MV/LV Transformers for Distribution Network Solutions transforma Distribution Transformers Up to 36 kV and up to 5 MVA IEC Standards Reliable innovation. Personal solutions. www.ormazabal.com transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Contents Introduction__________________________ 1 Preface 1 Your Electrical Network 2 Your Business and DNS Applications 2 Our Product Map (SSS & DNS) 3 Main features_________________________ 4 Safety 4 Reliability 6 Efficiency 6 Sustainability 7 Continuous innovation 7 Technical details_______________________ 8 Family 8 Technical data 9 Constructive structure 9 Dielectric liquids 10 Design characteristics__________________ 12 Equipment 12 Low voltage connection 13 Medium voltage connection 13 Type of transformers________________________________________14 Conventional 14 Conventional_IEC 18 Non-conventional 32 Handling, installation and after sales_ ______________________ 34 Handling 34 Indoor 34 Outdoor 35 Commissioning and after sales 35 Recycling and end‑of‑life 35 The quality of the products designed, manufactured and installed by Ormazabal is backed by the implementation and certification of a quality management system, based on international standard ISO 9001:2008. Our commitment to the environment is reaffirmed with the implementation and certification of an environmental management system as laid down in international standard ISO 14001. In view of the constant evolution in standards and design, the characteristics of the elements contained in this catalogue are subject to change without prior notification. These characteristics, as well as the availability of components, are subject to confirmation by Ormazabal. transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Introduction Preface The incorporation into Ormazabal in 2001 of the distribution transformer manufacturer Cotradis constituted a strategic milestone for us. The exchange of know-how between our technical teams has significantly reinforced the value added for our customers. Growing energy demands, higher quality requirements in energy supply and the priority to reduce the consumption of natural resources require the use of equipment which responds with high levels of reliability, safety and energy efficiency. Ormazabal is the leading provider of customized solutions to electrical utilities, to electrical end users as well as renewable energy systems applications based on its own technology. We encourage the development of the electrical sector towards the challenges of the future energy needs. We cooperate with the world’s leading local, regional and global companies in the electrical sector with a strong commitment to innovation towards personal safety, network reliability, energy efficiency, and sustainability. Our highly qualified and focused team of innovation-motivated professionals Focusing on the needs of our customers have developed our own products and mastering new technologies allows and solutions during our more us to offer products which comply with than a century long consolidated these requirements. history, always by establishing close relationship with our customers aimed Our specialisation in Medium Voltage at achieving mutual long term benefits. is backed by the certification of our transformers in major European electrical companies. Velatia is a family-run, industrial, technological and benchmark global group which operates in the areas of electrical networks, electronics and communication networks as well as in the consulting, security and aeronautics component sectors, where safety, efficiency and reliability are valued. Our customer orientation has led to the development of our extensive network of factories in Spain, France, Germany, Poland, Brazil, Mexico and China, helping to meet our customers’ needs in more than 50 countries. The solutions of the companies in Velatia seek to make the world a more and better connected, more sustainable, smarter, safer, more humane place. We manufacture a wide range of dielectric liquid immersed distribution transformers, compliant with all of the requirements in current international regulations and with a range of powers from 25 kVA to 5000 kVA and insulation levels up to 36 kV. In addition, our portfolio includes special transformers up to 72.5 kV and 10 MVA. Kalkbukt PV Plant (Republic of South Africa) Furthermore, close collaboration with our customers enables us to develop transformers conforming to their own particular standards and specifications. Currently more than 170,000 of Ormazabal’s transforma are installed in electric distribution networks, industry, wind farms and photovoltaic plants in more than 20 countries. Athletic Bilbao Stadium (Bilbao, Spain) Public Distribution EDF utility (France) 1 transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Your Electrical Network "Your dedicated partner for reliable and intelligent electrical network". Your Business and DNS Applications Close relationship with our customers and the profound knowledge of the electrical business are the keys to success that enable us to offer Distribution Network Solutions (DNS) based on high added value products and services adapted to the needs of the electrical utilities, electrical energy end users and renewable energies. 2 PUBLIC DISTRIBUTION END USERS RES Infrastructure Industry Services Wind Solar Dispatchable RES transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Our Product Map (SSS & DNS) We believe that excellence does not lie solely in offering effective products and services, but also in the ability to respond to individual requirements and demands. Our Business Lines SSS: Substation Solution for primary distribution We provide our clients with personalised projects for efficient energy management via Primary and Secondary Distribution equipment and solutions. DNS: Distribution Network Solutions for secondary distribution Our products for your segment cpg.1 cpg.0 gae1250kmax cgm.3 amc gae cibor transfoorma nvl.cibor Power transformers cgmcosmos [IEC - ANSI/IEEE] ga Prefabricated substations ormacontainer cgmcosmos [HN] ea transfoorma Distribution transformers ekorsys family Protection, automation and control Conventional Non-conventional transforma.tpc transforma.fine Extended range solutions Oil CURRENT® family Advanced metering, sensing & analytics, monitoring and communications organic Low voltage board Biodegradable dielectric liquid Concrete prefabricated transformer substations (TS) Underground Walk-in Compact Concrete enclosure for transformer substations (TS) Underground Walk-in Modular Metallic prefabricated TS CEADS Switching nodes Metallic enclosure for TS Photovoltaic substation Mobile substation 3 transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Main features Safety Our transformers are subjected to the tests described in the IEC 60076 series of standards. We have our own laboratories for this purpose, equipped with modern, precise measurement devices and systems that are certified and calibrated according to the directives of the ISO 9001 standard, to ensure that our products comply with the most demanding quality standards. Routine test Type test All of the transformers manufactured are subjected to the following routine tests, in accordance with IEC 60076-1: With our customer’s agreement, the following tests are performed in accordance with current international regulations: ●● Winding resistance measurement ●● Temperature-rise test ●● Measurement of the voltage ratio and verification of the vector group ●● Dielectric type tests: Lightning impulse (LI) test ●● Measurement of no -load losses and current ●● Dielectric routine tests: ●● Separate source AC withstand voltage test (also known as Applied over-voltage test or Power frequency test) ●● Induced AC voltage test (ACSD) (also known as Short duration induced AC withstand voltage test) Separate source AC withstand voltage test (Applied over-voltage test or Power frequency test) MV LV Highest voltage for the equipment, Um, (Insulation Level). [kV] 12 17.5 24 36 1.1 3.6 Rated withstand Voltage of the test (1 minute). [kV] 4 ●● Lightning impulse (LI) test ●● Measurement of the short-circuit impedance and load losses 28 38 50 70 3 10 MV LV Highest voltage for the equipment, Um, (Insulation Level). [kV] 12 17.5 24 36 1.1 3.6 Rated withstand Voltage for Lightning impulse test (1.2 / 50 μs). [kV] 75 95 125 170 20 20 transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Special tests Additional tests Special tests specifically requested by the customer: Dielectric Oil Tests ●● Special dielectric tests ●● Partial discharge measurement test ●● Winding capacities measurement – earth and between windings ●● Zero-sequence (homopolar) impedance measurement (in three-phase transformers) The transformer’s operative life is largely related to the quality of the dielectric liquid. We assure the highest quality standards by means of strict qualification and product auditing processes as well as by applying the most advanced technologies in the treatment process. ●● Density at 20°C ●● Ability to withstand Short-circuit test (IEC 60076-5), performed in accredited external and internal laboratories (HPL) ●● Water content ●● Sound level measurement (IEC 60076-10) ●● Dielectric dissipation factor ●● Measurement of no-load current harmonics ●● Acidity ●● Measurement of insulation resistance and/or measurement of the dissipation factor (tan delta) of the insulation capacitances ●● Viscosity at 40°C Tank Tests ●● EN 50464-4 Endurance test Paint Tests ●● Film Thickness measurement ●● Adherence test ●● Hardness test ●● Bend test ●● Impact test ●● Cupping test ●● Salt spray test ●● Breakdown voltage ●● Interfacial tension ●● Flash point 5 transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Reliability Efficiency The quality and reliability of our products is demonstrated through the testing and certification of our transformers in independent, internationally-renowned laboratories. Dielectric Liquid completely immersed Hermetically-Sealed Transformer Furthermore, the technological development and passion for innovation, which has been fundamentally apparent throughout the history of our company, is reinforced by our High Power Laboratory (HPL) with a capacity up to 2500 MVA. These are our own facilities which enable ongoing tests and which combined with our highly-qualified staff, further certify our technological independence. Together with external organisations and official bodies, we also participate in market quality control campaigns to assure the verification of our products. ●● Hermetically-sealed tanks: ●● No expansion tank is needed ●● Less dielectric liquid used than in other types of transformer ●● No contact between the dielectric liquid and external agents (air, humidity, pollution, etc.) ●● Prevents deterioration of the dielectric’s characteristics ●● Low-level maintenance ●● Minimal risk of leakages: ●● Tank robustness (high quality materials). ●● Welding processes carried out by qualified staff ●● Leak tests performed in all transformers Minimal Environmental Impact ●● Respect for the environment: ●● Use of highly-recyclable materials ●● Rationalisation in the use of raw materials ●● Optimised transformer dimensions ●● Optimum consumption of raw materials: ●● Materials selection ●● Maximisation of their characteristics ●● Low electrical energy consumption: ●● Advanced technology in design, manufacturing and testing ●● Minimal loss transformers ●● Safe, reliable products ●● ISO 14001 certification 6 Low Noise Level ●● An optimum design and assembly of the ferromagnetic core enables us to drastically reduce the level of noise generated by the transformer. ●● There are two components that identify the level of noise produced by a transformer: LwA = LpA + KS Where: ●● LwA: Acoustic Power (cause) ●● LpA: Acoustic Pressure (effect) ●● KS factor (>0) which depends on the size of the transformer To define a transformer, the use of Acoustic Power LwA is recommended since it is a value which is independent from the environment and is therefore the best magnitude for assessing the acoustic emissivity of a transformer. transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions PCB Free ●● Our transformers are only manufactured using new components and without any PCBs, in strict compliance with current regulations Sustainability Continuous innovation Sustainability, understood as the best compromise between satisfying social demands, caring for the environment and financial aspects. Our commitment to innovation places us at the technological forefront of Europe. Social Demands ●● Safety of people and goods ●● Continuity of service Financial Aspects ●● Optimum use of raw materials ●● Longer equipment life, endurance and robustness ●● Equipment adaptable to network evolution Therefore our products meet the most demanding worldwide requirements and are certified by internationally renowned laboratories. Recently we have extended our product range to 5 MVA and also we have developed several new transformers for different applications: transforma.fine for wind power generation, transformers with on-load tap changer, transformers for high voltage shore conection systems, etc. as well as transformers with a greater variety of lower losses. ●● Equipment durability Caring for the Environment Electromagnetic Compatibility Our transformers are passive elements in terms of electromagnetic compatibility. In other words, they work satisfactorily without adding electromagnetic noise that is intolerable for equipment in their surroundings and they withstand such interference caused by other devices. The currents that circulate through the conductors connected to the transformers, especially low-voltage ones, can cause significant electromagnetic fields. The installation designer must make sure that these cables are laid such that the fields are minimised or, if necessary, measures must be adopted to limit their effects. ●● Reduction in the volume of dielectric liquid ●● Minimal dimensions ●● Minimal losses in the transformer ●● Low risk of oil leakage ●● Non-aggressive for the surrounding environment ●● Recyclability Ecodesign Ormazabal complies with the requirements of the Ecodesigndirective from the European Commission (No 548 / 2014) that defines the guideline for the environmentally friendly design of the transformers in Europe. This regulation applies to all the transformers placing on the market or put into service from July 2015 throughout the European Union and doesn’t affect the products to be exported outside Europe.When supplied within the EU, this equipment will bear the CE mark as proof of compliance with European Union directives. The Ormazabal distribution and power transformers are being developed to contribute to commitment of this directive, that is, to improve energy efficiency and environmental performance. 7 transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Technical details Family transfoorma Non-conventional Conventional Distribution Transformers transforma.tpc transforma.fine Ur (max.) 24 kV / 36 kV 24 kV / 36 kV 36 kV Standard IEC-HN HN IEC Power (max.) 25 - 5000 kVA 50 - 630 kVA 5 MVA Losses A0Bk/A0Ck/D0Ck/C0Ck/C0Bk/E0Dk/ B036Bk36/A036Ak36 Consult availability Consult availability Self-protected transformers Small-sized transformers that are highly resistant to high temperatures Oil Dielectric liquid immersed hermetically sealed completely filled transformer Biodegradable dielectric liquid >> organic Extended range solutions - Other technical values (>36 kV, >5000 kVA....) - OLTC (On load tap charger) - Containerized generators - PV applications - Auxiliary services in nuclear power plants - High voltage shore connection systems - Extended features Transformer with natural biodegradable dielectric liquid (*) Other solutions on request Applicable electrical standards IEC EN 50464 Three-phase oil-immersed distribution transformers 50 Hz, from 50 kVA to 2 500 kVA with highest voltage for equipment not exceeding 36 kV IEC 60076-1 Power Transformers – Part 1: General IEC 60076-3 Power transformers - Part 3: Insulation levels, dielectric tests and external clearances in air EU Directive Regulation No 548/2014 8 Implementation of the Ecodesign Guideline 2009/125/EG with regard to power transformers transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Technical data ●● Three-phase transformers, for indoor or outdoor installation Constructive structure Active part 5 ●● Dielectric liquid immersed transformers: Hermeticallysealed completely immersed in oil in accordance with standard IEC 60296 The active part of the transformer is the energy transformation system, composed of the ferromagnetic core, the windings and the medium and low voltage connections. ●● ONAN cooling Tank and dielectric ●● Colour: RAL 7033 (other colours under request) ●● Conventional transformers: 4 3 The transformer’s tank and the dielectric liquid provide the necessary insulation and cooling. ●● From 25 to 5000 kVA 6 2 1 1 Tank and dielectric liquid 2 MV and LV windings ●● Insulation level: 24 and 36 kV 3 MV plug-in bushings The data and values shown correspond to the normal service conditions referred to in standard IEC 60076-1. 4 Low voltage (LV) terminals 5 Thermometer pocket For other configurations, please contact Ormazabal. 6 Ferro magnetic core WindingsAdvantages ●● Concentric windings ●● Insulation between layers: Cellulose with epoxy resin which compacts the coils, once cured ●● Coils are manufactured using the latest techniques and machinery ●● Expertise in coil cooling ●● Careful manufacturing of coils and cooling channels ●● Use of high-quality cellulosic materials ●● Optimum handling and storage to preserve insulation properties Connections and Tap Changer ●● MV and LV terminals ●● Off-circuit Tap changer Tank and Dielectric Liquid ●● Elastic Corrugated tank with cooling fins ●● Completely filled with dielectric liquid and hermetically sealed tank ●● Immersed in dielectric liquid ●● Surface treatment and paint ●● Optimised to withstand short circuit forces ●● Improved heat dissipation in the windings ●● Guaranteed insulation Advantages ●● Transformer connection to the outside ●● Secondary voltage can be adjusted precisely Advantages ●● Increased heat dissipation surface ●● Absorption of variations in the volume of the dielectric liquid caused by changes in its temperature ●● Mechanical and electrical protection ●● No aging of the dielectric liquid as there is no contact with the air ●● Minimal maintenance requirements ●● Small size ●● No expansion tank or air dehydrating needed ●● Lighter in weight ●● Electromagnetic field shielding ●● Lower noise level ●● Better behaviour in the event of overloads and harmonics ●● Protection against corrosion, atmospheric agents, insolation and impacts 9 transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Dielectric liquids ●● Mineral oil: Uninhibited mineral insulating oil according to IEC 60296 ●● Bioelectra®: Natural, biodegradable ester for application in organic transformers. Class K with fire point greater than 300°C ●● Dielectric liquid silicone according to the IEC 60836 standard, Class K with fire point greater than 300°C ●● Synthetic biodegradable ester for application in electrical transformers according to the IEC 61099 standard organic transformers Ormazabal offers, as part of its range of dielectric liquid immersed transformers, the organic transformers, which are characterised by the use of a natural biodegradable ester as a dielectric. This natural ester Bioelectra® developed and patented by Ormazabal is a dielectric coolant liquid obtained from vegetal oils and made without antioxidant additives. Its excellent antioxidant capacity is based on its special composition and a specific refining process that allows it to maintain its natural antioxidants. Natural ester features ●● Excellent dielectric properties: It has a high water saturation point, which allows it to maintain high breakdown voltage values with a high water content ●● High fire resistance: High flash point (>300°C) and fire point (>350°C), much higher than those of mineral oils. It is classified as a K class liquid (Fire point > 300°C) according to Standard IEC 61100. Better behaviour against fire than mineral oil transformers ●● High biodegradability in ground and water due to its natural composition ●● It is not ecotoxic ●● Long service life: It prolongs the life of the cellulosic insulations thanks to its high water retention capacity ●● Recyclable and reusable in other favourable environmental products (biodiesel) at the end of its service life ●● The electrical characteristics and dimensions of the transformer are not affected 10 transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Advantages compared to other dielectric liquids ●● Superior dielectric properties with high water content: ●● Higher breakdown voltage with high water content (much higher water saturation level than mineral oils) Advantages compared to other type of transformers In relation to dry transformers: In relation to silicone transformers: ●● Higher biodegradability Any transformer with dielectric liquid has the following advantages against dry transformers: ●● Zero toxicity against aquatic organisms ●● Better losses level: ●● Higher level of safety: ●● Higher fire and flash points than the rest Dry transformers have considerably higher no-load and load losses than dielectric liquid transformers of dielectric liquids ●● Non-toxic product ●● Recyclable and reusable at the end of its ●● Lower environmental impact at the end of its service life (recyclable and reusable dielectric liquid) In relation to mineral oil transformers: ●● Higher biodegradability (This difference can increase annual operation losses by more than 50%) service life ●● Increases the service life of the transformer: ●● Better behaviour against fire ●● Lower noise: ●● Increases the service life of the cellulosic ●● Lower environmental impact at the end of its service life (recyclable and reusable dielectric liquid) Dry transformers have a much higher noise level than dielectric liquid transformers (difference in acoustic power between 10 and 15 dB) insulations thanks to its high water saturation point ●● Lower generation of gas during the electrical stress that it endures during operation Noise ●● Overloadability ●● Severe oxidation tests show that the acids generated in the natural ester do not decrease its breakdown voltage or affect copper negatively Losses Environmental impact organic ●● Higher life expectancy Dry ●● Higher robustness against vibrations, environmental conditions and transient phenomena in the electrical network Biodegradability ●● Less space required, as it does not require a safety perimeter Fire resistance (fire point temp.) organic range Mineral oil range (common values) Additionally, being an organic transformer it is characterised by: ●● Similar safety levels against fire ●● Lower environmental impact at the end of its service life in its recycling process ●● Alternative for installing in natural areas Natural ester vs other dielectrics Fire Point Biodegradability Mineral oil Hydrocarbons with high molecular weight Silicone Oils Synthetic Esters 160°C 312°C 340°C 322°C 360°C low low null high very high Natural Esters 11 transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Design characteristics Equipment Conventional transformers 16 1 4.a 4.b 15 9 16 2.b 7 12 3 2.a 8 10 6 14 11 5 13 1 2.a 2.b 3 4.a 4.b 5 6 7 8 9 10 11 12 13 14 15 16 12 Off-circuit regulation tap changer (can only be operated without voltage) MV porcelain bushings MV plug-in bushings LV porcelain bushings LV connection flags (≥630 kVA) LV single pole busbar bushings Earthing terminals in the tank Draining and sampling device Filling device Protection relay Functions: Internal tank pressure control, dielectric liquid temperature control, oil level control and gas detection Rating plate 2 Lifting eyes 4 Latching eyes 4 Pulling eyes Thermometer pocket Thermometer: measures the temperature of the top layer of the insulation liquid Available with 2 contacts (alarm and trigger) and upper limit marker Wheels (≥250 kVA) Dielectric liquid collecting device Terminal cover box Pole mounting brackets and support for surge arresters (application for pole mounted transformers up to 160 kVA) StandardOptional IEC 60214 EN 50180 • • EN 50386 • • • • EN 50180 EN 50216-4 EN 50216-4 EN 50464-1 EN 50216-3 • • • EN 50464-1 EN 50464-1 EN 50464-1 EN 50464-1 EN-50216-4 • • • • • • • EN-50216-4 • • • • transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions LV single phase Busbar Bushings (optional) LV connection Flags Metric: from M20 to M55 Metric M12 Low voltage connection LV porcelain bushings for 420 V - B2* Rated Power Rated current Dimension - Metric d1 Material [kVA] 25 40 50 63 100 160 250 400 500 630 800 1000 1250 1600 2000 2500 [A] 250 250 250 250 250 250 630 630 1000 1000 1600 1600 2000 3150 3150 4000 M12 M12 M12 M12 M12 M12 M20 M20 M30 M30 M42 M42 M42 M48 M48 M55 Brass Brass Brass Brass Brass Brass Brass Brass Brass Brass Brass Brass Copper Copper Copper Copper M12 M12 M12 M12 M12 M12 M20 M20 M30 M30 M42 M42 M42 M48 M48 M55 Connections parts – LV Flags Metric e [mm] f0 [mm] Ø [mm] - - - - - - 32 32 32 32 40 40 40 40 40 70 40 40 40 40 40 40 60 60 60 60 100 100 100 120 120 150 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 18 LV single pole busbar bushings for indoor installation (optional) Rated Power Rated current Material [kVA] 25 40 50 63 100 160 250 400 500 630 800 1000 1250 1600 2000 2500 [A] - - - - - - 1600 1600 1600 1600 1600 1600 - - - - - - - - - - Copper Copper Copper Copper Copper Copper - - - - * Please contact Ormazabal for ohter secondary voltages and technical values above 2500 kVA. Medium voltage connection Connectors for mv plug-in bushings (not supplied with the transformer) Insulation [kV] 24 36 Type A elbow connector (250 A) Ref. EUROMOLD K-158LR Type B elbow connector (400 A) Ref. EUROMOLD M-400LR Type A straight connector (250 A) Ref. EUROMOLD K-152SR - 13 transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Type of transformers Conventional Transformers designed according to the requirements of the Ecodesign directive from the European Commission (No 548 / 2014) suitable for the European Union markets and worldwide where accepted. Characteristics 24 kV: A0 BK MV Porcelain Bushings MV Plug-In Bushings 250 - 2500 kVA Lifting Eyes MV Bushings F F LV Bushings MV Bushings J K J Draining and Sampling Device H H H Filling Device Thermometer Pocket Filling Device K J J Draining and Sampling Device H H H B MV Regulation Tap Changer A A MV Porcelain Bushings Up to 160 kVA F Lifting Eyes F MV Bushings Surge arresters support (Op) LV Bushings D1 80 C D2 140 Latching eyes Filling Device L H H H Draining and Sampling Device Thermometer Pocket (optional) B MV Regulation Tap Changer A 14 K J L Earth connection M12 Wheel Frames (skids) J L Earth connection M12 B MV Regulation Tap Changer Wheel Frames (skids) M Earth connection M12 M Wheel Frames (skids) L C C D3 D1 LV Bushings D2 F D2 Lifting Eyes F Thermometer Pocket transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Conventional Characteristics 24 kV: A0 BK Electrical characteristics 24 kV A0 BK Rated Power [kVA] Rated Voltage (Ur) 50 100 160 250 400 630 800 1000 1250 1600 2000 2500* <24 Primary [kV] 420 No-load Secondary [V] Vector Group Dyn11 No-Load Losses - P0 [W] List A0 90 145 210 300 430 600 650 770 950 1200 1450 1750 Load Losses - Pk [W] List Bk 875 1475 2000 2750 3850 5400 7000 9000 11000 14000 18000 22000 List A0 39 41 44 47 50 52 53 55 56 58 60 60 cosƒ=1 1.81 1.54 1.32 1.17 1.04 0.93 1.05 1.08 1.06 1.05 1.08 1.06 Short-Circuit Impedance (%) at 75°C Sound Power Level LwA [dB] Voltage drop at full load (%) load 100% Efficiency (%) load 75% 4 6 cosƒ=0.8 3.57 3.43 3.31 3.22 3.13 3.06 4.35 4.37 4.35 4.35 4.37 4.35 cosƒ=1 98.11 98.41 98.64 98.79 98.94 99.06 99.05 99.03 99.05 99.06 99.04 99.06 cosƒ=0.8 97.64 98.02 98.30 98.50 98.68 98.82 98.82 98.79 98.82 98.83 98.80 98.83 cosƒ=1 98.47 98.72 98.90 99.02 99.14 99.24 99.24 99.23 99.24 99.25 99.23 99.25 cosƒ=0.8 98.10 98.40 98.63 98.78 98.93 99.05 99.05 99.04 99.06 99.06 99.04 99.07 Dimensions [mm] 24 kV A0 BK Aluminum Windings Rated Power [kVA] A (Length) B (Width) C (Height to cover) D1 (Height to HV with porcelain bushings) D3 (Heigth to HV with plug-in-bushings) D2 (Height to LV with Flags) F (Distance betwen HV bushings) H (Distance betwen centre LV bushings) J (Wheel axis distance) K (Wheels width) Ø (Wheels) L (Wheel) Distance between pole mounting brackets 50 910 643 759 1144 849 919 275 80 520 40 125 110 530 100 940 733 767 1152 857 927 275 80 520 40 125 110 530 160 1046 743 873 1258 963 1033 275 80 520 40 125 110 530 250 1276 876 932 1317 1022 1166 275 150 670 40 125 110 – 400 1426 876 1032 1417 1122 1266 275 150 670 40 125 110 – 630 1526 936 1133 1518 1223 1394 275 150 670 40 125 110 – 800 1706 1046 1163 1548 1253 1496 275 150 670 40 125 110 – 1000 1776 1106 1163 1548 1253 1496 275 150 670 40 125 110 – 1250 1996 1256 1208 1593 1298 1541 275 150 820 70 200 165 – 1600 1940 1180 1540 1925 1630 1910 275 200 820 70 200 165 – 2000 1960 1160 1760 2145 1850 2130 275 200 820 70 200 165 – 2500 2060 1320 1810 2195 1900 2240 275 200 1070 70 200 165 – Oil volume (Litres) Total weight (Kg) 138 486 148 572 213 753 300 1075 377 1389 441 1817 572 2233 582 2342 692 2826 980 4120 1190 4970 1380 5830 Other dimensions on request. (*) Please contact Ormazabal for technical values above 2500 kVA. 15 transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Conventional Transformers designed according to the requirements of the Ecodesign directive from the European Commission (No 548 / 2014) suitable for the European Union markets and worldwide where accepted. Characteristics 24 kV: A0 CK MV Porcelain Bushings MV Plug-In Bushings 50 - 1000 kVA F HV BUSHINGS MVM-12 Bushings 250A F LIFTING LIFTING Lifting Eyes EYE-BOLTS Lifting Eyes EYE-BOLTS HIGH VOLTAGE BUSHINGS S24 F MV Bushings K180AR-1 250 A K J H L J H Filling FILLINGDevice DEVICE H H 2U N 2V 2U N B B 2W Off-Load Regualation OFF-LOAD REGULATION Tap Changer TAP CHANGER 1U 1V A 16 1W 1U 1V A D3 J ThermometerPOCKET Pocket THERMOMETER ThermometerPOCKET Pocket THERMOMETER 2V H J Earth connection M-12 EARTHING M12 TERMINAL 2W H Filling FILLINGDevice DEVICE K M Draining and DRAINING ANDSampling SAMPLING Device DEVICE M Draining and DRAINING ANDSampling SAMPLING Device DEVICE Earth connection M-12 EARTHING TERMINAL M12 Wheel WHEELFrames BASE Wheel Frames WHEEL BASE L C C D1 D2 D2 F 1W transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Conventional Characteristics 24 kV: A0 CK Electrical characteristics 24 kV A0 CK Rated Power [kVA] Rated Voltage (Ur) 50 100 160 250 400 630 800 1000 <24 Primary [kV] 420 No-load Secondary [V] Vector Group Dyn11 No-Load Losses - P0 [W] List A0 90 145 210 300 430 600 650 770 Load Losses - Pk [W] List Ck 1100 1750 2350 3250 4600 6500 8400 10 500 List A0 39 41 44 47 50 52 53 55 cosƒ=1 2.26 1.81 1.54 1.37 1.22 1.11 1.22 1.22 Short-Circuit Impedance (%) at 75°C Sound Power Level LwA [dB] Voltage drop at full load (%) load 100% Efficiency (%) load 75% 4 6 cosƒ=0.8 3.77 3.57 3.43 3.33 3.25 3.17 4.47 4.47 cosƒ=1 97.68 98.14 98.43 98.60 98.76 98.89 98.88 98.89 cosƒ=0.8 97.11 97.69 98.04 98.26 98.45 98.61 98.61 98.61 cosƒ=1 98.15 98.52 98.74 98.88 99.00 99.11 99.11 99.12 cosƒ=0.8 97.69 98.15 98.43 98.60 98.76 98.89 98.89 98.90 Dimensions [mm] 24 kV A0 CK Aluminum Windings 50 100 160 250 400 630 800 1000 A (Length) 1028 1020 1226 1070 1216 1496 1586 1686 B (Width) 728 750 786 833 876 936 946 1006 D1 (Height to HV with porcelain bushings and wheels) 1314 1365 1506 1538 1658 1722 1782 1850 C (Height to cover) 819 870 1011 1043 1163 1227 1287 1355 D2 (Height to LV without Flags) 955 1006 1147 1218 1338 1412 1502 1570 F (Distance betwen HV bushings) 275 275 275 275 275 275 275 275 H (Distance betwen centre LV bushings) 80 80 80 150 150 150 150 150 J (Wheel axis distance) 520 520 520 670 670 670 670 670 K (Wheels width) 40 40 40 40 40 40 40 40 Ø (Wheels) 125 125 125 125 125 125 125 125 Rated Power [kVA] L (Wheel) 110 110 110 110 110 110 110 110 Oil volume (Litres) 160 180 230 275 355 390 590 590 Total weight (Kg) 530 690 960 1150 1540 1990 2500 2730 Other dimensions on request. 17 transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Conventional Transformers designed according to the requirements of the Ecodesign directive from the European Commission (No 548 / 2014) suitable for the European Union markets and worldwide where accepted. Characteristics 36 kV: A0 BK MV Porcelain Bushings MV Plug-In Bushings 50 - 2500 kVA Lifting Eyes MV Bushings F F LV Bushings MV Bushings J H H H Filling Device A 18 Thermometer Pocket J Filling Device H H H J Draining and Sampling Device B MV Regulation Tap Changer A L K Earth connection M12 J B MV Regulation Tap Changer Draining and Sampling Device Wheel Frames (skids) M K Earth connection M12 M Wheel Frames (skids) L C C D3 D1 LV Bushings D2 F D2 Lifting Eyes F Thermometer Pocket transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Conventional Characteristics 36 kV: A0 BK Electrical characteristics 36 kV A0 BK Rated Power [kVA] Rated Voltage (Ur) 50 100 160 250 400 630 800 1000 1250 1600 2000 2500* <30 Primary [kV] 420 No-load Secondary [V] Vector Group Dyn11 No-Load Losses - P0 [W] List A0 103.5 166.7 241.5 345 494.5 690 747.5 885.5 1093 1380 1668 2013 Load Losses - Pk [W] List Bk 963 1623 2200 3025 4235 5940 7700 9900 12100 15400 19800 24200 List A0 39 41 44 47 50 52 53 55 56 58 60 68 cosƒ=1 2.01 1.71 1.47 1.30 1.15 1.04 1.14 1.17 1.14 1.14 1.17 1.14 Short-Circuit Impedance (%) at 75°C Sound Power Level LwA [dB] Voltage drop at full load (%) load 100% Efficiency (%) load 75% 4.5 6 cosƒ=0.8 4.00 3.85 3.70 3.61 3.51 3.44 4.41 4.43 4.41 4.41 4.43 4.41 cosƒ=1 97.91 98.24 98.50 98.67 98.83 98.96 98.96 98.93 98.96 98.96 98.94 98.96 cosƒ=0.8 97.40 97.81 98.13 98.34 98.54 98.70 98.70 98.67 98.70 98.71 98.68 98.71 cosƒ=1 98.31 98.58 98.78 98.92 99.05 99.15 99.16 99.15 99.16 99.17 99.15 99.17 cosƒ=0.8 97.89 98.23 98.48 98.65 98.82 98.94 98.95 98.94 98.96 98.96 98.94 98.97 Dimensions [mm] 36 kV A0 BK Aluminum Windings Rated Power [kVA] A (Length) B (Width) D1 (Height to HV with porcelain bushings and wheels) C (Height to cover) D2 (Height to LV with Flags) F (Distance betwen HV bushings) H (Distance betwen centre LV bushings) J (Wheel axis distance) K (Wheels width) Ø (Wheels) L (Wheel) 50 1040 758 1364 801 937 375 80 520 40 125 110 100 1040 763 1457 894 1030 375 80 520 40 125 110 160 1110 746 1587 1024 1160 375 80 520 40 125 110 250 1206 796 1668 1120 1295 375 150 670 40 125 110 400 1220 886 1770 1222 1397 375 150 670 40 125 110 630 1280 936 1831 1283 1468 375 150 670 40 125 110 800 1596 986 1837 1289 1504 375 150 670 40 125 110 1000 1596 996 1847 1299 1514 375 150 670 40 125 110 1250 1796 1056 2137 1534 1749 375 150 820 70 200 165 1600 1960 1220 1980 1540 1910 375 200 820 70 200 165 2000 1960 1180 2160 1720 2150 375 200 820 70 200 165 2500 2160 1340 2240 1800 2230 375 200 1070 70 200 165 Oil volume (Litres) Total weight (Kg) 200 653 215 849 270 1064 350 1331 410 1589 480 2143 610 2694 630 3098 805 3565 1000 4000 1190 4800 1460 5680 Other dimensions on request. (*) Please contact Ormazabal for technical values above 2500 kVA. 19 transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Conventional Transformers designed according to the requirements of the Ecodesign directive from the European Commission (No 548 / 2014) suitable for the European Union markets and worldwide where accepted. Characteristics 36 kV: A0 CK MV Porcelain Bushings MV Plug-In Bushings 50 - 1000 kVA F HV BUSHINGS MVM-12 Bushings 250A F LIFTING LIFTING Lifting Eyes EYE-BOLTS Lifting Eyes EYE-BOLTS HIGH VOLTAGE BUSHINGS S24 F MV Bushings K180AR-1 250 A K J H L J H Filling FILLINGDevice DEVICE H H 2U N 2V 2U N B B 2W Off-Load Regualation OFF-LOAD REGULATION Tap Changer TAP CHANGER 1U 1V A 20 1W 1U 1V A D3 J ThermometerPOCKET Pocket THERMOMETER ThermometerPOCKET Pocket THERMOMETER 2V H J Earth connection M-12 EARTHING M12 TERMINAL 2W H Filling FILLINGDevice DEVICE K M Draining and DRAINING ANDSampling SAMPLING Device DEVICE M Draining and DRAINING ANDSampling SAMPLING Device DEVICE Earth connection M-12 EARTHING TERMINAL M12 Wheel WHEELFrames BASE Wheel Frames WHEEL BASE L C C D1 D2 D2 F 1W transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Conventional Characteristics 36 kV: A0 CK Electrical characteristics 36 kV A0 CK Rated Power [kVA] Rated Voltage (Ur) 50 100 160 250 400 630 800 1000 <30 Primary [kV] 420 No-load Secondary [V] Vector Group Dyn11 No-Load Losses - P0 [W] List A0 103.5 166.7 241.5 345 494.5 690 747.5 885.5 Load Losses - Pk [W] List Ck 1210 1925 2585 3575 5060 7150 9240 11500 List A0 39 41 44 47 50 52 53 55 cosƒ=1 2.52 2.03 1.70 1.52 1.36 1.23 1.33 1.33 Short-Circuit Impedance (%) at 75°C Sound Power Level LwA [dB] Voltage drop at full load (%) load 100% Efficiency (%) load 75% 4.5 6 cosƒ=0.8 4.58 4.34 3.84 3.74 3.64 3.56 4.54 4.54 cosƒ=1 97.44 97.95 98.26 98.46 98.63 98.77 98.77 98.77 cosƒ=0.8 96.82 97.45 97.84 98.08 98.29 98.47 98.46 98.47 cosƒ=1 97.95 98.36 98.61 98.76 98.90 99.01 99.02 99.03 cosƒ=0.8 97.45 97.96 98.26 98.45 98.63 98.77 98.78 98.78 Dimensions [mm] 36 kV A0 CK Aluminum Windings 50 100 160 250 400 630 800 1000 A (Length) 1018 1010 1256 1150 1246 1616 1626 1736 B (Width) 743 748 796 788 886 1006 976 1060 D1 (Height to HV with porcelain bushings and wheels) 1431 1457 1603 1606 1716 1726 1840 1863 C (Height to cover) 868 894 1040 1058 1168 1178 1292 1315 D2 (Height to LV without Flags) 1004 1030 1176 1233 1343 1363 1507 1530 F (Distance betwen HV bushings) 375 375 375 375 375 375 375 375 H (Distance betwen centre LV bushings) 80 80 80 150 150 150 150 150 J (Wheel axis distance) 520 520 520 670 670 670 670 670 K (Wheels width) 40 40 40 40 40 40 40 40 Ø (Wheels) 125 125 125 125 125 125 125 125 Rated Power [kVA] L (Wheel) 110 110 110 110 110 110 110 110 Oil volume (Litres) 200 200 200 320 356 494 548 573 Total weight (Kg) 635 701 988 1122 1417 2040 2382 2768 Other dimensions on request. 21 transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Conventional Transformers designed according to the requirements of the IEC standard suitable for worldwide markets out of the European Union. Characteristics 24 kV: D0 CK MV Porcelain Bushings MV Plug-In Bushings 250 - 2500 kVA Lifting Eyes MV Bushings F F LV Bushings MV Bushings J K J Draining and Sampling Device H H H Filling Device Thermometer Pocket Filling Device J J Draining and Sampling Device H H H B MV Regulation Tap Changer A A MV Porcelain Bushings Up to 160 kVA F Lifting Eyes F MV Bushings Surge arresters support (Op) LV Bushings D1 80 C D2 140 Latching eyes Filling Device L H H H Draining and Sampling Device Thermometer Pocket (optional) B MV Regulation Tap Changer A 22 K J L Earth connection M12 Wheel Frames (skids) J L Earth connection M12 K B MV Regulation Tap Changer Wheel Frames (skids) M Earth connection M12 M Wheel Frames (skids) L C C D3 D1 LV Bushings D2 F D2 Lifting Eyes F Thermometer Pocket transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Conventional Characteristics 24 kV: D0 CK Electrical characteristics 24 kV D0 CK 50 Rated Power [kVA] Rated Voltage (Ur) 100 160 250 400 630 Vector Group No-Load Losses - P0 [W] Load Losses - Pk [W] Short-Circuit Impedance (%) at 75°C Sound Power Level LwA [dB] Voltage drop at full load (%) load 100% load 75% Efficiency (%) List D0 List Ck List D0 cosƒ=1 cosƒ=0.8 cosƒ=1 cosƒ=0.8 cosƒ=1 cosƒ=0.8 800 1000 1250 1600 2000 2500** Dyn11 1150 1400 8400 10500 6 6 66 68 1.22 1.22 4.47 4.47 98.82 98.82 98.53 98.53 99.03 99.04 98.79 98.80 1750 13500 6 69 1.25 4.49 98.79 98.50 99.01 98.77 2200 17000 6 71 1.24 4.48 98.81 98.52 99.03 98.79 2700 21000 6 73 1.22 4.47 98.83 98.54 99.04 98.81 3200 26500 6 76 1.23 4.47 98.83 98.54 99.04 98.81 < 24 420 Primary [kV] No-load Secondary [V] Yzn11/Dyn11* 145 260 1100 1750 4 4 50 54 2.26 1.81 3.77 3.57 97.57 98.03 96.98 97.55 98.00 98.37 97.52 97.97 375 2350 4 57 1.54 3.43 98.33 97.92 98.61 98.26 530 3250 4 60 1.37 3.33 98.51 98.15 98.76 98.45 750 4600 4 63 1.22 3.25 98.68 98.36 98.90 98.63 Dimensions [mm] 1030 6500 4 65 1.11 3.17 98.82 98.53 99.02 98.78 24 kV D0 CK Copper Windings Rated Power [kVA] A (Length) B (Width) C (Height to cover) D1 (Height to HV with porcelain bushings) D3 (Heigth to HV with plug-in-bushings) D2 (Height to LV with Flags) F (Distance betwen HV bushings) H (Distance betwen centre LV bushings) J (Wheel axis distance) K (Wheels width) Ø (Wheels) L (Wheel) Distance between pole mounting brackets 50 830 620 727 1112 817 887 275 80 520 40 125 110 530 100 940 723 799 1184 889 959 275 80 520 40 125 110 530 160 1126 738 761 1146 851 921 275 80 520 40 125 110 530 250 1286 886 821 1206 911 1055 275 150 670 40 125 110 – 400 1436 896 901 1286 991 1135 275 150 670 40 125 110 – 630 1516 916 982 1367 1072 1243 275 150 670 40 125 110 – 800 1806 1106 982 1367 1072 1315 275 150 670 40 125 110 – 1000 1866 1186 1042 1427 1132 1375 275 150 670 40 125 110 – 1250 1876 1166 1092 1477 1182 1425 275 150 820 70 200 165 – 1600 1796 1166 1557 1947 1646 1927 275 200 820 70 200 165 – 2000 1916 1216 1741 2126 1830 2111 275 200 820 70 200 165 – 2500** 2056 1416 1716 2146 1850 2191 275 200 1070 70 200 165 – Oil volume (Litres) Total weight (Kg) 101 424 155 581 196 755 255 1015 323 1307 412 1753 481 2163 522 2440 554 2758 951 3801 1164 4784 1309 5497 Rated Power [kVA] A (Length) B (Width) C (Height to cover) D1 (Height to HV with porcelain bushings) D3 (Heigth to HV with plug-in-bushings) D2 (Height to LV with Flags) F (Distance betwen HV bushings) H (Distance betwen centre LV bushings) J (Wheel axis distance) K (Wheels width) Ø (Wheels) L (Wheel) Distance between pole mounting brackets 50 910 643 759 1144 849 919 275 80 520 40 125 110 530 100 940 733 767 1152 857 927 275 80 520 40 125 110 530 160 1046 743 873 1258 963 1033 275 80 520 40 125 110 530 250 1276 876 932 1317 1022 1166 275 150 670 40 125 110 – 400 1426 876 1032 1417 1122 1266 275 150 670 40 125 110 – 630 1526 936 1133 1518 1223 1394 275 150 670 40 125 110 – 800 1706 1046 1163 1548 1253 1496 275 150 670 40 125 110 – 1000 1776 1106 1163 1548 1253 1496 275 150 670 40 125 110 – 1250 1996 1256 1208 1593 1298 1541 275 150 820 70 200 165 – 1600 1866 1256 1661 2046 1750 2031 275 200 820 70 200 165 – 2000 2116 1306 1771 2156 1860 2141 275 200 820 70 200 165 – 2500** 2286 1426 1831 2269 1966 2201 275 200 1070 70 200 165 – Oil volume (Litres) Total weight (Kg) 138 486 148 572 213 753 300 1075 377 1389 441 1817 572 2233 582 2342 692 2826 1005 3864 1182 4460 1520 5458 Aluminum Windings Other dimensions on request. (*) dimensions could be affected depending on the chosen vector group. (**) Please contact Ormazabal for technical values above 2500 kVA. 23 transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Conventional Transformers designed according to the requirements of the IEC standard suitable for worldwide markets out of the European Union. Characteristics 24 kV: C0 CK MV Porcelain Bushings MV Plug-In Bushings 250 - 2500 kVA Lifting Eyes MV Bushings F F LV Bushings MV Bushings J K J Draining and Sampling Device H H H Filling Device Thermometer Pocket Filling Device J J Draining and Sampling Device H H H B MV Regulation Tap Changer A A MV Porcelain Bushings Up to 160 kVA F Lifting Eyes F MV Bushings Surge arresters support (Op) LV Bushings D1 80 C D2 140 Latching eyes Filling Device L H H H Draining and Sampling Device Thermometer Pocket (optional) B MV Regulation Tap Changer A 24 K J L Earth connection M12 Wheel Frames (skids) J L Earth connection M12 K B MV Regulation Tap Changer Wheel Frames (skids) M Earth connection M12 M Wheel Frames (skids) L C C D3 D1 LV Bushings D2 F D2 Lifting Eyes F Thermometer Pocket transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Conventional Characteristics 24 kV: C0 CK Electrical characteristics 24 kV C0 CK 50 Rated Power [kVA] Rated Voltage (Ur) 100 160 250 400 630 Vector Group No-Load Losses - P0 [W] Load Losses - Pk [W] Short-Circuit Impedance (%) at 75°C Sound Power Level LwA [dB] Voltage drop at full load (%) load 100% load 75% Efficiency (%) List C0 List Ck List C0 cosƒ=1 cosƒ=0.8 cosƒ=1 cosƒ=0.8 cosƒ=1 cosƒ=0.8 800 1000 1250 1600 2000 2500** Dyn11 930 1100 8400 10500 6 6 61 63 1.22 1.22 4.47 4.47 98.85 98.85 98.56 98.57 99.07 99.07 98.84 98.85 1350 13500 6 64 1.25 4.49 98.83 98.54 99.06 98.82 1700 17000 6 66 1.24 4.48 98.84 98.56 99.07 98.84 2100 21000 6 68 1.22 4.47 98.86 98.58 99.08 98.85 2500 26500 6 71 1.23 4.47 98.85 98.57 99.08 98.85 < 24 420 Primary [kV] No-load Secondary [V] Yzn11/Dyn11* 125 210 1100 1750 4 4 47 49 2.26 1.81 3.77 3.57 97.61 98.08 97.03 97.61 98.06 98.43 97.58 98.05 300 2350 4 52 1.54 3.43 98.37 97.97 98.67 98.34 425 3250 4 55 1.37 3.33 98.55 98.20 98.81 98.52 610 4600 4 58 1.22 3.25 98.71 98.40 98.95 98.69 Dimensions [mm] 860 6500 4 60 1.11 3.17 98.85 98.56 99.05 98.82 24 kV C0 CK Copper Windings Rated Power [kVA] A (Length) B (Width) C (Height to cover) D1 (Height to HV with porcelain bushings) D3 (Heigth to HV with plug-in-bushings) D2 (Height to LV with Flags) F (Distance betwen HV bushings) H (Distance betwen centre LV bushings) J (Wheel axis distance) K (Wheels width) Ø (Wheels) L (Wheel) Distance between pole mounting brackets 50 830 620 727 1112 817 887 275 80 520 40 125 110 530 100 940 723 799 1184 889 959 275 80 520 40 125 110 530 160 1126 738 761 1146 851 921 275 80 520 40 125 110 530 250 1286 886 821 1206 911 1055 275 150 670 40 125 110 – 400 1436 896 901 1286 991 1135 275 150 670 40 125 110 – 630 1516 916 982 1367 1072 1243 275 150 670 40 125 110 – 800 1806 1106 982 1367 1072 1315 275 150 670 40 125 110 – 1000 1866 1186 1042 1427 1132 1375 275 150 670 40 125 110 – 1250 1876 1166 1092 1477 1182 1425 275 150 820 70 200 165 – 1600 1796 1166 1557 1942 1646 1927 275 200 820 70 200 165 – 2000 1776 1226 1681 2066 1770 1951 275 200 820 70 200 165 – 2500** 2106 1306 1706 2091 1795 2136 275 200 1070 70 200 165 – Oil volume (Litres) Total weight (Kg) 98 407 149 647 190 785 264 1082 316 1351 389 1792 487 2207 505 2509 732 2832 910 3865 1007 4379 1126 5150 Rated Power [kVA] A (Length) B (Width) C (Height to cover) D1 (Height to HV with porcelain bushings) D3 (Heigth to HV with plug-in-bushings) D2 (Height to LV with Flags) F (Distance betwen HV bushings) H (Distance betwen centre LV bushings) J (Wheel axis distance) K (Wheels width) Ø (Wheels) L (Wheel) Distance between pole mounting brackets 50 910 643 759 1144 849 919 275 80 520 40 125 110 530 100 940 733 767 1152 857 927 275 80 520 40 125 110 530 160 1046 743 873 1258 963 1033 275 80 520 40 125 110 530 250 1276 876 932 1317 1022 1166 275 150 670 40 125 110 – 400 1426 876 1032 1417 1122 1266 275 150 670 40 125 110 – 630 1526 936 1133 1518 1223 1394 275 150 670 40 125 110 – 800 1706 1046 1163 1548 1253 1496 275 150 670 40 125 110 – 1000 1776 1106 1163 1548 1253 1496 275 150 670 40 125 110 – 1250 1996 1256 1208 1593 1298 1541 275 150 820 70 200 165 – 1600 1856 1216 1651 2036 1740 2021 275 200 820 70 200 165 – 2000 2076 1286 1771 2156 1860 2141 275 200 820 70 200 165 – 2500** 2056 1456 1881 2319 2016 2311 275 200 1070 70 200 165 – Oil volume (Litres) Total weight (Kg) 131 510 141 601 202 791 285 1129 358 1458 419 1908 543 2345 553 2459 657 2967 946 3777 1181 4492 1413 5542 Aluminum Windings Other dimensions on request. (*) dimensions could be affected depending on the chosen vector group. (**) Please contact Ormazabal for technical values above 2500 kVA. 25 transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Conventional Transformers designed according to the requirements of the IEC standard suitable for worldwide markets out of the European Union. Characteristics 24 kV: C0 BK MV Porcelain Bushings MV Plug-In Bushings 250 - 2500 kVA Lifting Eyes MV Bushings F F LV Bushings MV Bushings J K J Draining and Sampling Device H H H Filling Device Thermometer Pocket Filling Device J J Draining and Sampling Device H H H B MV Regulation Tap Changer A A MV Porcelain Bushings Up to 160 kVA F Lifting Eyes F MV Bushings Surge arresters support (Op) LV Bushings D1 80 C D2 140 Latching eyes Filling Device L H H H Draining and Sampling Device Thermometer Pocket (optional) B MV Regulation Tap Changer A 26 K J L Earth connection M12 Wheel Frames (skids) J L Earth connection M12 K B MV Regulation Tap Changer Wheel Frames (skids) M Earth connection M12 M Wheel Frames (skids) L C C D3 D1 LV Bushings D2 F D2 Lifting Eyes F Thermometer Pocket transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Conventional Characteristics 24 kV: C0 BK Electrical characteristics 24 kV C0 BK 50 Rated Power [kVA] Rated Voltage (Ur) 100 160 250 400 630 Vector Group No-Load Losses - P0 [W] Load Losses - Pk [W] Short-Circuit Impedance (%) at 75°C Sound Power Level LwA [dB] Voltage drop at full load (%) load 100% load 75% Efficiency (%) List C0 List Bk List C0 cosƒ=1 cosƒ=0.8 cosƒ=1 cosƒ=0.8 cosƒ=1 cosƒ=0.8 800 1000 1250 1600 2000 2500** Dyn11 930 1100 7000 9000 6 6 61 63 1.05 1.08 4.35 4.37 99.02 99.00 98.78 98.75 99.20 99.19 99.00 98.98 1350 11000 6 64 1.06 4.35 99.02 98.78 99.20 99.00 1700 14000 6 66 1.05 4.35 99.03 98.79 99.21 99.01 2100 18000 6 68 1.08 4.37 99.00 98.76 99.19 98.99 2500 22000 6 71 1.06 4.35 99.03 98.79 99.21 99.02 < 24 420 Primary [kV] No-load Secondary [V] Yzn11/Dyn11* 125 210 875 1475 4 4 47 49 1.81 1.54 3.57 3.43 98.04 98.34 97.56 97.94 98.38 98.63 97.98 98.30 300 2000 4 52 1.32 3.31 98.58 98.23 98.83 98.54 425 2750 4 55 1.17 3.22 98.75 98.44 98.96 98.70 610 3850 4 58 1.04 3.13 98.90 98.63 99.08 98.86 Dimensions [mm] 860 5400 4 60 0.93 3.06 99.02 98.77 99.18 98.98 24 kV C0 BK Copper Windings Rated Power [kVA] A (Length) B (Width) C (Height to cover) D1 (Height to HV with porcelain bushings) D3 (Heigth to HV with plug-in-bushings) D2 (Height to LV with Flags) F (Distance betwen HV bushings) H (Distance betwen centre LV bushings) J (Wheel axis distance) K (Wheels width) Ø (Wheels) L (Wheel) Distance between pole mounting brackets 50 890 623 752 1137 842 912 275 80 520 40 125 110 530 100 940 723 737 1122 827 897 275 80 520 40 125 110 530 160 1126 738 761 1146 851 921 275 80 520 40 125 110 530 250 1286 886 821 1206 911 1055 275 150 670 40 125 110 – 400 1436 896 901 1286 991 1135 275 150 670 40 125 110 – 630 1466 916 1052 1437 1142 1313 275 150 670 40 125 110 – 800 1866 1186 1042 1427 1132 1375 275 150 670 40 125 110 – 1000 1866 1186 1042 1427 1132 1375 275 150 670 40 125 110 – 1250 1836 1126 1202 1587 1292 1535 275 150 820 70 200 165 – 1600 1796 1166 1657 2042 1746 2027 275 200 820 70 200 165 – 2000 1836 1216 1741 2126 1830 2111 275 200 820 70 200 165 – 2500** 2076 1366 1716 2101 1805 2146 275 200 1070 70 200 165 – Oil volume (Litres) Total weight (Kg) 122 502 144 579 189 815 244 1083 313 1414 385 1911 547 2526 498 2632 596 3035 938 4255 1209 4975 1131 5405 Rated Power [kVA] A (Length) B (Width) C (Height to cover) D1 (Height to HV with porcelain bushings) D3 (Heigth to HV with plug-in-bushings) D2 (Height to LV with Flags) F (Distance betwen HV bushings) H (Distance betwen centre LV bushings) J (Wheel axis distance) K (Wheels width) Ø (Wheels) L (Wheel) Distance between pole mounting brackets 50 910 643 759 1144 849 919 275 80 520 40 125 110 530 100 980 743 757 1142 847 917 275 80 520 40 125 110 530 160 1040 758 893 1278 983 1053 275 80 520 40 125 110 530 250 1296 896 1001 1386 1091 1235 275 150 670 40 125 110 – 400 1446 886 1091 1476 1181 1325 275 150 670 40 125 110 – 630 1516 906 1192 1577 1282 1453 275 150 670 40 125 110 – 800 1886 1166 1173 1558 1263 1506 275 150 670 40 125 110 – 1000 1886 1166 1173 1558 1263 1506 275 150 670 40 125 110 – 1250 1996 1256 1248 1633 1338 1581 275 150 820 70 200 165 – 1600 1736 1216 1701 2086 1790 2071 275 200 820 70 200 165 – 2000 2066 1266 1781 2166 1870 2151 275 200 820 70 200 165 – 2500** 2236 1306 1826 2264 1961 2256 275 200 1070 70 200 165 – Oil volume (Litres) Total weight (Kg) 137 493 165 580 213 754 315 1195 368 1518 475 2136 598 2579 589 2570 716 2908 964 3796 1168 4741 1449 5573 Aluminum Windings Other dimensions on request. (*) dimensions could be affected depending on the chosen vector group. (**) Please contact Ormazabal for technical values above 2500 kVA. 27 transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Conventional Transformers designed according to the requirements of the IEC standard suitable for worldwide markets out of the European Union. Characteristics 24 kV: B0 BK MV Porcelain Bushings MV Plug-In Bushings 250 - 2500 kVA Lifting Eyes MV Bushings F F LV Bushings MV Bushings J K J Draining and Sampling Device H H H Filling Device Thermometer Pocket Filling Device J J Draining and Sampling Device H H H B MV Regulation Tap Changer A A MV Porcelain Bushings Up to 160 kVA F Lifting Eyes F MV Bushings Surge arresters support (Op) LV Bushings D1 80 C D2 140 Latching eyes Filling Device L H H H Draining and Sampling Device Thermometer Pocket (optional) B MV Regulation Tap Changer A 28 K J L Earth connection M12 Wheel Frames (skids) J L Earth connection M12 K B MV Regulation Tap Changer Wheel Frames (skids) M Earth connection M12 M Wheel Frames (skids) L C C D3 D1 LV Bushings D2 F D2 Lifting Eyes F Thermometer Pocket transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Conventional Characteristics 24 kV: B0 BK Electrical characteristics 24 kV B0 BK 50 Rated Power [kVA] Rated Voltage (Ur) 100 160 250 400 630 Vector Group No-Load Losses - P0 [W] Load Losses - Pk [W] Short-Circuit Impedance (%) at 75°C Sound Power Level LwA [dB] Voltage drop at full load (%) load 100% load 75% Efficiency (%) List B0 List Bk List B0 cosƒ=1 cosƒ=0.8 cosƒ=1 cosƒ=0.8 cosƒ=1 cosƒ=0.8 800 1000 1250 1600 2000 2500** Dyn11 800 940 7000 9000 6 6 56 58 1.05 1.08 4.35 4.37 99.03 99.02 98.80 98.77 99.22 99.21 99.02 99.01 1150 11000 6 59 1.06 4.35 99.04 98.80 99.22 99.03 1450 14000 6 61 1.05 4.35 99.04 98.81 99.23 99.04 1800 18000 6 63 1.08 4.37 99.02 98.78 99.21 99.02 2150 26500 6 66 1.23 4.47 98.87 98.59 99.10 98.88 < 24 420 Primary [kV] No-load Secondary [V] Yzn11/Dyn11* 110 180 875 1475 4 4 42 44 1.81 1.54 3.57 3.43 98.07 98.37 97.60 97.97 98.42 98.67 98.03 98.35 260 2000 4 47 1.32 3.31 98.61 98.27 98.86 98.58 360 2750 4 50 1.17 3.22 98.77 98.47 98.99 98.74 520 3850 4 53 1.04 3.13 98.92 98.65 99.11 98.89 Dimensions [mm] 730 5400 4 55 0.93 3.06 99.04 98.80 99.21 99.01 24 kV B0 BK Copper Windings Rated Power [kVA] A (Length) B (Width) C (Height to cover) D1 (Height to HV with porcelain bushings) D3 (Heigth to HV with plug-in-bushings) D2 (Height to LV with Flags) F (Distance betwen HV bushings) H (Distance betwen centre LV bushings) J (Wheel axis distance) K (Wheels width) Ø (Wheels) L (Wheel) Distance between pole mounting brackets 50 865 620 757 1142 847 917 275 80 520 40 125 110 530 100 940 723 779 1164 869 939 275 80 520 40 125 110 530 160 1066 738 803 1188 893 963 275 80 520 40 125 110 530 250 1226 866 901 1286 991 1135 275 150 670 40 125 110 – 400 1376 896 921 1306 1011 1155 275 150 670 40 125 110 – 630 1446 926 1053 1438 1143 1314 275 150 670 40 125 110 – 800 1666 986 1053 1438 1143 1386 275 150 670 40 125 110 – 1000 1866 1186 1112 1497 1202 1445 275 150 670 40 125 110 – 1250 1606 1186 1163 1548 1253 1496 275 150 820 70 200 165 – 1600 1616 1236 1611 1996 1700 1981 275 200 820 70 200 165 – 2000 1866 1216 1659 2044 1748 2029 275 200 820 70 200 165 – 2500** 2156 1366 1726 2111 1815 2156 275 200 1070 70 200 165 – Oil volume (Litres) Total weight (Kg) 118 491 147 620 191 774 231 1102 290 1361 412 1859 466 2468 526 2761 597 2966 834 4130 883 4256 1228 5559 Rated Power [kVA] A (Length) B (Width) C (Height to cover) D1 (Height to HV with porcelain bushings) D3 (Heigth to HV with plug-in-bushings) D2 (Height to LV with Flags) F (Distance betwen HV bushings) H (Distance betwen centre LV bushings) J (Wheel axis distance) K (Wheels width) Ø (Wheels) L (Wheel) Distance between pole mounting brackets 50 930 648 759 1144 849 919 275 80 520 40 125 110 530 100 980 753 776 1161 866 936 275 80 520 40 125 110 530 160 1030 763 873 1258 963 1033 275 80 520 40 125 110 530 250 1296 896 1001 1386 1091 1235 275 150 670 40 125 110 – 400 1326 946 1111 1496 1201 1345 275 150 670 40 125 110 – 630 1356 986 1202 1587 1292 1463 275 150 670 40 125 110 – 800 1756 1026 1223 1608 1313 1556 275 150 670 40 125 110 – 1000 1796 976 1213 1598 1303 1546 275 150 670 40 125 110 – 1250 1806 1046 1369 1754 1459 1702 275 150 820 70 200 165 – 1600 1876 1136 1721 2106 1810 2091 275 200 820 70 200 165 – 2000 2076 1256 1781 2166 1870 2151 275 200 820 70 200 165 – 2500** 2216 1296 1856 2294 1991 2286 275 200 1070 70 200 165 – Oil volume (Litres) Total weight (Kg) 140 527 172 666 199 794 327 1166 388 1526 486 2074 644 2584 591 2568 749 3266 973 3979 1188 4623 1463 5805 Aluminum Windings Other dimensions on request. (*) dimensions could be affected depending on the chosen vector group. (**) Please contact Ormazabal for technical values above 2500 kVA. 29 transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Conventional Transformers designed according to the requirements of the IEC standard suitable for worldwide markets out of the European Union. Characteristics 24 kV: E0 DK MV Porcelain Bushings MV Plug-In Bushings 250 - 2500 kVA Lifting Eyes MV Bushings F F LV Bushings MV Bushings J K J Draining and Sampling Device H H H Filling Device Thermometer Pocket Filling Device J J Draining and Sampling Device H H H B MV Regulation Tap Changer A A MV Porcelain Bushings Up to 160 kVA F Lifting Eyes F MV Bushings Surge arresters support (Op) LV Bushings D1 80 C D2 140 Latching eyes Filling Device L H H H Draining and Sampling Device Thermometer Pocket (optional) B MV Regulation Tap Changer A 30 K J L Earth connection M12 Wheel Frames (skids) J L Earth connection M12 K B MV Regulation Tap Changer Wheel Frames (skids) M Earth connection M12 M Wheel Frames (skids) L C C D3 D1 LV Bushings D2 F D2 Lifting Eyes F Thermometer Pocket transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Conventional Characteristics 24 kV: E0 DK Electrical characteristics 24 kV E0 DK 50 Rated Power [kVA] Rated Voltage (Ur) 100 160 250 400 630 Vector Group No-Load Losses - P0 [W] Load Losses - Pk [W] Short-Circuit Impedance (%) at 75°C Sound Power Level LwA [dB] Voltage drop at full load (%) load 100% load 75% Efficiency (%) List E0 List Dk List E0 cosƒ=1 cosƒ=0.8 cosƒ=1 cosƒ=0.8 cosƒ=1 cosƒ=0.8 800 1000 1250 1600 2000 2500** Dyn11 1400 1700 10500 13000 6 6 71 73 1.48 1.47 4.64 4.63 98.53 98.55 98.17 98.20 98.80 98.81 98.50 98.52 2100 16000 6 74 1.45 4.62 98.57 98.22 98.83 98.54 20000 2600 6 76 1.42 4.60 98.61 98.27 98.86 98.58 26000 3100 6 78 1.47 4.63 98.57 98.21 98.83 98.54 32000 3500 6 81 1.45 4.62 98.60 98.26 98.87 98.59 < 24 420 Primary [kV] No-load Secondary [V] Yzn11/Dyn11* 190 320 1350 2150 4 4 55 59 2.76 2.21 4.33 3.75 97.01 97.59 96.29 97.00 97.53 98.00 96.93 97.51 460 3100 4 62 2.00 3.68 97.82 97.29 98.20 97.76 650 4200 4 65 1.75 3.54 98.10 97.63 98.42 98.03 930 6000 4 68 1.57 3.45 98.30 97.88 98.59 98.24 Dimensions [mm] 1300 8400 4 70 1.40 3.35 98.48 98.11 98.74 98.43 24 kV E0 DK Copper Windings Rated Power [kVA] A (Length) B (Width) C (Height to cover) D1 (Height to HV with porcelain bushings) D3 (Heigth to HV with plug-in-bushings) D2 (Height to LV with Flags) F (Distance betwen HV bushings) H (Distance betwen centre LV bushings) J (Wheel axis distance) K (Wheels width) Ø (Wheels) L (Wheel) Distance between pole mounting brackets 50 830 620 749 1134 839 909 275 80 520 40 125 110 530 100 940 743 809 1194 899 969 275 80 520 40 125 110 530 160 1126 738 769 1154 859 929 275 80 520 40 125 110 530 250 1386 886 811 1196 901 1045 275 150 670 40 125 110 – 400 1476 976 881 1266 971 1115 275 150 670 40 125 110 – 630 1596 1076 992 1377 1082 1253 275 150 670 40 125 110 – 800 1866 1166 970 1355 1060 1303 275 150 670 40 125 110 – 1000 1866 1186 1092 1477 1182 1425 275 150 670 40 125 110 – 1250 2036 1326 1127 1512 1217 1460 275 150 820 70 200 165 – 1600 2096 1356 1561 1946 1650 1931 275 200 820 70 200 165 – 2000 2116 1396 1611 1996 1700 1981 275 200 820 70 200 165 – 2500** 2176 1386 1717 2102 1806 2147 275 200 1070 70 200 165 – Oil volume (Litres) Total weight (Kg) 105 418 162 596 201 742 270 1034 343 1350 422 1804 515 2094 573 2428 620 2754 915 3671 1078 4415 1134 4856 Rated Power [kVA] A (Length) B (Width) C (Height to cover) D1 (Height to HV with porcelain bushings) D3 (Heigth to HV with plug-in-bushings) D2 (Height to LV with Flags) F (Distance betwen HV bushings) H (Distance betwen centre LV bushings) J (Wheel axis distance) K (Wheels width) Ø (Wheels) L (Wheel) Distance between pole mounting brackets 50 990 663 740 1125 830 900 275 80 520 40 125 110 530 100 1020 758 769 1154 859 929 275 80 520 40 125 110 530 160 1046 743 873 1258 963 1033 275 80 520 40 125 110 530 250 1276 876 932 1317 1022 1166 275 150 670 40 125 110 – 400 1426 876 1032 1417 1122 1266 275 150 670 40 125 110 – 630 1606 1016 1133 1518 1223 1394 275 150 670 40 125 110 – 800 1706 1046 1163 1548 1253 1496 275 150 670 40 125 110 – 1000 1816 1146 1183 1568 1273 1516 275 150 670 40 125 110 – 1250 1996 1256 1248 1633 1338 1581 275 150 820 70 200 165 – 1600 1946 1206 1751 2136 1840 2121 275 200 820 70 200 165 – 2000 2136 1376 1671 2056 1760 2041 275 200 820 70 200 165 – 2500** 2336 1506 1811 2249 1946 2241 275 200 1070 70 200 165 n/a Oil volume (Litres) Total weight (Kg) 170 539 206 590 218 714 311 962 388 1324 468 1807 590 2150 617 2359 765 2839 1114 3980 1035 4174 1494 5425 Aluminum Windings Other dimensions on request. (*) dimensions could be affected depending on the chosen vector group. (**) Please contact Ormazabal for technical values above 2500 kVA. 31 transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Conventional Transformers designed according to the requirements of the IEC standard suitable for worldwide markets out of the European Union. Characteristics 36 kV: B036 BK36 MV Porcelain Bushings MV Plug-In Bushings 250 - 2500 kVA Lifting Eyes MV Bushings F F LV Bushings MV Bushings J K J Draining and Sampling Device H H H Filling Device Thermometer Pocket Filling Device J J Draining and Sampling Device H H H B MV Regulation Tap Changer A A MV Porcelain Bushings Up to 160 kVA F Lifting Eyes F MV Bushings Surge arresters support (Op) LV Bushings D1 80 C D2 140 Latching eyes Filling Device L H H H Draining and Sampling Device Thermometer Pocket (optional) B MV Regulation Tap Changer A 32 K J L Earth connection M12 Wheel Frames (skids) J L Earth connection M12 K B MV Regulation Tap Changer Wheel Frames (skids) M Earth connection M12 M Wheel Frames (skids) L C C D3 D1 LV Bushings D2 F D2 Lifting Eyes F Thermometer Pocket transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Conventional Characteristics 36 kV: B036 BK36 Electrical characteristics 36 kV B036 BK36 50 Rated Power [kVA] Rated Voltage (Ur) 100 160 250 400 630 Vector Group No-Load Losses - P0 [W] Load Losses - Pk [W] Short-Circuit Impedance (%) at 75°C Sound Power Level LwA [dB] Voltage drop at full load (%) load 100% load 75% Efficiency (%) List B036 List Bk36 List B036 cosƒ=1 cosƒ=0.8 cosƒ=1 cosƒ=0.8 cosƒ=1 cosƒ=0.8 800 1000 1250 1600 2000 2500** Dyn11 1500 1700 8400 10500 6 6 68 68 1.22 1.22 4.47 4.47 98.78 98.79 98.48 98.50 98.97 99.00 98.72 98.75 2100 13500 6 70 1.25 4.49 98.77 98.46 98.98 98.72 2600 1700 6 71 1.24 4.48 98.79 98.49 99.00 98.75 3150 21000 6 73 1.22 4.47 98.81 98.51 99.01 98.77 3800 26500 6 76 1.18 4.44 98.88 98.61 99.09 98.86 <30 420 Primary [kV] No-load Secondary [V] Yzn11/Dyn11* 190 320 1250 1950 4.5 4.5 52 56 2.57 2.03 4.26 4.01 97.20 97.78 96.53 97.24 97.67 98.15 97.11 97.69 460 2550 4.5 59 1.68 3.83 98.15 97.70 98.45 98.06 650 3500 4.5 62 1.49 3.72 98.37 97.97 98.62 98.28 930 4900 4.5 65 1.32 3.62 98.56 98.21 98.79 98.49 Dimensions [mm] 1300 6500 4.5 67 1.13 3.50 98.78 98.48 98.96 98.71 36 kV B036 BK36 Copper Windings Rated Power [kVA] A (Length) B (Width) C (Height to cover) D1 (Height to HV with porcelain bushings) D3 (Heigth to HV with plug-in-bushings) D2 (Height to LV with Flags) F (Distance betwen HV bushings) H (Distance betwen centre LV bushings) J (Wheel axis distance) K (Wheels width) Ø (Wheels) L (Wheel) Distance between pole mounting brackets 50 890 623 727 1180 862 887 375 80 520 40 125 110 530 100 940 723 799 1252 934 959 375 80 520 40 125 110 530 160 1126 738 761 1214 896 921 375 80 520 40 125 110 530 250 1286 886 821 1259 956 1055 375 150 670 40 125 110 – 400 1436 896 901 1339 1036 1135 375 150 670 40 125 110 – 630 1516 916 982 1420 1117 1243 375 150 670 40 125 110 – 800 1806 1106 982 1420 1117 1315 375 150 670 40 125 110 – 1000 1866 1186 1042 1480 1177 1375 375 150 670 40 125 110 – 1250 1876 1166 1092 1530 1227 1425 375 150 820 70 200 165 – 1600 1956 1236 1491 1929 1626 1861 375 200 820 70 200 165 – 2000 1976 1256 1646 2084 1781 2016 375 200 820 70 200 165 – 2500** 2236 1376 1711 2149 1846 2141 375 200 1070 70 200 165 – Oil volume (Litres) Total weight (Kg) 122 446 156 560 195 745 263 1018 335 1306 403 1776 475 2125 514 2455 559 2763 865 3743 1026 4221 1248 5422 Rated Power [kVA] A (Length) B (Width) C (Height to cover) D1 (Height to HV with porcelain bushings) D3 (Heigth to HV with plug-in-bushings) D2 (Height to LV with Flags) F (Distance betwen HV bushings) H (Distance betwen centre LV bushings) J (Wheel axis distance) K (Wheels width) Ø (Wheels) L (Wheel) Distance between pole mounting brackets 50 990 663 740 1193 875 900 375 80 520 40 125 110 530 100 1000 763 791 1244 926 951 375 80 520 40 125 110 530 160 1076 743 873 1326 1008 1033 375 80 520 40 125 110 530 250 1276 876 932 1370 1067 1166 375 150 670 40 125 110 – 400 1426 876 1032 1470 1167 1266 375 150 670 40 125 110 – 630 1526 936 1133 1571 1268 1394 375 150 670 40 125 110 – 800 1706 1046 1163 1601 1298 1496 375 150 670 40 125 110 – 1000 1776 1106 1203 1641 1338 1536 375 150 670 40 125 110 – 1250 2016 1236 1227 1665 1362 1560 375 150 820 70 200 165 – 1600 1906 1216 1661 2099 1796 2031 375 200 820 70 200 165 – 2000 2036 1286 1791 2229 1926 2161 375 200 820 70 200 165 – 2500** 2236 1416 1831 2269 1966 2261 375 200 1070 70 200 165 – Oil volume (Litres) Total weight (Kg) 167 544 167 544 225 730 299 1051 382 1336 442 1782 589 2172 601 2507 788 2914 984 3781 1189 4610 1411 5415 Aluminum Windings Other dimensions on request. (*) dimensions could be affected depending on the chosen vector group. (**) Please contact Ormazabal for technical values above 2500 kVA. 33 transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Conventional Transformers designed according to the requirements of the IEC standard suitable for worldwide markets out of the European Union. Characteristics 36 kV: A036 AK36 MV Porcelain Bushings MV Plug-In Bushings 250 - 2500 kVA Lifting Eyes MV Bushings F F LV Bushings MV Bushings J K J Draining and Sampling Device H H H Filling Device Thermometer Pocket Filling Device J J Draining and Sampling Device H H H B MV Regulation Tap Changer A A MV Porcelain Bushings Up to 160 kVA F Lifting Eyes F MV Bushings Surge arresters support (Op) LV Bushings D1 80 C D2 140 Latching eyes Filling Device L H H H Draining and Sampling Device Thermometer Pocket (optional) B MV Regulation Tap Changer A 34 K J L Earth connection M12 Wheel Frames (skids) J L Earth connection M12 K B MV Regulation Tap Changer Wheel Frames (skids) M Earth connection M12 M Wheel Frames (skids) L C C D3 D1 LV Bushings D2 F D2 Lifting Eyes F Thermometer Pocket transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Conventional Characteristics 36 kV: A036 AK36 Electrical characteristics 36 kV A036 AK36 50 Rated Power [kVA] Rated Voltage (Ur) 100 160 250 400 630 Vector Group No-Load Losses - P0 [W] Load Losses - Pk [W] Short-Circuit Impedance (%) at 75°C Sound Power Level LwA [dB] Voltage drop at full load (%) load 100% load 75% Efficiency (%) List A036 List Ak36 List A036 cosƒ=1 cosƒ=0.8 cosƒ=1 cosƒ=0.8 cosƒ=1 cosƒ=0.8 800 1000 1250 1600 2000 2500** Dyn11 1300 1450 7000 8900 6 6 66 67 1.05 1.07 4.35 4.36 99.02 98.98 98.78 98.72 99.20 99.15 99.00 98.94 1750 11500 6 68 1.10 4.38 98.95 98.69 99.13 98.92 2200 14500 6 69 1.08 4.37 98.97 98.71 99.14 98.93 2700 18000 6 71 1.08 4.37 98.98 98.72 99.15 98.94 3200 22500 6 73 1.08 4.37 98.98 98.73 99.16 98.95 <30 420 Primary [kV] No-load Secondary [V] Yzn11/Dyn11* 160 270 1050 1650 4.5 4.5 50 54 2.18 1.74 4.09 3.86 97.64 98.12 97.06 97.66 98.04 98.43 97.56 98.04 390 2150 4.5 57 1.44 3.69 98.44 98.05 98.68 98.36 550 3000 4.5 60 1.29 3.60 98.60 98.26 98.82 98.53 790 4150 4.5 63 1.13 3.50 98.78 98.48 98.97 98.71 Dimensions [mm] 1100 5500 4.5 65 0.97 3.39 98.96 98.71 99.12 98.90 36 kV A036 AK36 Copper Windings Rated Power [kVA] A (Length) B (Width) C (Height to cover) D1 (Height to HV with porcelain bushings) D3 (Heigth to HV with plug-in-bushings) D2 (Height to LV with Flags) F (Distance betwen HV bushings) H (Distance betwen centre LV bushings) J (Wheel axis distance) K (Wheels width) Ø (Wheels) L (Wheel) Distance between pole mounting brackets 50 1040 633 761 1214 896 921 375 80 520 40 125 110 530 100 940 733 719 1172 854 879 375 80 520 40 125 110 530 160 1126 738 801 1254 936 961 375 80 520 40 125 110 530 250 1226 866 901 1339 1036 1135 375 150 670 40 125 110 – 400 1436 896 901 1339 1036 1135 375 150 670 40 125 110 – 630 1516 946 1052 1490 1187 1313 375 150 670 40 125 110 – 800 1866 1136 1052 1490 1187 1333 375 150 670 40 125 110 – 1000 1866 1186 1112 1550 1247 1445 375 150 670 40 125 110 – 1250 1836 1126 1272 1710 1407 1605 375 150 820 70 200 165 – 1600 1816 1196 1657 2095 1792 2027 375 200 820 70 200 165 – 2000 2026 1226 1657 2095 1792 2027 375 200 820 70 200 165 – 2500** 2116 1266 1767 2205 1902 2197 375 200 1070 70 200 165 – Oil volume (Litres) Total weight (Kg) 180 521 151 572 210 779 235 1040 319 1419 450 1976 540 2.422 550 2612 634 3055 1015 4340 1025 4570 1289 5526 Rated Power [kVA] A (Length) B (Width) C (Height to cover) D1 (Height to HV with porcelain bushings) D3 (Heigth to HV with plug-in-bushings) D2 (Height to LV with Flags) F (Distance betwen HV bushings) H (Distance betwen centre LV bushings) J (Wheel axis distance) K (Wheels width) Ø (Wheels) L (Wheel) Distance between pole mounting brackets 50 980 653 740 1193 875 900 275 80 520 40 125 110 530 100 980 758 767 1220 902 927 275 80 520 40 125 110 530 160 1040 768 893 1346 1028 1053 275 80 520 40 125 110 530 250 1296 896 1001 1439 1136 1235 275 150 670 40 125 110 – 400 1326 946 1091 1529 1226 1325 275 150 670 40 125 110 – 630 1396 1046 1142 1580 1277 1403 275 150 670 40 125 110 – 800 1766 1076 1224 1662 1359 1557 275 150 670 40 125 110 – 1000 1886 1166 1173 1611 1308 1506 275 150 670 40 125 110 – 1250 1976 1196 1301 1739 1436 1634 275 150 820 70 200 165 – 1600 1946 1176 1701 2139 1836 2071 275 200 820 70 200 165 – 2000 2096 1256 1781 2219 1916 2151 275 200 820 70 200 165 – 2500** 2276 1366 1821 2259 1956 2251 275 200 1070 70 200 165 – Oil volume (Litres) Total weight (Kg) 150 552 183 633 233 762 331 1132 396 1440 472 1932 623 2338 590 2594 831 3239 1033 3986 1208 4668 1492 5933 Aluminum Windings Other dimensions on request. (*) dimensions could be affected depending on the chosen vector group. (**) Please contact Ormazabal for technical values above 2500 kVA. 35 transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Non-conventional transforma.fine transforma.tpc Extended range solutions Small-sized compact transformers, transforma.fine, that are highly resistant to high temperatures, are incorporated in the wide range of transformers immersed in dielectric liquid, both mineral oil or natural biodegradable fluid, transforma.organic. Self-protected transformers, transforma.tpc, immersed in dielectric liquid, both mineral oil or natural biodegradable fluid, transforma.organic. for indoor or on-pole uses, mainly for rural network applications. OLTC (On load tap changer) They are characterised by their high capability to adapt to reduced spaces and for use in specific applications such as wind power generation. Standards IEC60076-1 IEC60076-14 IEC60076-16 Technical features Up to 36 kV Up to 5000 kVA Width ≥846 mm More information: CA409EN. They are characterised by their resistance against overloads, the low losses and reduced noise levels. Standards IEC 60076-13 HN 52-S-24 Technical features Up to 36 kV Up to 630 kVA (transformer substation) Up to 160 kVA (pole) HV fused protection and switching performance. More information: CA120FR & CA337FR. Transformers that solve the problem of voltage unbalance due to distributed generation. Distribution substations with small solar or small wind are exposed to big voltage variations between days with low consumption and high generation (sunny or windy days) and days with low generation and high consumption. It is necesary a voltage regulation to allow the system work properly. Standards IEC 60076 series Technical features Up to 1000 kVA and 24 kV Photovoltaic applications Step-up transformers for photovoltaic applications featured by the multiple energitations carried out per year and low losses. Multiple windings to be feeded by several inverters (Dy11y11, Ynd11d11, Dy11y11y11...) so that the number of transformers is reduced. Standards IEC60076-1 EN 50464-1 Technical features Up to 52 kV Up to 4000 kVA 36 transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Containerized generators Transformers mutti voltage and multi frequency that allow the adaptation of the electrical supply coming from a generator according to the characteristics of any country. The different voltages in MV are obtained by: ●● Different LV generation voltages ●● Different vector groups (changing the vector group tap changer) ●● Different tapping (changing the voltage selection tap changer) ●● Different % adjustment over the main tap (changing the voltage changeover tap changer) Standards High voltage shore connection systems (HVSC) Auxiliary services in nuclear power plants Transformers with a very balanced voltage (voltage variations <3%) for complete power solutions to supply energy to ships in harbours (HV shore connection systems). Transformers specifically designed for high requisite environments, such as auxiliary circuits in nuclear power plants, where safety, long endurance, robustness, continuity of service and high performance are mandatory. The solution is based in a containerized compact substation where the transformer is installed. This turn-key solution is characterized by: ●● On load voltage regulation ●● Plug and play concept: Extensible cable to plug the facility to ships ●● Advanced communication protocol between ship and substation IEC60076 Standards Technical features IEC60076 Up to 5000 kVA and 36 kV ISO80005 Technical features Up to 10 000 kVA and 52 kV Extended features ●● Technical values ●● >36 kV ●● > 5000 kVA ●● Direct connection to Ormazabal cubicles ●● Design for ultra-compact Ormazabal substations ●● High temperature transformers 37 transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Handling, installation and after sales Handling Indoor Conventional transformers have fourbracing eyes located on the corners for transportation and so prevent damage to the cooling elements. Inside mobile / prefabricated transformer substations The transformers can be transported and handled using a forklift truck, crane or their own wheels: Forklift truck Transformer fitted and fastened to a pallet. ●● Turn-key solutions (fully assembling, testing and transportation from factory) ●● Uniform quality ●● Significant reduction of installation costs and time ●● Dielectric liquid collector ●● Possibility of transformer on-site installation ●● Wide range of Ormazabal’s TS: Walk-in, underground, kiosk, compact… Inside wind turbines ●● Off-shore & On-shore wind farms ●● Over 10 years of experience in the offshore wind sector ●● transforma.fine: Small-sized compact transformers, that are resistant to high temperatures, are characterised by their high capability to adapt to reduced spaces and for use in specific applications such as wind power generation ●● Availability of having an operational Transformer Substation in short time ●● Under pole solutions to protect the transformer against solar radiation and harsh environmental conditions as well as avoid bird nesting problems Crane The tank is robust enough for lifting the transformer by means of the lifting eyes. Own wheels For handling and installation instructions request the corresponding manuals to Ormazabal. 38 ≥846 mm Inside buildings The transformer site mustbe designed according to the local regulations and allow for adequate cooling. transfoorma Dielectric liquid immersed transformers Transformers for Distribution Network Solutions Outdoor Substations Commissioning and after sales Recycling and end‑of‑life transforma in outdoor facilities. Services As a part of its after sales services, Ormazabal provides electrical utilities and electrical end users recycling services for its transformers. Technical assistance FAT Pick-up & delivery Supervision & installation Commissioning Training Warranty Inspection & maintenance Spare part Repair Retrofitting Recycling On-pole Rural distribution transformers for on-pole installation: transforma conventional or tpc. Engineering Procurement EPCM Our quality, environmental and health & safety prevention policies establish our commitment to fostering and being part of an environmentally responsible society. Within this framework, our quality management system is internationally recognised through ISO 9001certification. Furthermore, our strong commitment to the environment is reflected in the implementation of an environmental management system, certified according to the ISO 14001 standard, which monitors the impact of activities on the environment. This policy also aims to promote and establish a culture of excellence and respect for personal health and safety, in accordance with standard OHSAS 18001. Its scope ranges from our team of professionals and partners to the end user. 39 transfoorma Dielectric liquid immersed transformers Notes 40 Transformers for Distribution Network Solutions Transformers for Distribution Network Solutions transfoorma Dielectric liquid immersed transformers Notes 41 www.ormazabal.com CA-109-EN-1508