Reference: Metering Standards Title: BASIC USE OF BIRD DOG ANALYZER FOR METER COMMISSIONING 1.0 Rev.: MS 8.2 Page: 1 of 6 Date: December 22, 2003 1 PURPOSE The purpose of this procedure is to describe the method for using the Bird Dog analyzer to commission transformer rated meters. 2.0 SCOPE This procedure applies to the use of the Bird Dog analyzer as part of reference 3.1 document “Commissioning Procedure For Transformer Rated Meters”. 3.0 REFERENCE 3.1 3.2 4.0 MS 2.2, “Commissioning Procedure for Transformer Rated Metering Installations” Bird Dog Plus Instruction Manual for NSPI. EQUIPMENT 4.1 Safety Equipment - 5.0 Safety Glasses Safety Footwear Hard Hat Work Gloves Rubber Gloves Fire retardant clothing Alternate light Source POWER REQUIREMENTS 5.1 Verify that the Bird Dog is adequately charged before using it in the field. Refer to reference 3.2 for details. Note: The Bird Dog can be operated using the battery charger if the battery is low. This would require a 120volt outlet at site. If there is no 120 volt supply the Bird Dog can not be used and refer to reference 3.1 clause 10.5.1. 6.0 PORT CONNECTIONS 6.1 Verify that the voltage lead is connected properly to Port P1 on the front of the Bird Dog. 6.2 Verify that the secondary CT lead is connected properly to Port P2 on the front of the Bird Dog. 6.3 Verify that primary CT flex coil is connected properly to Port P3 on the front of the Bird Dog. Developed by: Erika Smeltzer Methodology approved by: Dave Stanford C:\Documents and Settings\AG976\Desktop\Metering Standards\MS 8-2.doc Reference: Rev.: MS 8.2 BASIC USE OF BIRD DOG ANALYZER FOR METER COMMISSIONING 7.0 2 of 6 Date: December 22, 2003 PHASE ROTATION TEST 7.1 8.0 Page: 1 Connect the three voltage leads to the test block for automatic phase rotation test. If the Black lead is connected to the test block the Bird Dog will automatically select the phase rotation. This step must be done as it can affect the data/vector results. Meter Type AutoRotation Configuration 3 Phase, 3 Wire Delta Red lead to R (hot). White lead to W (hot). Black lead to B (hot). 3 Phase, 4 Wire Delta Red lead to R (hot). White lead to Y (hot). Black lead to B (hot). 3 Phase, 4 Wire Wye (2.5 Element) Red lead to R (hot). White lead to W (neutral). Black lead to B (hot). 3 Phase, 4 Wire Wye (3.0 Element) Red lead to R (hot). White lead to W (neutral). Black lead to B (hot). SETUP 8.1 Power up the Bird Dog by pressing the ON/OFF button on the front of the analyzer. 8.2 If Meter Circuit Selected is not correct Press No. 8.3 Select one of the following options for ‘Meter Circuit Types”depending on the meter type: Note: Use the ‘Next Item’ button to stroll through the selections. To select a meter circuit type Press either the ABC or the CBA button depending on the circuit rotation. If the black lead is connected to the test block it will automatically select the phase rotation regardless of which button is selected. Meter Type Meter Circuit Type Single phase 120 volt (2 wire, one 2-wire CT) FORM 3 Single Phase 240 volt (2 wire, one 3-wire CT) FORM 3 Single Phase (3 wire, two 2-wire CT) FORM 4 3 Phase, 3 Wire Delta (2 Element) FORM 5 3 Phase, 4 Wire Delta (2 Element) (2.5 Element) (3.0 Element) FORM 5 FORM 8 FORM 9 3 Phase, 4 Wire Wye (2.5 Element) FORM 6 3 Phase, 4 Wire Wye (3.0 Element) FORM 9 8.4 Enter the meter number of the meter to be commissioned as the Location Code. Press Save to store number. C:\Documents and Settings\AG976\Desktop\Metering Standards\MS 8-2.doc Reference: Rev.: MS 8.2 BASIC USE OF BIRD DOG ANALYZER FOR METER COMMISSIONING 9.0 3 of 6 Date: December 22, 2003 CONNECTION 9.1 10.0 Page: 1 Connect the voltage and secondary CT clip leads to the test block where the wires from the CTs and PTs are terminated. Ensure that the arrow on the secondary CT clip points to the meter side. At the CT cabinet install the primary flex coil around the bus bar, ensuring the arrow is pointed in the direction of current flow. See the following table for connection configurations based on Meter Type. Meter Type Connection Configurations Single phase 120 volt (2 wire, one 2-wire CT) Red lead to R (red, hot). White lead to BK (neutral). CT clip to R/W (current). Single Phase 240 volt (2 wire, one 3-wire CT) Red lead to R (hot). White lead to BK (hot). CT clip to R/W (current). Single Phase (3 wire, two 2-wire CT) Test 1 : Red lead to R (hot). White lead to BK (hot). CT clip to R/W (current). Test 2: Red lead to BK (hot). White lead to R (hot). CT clip to Y/W (current) 3 Phase, 3 Wire Delta (2 Element) Test 1: Red lead to R (hot). White lead to W (hot). CT clip to R/W (current). Test 2: Red lead to B (hot). White lead to W (hot). CT clip to B/W (current). 3 Phase, 4 Wire Delta Test 1: Red lead to R (hot). White lead to Y (hot). CT clip to R/W (current) Test 2: Red lead to B (hot). White lead to W (neutral). CT clip to B/W (current). 3 Phase, 4 Wire Wye (2.5 Element) Test 1: Red lead to R (hot). White lead to W (neutral). CT clip to R/W (current). Test 2: Red lead to R (hot). White lead to W (neutral). Black lead to B (hot). CT clip to Y/W (current). Test 3: Red lead to B (hot). White lead to W (neutral). CT clip to B/W (current). 3 Phase, 4 Wire Wye (3.0 Element) Test 1: Red lead to R (hot). White lead to W (neutral). CT clip to R/W (current). Test 2: Red lead to Y (hot). White lead to W (neutral). CT clip to Y/W (current). Test 3: Red lead to B (hot). White lead to W (neutral). CT clip to B/W (current). WIRE VERIFY GRAPH TEST 10.1 10.2 10.3 10.4 Select Ratio/Burden Tests from the Main Menu. Select Wire Verify Graph, and select the phase to analyze. Consult the vector diagrams included in this procedure to see if the results are good. If they are not go to clause 5.7. Record the secondary voltage on the MICS in the appropriate section. Use a voltmeter to measure the phase-to-phase voltage at the test block and record the value. C:\Documents and Settings\AG976\Desktop\Metering Standards\MS 8-2.doc Reference: Rev.: MS 8.2 BASIC USE OF BIRD DOG ANALYZER FOR METER COMMISSIONING 10.5 10.6 10.7 10.8 10.9 10.10 10.11 Page: 4 of 6 Date: December 22, 2003 1 Press EXIT and select CT Ratio/Burden Test and ensure the results are good. Press MORE OPTN and then press GLB SAVE + STORE. Press R+B Menu and select CT Ratio Test and phase to analyze. Verify CT ratio is acceptable; refer to reference 3.1.Record the values on the MICS in the appropriate section. Press STORE twice to save the data. Press EXIT. Verify Move probes to next phase*, refer to section 5.4.1 above for details. Go to 5.5.2. Note: This includes the voltage leads at the test block, the secondary CT clip at the test block and the primary flex coil at the CT. 11.0 COMPLETION 11.1 12.0 Once the commissioning is complete disconnect the Bird Dog and remove all the test leads, voltage and current leads before neutral. Put the cabinets and test block back to normal and seal with approved NSPI seals TROUBLESHOOTING 12.1 If the vector diagram is not acceptable, it could be caused by one or more of the following reasons: - 13.0 Secondary CT clip not closed Voltage leads not securely clamped on test switch Leads are not measuring same phase; i.e. the voltage leads are measuring the same phase as the current lead. Very poor power factor, refer to reference 3.1 clause 10.5.3. Defective wiring, refer to reference 3.1 clause 11.0 Auto Phase Rotation Test not done, see clause 5.2 of this procedure. COMMUNICATION 13.1 13.2 13.3 13.4 Connect the Bird Dog to your PC. Make sure the serial cable is securely connected to the port on the back of the Bird Dog. Turn ON the Bird Dog and select UNDEFINED and then EXIT. Select COMM.(9600)/Records and then select PC UPLOAD/RECORDS. Select UPLOAD ALL RECORDS. A % status indicator appears on the screen and indicates 100% when complete. C:\Documents and Settings\AG976\Desktop\Metering Standards\MS 8-2.doc Reference: Rev.: MS 8.2 BASIC USE OF BIRD DOG ANALYZER FOR METER COMMISSIONING C:\Documents and Settings\AG976\Desktop\Metering Standards\MS 8-2.doc Page: 5 of 6 Date: December 22, 2003 1 Reference: Rev.: MS 8.2 BASIC USE OF BIRD DOG ANALYZER FOR METER COMMISSIONING C:\Documents and Settings\AG976\Desktop\Metering Standards\MS 8-2.doc Page: 6 of 6 Date: December 22, 2003 1