wheatland EMT tubing installation, reference 2014 NEC Article 358 which covers Electrical Metallic Tubing (EMT) and all applicable Articles of the Code, as well as any listing, labeling or manufacturer’s instructions. • Examine conduit supports prior to pulling cable to assure total system integrity. CABLE SIZE Authorities Having Jurisdiction should be consulted before installation. For installation of all other UL 2196 certified system components, consult each manufacturer’s installation instructions. See page 2 for list of manufacturers. 55.41 59.01 6 DuraLifeTM FPL UL 2196 Fire Rated Alarm Cables INSTALLATION Bend Radius DuraLifeTM FPL is designed to be highly flexible for easier installation. No special equipment is required to bend or straighten this cable. Cable Pulling Use Polywater J lubricant prior to pulling cables. Use a pulling rope which can handle the maximum allowable pulling tension on each cable pull without causing damage to the equipment or cables. Refer to the pulling equipment/rope manufacturer’s specifications for capacity limitation. Maximum Recommended Bend Radius: 2X Cable Diameter Maximum Allowable Pulling Tension CABLE SIZE TENSION (LBS) Solid 16 AWG & 14 AWG 15 7-Strand 14 AWG 15 ! Cable Preparation for Splicing DuraLife requires no special tooling or procedures for jacket/insulation stripping. Take care when stripping jacket not to damage cable insulation. Follow all NEC splicing and termination standard practices for this category of cable. Install Procedure for NEMA Splice Enclosures/Pull Boxes See pages 9 - 12 for step-by-step instructions. Do not exceed Radix’s recommended pulling tension for DuraLifeTM FPL as this may damage the jacket, insulation or conductor which can lead to failure in a fire event. ! Conduit fill should not exceed allowable limits. See page 3 for Fill Ratings. DuraLife FPL cables of different gauge sizes can be installed together in a single conduit up to the maximum allowed by the 14 AWG cable. (see chart on page 3) No other cables or wires can be installed in the same conduit with DuraLife FPL cables. 7 DuraLifeTM FPL UL 2196 Fire Rated Alarm Cables INSTALLATION OVERVIEW Vertical Installation Horizontal Installation • Wheatland EMT support brackets must be installed no further apart than 72 inches in vertical runs • Wheatland EMT support brackets must be installed no further apart than 60 inches in horizontal runs • Maximum of 28 Feet Between Terminating Points • No length limit between Terminating Points See Page 13 for Representative Pull-Box Installation Photo ! No other cables or wires can be installed in the same conduit with DuraLife FPL cables. See Page 2 for UL 2196 Approved System Components See Page 2 for UL 2196 EMT Fill list and DuraLife Certifications Authorities Having Jurisdiction should be consulted before construction in all cases as to the particular requirements covering the installation and use of UL Certified products, equipment, system, devices, and materials. 8 DuraLifeTM FPL UL 2196 Fire Rated Alarm Cables SPLICE PROCEDURE FOR FIRE ALARM CABLES • Steel ¼”-20 X ½” Hex Head Cap Screws Cooper B-Line NEMA 1 Splice Enclosure/Pull Box • Steel ¼” Screw Size Washers Required Materials: • Cooper B-Line NEMA 1 Box (i.e., Cooper B-Line SC Series) • Rubber -010 Size O-Rings (i.e., McMaster Carr Product No.9452K18) • Ceramic 1” Length, ¾” OD, ¼”-20 Female Thread Standoffs (i.e., McMaster Carr Product No.94335A151) NOTE: Splice boxes require 8x8x4 box Pull boxes can be sized up to 12x12x4 • Steel ¼”-20 X 1¼” Fully Threaded Studs • Copper Set Screw Lug Offset Tongue Terminal (i.e., McMaster Carr Product No. 6923K32) • Steel ¼”-20 Hex Nuts • 17/64” Drill Bit (not shown) ! Alternative Components: • Longer Ceramic Standoff (i.e., McMaster Carr Product No. 94335A152) DuraLifeTM FPL cable must be installed in Wheatland EMT tubing to comply with UL 2196. DuraLife™ cables are not approved for use in rigid conduit systems. • Straight Tongue (Non-Offset) Copper Terminal (i.e., McMaster Carr Product No. 6923K62) Conduit fill should not exceed allowable limits. See page 3 for Fill Ratings. 9 DuraLifeTM FPL UL 2196 Fire Rated Alarm Cables SPLICE PROCEDURE FOR FIRE ALARM CABLES 1. Drill two holes into the back of the NEMA 1 box spaced at least 1¼” apart to mount ceramic standoffs. 3. Apply O-rings to screws inside NEMA box. Spaced at Least 1 1/4” Apart 4. Install ceramic standoffs to screws until O-rings are slightly compressed. 2. Insert ¼” hex cap screws with washers from back of NEMA 1 box. Washer/ Hex Nut ! 10 Requires Cooper B-Line NEMA 8x8x4 Splice Enclosure DuraLifeTM FPL UL 2196 Fire Rated Alarm Cables SPLICE PROCEDURE FOR FIRE ALARM CABLES 5. Insert threaded studs into ceramic standoffs. 7. Affix hex nuts to studs until O-rings are slightly compressed. 6. Apply O-rings to studs. 8. Strip leads for termination. O-Ring ! 11 Requires Cooper B-Line NEMA 8x8x4 Splice Enclosure DuraLifeTM FPL UL 2196 Fire Rated Alarm Cables SPLICE PROCEDURE FOR FIRE ALARM CABLES 9. Bend stripped end 180° to provide more secure terminal attachment. 11. Place terminals onto studs. 12. Install washers onto studs. 10. Securely attach terminals to stripped ends. 13. Fasten hex nuts onto stud and, while holding ceramic insert to immobilize assembly, tighten hex nut. ! Requires Cooper B-Line NEMA 8x8x4 Splice Enclosure This installation segment is now completed! 12 DuraLifeTM FPL UL 2196 Fire Rated Alarm Cables REPRESENTATIVE PULL BOX INSTALLATION SINGLE CABLE (Can also be oriented as horizontal straight-through) MULTIPLE CABLES ! Cooper B-Line NEMA Pull Boxes can be sized up to 12x12x4 TESTING UL 2196 should be referenced as the test standard used to evaluate fire-resistive performance of electrical cables. UL 2196 is one of the testing standard for FHIT Certified assemblies. All manufacturers’ installation instructions should include any design elements beyond the minimum NEC requirements used to pass the performance testing. If you have any questions about the installation of this system, please contact: Radix Wire 26000 Lakeland Blvd. • Euclid, OH 44132 • Toll-Free: 877.722.5444 •Local: 216.731.9191 www.Radix-Wire.com •Email: info@radix-wire.com 13 © 2014 Radix Wire