INSTALLATION INSTRUCTIONS
E-PG PARKING/GARAGE LIGHT FIXTURE
CI308X50R2
Document:
Date
2015-8-24
Created By: TMT2015-226
DCR#
PENDANT MOUNTING
1. Using a 1/2" NPT threaded pipe (supplied by others) feed
the wire coming out of the fixture through the conduit pipe
as shown in Figure 2.
2. Screw pipe into threaded fitting on top of fixture.
3. Connect opposite end of the pipe to mounting surface and
wire as shown in Electrical Connection section.
13.00
JUNCTION BOX MOUNTING
11.20
1. Remove the cover from the fixture by removing (4) screws
around the perimeter.
2. Remove lower assembly from the cover by disconnecting
two quick connect splice connectors and set lower
assembly aside for reinstallation later.
3. Make wire connections between leads coming from the top
of the cover to supply leads in junction box as shown in
Electrical Connection section.
4. Once electrical connections have been made attach cover
to junction box using slots on the cover. See Figure 3.
5. Reattach lower assembly to cover by reconnecting two
quick connect splice connectors that were disconnected in
Step 2 above.
6. Push lower assembly up into cover ensuring that no leads
are pinched, and align holes on cover with corresponding
holes on the lower assembly.
7. Replace (4) screws removed in Step 1.
5.43
CAUTIONS
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety
precautions should always be followed including the
following:
READ AND FOLLOW ALL
SAFETY INSTRUCTIONS
1.
2.
3.
4.
5.
DANGER- Risk of shock- Disconnect power before installation.
DANGER – Risque de choc – Couper l’alimentation avant
l’installation.
This luminaire must be installed in accordance with the NEC
or your local electrical code. If you are not familiar with these
codes and requirements, consult a qualified electrician.
Ce produit doit être installé conformément à NEC ou votre code
électrique local. Si vous n’êtes pas familier avec ces codes et
ces exigences, veuillez contacter un électricien qualifié.
This light is suitable for damp, wet locations
Convient aux emplacements humides ou emplacements
mouillés.
WARNING : Risk of fire.
ATTENTION - Risque d’incendie.
Do not allow the fixture to hang from the harness. This may
cause damage to the circuit.
FIGURE 2
Apply teflon tape to pipe
before installation
1/2 NPT Threaded Pipe
SAVE THESE INSTRUCTIONS
FOR FUTURE REFERENCE
INSTALLATION INSTRUCTIONS
1. Unpack fixture from both boxes. Fixture consists of two
power supplies mounted on the inside of the top hat lid of
the fixture. The lower assembly has the light engine and
harness.
2. The LED Garage Light fixture can be pendant mounted to
a 1/2"NPT threaded fitting or flush mounted directly to a 4"
square or 4" octagonal J-Box.
FIGURE 3
Slots
FIGURE 1
www.e-conolight.com
|
888.243.9445
|
FAX: 262.504.5409
INSTALLATION INSTRUCTIONS
E-PG PARKING/GARAGE LIGHT FIXTURE
CI308X50R2
Document:
Date
2015-8-24
Created By: TMT2015-226
DCR#
ELECTRICAL CONNECTION
FCC NOTICE
Fixture is equipped with universal volt driver 120-277V
CAUTION: Changes or modifications not expressly approved could void
your authority to use this equipment.
(ie. 120V, 208V, 240V or 277V)
PHASE TO NEUTRAL WIRING 120/277V
1. Connect supply ground to fixture ground (green) lead.
2. Connect supply common to fixture neutral (white) lead.
3. Connect supply Vin to fixture hot (black) lead.
PHASE TO PHASE WIRING 208/240V
1. Connect supply ground to fixture ground (green) lead.
2. Connect supply L1 (Hot) to fixture neutral (white) lead.
3. Connect supply L2 (Hot) to fixture hot (black) lead.
NOTE: The fixture can be dimmed with a 0-10V dimming control using violet and grey leads on driver. Refer to instructions
supplied with dimmer.
LED
NEUTRAL DRIVER
GND
– OUT
+ DIM
– DIM
WHI
NEUTRAL
GRN
GND
CONNECT TO 0-10V
DIMMING CONTROL
LED
LIGHT
ENGINE
+ OUT
LINE
GRN
WHI
BLK
CONNECT TO AC POWER
LINE
SP
NEUTRAL
GND
– OUT
LED
DRIVER + DIM
– DIM
This device has been tested and found to comply with the limits for
a Class B digital device, pursuant to Part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful
interference when the device is operated in a commercial environment.
This device generates, uses, and can radiate radio frequency energy
and, if not installed and used in accordance with the instruction manual,
may cause harmful interference to radio communications. Operation of
this device in a residential area is likely to cause harmful interference
in which case the user will be required to correct the interference at his
own expense.
INDUSTRY CANADA STATEMENT
This device complies with Industry Canada licence-exempt RSS
standard(s). Operation is subject to the following two conditions: (1) this
device may not cause interference, and (2) this device must accept any
interference, including interference that may cause undesired operation
of the device. In addition, this device complies with ICES-003 of the
Industry Canada (IC) Regulations.
+ OUT
BLK
LINE
This device complies with Part 15 of the FCC Rules. Operation to
the following two conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation.
CONNECT TO 0-10V
DIMMING CONTROL
Le présent appareil est conforme aux CNR d’Industrie Canada
applicables aux appareils radio exempts de licence. L’exploitation est
autorisée aux deux conditions suivantes : (1) l’appareil ne doit pas
produire de brouillage, et (2) l’utilisateur de l’appareil doit accepter tout
brouillage radioélectrique subi, même si le brouillage est susceptible
d’en compromettre le fonctionnement.
black - line
white - neutral
green - ground
Warning!
Do not allow the fixture to hang from the harness.
This may cause damage to the circuit.