TECHNICAL SPECIFICATIONS 63 KVA three phase Oil Cooled Aluminium wound Distribution Transformer – Quantity 1 No. 1 Reference standard IS 2026 2 Type of Transformer Oil Cooled 3 Normal continuous rating (KVA) 63 KVA 4 Voltage Ratio 11KV/433 V 5 Current ratio 3.306 A / 84 A 6 Rated frequency 50 Hz 7 Number of phases 3 8 Type of cooling ONAN (Oil Natural Air Natural) 9 Vector group Dyn 11 10 Connections (HV/LV) Delta/Star (Neutral brought out on LV side 11 Winding material Aluminium 12 Insulation of winding Double paper covered or enamel class H 13 Current density for Al conductor 1.6 A/sq mm (5% tolerance allowed) 14 Star rating 3 star (minimum) as per BEE guideline 15 Percentage impedance 4.5% 16 Noise level at rated voltage and frequency 50 db 17 Class of insulation Class A 18 Lamination CRGO (M-4 grade) 19 Permissible temperature rise over ambient (1)Of top oil measured by thermometer (2)Of winding measured by resistance 35 degree 20 Terminal arrangement (HV/LV) Cable box/cable box 21 Type of installation Out door 40 degree 22 Fittings and accessories as per relevant Indian Standards • • • • • • • • • • • • • • • • • Rating and diagram plate Top filter valve Bottom filter cum drain valve Lifting lugs (2 Nos minimum) for whole transformer Pulling legs 4 Nos HV bushings 3 Nos LV Bushings 4 Nos Terminial connectors on HV/LV bushings Earthing terminals 2 Nos Thermometer pocket with cap 1 No Air release plug on tank cover Oil conservator tank with drain plug, filling holes and cap Oil level indicator Drain-cum Filter valve with plug Silica-gel breather Air release plug, Explosion vent etc. Suitable Base channel